Notes For Checkers

This document contains punching shear calculations for two internal columns, G4' and E1', at the roof level of a building. For each column, it provides the column dimensions, slab thickness, concrete type, and notes to refer to general notes. It also lists information about finishes, the supporting masonry wall, and area supported. For both columns, it notes concern about high stress under punching shear check, though no visible distress was observed. The conclusion is yellow status due to a factor of safety of 1.81, and it recommends limiting live load to 1kPa.

Uploaded by

Sajoyan Haque
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views

Notes For Checkers

This document contains punching shear calculations for two internal columns, G4' and E1', at the roof level of a building. For each column, it provides the column dimensions, slab thickness, concrete type, and notes to refer to general notes. It also lists information about finishes, the supporting masonry wall, and area supported. For both columns, it notes concern about high stress under punching shear check, though no visible distress was observed. The conclusion is yellow status due to a factor of safety of 1.81, and it recommends limiting live load to 1kPa.

Uploaded by

Sajoyan Haque
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Calculations

Punching Shear Calculations

Notes for checker of


report (G4)

Information for punching shear at internal column G4 at Roof


Column dimensions 510x305 mm
Slab thickness=150mm
Slab with stone aggregate concrete
Also refer general notes at start of section

Allow 50mm finishes


Column on a masonry internal partition wall line. Total wall length is 11.602m,
height only 2.663m Thickness .150
Use of area supported by this column is : Walls only
Concerns (Y/N) : YES as highly stressed under a punching shear check.
However there was no visible distress to the soffit of the slab around columns
generally (although this specific location may not have been checked)
Conclusion as to why (R/A/Y/G): Yellow as FOS is 1.81
Recommend that live load is limited to 1kPa.

Falcon knit composite Internal Column Punching Shear Spreadsheet

Notes for checker of


report (E1)

Information for punching shear at internal column E1 at Roof


Column dimensions 510x305 mm
Slab thickness=150mm
Slab with stone aggregate concrete
Also refer general notes at start of section

Allow 50mm finishes


Column on a masonry internal partition wall line. Total wall length is 11.602m,
height only 2.663m Thickness .150
Use of area supported by this column is : Walls only
Concerns (Y/N) : YES as highly stressed under a punching shear check.
However there was no visible distress to the soffit of the slab around columns
generally (although this specific location may not have been checked)
Conclusion as to why (R/A/Y/G): Yellow as FOS is 1.81
Recommend that live load is limited to 1kPa.