Inspection and Testing 05
Inspection and Testing 05
2. Select and train individuals with appropriate mechanical aptitude to conduct the
inspections and tests of fire protection equipment.
3.
Initiate a complete survey of the facility's fire protection equipment for the purpose
of developing a customized inspection report form. Examples of forms are attached.
4.
5.
6.
Establish contacts with sprinkler contractors for periodic testing and emergency
maintenance of fire protection equipment.
State of Minnesota
C. Background
Once the qualified persons are selected, it is important that they be properly trained.
This training should include the following features:
1. Review of existing protection equipment and its maintenance, operation, and
testing techniques, and familiarization with installed fire protection equipment.
2.
State of Minnesota
control valves, portable fire extinguishers, fire pumps, dry pipe valves, etc. Such forms
not only serve as a guide for conducting inspections, but also provide a method of
proper record keeping. The inspector should carry the form and use it as a checklist. It
should be filled in as rounds are made, not after the completion of an inspection. A
sample form is provided at the end of this section.
D. Marking and Identification of Equipment
Sprinkler control valves should be numbered for inspection and identification purposes.
The number listed on the valve should correspond with the number on the inspection
form and fire diagram.
Valves should be plainly marked with the direction to open. If not marked by the
manufacturer, a sign should be posted near the valve indicating direction to open. If
underground curb box valves are used, a T wrench should be provided near the valve
with a sign indicating location of the valve.
E. Frequency of Inspection
The frequency of inspection of fire protection equipment depends on numerous factors.
For example, dry pipe systems should be checked daily in the winter; but less frequent
checks would be acceptable in the summer. The recommended frequency for testing and
maintenance of critical sprinkler system components appears on the attached schedule.
State of Minnesota
All fire protection control valves (OSY - PIV - Butterfly) shall be locked
and chained in the open position.
All valves shall be visually inspected on a monthly basis to show they are
open and are not blocked.
All valves shall be exercised. Manually close and manually reopen every
6 months. Lubricate as needed.
Fire Pump
All fire pumps shall be started weekly by drop of pressure and allowed to
run for five minutes before placing back in automatic position (churn test).
All fire pumps shall be tested annually with a full flow test measuring
waterflow and pressure. (Qualified sprinkler company should perform the
test). Test results should be kept on file for review.
Alarms:
Low Air
Pump Running
Electric Power to Pump
(Electric Pump)
Detectors
(Smoke and Heat)
Quarterly
Quarterly
Quarterly
Weekly
Monthly
Annually
All dry pipe valves shall be tripped annually, with test results kept on file
for review.
FM-200
Anti-Freeze
Concentration
Annual test
Outside Local
Waterflow Alarms
Quarterly
State of Minnesota
Extinguishers
Hydrants