0 ratings0% found this document useful (0 votes) 227 views66 pagesDewaregulations PDF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
2-4 JUN 1997
civiL
ENGG.
REGULATIONS
FOR ELECTRICAL INSTALLATIONS
1997 EDITION
P.O. BOX 564
busal
UNITED ARAB EMIRATES.DUBAI ELECTRICITY & WATER AUTHORITY (DEWA)
REGULATIONS FOR ELECTRICAL INSTALLATIONS
1997 - EDITION
INTRODUCTION
This edition supersedes the ‘WIRING REGULATIONS FOR ELEC-
TRICAL INSTALLATION AND APPROVED CODE OF PRACTICE IN
DUBAI’ issued in the year 1985 by the then DUBAI ELECTRICITY
COMPANY.
The object of the Regulations is to provide Consultants, Contractors,
Wiremen and Consumers with a general guide for compliance with
DEWA's requirements for electric installations in order to safeguard
persons and property from hazards arising from the use of electricity
The Regulations, however, are not intended to substitute detailed
specifications nor to serve as an instruction manual for untrained
persons. It is essential that all Consultants, Contractors and Wiremen
study and abide by these Regulations. This, of course, does not absolve
the concemed parties from obtaining other necessary approvals from
DEWA.
Some of the practices followed generally in the AGCC Countries
have been adapted as appropriate. References are generally made
to the sixteenth edition of the IEE Wiring Regulations, British Stan-
dards (BS) and International Electrotechnical Commission (IEC) doc-
uments. Consideration has been given to the prevention of fire and
shock hazards as well as proper operation and maintenance of wir-
ing installations and equipment.Clause
14
12
13
14
15
16
a7
18
13
1.10
41m
1.12
4.13
34
32
33
44
42
424
422
423
424
425
426
427
43
434
432
44
48
454
452
ENT
Page
INTRODUCTION i
SECTION 1: GENERAL REQUIREMENTS 1-4
Scope
Electncity Supply
Ambient Conditions
Approved Contractors
Workmanship
Standards for equipment and materials
Submission of Drawings
Power Factor (P-F.) Correction
Under Voltage (U.V.) Relays with Auto-Reset Timer
Harmonies and rapid voltage changes
Inspection and testing of installations
Maintenance, periodic inspection and testing
Extensions and alterations
SECTION 2: DEFINITIONS 5-8
SECTION: DEWA INCOMING SUPPLY AND TARIFF METERING — 9-11
General
Point of Supply
Tariff Metering
SECTION 4: SELECTION OF CABLES, EQUIPMENT, MATERIALS &
WIRING SYSTEMS 12-20
General
Cables and Conductors
Selection
Minimum Size of Conductors
Current rating, size and Voltage drop
Colour Identitication
Wiring Installations Exposed to High Temperatures
Wiring Installations in Hazardous areas
Load Balancing
Wiring Accessories and Fittings
Conduits and Fittings
Trunking
Cable Trays & supports
Low Voltage Switchgear and Control Gear Assemblies
Main & Sub-Main Distribution Boards
Final Distribution BoardsClause Page
46 Apparatus & Accessories
46.1 Switches
46.2 Plugs and Socket-Outlets
463 Cooker Control Units
45.4 Household and similar electrical appliances
465 Control of Water Heaters
466 Control of Air Conditioning Univequipment
487 Extra Low Voltage Safety Apparatus
458 HV. Discharge Lighting Equipment
4.69 Satety and Emergency Light Fittings
4.6.10 Electric Motors and Starters
4.6.11 Standby Generators
47 Assessment of connected load and max. demand
474 Lighting & small power circuits
472 Maximum demand
SECTIONS: EARTHING AND EARTH LEAKAGE PROTECTION 21-22
81 Consumer's Earthing System
52 Consumer's Main Earth Electrode
53 Earth Continuity Conductor (ECC)
54 Earth Leakage Protection
55 Equipotential Bonding
SECTION 6: INSTALLATION OF CONDUITS, TRUNKING,
TRAYS & ACCESSORIES 23-25
61 Trunking and Conduits
62 Cable Trays
SECTION 7: INSTALLATION OF CABLES, EQUIPMENT,
ACCESSORIES AND WIRING SYSTEMS 26-28
7A Armoured Cables
72 Distribution Boards
73 Busbar trunking systems (Busways)
74 Wiring systems and Accessories
741 Segregation of circuits, Phases and wiring systems
742 Mounting heights of Accessories
743 Identification Labels and Notices
SECTION 8: POWER FACTOR CORRECTION CAPACITORS AND
UNDER VOLTAGE RELAYS 29-30
a4 Power Factor (PF) Correction
82 Under Voltage (U.V.) Relays with Auto-reset timerclause
a4
92
93
Appendix
noosene
10,
"
12
13,
14
15,
16.
(A)
(B)
(Cc)
(0)
SECTIONS: CONSTRUCTION SITE INSTALLATIONS
General
Wiring systems and Distribution Boards
Earth Leakage Protection
APPENDICES
Reference Standards
Details of Connected Load/Max. Demand (format)
Load Distribution Schedule - 3 phase (format)
Load Distribution Schedule - 1 phase (Jorma!)
Electrical Symbols
Contractor's Inspection Certificates (format)
Typical arrangement of Metering Cabinet on Compound wall
‘Typical arrangement of kWh meters in Electrical Service Room
Typical Electrical services room with 1 No. MDB
‘Typical Electrical services room with 1 No. Cubicle tyPe |- vy. Switchboard!
Panel
Selection of Cables
Table 1. Single Core PVC Insulated non-armoured,
Stranded Copper Conductors,
Table 2 :- Multi Core armoured PVC insulated,
Copper Conductors.
Table 3 :- Muli Core armoured XLPE insulated,
Copper Conductors.
Colour Identification of unarmoured, armoured and
flexible cable cores and bare conductors.
Specifications of MDBs/SMDBs (format)
Specifications of DBs (format)
Earth Continuity Conductors (ECCs) and Equipotential
Bonding Conductors.
Earth Leakage Protection.
‘Spacing of Supports for Trunking, Conduits and Cables
Number of Cables that may be installed in Trunking,
Conduits and Trays.
Data Schedule for LV Electricity Meters and Current Transiormers
Page
3t
33
34
35
36
37
38 - 40
41-42
43
44
45
46
47
48
49
50
51-53
54-56
87
58
59
60
aat
12
DUBAI ELECTRICITY & WATER AUTHORITY
REGULATIONS FOR ELECTRICAL INSTALLATIONS.
SECTION - 1
GENERAL REQUIREMENTS
SCOPE
The Regulations apply to the requirements of all electrical installations in or about
buildings and any additions, alterations and extensions to the existing buildings and
installations therein, in the Emirate of Dubai
Installations, wherein construction of High Voltage substationis is required, shall be
relerred to DEWA at the preliminary design stage for incorporating any specific
requirements.
The Regulations are not intended to take the place of a detailed specification or to
instruct untrained persons or to provide for every circumstance. Where a difficult or
special situation arises which is not covered or allowed for in the Regulations, the
DEWA may be sought to obtain specitic advice
ELECTRICITY SUPPLY
The nominal electric supply voltage from DEWA is 220/380V + 10%, 50 Hz, 3- Phase,
4 wire with separate neutral and protective conductor (generally metallic covering of
the cable supplying the installations). The neutral is solidly earthed at DEWA's
substations and shall not normally be earthed elsewhere in the electrical installations
The design fault level within the substation is 40 kA (fault duration - 1 Sec), except for
fuse protected equipmenticircut.
The nominal voltage of existing 220V/S8OV system shall evolve towards the IEC
recommended value of 230/400V + 10% (IEC .38) before the year 2005.
All equipment, apparatus, materials and accessories used in the electrical installations.
shall be designed and rated for operation on this electric supply. Appropriate
protective devices against over-voltages, fluctuations, transients & harmonics, loss of
one or more phases and any unforeseen interruptions shall be provided in all consumer
installations as deemed essential, in addition to overload, short-circuit and earth
leakage protective devices13
14
15
16
AMBIENT CONDITIONS
All equipment, apparatus, materials and accessories used in the electrical installations
shall be suitable for the purpose intended and capable of operating with satisfactory
Performance in the climatic conditions of the Emirate of Oubai which are as follows
Altitude Sea Level (Coastal)
‘Max. outdoor ambient temperature (shade) 48°C
Min. Ambient Air Temperature 28°C
Max. Ambient Air Termperature 48°C
> Max. average over 24 Hrs, 378°C
- Max. average over 1 Year 26.9°C
+ Relative humidity 100 % (Max.)
+ Thunder storms per year Occasional
+ Earthquake Loading 0.079
- Wind speed : 45 m/s at 10 m height
- Ground Temperature : 35°C
(at depth of 0.9 mt.)
Soil thermal resistivity 2.0° Cimiw
Heavy condensation and sand storms also prevail
APPROVED CONTRACTORS
Each contractor who undertakes electrical installations is required to have at least one
electrical engineerielectrician who holds a valid Competency Licence issued by
DEWA and is responsible for correct installation and shall supervise and test the entire
electrical works. The Competency Licences will be issued by DEWA only to those
individuals who fulfil the requirements set-orth by DEWA, can understand and apply
DEWA's Regulations.
WORKMANSHIP.
All electrical installations shall be carried out in a neat, orderly workman like manner.
Caretul attention shall be paid to the mechanical execution of the work in connection
with any electrical installation.
STANDARDS FOR EQUIPMENT AND MATERIALS
All electrical installations shall comply with the requirements of the Regulations,
relevant DEWA's Technical Specitications, latest Edition of the IEE Wiring Regulations,
and any other Regulations issued by DEWA from time to time. In case of contradiction,
DEWA’s Regulations shall prevail
All equipment, apparatus, materials and accessories complying with the current
Standards quoted in Appendix-1 and/or conforming to relevant IEC (International
Electrotechnical commission) and ISO (Intemational Standards Organization) recom-
mendations shall be deemed to satisty the requirements of the Regulations, unless
otherwise specifiedww?
18
19
1.10
SUBMISSION OF DRAWINGS
Before the commencement of any electrical installations, large or small, new or
additional, following details and drawings of the proposed installations ‘shall be
submitted to DEWA, for review and approval thereof
') Connected Load/Maximum Demand in the prescribed form given in Appendix.2
H) Single Line Diagram, showing the L.V Distribution and tariff (kWh) metering
(Refer to Appendix-5, for symbols) and relevant technical specifications
") Load Distribution Schedule/s of final distribution board/s as per prescribed
forms, given in Appendix-3 & 4,
vy) General arrangement and dimensional layout of electrical switch room/s and/or
enclosure/s with KWh metering facilities, as applicable.
¥) Site setting-out plan/key plan with details of all external electrical services.
v) Wiring layouts of the installations. (Reter to Appendix-5, for symbols)
The design and layout drawings of substations which are specified for individual
installations, shall also be prepared in compliance with DEWA's Regulations for
Substations, and submitted in advance for approval
POWER FACTOR (P. F.) CORRECTION
The overall Power Factor of all consumer installations shall be maintained within 0,9
(lagging) and unity.
Generally all central air-conditioning plants, window & split type air-conditioning
units/equipment shall incorporate integral means for power factor correction to
achieve and maintain a power factor not less than 0.9 lagging throughout their normal
working range.
All light fittings with discharge lamps, mercury vapour/sodium vapour, fluorescent
{ubes, etc. shall incorporate capacitors to obtain a power factor of 0.9 or above,
lagging. Guidelines on requirement of PF improvements is also given in Section 8.1 of
the Regulations.
UNDER VOLTAGE (U.V.) RELAYS WITH AUTO-RESET TIMER
All air-conditioners or air-conditioning units/plants/equipment installed within the
Consumer installation shall be provided with U.V, relays with auto-reset timer. The
guidelines on requirement of UV relays are also given in Section 8.2 of the regulations.
HARMONICS AND RAPID VOLTAGE CHANGES
Harmonics of the supply voltage are caused mainly by consumer's non linear loads
Connected to the supply system.
A consumer's load is not allowed to cause deviations of the voltage characteristics
ciher than those allowed in European Standard EN 50160, Nov. 1994. Any excess
Geviations shall be compensated by the consumer at his cost414
1.12
INSPECTION AND TESTING OF INSTALLATIONS
Contractors shall be required to submit their “inspection Certificates” in the prescribed
form, given in Appendix-6, on completion of the electrical installations. All installations
and equipment installed therein, shall be subject to DEWA's inspection, testing and
final approval before connecting the electric supply
The first inspection and testing by DEWA may be free of charge. All installations
which require re-inspection and re-testing may be charged for each subsequent
inspection, based on the type of consumer installation, connected load, etc. and as
specified in Regulation 3.1.1 of Section-3
MAINTENANCE, PERIODIC INSPECTION AND TESTING
Maintenance, periodic inspection and testing of every installation shall be cartied out
to ensure safety and satistactory performance. The trequency of periodic inspection
and testing of an installation shall be determined by the type of installation, its use and
Operation, the frequency of maintenance and the external influences to which it is
Subjected. Industrial and commercial installations shall at least be inspected every 2
years by an independant ConsultantiContractor. The Consultant/Contractor or person
Tesponsible for the maintenance, inspection and testing shall report to DEWA, in
writing, any detects found in related parts of the existing installations and their rectifica-
tion, together with a schedule of test results,
Every installation shall also be subject to periodic, random inspection by DEWA. The
consumer shall arrange rectification of the defects, if any, notiied by DEWA, at his,
own cost.
EXTENSIONS AND ALTERATIONS.
The consumer shall not make any extensions or alterations to his electrical installation
without obtaining prior approval from DEWA
Application in DEWA’s prescribed form shall be submitted for every project/installation
whatsoever, large or small, new or additions, for provision of DEWA's supply lines and
equipment, subject to terms and conditions issued by DEWA trom time to time.SECTION - 2
DEFINITIONS
Following definitions shall apply for the purpose of the Regulations,
Accessory. A device, other than cutrent-using equipment, associated with Such equipment or
with the wiring of an installation
Ambient temperature. The temperature of the air or other medium where the equipment is to
be used
Appliance. An iter of current-using equipment other than a luminaire or an independent motor
Aim's reach. A zone of accessibility to touch, extending from any point on a surtace where per.
Greeti Stand or move about to the limits which a person can reset nth < hand in any
direction without assistance.
Barrier. A part providing a defined degree of protection against contact with live parts from any
usual direction of access.
Bonding conductor. A protective conductor providing equipotential bonding
Bunched. Cables are said to be bunched when two or more are contained within a single
spect ct dueting, oF trunking or, if not enclosed, are not separated tan en other by a
specified distance.
Sable cleat. A component of a support system, which consists of elements spaced at intervals
along the length of the cable or conduit and which ‘mechanically retains the cable or conduit,
Gable Tray. A cable support consisting of a continuous base with raised edges and no cover-
eaeeable tray is considered to be non-perforated, where less than Soerg, the material is
Temoved from the base.
Cable trunking. A manufactured enclosure for the protection of Cables, normally of rectangular
FOSS section, of which one side is removable or hinged
Gircuit. An assembly of electrical equipment supplied from the same origin and protected
against overcurrent by the same protective device(s)
Sircuit-breaker. A device capable of making, carrying and breaking normal load current and
aang making and automatically breaking, under pre-determined conditics abnormal currents
Such as short-circuit currents. Its usually required to operate infrequently although some types
are suitable for frequent operation
Conduit. part of closed wiring system for cables in electrical installations, allowing them to be
Grawn in andor replaced, but not inserted laterally,
Current carrying capacity of a conductor. The maximum current which ean be carried by a
vatug Ct Under Specified conditions without its steady state temperate exceeding a specified
Surrent-using equipment. Equipment which converts electrical energy into another form of
energy, such as light, heat or motive power.
Bigiseilve circuit conductors, it may also include signalling and other eoctsol devices. Means of
'solation may be included in the board or may be provided ‘separately,Double insulation. insulation comprising both basic insulation and supplementary insulation.
Duct. A closed passageway formed underground or in a structure and intended to receive one
or more cables which may be drawn in,
Earth. The conductive mass of the Earth, whose electric potential at any point is conventionally
taken as zero
Earth electrode. A conductor or group of conductors in intimate contact with, and providing an.
electrical connection to, Earth,
Earth electrode resistance. The resistance of an earth electrode to Earth.
Earth fault current. A fault current which flows to Earth
Earth leakage current. A current which flows to Earth, or to extraneous-conductive-parts, in a
Circuit which is electrically sound. This current may have a capacitive component including that
resulting from the deliberate use of capacitors.
Earthing. Connection of the exposed-conductive-parts of an installation to the main earthing
terminal of that installation.
Earthing conductor. A protective conductor connecting the main earthing terminal of an
installation to an earth electrode or to other means of earthing.
Electric shock. A dangerous physiological effect resulting from the passing of an electric
current through a human body or livestock.
Electrical installation, An assembly of associated electrical equipment supplied from a
common origin to fulfil a specific purpose and having certain co-ordinated characteristics.
Emergency switching. An operation intended to remove, as quickly as possible, danger, which
may have ocourred unexpectedly.
Enclosure. A part providing protection of equipment against certain external influences and in
any direction protection against direct contact.
Equipment. Any item for such purposes as generation, conversion, transmission, distribution or
utilisation of electrical energy, such as machines, transformers, apparatus, measuring
instruments, protective devices, wiring systems, accessories, appliances and luminaires.
Equipotential bonding. Electrical connection maintaining various exposed-conductive parts
and extraneous conductive-parts at substantially the same potential
Exposed-conductive part. A conductive part of equipment which can be touched and which is
not a live part but which may become live under fault conditions.
External influence. Any influence external to an electrical installation which affects the design
and safe operation of that installation.
Fault. A circuit condition in which current flows through an abnormal ot unintended path. This
may result from an insulation failure or a bridging of insulation. Conventionally the impedance
between live conductors or between live conductor and exposed-or extraneous-conductive-parts
at the fault position is considered negligible.Fault current. 4 current resulting from a fault
Final circuit, A circuit connected directly to current-using equipment, or to a socket-outlet or
Socket-outlets or other outlet points for the connection of such equipment
Fixed equipment. Equipment designed to be fastened to support or othenwise secured in a
specific location.
Flexible cable. A cable whose structure and materials make it suitable to be flexed while in
service,
Flexible cord. A flexible cable in which the cross-sectional area of each conductor does not
exceed 4mm’,
Insulation. Suitable non-conductive material enclosing Surrounding or supporting a conductor.
tsolation. A mechanical switching device which, in the open Position, complies with the
“eauirements specitied for isolation. An isolator is otherwise known as a dieconnocter
nive bar. A conductor or conductive pat intended to be energised in normal use, including a
neutral conductor.
LY Suitchgear and controlgear assembly. A combination of one or more low-voltage
eau devices together with associated control, measuring, signaling, Protective, regulating
Main earthing terminal. The terminal or bar provided for the connection of protective
soreuctors, including equipotential bonding conductors, and conductors lor usctionay earthing,
it any, to the means of earthing,
Neutral conductor. The neutral conductor of a 3-phase 4-wire system or the conductor of a
Single phase installation which is earthed at the source of the supply.
Nen-combustible. A non-combustible material is one which is not capable of undergoing
Combustion and satisfies the performance requirements complying with BS 476 Port ¢ Parts
Nominal voltage. Voltage by which an installation (or part of an installation) is designated. The
following ranges of nominal voltage (rms, values for 2.0) are detned
* Extra low, Normally not exceeding 50 V a.c. or 120 V ripple free d.c., whether
between conductors or Earth
* bow Normally exceeding extraiow voltage but not exceeding 1000 V acc. or 1500 v
6 belween conductors, or 600 V a.c. or 300 V dc. between conductors and Larin
Zhe actual voltage of the installation may difer from the nominal value by @ quantity within
normal tolerances.Overcurrent. & current exceeding the rated value. For conductors the rated value is the
current-carrying capacity,
Overload current. An overcurrent occurring in a citcull which is electrically sound
cout wiring) & termination of the fixed wiring inlended for the connection of current-using
equipment
EY S,{eS Insulation or sheath of cable). Polyvinyl Chloride Compound complying with
BS 6746,
Protective Conductor/Earth Continuity Conductor (ECC). A conducior used for some
Doliowina yo Protection against electric shock and intended for connecting together any of the
following pans,
' exposed-conductive-pars.
') extraneous-conductive-parts,
ti) the main earthing terminal
'v) earth electrode(s)
¥) the earthed point of the source, or an artificial neutral
Residual current. The vector sum of the instantaneous values of current flowing through all live
Conductors of a circuit at a point in the electrical installation,
Residual current device. A mechanical switching device or association of devices intended to
cause ihe opening of the contacts when the residual current attains a given value under
specified conditions.
Resistance area (for an earth electrode only). The surface area of ground (around an earth
electrode) on which a significant voltage gradient may exist
Ring circuit. & circuit arranged in the form of a ring and connected to a single point of supply.
Short-circuit current, An overcurrent resulting trom a fault of negligible impedance between
live conductors having a difference in potential under normal operating conditions.
Socket-outlet. A device, provided with female contacts, which is intended to be installed with
the ited wiring, and intended to receive a plug. A luminaire track system is not regarded ae
socket-outlet system,
Space factor. The ratio (expressed as a percentage) of the sum of the effective overall
Gross-sectional area of cables forming a bunch to the internal cross-sectional area of the con.
Gull, pipe, duct, trunking or channel in which they are installed
Switch. A mechanical device capable of making, carrying and breaking current under normal
cxcut conditions, which may include specified operating overload conditions, and also ot
Seca Sutrent for a specified abnormal circuit conditions such as those of short-circuit. It may
also be capable of making, but not breaking, short-circuit currents,
Switchboard. An assembly of switchgear with or without instruments, but the term does not
apply 10 groups of Iocal switches in final circus.
Switchgear. An assembly of main and auxiliary switching apparatus for operation, regulation,
Protection or other control of an electrical installation
XLPE (as insulation of cable). Cross linked polyethylene complying with BS 5467.a4
344
313
3.44
315
32
321
322
323
32.4
32.5
SECTION -3
DEWA INCOMING SUPPLY AND TARIFF METERING
GENERAL
Power supply from DEWA network shall be Subject to terms, conditions, tees, tariffs
and instructions issued by DEWA from time to tins,
The etalis of nominal electric supply from DEWA and general requirements, for
Compliance, are speciied in Seetion.1 of the Regulator,
Consumer shall, before commencement of building construction, obtain confirmation
‘rom DEWA on availabilty of power supply.
{n General, where the total connected load exceeds 400 kW, provision shall be made
within the building or plot for DEWA's substation in Some circumstances a substation
ray be required for connected load less than 400 kw. These requirements shall be
confitmed in the issue of DEWA's No Objection Certificate which shall be revalidated
at the end of every six month period.
{nes and equipment and shall immediately eport any defect in or damage to any of
DEWA's lines or equipment.
POINT OF SUPPLY
‘The point of supply which defines the Boundary of DEWA equipment and where elec.
Helly is made available to the consumer shall be decided by DEWA. Point of
Supply shall be made available only at one location, within a plotiproject, unless
otherwise approved / specified by DEWA.
The circuit breaker/s andlor main distribution board/s provided at the incoming point of
supply shall be designed and rated to suit particular applications and complying with
regulations specified in clauses 4.5 & 7.2
Where a main L.V. distribution panel is Connected directly to the low voltage side of
{he transformer, the main incomer circuit breaker proposed in the L.V. panel ig
‘Scommended to be totally withdrawable type air circuit breaker.
{here consumer's Main Low Voltage distribution board/panel is connected to DEWA's
Meo of More distribution transformers, separate bus-sections with mechanically ang
lectrcaly interiocked bus-section breakersiisolaton, shall be provided.326
327
3.28
3.29
3.2.10
33
334
3.32
3.33
334
335
All incoming cable terminations/Live connections in metering cabinets and other main
2nd sub-main distribution boards shall be adequately shrouded and insulated
All exposed Live terminal Connections and bus bars in any low voltage distribution
board shall be shrouded and/or insulated to DEWA's approval
Consumer's main & sub-main Panels/Distribution Board/s and final distribution boards
shall be installed in locations to which access is available at all times. A minimum
‘space of 1500 mm shall be provided in the front and 750 mm on the sides, to permit
safe operation, inspection, testing and maintenance, for cubicle type panels/switch
boards. Panels with rear access doors shall have, in addition, a minimum space of 750
mm in the rear. The mounting height (to the top of the board/s) shall normally be 2
metres from the grounditioor level
All electrical switch rooms shall be adequately ventilated and provided with necessary
heavy duty exhaust fan/s and fire resistant/metallic louvered door/s, as applicable
Adequate level of illumination shall be provided to facilitate safe operation at all times,
Incoming supply cable/s to the consumer's main Distribution Board/s shall be totally
Segregated and identified from the consumer's cables.
Termination of incoming supply cable at the Consumer's Metering Cabinet/Main
Distribution Board (MDB) shall be carried out by consumer's contractor, in accordance
with Regulations 7.1.8 and 7.1.9.
TARIFF METERING
For individual consumer premises, such as villas, farms, gardens, accommodation
blocks, etc, the metering cabinet, with main incomer circuit breaker and metering shall
be installed outside, recessed, in the compound wall
|n multiple consumer premises such as residentialicommercial buildings, industries,
large utility complexes, schools, etc, the main and sub-main distribution boards with
associated metering shall be installed in separate electrical switch rooms, in locations
close to the entrance boundary line and to which access is available at all times for
operation, testing, inspection, maintenance and repair. Prior approval shall be ob-
tained from DEWA as specified in Clause 1.7 of Section 1 for every such premises,
All tariff metering will normally be provided by DEWA and restricted to one for each
Consumer installation, unless otherwise approvedispecified by DEWA.
The minimum space required for installation of kWh meter shall be 300 mm wide and
400 mm high,
The general arrangement and dimensional layout of the metering cabinets and array
of meters installed in electrical switch room/s and enclosure along with associated
winng shall be subject to DEWA's approval. The typical arrangement of kWh metering
cabinevkWh meters is given, for guidance, in Appendix 7.
-10336
337
3.38
339
3.3.10
3341
3.3.12
Metering by means of Current Transformers (CTs) shall be installed where the circuit
breaker rating at the point of supply is 200 Amps and above. DEWA will provide the
RUN meter/s and associated CTS for all tarif metering. in some circumstances cent
The current transformer of folowing lated Transformation Ratio shall be used as a
standard requirement ;
a) 20/5
b) 3800/5
©) 40/5
a) 60015
e) 80/5
f) 12005
9) 1600/5
h) 2400/5
Each Curtent Transformer shall have the folowing markings ;
@) Manufacturer's name and/or trade mark,
©) Rated primary current and secondary current,
©) Rated Frequency and primary maximum voltage
d) Accuracy Class.
e) Rated output (VA).
1) Terminal (secondary winding) indentification (81, Se, oe)
9) Power flow direction (Ps, Pa)
Manufacturer may include any other markings that he considers to be included
Transparent viewing window shall be provided in all metering cabinets and doors of
enclosures housing the meters with associated distibution switchgear, for facilitating
meter reading.
ae anatering cabinets and enclosures shall be constructed from fre-resistanvnon-
combustible material
When meters are installed in electrical switch room/s, fire-resistantinon-combustible
base plates shall be provided. Single core PVG or XLPE insulated & PVC sheathed
Gables to BS 6004 shal be used for connection to kWh meters, except when installed
Segregated within separate metering cabinets,
All ‘metering cabinets/compariments shall be provided with Padlocking and
fite-sealing facilities on their external doot/cover which shall normally be of hinged
eon Rally all apparatus, circuit breakers, isolators, bus bars. removatle: ga
Section of bus bar - trunking, etc, installed on the supply side of any DEWA's metering
Shall have provision for sealing by DEWA,
The metering section/compartment in all MDB/s and SMDBis if and when incorporated
within, shall completely be segregated from other sectionsicompartmente
-u-SECTION -4
‘SELECTION OF CABLES, EQUIPMENT, MATERIALS & WIRING SYSTEMS
41 GENERAL
4.1.1 All equipment and matenals used in electrical installations shall be of good quality
Complying with the relevant sectionsiclauses of the Regulations is a minimum
requirement
412 Every item of equipment used in the installation shall be designed and rated for
Operation on the nominal electric supply voltage declared by DEWA.
42 CABLES AND CONDUCTORS
42.1 Selection
For general purposes and in normal situations PVC/XLPE insulated, standard copper
Conductor cables complying with BS 6004 & BS 6346/BS 5467 shall be used for all
fixed wiring installation of buildings.
'n inflammable/explosive situations, the cables shall be mineral insulated copper
sheathed complying with BS 6207.
Flexible cables and cords for use in electrical installation shall be PVC insulated and
sheathed, stranded copper conductors complying with BS 6500/BS 6004.
Cables for connection between ceiling rose and lamp holder for pendant type light
fittings and for enclosed luminaire shail be heat resistant silicone rubber insulated with
Stranded copper conductor complying with BS 6141
For lifts and similar applications rubber insulated or PVC insulated flexible cables
complying with BS 6977 shall be used
kWh meter tails shall normally be single core PVC insulated and sheathed cables
complying with 8S 6004, as specified in Regulation 33.
Single core cables armoured with steel wire or tape shall not be used for a.c. circuits,
4.2.2 — Minimum Size of Conductors
The minimum size of conductor used for lighting circuit shall be 1.5 mm? and 4 mm? for
ulilty socket outlets.
Minimum size of conductor for flexible cables and cords shall be 1 mm’,
4.23 Current rating, size and Voltage drop
All cables shall be adequately sized to carry continuously the normal current of the
individual circuits based on various laying conditions, as applicable, and the maximum
ambient temperature
Typical selection of the cables, recommended as a minimum, for general purpose
applications, in the Emirate of Dubai, is given in Appendix - 8, Tables 1,2 &3,
-12-425
4.26
427
43
434
432
Zhe maximum voltage drop from the point of supply to any Pointequipment, appliances
ani Bbparatus connected inthe wiring installation shall nat exceed #4 of nominal
voltage of the electric supply, unless otherwise specified
Colour Identification
Wiring Installations Exposed to High Temperatures
Ruy part of the wiring installations such as the individual circuit cables, final
Sonnections to equipment, appliances and light fitings shall be suitably rated for their
meet Performance at temperatures likely to be encountered, by Providing heat
‘esistant sleeves/beeds for individual cores andior heat resistant cabley,
Wiring Installations in Hazardous areas
All ight fitings & wiring accessories and other electrical equipment for use in potentially
hazardous atmospheres shall be selected as per ie quicblines specified in BS 5345,
Load Balancing
WIRING ACCESSORIES AND FITTINGS
Conduits and Fittings
ENC conduits and fittings used in building installation shall be from high impact rigig
ENC complying with BS 4607, BS 6053 & BS 6099 Pan 2 section o 2, suitable tor use
Trunking
\inere applicable, surface and undertioor (duct) trunking and their fitings shall comply
un BS 4678. Trunking and titings shall be constructed of steel, her dip galvanized,
path side and outside or non-combustibie insulating material with removable covers.
[sialation of the trunking shall be carried out strictly as er the manufacturers’
elines.
=13-44
444
442
45
45.1
452
CABLE TRAYS & SUPPORTS
Steel cable trays, accessories and supports shall normally be hot dip galvanized or
PVC coated and shall be either of the perforated type or ladder.
The cable trays shall have adequate strength and rigidity to support the cables
installed. The trays shall be provided with upstands on both sides
All Fittings, Bends, Tees, Elbows, Couplers, ete. shall be of substantial sections and of
the same quality as the trays. Cables shall be fastened securely by puropse made
Clips, cleats or saddles.
LOW VOLTAGE SWITCHGEAR AND CONTROL GEAR ASSEMBLIES
Main & Sub-Main Distribution Boards
The Main & Sub-Main Distribution Board/s (MDB/s & SMDB/S) which are installed
within the consumer installations shall be factory built assembly complying with relevant
BS EN 60439,
‘The assemblies shall be constructed only of materials capable of withstanding the
mechanical, electrical and thermal stress as well as the effects of humidity which are
likely to be encountered in normal service.
Apparatus forming part of the assembly shall have clearances, creepage distances and
isolating distances complying with BS EN 60439-1, maintained during the normal and
relevant service conditions.
The phase busbar, neutral bar and earth bar colour identified as given in Appendix 9
The neutral bar shall be of the same cross section as the phase bus bar.
The Circuit Breakers, Bus Bars, etc. Provided in the MDBs and SMDBs shall be
designed and rated to suit individual applications at the site conditions. The details and
Parameters of the individual equipment & components in MDBs/SMDBs, in generat,
may be appropriately selected and specified as per the typical guidelines given in
Appendix 10.
In general a Voltmeter (with R-Y-B OFF" selector switch), Ammeter (with CTs as
applicable), Max. Demand indicatorlrecorder, P.F. meter, indicating lamps and
seore, ued Protective devices shall be provided in all MDBIs of 200 Amps rating and
above. Provision of these in SMDBIs is not precluded
The switchgear, equipment and accessories shall generally comply with the standards
specified in Appendix 1
Final Distribution Boards
The Distruibution Board/s (DB/s) installed for connection of the final Cicuts within the
electrical installations shall be factory built complying with BS EN 60439. An
integral isolator shall be provided for isolation ofthe incoming supply.
14.46
46.1
46.2
463
The circuit breaker accessories, etc, shall generally comply with the standards
Specified in Appendix-1
Rewirable type fuses shall not be permitted in any type of wiring installation,
Zhe detaits of parameters of the individual equipment & components and the DBs, in
General, may appropriately be selected and spectied as por the 'ypical guidelines given
in Appendix-11
APPARATUS & ACCESSORIES
Switches
The switches provided for local isolation of electric Supply to individual apparatus andy
OF circuits shall comply with BS 3676. The fating of the switches shall be selected
Switches installed for control of discharge lighting shall have a current rating not less
‘han twice the steady state continuous current of the crear
Plugs and Socket-Outlets
Plugs and socket-outlets used in domestic and commercial
snalations shall comply with 8S 1363. The socketoutlen shall be shuttered type,
double pole, 3 pin flat type with switch,
The industrial plugs and socket-outlets shall Comply with BS 4343 and shall be with
pigs stestaly builtin or attached to i, The rating and type of socket-outlets with
plugs Provided shall be selected to suit individuc applications and shall not be
interchangeable for different current ratings,
Cooker Control Units
sail COoKer eontrol unit incorporating a general purpose socket outlet shall be
section ‘© SNOW Grouping of socketoutlet circuits in’ sepernie dome RCD/ELCB
section,
-15-46.4
465
466
467
468
Household and similar electrical appliances
The electrical appliances such as water heaters, cookers, hot plates, ete, which are
used in consumer installation shall generally comply with BS3456
Control of Water Heaters
Double pole switches (with neon indicator) of appropriate rating shall be provided for
Control of water heaters. The final connection to the heater shall be made from a flex
Outlet plate mounted adjacent to the heater. The control switch for water heater
Situatediinstalled in a bathroom or toilet shall be installed immediately outside the
bathroom Ait.
Water heater shall be connected to a separate final sub-circuit from the distribution
board. The heater shall incorporate an integral earthing terminal adjacent to the phase
and neutral terminals. All terminals shall be housed in suitable recess with a splash
Proot removable cover. Every heater circuit shall be protected by 30 mA RCCB/ELCB.
Control of Air Conditioning Univequipment
A 15 Amp switched socket outlet shall be provided for room air-conditioners to connect
Units only with cooling capacity upto to 18000 Btu/hour. Double pole switch, of
appropriate rating, with flex outlet mounted adjacent to the unit shall be provided for
Control of other room air-conditioning units,
Each room air-conditioning unit shall be connected to a separate final sub-circuit, from
the distribution board.
‘A maximum of two ait-conditioning units are permitted to connect on a single phase
supply. Where three or more units are installed they shall be balanced as nearly as
Possible over a three phase supply.
Extra Low Voltage Safety Apparatus
The extra low voltage safety apparatus such as electric buzzers & bells, mirrors lights &
Shaver socket outlets for installation in bathroom, light fittings tor underwater
installations, etc. shall incorporate appropriately rated double wound safety isolating
transformer either integrally built-in or mounted separately, with cartridge fuse or MCB
in the secondary circuit
The satety isolation transformer shall comply with BS 3535. Segregation of low voltage
and extra low voltage circuits shall be in accordance with Regulation 7.4.1
H.V. Discharge Lighting Equipment
Every High Voltage Discharge lighting equipment & installations shall be rated for
voltages not exceeding 5 kV, RMS to earth, measured on open circuit and shall comply
with BS 559.
H.V. discharge lighting equipment, including neon signs for advertising or any other
Purposes, shail not be installed whithout prior approval fram DEWA
-16-489 Safety and Emergency Light Fittings
Safety lighting to meet operational requirements shall be Provided to suit particular
gpplications such as industries, production ines, hospitals, uty Complexes, stadiums
shopping centres, auditoriums, etc
he source of supply for safety lighting shall be either maintained or ron-maintained
‘ype as appropriate to sult individual applications
All electrical switch-rooms and operational areas shall be Provided with adequate
number of emergency light fittings
The safety and emergency light fitings installed shall comply with BS 5266 and shall be
‘led for a period not less than 3 hours continuous operation,
46.10 Electric Motors and Starters
(A Electic motors shall be adequately protected against Overload, short circuit, earth
leakage and additionally, against loss of one or mors Phases, voltage fluctuations, etc.
a8 deemed essential to suit individual applications
Provided with current limiting starting equipment to effectively keep the starting current
within the following limits,
Type of Supply Rating of Motor Max. permissible
Starting current
Single Phase 1 HP - 5 HP 5 times full load current
Three Phase Less than 15 HP. 5 times full load current
15 HP 10 < 50 HP 2 times full load current
50 HP and above. 15 times full load current
Motors upto and including 11 KW (15 HP) may be connected for direct on-line starting
with over current protection,
17.4641
47
474
The starting equipment to limt the current may consist of any of the following type or
other approved by DEWA,
2) Star- Delta
») Primary - Resistance
©) Auto - Translormer
Ail motors shall be provided with an isolator, for isolating the motor from the supply
Guring periods of inspection or maintenance, Such means of isolation shall effectively
interrupt the suppiy on all phases. The isolator may be integral with the control gear or
Separate, but shall be in close proximity to the motor. An emergency stop push button
shall be incorporated in the control gear
When motor starting gear is energised trom an auxilary circut, the circutt shall also be
'solated during maintenance
Ail starters, isolators and push buttons shall be clearly marked in Arabic and English
Stating which machine they control and their function. To avoid confusion the words
‘START and ‘STOP’ instead of ‘OPEN’ and ‘CLOSED’ shall be used.
Motors and their control gear shall be located in well ventilated situations with adequate
Space for operation, inspection and maintenance.
Stand-by Generators
Installation and connection of standby generators in the consumer's installation, for the
Purpose of maintaining power supply under mains tailure conditions, shall be permitted
only with prior approval from DEWA.
The change-over circuit breaker or isolator shall have 4 - Poles for 3 - Phase supply
and 2 - Poles for 1 - Phase supply to ensure that the phases and neutral of the two
systems remain separate and distinct. The installation shall ensure that there will be no
Possibility to parallel generator supply with DEWA supply under any circumstances or
Conditions. Adequate mechanical and electrical interlock between the incomer circuit
breakers or isolators of both generator and DEWA supplies shall be provided,
The full details of the equipment, circuit and wiring diagrams, details of essential loads,
etc, shall be submitted to DEWA for approval before commencement of the work
ASSESSMENT OF CONNECTED LOAD AND MAXIMUM DEMAND
Lighting and small power circuits
All lighting and fan circutts shall generally be installed with maximum load per circuit
within 600 W & circuit breaker rating 6 A (1.5 mm? circuit conductors), or 1200 W & cir-
Cult breaker rating 10 A (2.5 mm? /1.5 mm circuit conductors). A minimum of 100 W
Shall be considered for each normal lighting and fan points, Fluorescent lamp may be
assessed as 1.8 x lamp W
Wherever fitings with discharge light, compact fluorescent lamps or low volt lamps are
installed, the circuit breaker rating, cicut conductor sizes and number of fittings may
02 suitably selected based on the actual load, including losses. for specific application
Prior approval from DEWA shall be obtained for every installation.
18+472
Need separate circuits.
A Current demand of 15 A shall be assumed for each 15 A switched socket-outlet
perul. However, for general purpose utity socket-outlety ap assumed load of 1000 W
eereaeketoullet installed in commercial and industrial prerciace and 500 W per socket.
Outlet in residential premises may be permitted
For stationary appliance and equipment including air-conditioners, the actual load of
ach appliance and equipment shall be considered ae connected load
rating not greater than § VA may be neglected
For multi consumer installation which includes commercial type of premises such as
Shops, Showrooms, Garages, Workshops, ete where provision for connection of
additional load may be required, the assumed connectes load of each spare/space/
Spprovah 8180 be indicated in the load distnbution schedules submitted for DEWA's
approval
Maximum Demand
The demand load of each final sub-circuit is Getermined by adding the actual or
assumed load of individual soma apoliancelequipment, whichever is higher Ag
allowance for diversity may be permitted where appropriate.
{The delails of load distribution schedules shall be Submitted for DEWA's approval in the
format given in Appendix 2,3 & 4. The total Connected load of individual distribution lev.
elsicircuits shall be determined as recommended in Regulation 4.7.1. an
SPeropriate diversity factor, worked out by Suitably qualified electrical engineer, shail
pe Permitted to determine the maximum demana op the main or sub-main distribution
Zhe limit of ‘Maximum Demand’ in kW, permitted at Main Distribution Board (MDB) con.
"ected to DEWA's supply feedertranstormer is noted bole for guidance.
a) 400 A Feeder . 200 kW
b) 1500 kVA Transformer 3 1200 kW
°) 1000 kVA Transformer F 800 kW
9) 500 kVA Transformer 7 400 kWThe overload protective device/incomer circuit breaker in the MDB shall be suitably set
at the corresponding design current,
Since maximum demand can vary on each type of project such as residential,
commercial, industrial, etc. other method, used by an installation designer with suitable
Gegree of knowledge and experience of the diversity applicable to 2 particular
installation, is permitted. However, the design method and the proposed diversity shall
be clearly indicated in the design drawings and load schedules submitted for DEWA's
approval
=20-54
Sat
52
5.24
5.22
523
5.2.4
53
5.3.1
SECTION -5
EARTHING AND EARTH LEAKAGE PROTECTION
CONSUMER'S EARTHING SYSTEM
Every consumer installation shall be provided with ‘Separate earthing system, installed
and maintained by the consumer,
oF nected between the ‘Earth electiode/s' and the consumer's man earthing terminals,
Soar Earth continuity conductors (ECCS) of every Outgoing circuit from the main,
Sub-main & final distribution boards, equipotential bonding of all metal work & exposed
Conductive parts and enclosures, ete
In general, minimum one Main Earth electrode shall be Provided for each incoming
pramisng UPPIvconsumers Main Distribution Board (MOB) man the consumer's
premises,
The ‘Earth electrode’ shall normally comprise of 2omm / 16mm diameter copper/stee!
Fray Conced earth rod set with driving pin and head driven ta a minimum depth of 3
shal
metres. The earth electrode shall be installed insise 300mm x 300mm x 300mm
enh pit with inspection cover. The connection to the earth electrode, within the
‘Supply/MDB.
[The resistance from any point of the Earth Continuity Conductor to the Main Earth
Electrode shall not exceed 0.5 ohm.
The consumer's earth electrode resistance and Continuity of ECs shall be periodically
checked and maintained as above, to ensure coneume, safety.
EARTH CONTINUITY CONDUCTOR (Ecc)
Every circuit in the Main, Sub-Main and final distribution boards shall be provided with
Soeteaiate. green and yellow (G/Y), PVC insulated copper Loe: The minimum cross.
Sectional area of ECs shall be selected as specified Appendix-12,
-21-533
5.43
55
55.1
552
553
The ECCs shall be terminated at electrical equipment, apparatus and distribution
Switchgear, light ftings, mounting boxes of switches & sockel-oullets, etc, with tinned
Copper lugs, as applicable, at both ends on purpose made earth terminals.
All bus bar risers insialled for electrical distribution in high rise buildings and other
Consumer installations shall incorporate an adequately sized ‘ECC’ either integrally
within oF run separately along the riser.
EARTH LEAKAGE PROTECTION
The earth leakage protection shall be suitably designed and incorporated in each and
every consumer installation
The Earth Leakage Circut Breakers (ELCBs\/Residual Current Circuit Breakers
(RCCBs) shail generally comply with BS 4283. Recommended value of operating cur.
rent of ELCBSIRCCBs are specified in Appendix-13,
Operation of the ELCBS/RCCBs, earth leakage detection system, elc. shall be
Periodically checked and tested to ensure consumer safely,
EQUIPOTENTIAL BONDING
All metal work of the consumer's installation, other than current carrying parts, including
Cable armour, metal conduits. metal cable tray & trunking sections, metal accessory
Boxes, exposed metal works of consumer's appliance, apparatus, equipment,
Machines, building structures and the like with metallic enclosure and parts, metal
water pipes, etc, shall be provided with equipotential bonding conductors,
The cross-sectional area of equipotential bonding conductors shall be selected as
specified in Appendix-12.
The equipotential bonding conductors shall be connected to the main earthing terminal
within the consumer's wiring installations and the continuity shall be tested and
maintained by the consumer.
-22-61
614
6.12
613
6.14
6.15
6.1.10
6441
6.112
SECTION -6
INSTALLATION OF CONDUITS, TRUNKING, TRAYS & ACCESSORIES
TRUNKING AND CONDUITS
The type and material ol the trunking and conduits shall be selected ‘appropriately to
satindividual site locations and complying with Regulations specitied i Clause 4.3 of
Section 4
‘The trunking and conduit wiring installations shall be carried out in a neat, orderly
Workmanlike manner with purpose - made accessories such as inspection bendsitees,
terminal/draw - in boxes, etc,
Trunking and wing conduit installations which are surtace exposed shall, as far as
Possible, Nave straight runs with branches at right angle only
Crawin boxes shall be provided in all straight conduit runs exceeding 15 metres,
Conduit runs having ‘90° bends’ shall be Provided with draw-in boxes for every 2
bends.
Trunking and conduit shall be completely installed betore any cable is drawn in,
prawewires shall be provided in all concealed conduits (and ducts) with the ends tett
‘ree at the outlet boxes for pulling the wiring cables
All he terminal and intermediate ends of the PVC conduits shall be firmly secured with
Sutable adhesives as recommended by the manulacturer
+236.1.13
6.1.44
6.1.15
61.16
6.1.17
6.118
61.19
6.1.20
6.1.21
6.1.22
6.1.23
6.1.24
62
624
622
The circuit wires, bunched and installed in al vertical trunking runs shall be clamped’
feeied within the trunking at regular intervals, not exceeding 2 metres and at the
terminal ends
Zhe standard conduit boxes, draw-in boxes and mounting boxes of light fitings and
Sppiliances shall be fixed to the building structure independently of the wiring conaute
All exposed threads, tool-marks or visible damage to the protective finish of the steel
‘ranking and conduits shall be coated with Zine rich paint immediately after inctaletin,
Suitable expansion couplers shall be provided in all trunking and conduit runs at the
mete ae daints in the building structure and at regular intervals in all runs exceeding 7
metres in length or as recommended by the manufacturer
Suitable purpose-made boxes with adapters, celing roses etc. shall be provided at all
individual outlet points of the wiring installations,
[iGht tings used with tungsten filament and halogen lamp shall be suitably
See dated and supported trom the PVC conduit and terminal outlet boxes to provera
deterioration due to associated high temperature rise.
The conduit runs which are concealed within the building structure such as in floor,
wall, roof, column etc. shall be Provided with a minimum screed cover of 10 mm.
When the trunking and conduit runs are installed with chases in the building structure
they shall be firmly fixed at regular intervals with purpose-made rimpets and/or
saddles,
The standard conduit boxes, draw-in boxes, floor-outlet boxes ele. shall be installed
with tS coverfi flush with the outer finish of the building structure
Only flush type switches, socket outlets and accessories shall be used for concealed
wiring
In Surface mounted industrial installations and where situations subject to fire risk, only
galvanised steel conduits shall be used. PVC conduits shall nol be used for such
applications,
Galvanised steel conduits shall not be used under floor tiles of buildings in concealed
Sang systems embedded in walls or floors. PVC conduits shall be used for all euch
applications.
CABLE TRAYS
Trays for supporting cables are recommended for use in warehouses, industrial plant
and equipment room, cable trenches, shatts in buildings, ste
The type and material of the cable trays shall be selected appropriately to suit
seyiGual site locations, and complying with Regulations specilied in clause 4.4 at
Section4
24623
62.4
625
6.26
6.27
{The cable trays shall be supported at regular intervals with Purpose made supports ang
the number of cables installed in the trays shall Suitably be selected as recommended
in Appendix-14 & 15.
and as recommended by the manufacturers
cables amended in Appendix-14. Cable ties shall not be used 10 Support multicore
Cables installed on cable trays fitted verically
Cable trays shall not be used in locations where they will be subjected to severe
Physical damage.
Sullicient space shall be provided and maintained around cable tray t0 permit
adequate access for installing and maintaining the enbies
-25-SECTION -7
INSTALLATION OF CABLES, EQUIPMENT, ACCESSORIES AND WIRING SYSTEMS
7a
TAA
7.42
713
TAs
741.9
7.4.40
TAA
7.22
7.23
ARMOURED CABLES
qeeiUreG cables may be installed either directly buried in ground, drawn through
ducts, laid in concrete trenches - cleated to walll, or mounted on cable trays.
The current carting capacity of the cables shall be determined only alter applying
Suitable correction factors based on the installation method of the cables
Only armoured cables shall be used for underground installations
phe, armoured cables, for underground instalation shall normally be laid at 90 om
Below the ground level and provided with a layer of at least 15 cm impervioge cov
tne Ae Where protective covers are required, they shall be carefully centered over
{Pe cables, throughout their length. The covers shall be of adequate width protect
{he cables, with a minimum overlap on each side of 50 mm Coloured PYG warning
‘apes shal be laid after filing, above the cable, upto 30 em below ine ground leva
The routes of all cables shall be clearly marked by cable route markers, at regular
oats Ts bot exceeding 10 metres along straight runs and 2 metres at deviations is the
Toute, The route markers shall normally incicate the voltage level in Arabic and English
Gables may be installed on cable trays at specific locations and as recommended in
Clause 6,2 of the Regulations.
{Minimum internal raclus of bend for cable in fixed wiring installation shall not be less
than 8 times the overall diameter of the cable.
No joints shall be permitted on any cable runs in Consumer's fixed wiring installation,
Where cables or wiring system passes through floor, wall, partitions or ceiling, the
ores as femaining alter passage of the wiring systems shail be Sealed to the degios
of fire resistance required.
Cable glands used for armoured cables shall be of brass compression type, ‘complying
with BS 6121, with earth tag and PVC shroud,
All terminations of cable conductors shall be mechanically and electrically sound.
egy, termination shall be made by means of a terminal or Compression type cage)
109, to the approval of DEWA, and shall not impose any mechanical siren worse
terminal or sockevlug.
Separate Earth Continuity Conductors (ECCs) shall be installed and terminated for
each feeder/ctcuit, as specified in Section-§ of the Regulations.
DISTRIBUTION BOARDS
{hi distribution boards either main, sub-main or final DBs shall be installed in locations
Bahich access is available at all imes for operation, testing, inspection, mainrernons
and repair,
{Main sub-main or final Distribution Boards shall not be installed within bathrooms,
let. damp or wet locations, bedrooms, kitchen, above sinks, store rome: high
ambient rooms, dangerous or hazardous locations or below any staircase,
themain, sub-main and ina distribution boards shall be selected and designed based on
UNe guidelines spectied in clause 3.2 (section-3) and 4 $ (Section) of the Regulatencs
= 26-7.25
7.26
727
7.28
7.2.9
73
7.3.4
7.3.2
733
7.3.4
7.35
7.36
7.37
7.4
7.4.4
Fach distribution board shall incorporate ater sof isolation of mains supply in the
Every circuit breaker of fuse within the rsiribution board shall be identitied and
labelled to indicate the apparatus of cient i Controls.
Fach fina distribution board shall only pt ihe citults in the same floor area, where
ihe distribution board is located, except fe mpecite applications such as ‘staircase
Common corridor-ighting’ in high rise Duildings, etc. Prior approval shat te obtained
from DEWA for every application, ae Speciied in clause 1.7 (Section 1) ca the
Regulations,
[multi Consumer installation, such ag stag Gal OF residential buildings, the
consumer's distribution boards shall be ‘nstalled within the respective consumnere
Premises (e.9. Shops, Flals, etc)
Incoming supply cable instalied to any ¢istribution board shail be totally Segregated
and identilied from the outgoing cisect cables/wiring,
All Distribution Boards shall be installed flush or surface mounted at a height not
Exceeding 2 metres to the top of the distnbuticn Board from the finished floor lever
BUSBAR TRUNKING SYSTEMS (Busways)
usways shall be permitted for installation oe there adequate access is available for
inspection and repair throughout their ening length,
Each busbar riser, proposed for installation (9 high rise buildings, is recommended to
SUPPIY @ maximum of 6 floors only.
The requirement of earth Sol nulty Conductor (ECC) and equipotental bonding shail
be as specitied in Section-5 of the Regulations.
Wherever the busway passes ough the wall or floor, it shall be Provided with fire
WIRING SYSTEMS AND ACCESSORIES
Segregation of circuits, phases and wiring systems
F copand #Cc88scries shall be selected and instalied to suit individual locations
All
faneyeoTPING with relevant Regulates Specified in Section-4, in addition to tne
following requirements
The circuit wires of diferent sot28° grades shall be segregated with barriers in
‘runking runs or installed in separate conduits
-27-7.4.2
7.43
Ihe Circuit wires of individual categories such as lighting, power, emergency, etc. shall
be segregated with barriers in trunking runs or installed in separate conduite
Winere a residential premises is supplied with a three phase supply, as far as possible,
ine light fitings, socket outlets, water heaters, cookers and other single phese
WeRtatus installed within any room shall not be connected to more than one phase
Wiherever more than one phase cannot be aveided, a minimum distance of 2.0 mets
Shall be maintained between any outlet, accessory or appliance connected to
diferent phases of the supply.
Where switch box contains more than one phase, for group switching, approved
Switch boxes with phase barriers shall be used and labelled 0 indicate that 380 Volts
©xist at the box. All circuit wires shall be colour identified as specified in Regulation
42.4,
Where a wiring system is located in close proximity to non-electrical service, the wiring
realem shall be adequately segregated and protected against hazards likely to arise
trom the presence of the other service in normal use. Provision shall be mad for eata
and adequate access to all parts of the wiring system which may require inspection,
‘maintenance or replacement
[No switches controling light fitting or water heater, etc, shall be installed in bathroom,
In Kitchen and in situations where water is regularly used, no switch shall be mounted
eithin 2 metres of any water tap, wash basin or sink. Wf this is Not possible. celing
Mounted insulated cord operated switches shall be used.
No socket-outlet shall be mounted within 2 metres of any water lap, wash basin or sink
ina kitchen
Mounting heights of accessories
All lighting switches, D.P. switches of Air Conditioning units & Water heaters, Ceiling
Fan Regulators, Shaver Socket outlets, etc. generally used in the electrical installation
shall be mounted at 125 cm from the finished floor level
All switches shall be mounted in readily accessible positions.
13 A switched socket outlets used for general purpose shall be installed at 45 ¢m
above the finished floor level. 13A switched socket outlet provided in the kitchen ¢hall
be generally at a height of 25 cm from the work top.
All accessories shall be sullably selected and installed as recommended in Section-&
of the Regulations.
Identification labels and notices
In General all sections of the consumer installation, circuits, protection devices in the
Gsiibution boards ete shall be provided with sultabie identilcation labels to clearly
{Ndicate the location and purpose of each item or circuit, Instructions or Caution notices
{or correct operation shall also be provided wherever there is a possibility of confusion.
All labels must be in both English and Arabic and of letter sizes to suit individual
application
28 -SECTION - 8
POWER FACTOR CORRECTION CAPACITORS AND UNDER VOLTAGE RELAYS
ar
a1
812
8.1.4
ans
POWER FACTOR (PF) CORRECTION ;
png Power factor of every consumer instalation Shall be within the range of 0.9
lagging and unity
Spectied in clause 1.2 8 1.3 (Section-1) and selection details recommended. in
Section 4 of the Regulations
[The current carrying capacity of the Tor gUatOrs Used in capacitor circuit shal! not be
[ess than 1.5 times of the rated currerg Of the capacitor,
The current carrying capacity of ep euStors that connect a capacitor to the terminals of
canto! OF to motor circuit conductors era ol Be less than one third of the curresr
PatTying capacity of the motor circuit Conductors and in no case less than 1.5 times the
rated current of the capacitor.
+29.8.1.10
8141
8.1.12
8113
61.14
82
824
82.2
8.23
824
The contactors used in the capacitor bank shall be able to withstand switching surges.
Means shall be installed to isolate each capacitor, capacitor bank, or capacitor
installation from all sources of voltage and to remove from service as unt.
All non-current carrying metal parts of capacitors shall be earthed as specitied in
Clause 5.5, Section 5.
Each capacitor shall be provided with a nameplate indicating rated voltage, frequency,
ivan, number of phases, details of liquid filed (it any), discharge device and none of
the manufacturer.
The controls and protection device provided in the capacitor bank shall be checked
and maintained regularly
Wherever capacitor bank/panel is installed on the supply side of any DEWA’s kWh
Tr aeind: adequate sealing provision shall be made as specified in Regulation 2.5.11
of Section 3.
UNDER VOLTAGE (U.V,) RELAYS WITH AUTO-RESET TIMER
Ay aitconcitioners or airconditioning units/plants/equipment installed within the
COReUmer's installation shail be provided with Under Voltage (U.V.) relays with fixed
Yollage cut offsetting at 75% of the nominal supply voliage, within 0.1 seconde, eg
auto-reset timer with adjustable time setting between § and 10 minutes,
‘The auto-reset timer of the ULV. relays shall be set at values specified in the schedules,
Dene! EWA to suit individual installation. Necessary provision for sealing may
be incorporated inthe relay to restrict access for adjustments of the setting,
The U.V. relays with auto-reset timer shall normally be incorporated within the
fespective air-conditioning unitequipment or in their control Panels. For small
Gstribution board shall be permitted for.individual or group of units. Prior approval
shall be obtained trom DEWA on every such application
The U.V. relays with associated controls shall be checked and maintained regularly.
-30-ot
O44
913
9.1.4
92
9.24
9.22
92.3
9.2.4
92.5
93
934
9.3.2
9.33
SECTION -9
CONSTRUCTION SITE INSTALLATIONS
General
Application for temporary power supply shall be submitted to DEWA at least one
month in advance of the power requirement
Temporary power supply shall be permitted for construction Purposes subject to terms,
conaitions fees, tants and instructions issued by DEW toh time to time,
The consumer shall comply with the Safely requirements specitied for permanent
instalation, in addition to the specific requirements nc installation at construction sites
recommended in this section ofthe Regulations,
Every assembly for the distribution of Electricity on construction sites shall comply with
the requirements of BS 4363 and BS EN sodag-g
WIRING SYSTEMS AND DISTRIBUTION BOARDS
No cable shall run across a site road or a walkway unless adequate protection of the
cable against mechanical damage is provided
The metering cabinet, distribution board/s or any wiring installations, installed outdoor,
shall be of weather proot type,
EARTH LEAKAGE PROTECTION
Iroatilion to the over current and short circuit Protection, every circuit shall be
Protected for earth leakage.
Consumer shall check and test the earthing systems, operation of ELCBS/RCCBs,
wiring installation, etc, regularly to ensure Safety of the installation,
-31-32-Appendix
10.
"
12.
13,
14.
15.
16,
(A)
(Cc)
(0)
APPENDICES
Reference Standards
Details of Connected Load/Max. Demand (format)
Load Distribution Schedule - 3 phase (format)
Load Distribution Schedule - 1 Phase (format)
Electrical Symbols
Contractor's Inspection Certificate (format)
Typical arrangement of Metering Cabinet
on Compound Wall
Typical arrangement of kWh meters in
Electrical Service Room
Typical Electrical Services Room with 1 No. MDB
Typical Electrical Services Room with 1 No.
cubicle type L.V. switchboard/panel
Selection of Cables
Table-1:- Single Core PVC Insulated non-armoured,
Stranded Copper Conductors.
Table-2:- Multi Core armoured PVC insulated,
Copper Conductors.
Table-3:- Multi Core armoured XLPE insulated,
Copper Conductors.
Colour Identification of unarmoured, armoured and
flexible cable cores and bare conductors.
Specifications of MDBs/SMDBs (format)
Specitications of DBs (format)
Earth Continuity Conductors (ECCs) and Equipotential
Bonding Conductors.
Earth Leakage Protection.
Spacing of Supports for Trunking, Conduits and Cables.
Number of Cables that may be installed in Trunking,
Conduits and Trays.
Data Schedule for LV Electricity Meters and Current
Transformers
-33-
Page
34
35
36
37
38-40
41-42
43
44
45
46
47
48
49
50
51-53
54-56
5s7
58
59
60
61APPENDIX «1
REFERENCE STANDARDS
ei eaUlpMeNt. apparatus, materials and accessories complying wih relevant recommendations in
following standards/documents shall be deemed to satisfy
otherwise specified (Clause 1.6. Section 1).
Subject
Cable
PVC insulation (for power & lighting)
C insulation (tor switchgear & control
wiring)
2 Thermo-setting insulation
+ Mineral insulation
Flexible cables & cords
Cable glands
Conduits and Conduit fittings
Steel
> PVC
+ Flexible Steet
Degrees of Protection
Distribution assemblies for construction site
Earthing
Electrical Accessories
> General
Ceiling rose
+ Cooker control units
> Plugs & Socket-outlets
+ Switches
Emergency Lighting
Hazardous areas
Household appliances
Isolating Transtormer
Low Voltage Switchgear and Control gear
assemblies
General
MCB & MCce
> RCCBELCB
Fuses
Busbar trunking system
~ Neon Signs
Non combustibility test
Trunking, Ducting and Fittings
Thermal classificat
Bs British Standard
lec Intemational Electrotechnical Commission
the requirements of these Regu
BS 6004, BS 6346,
8S 6231
BS 5467, BS 6234, BS 7211
BS 6207, BS 6081
BS 6500, BS 6141, BS 6004
8S 6977
BS 6121
BS 4568, BS 6053, BS 6099
BS 31
BS 4607, BS 6053, BS 6099
BS 731
BS EN 60529,
8S 4363
BS 7430, BS 951
Bs 5733
BS 67
BS 4177
BS 846, BS 196, BS 1363, BS
4343
BS 3676, BS EN 60947.3
BS 5266
BS 5345, BS 5501
BS 3456, BS EN 60335
Bs 3535
BS EN 60439, 8S EN 60947,
BS EN 60947-1
8S EN 60898, BS 3871
BS 4293
BS 88, BS 1361
BS EN 60439-2
BS 559
BS 476
es 4678
lations, unite:
502
227
702
227, 245,
423, 614
423,
529
364-7-704
364-5-54
947
439-183
898
755
439-2
1084
a(eseug 6) (oseud 1)
vy 1 19 AH poy ’ 4OAT() vosi-szt le) Yoor one) yogoidn (1) 4) 01094 0 oh
xvd va HoLovHANOD
a (ua ©) v0 a3193NNOO W1OL AuISuaAIO ay mo (Hd 8) aNWHaG xe
aan
01. 03103NNO9 sans.
even
180 411 viNaId | 01 03193NNOO Ba
|
L E
ONIODINO
“ tend sho [id ana Bhs] Sse ihe uBNOONI
® oe le Pe re a | aor] ong aon | 22”
owuvnay {ata [dee [vdeo | ndes fname | ada | eet Ome | “xe | ms |. aoni a | 2489,
fas
iinws iNDuIO
40 on SEEM sous | avo7 31D3NN00 azosavo | Bey Sunv ONY
= 95 -ee aT ap vic
f * [a
73
7
rm
: +
(eseud -¢)
31NG3HIS NOILNEIYLSIC GVO t yo us) ON aa
© aNaav
(1 uonsag ‘21 asneio)
= 38Ban NaS = 5, 8 ON mop = a KG
ue = a
(eo 81ea =
‘993 "9nd 9 sr
‘DEX + ORM NO -M
xe 3218 30
op Jane =O HS HE RE = VG BaD = WH9 293 ond 19 gh 4 + OnaHNSATACORA MO gm owe ga av
hvion
-
os
ole
|e
so [9
= [3
we
woe
z[2
of
sowwnay ee Laon _L_ Etonl 8 | [5 foes] om Juma} Pi] Ss FSIS TOI od ame | ow [oT ay 013 | ssnoow
aetna | SiNodSa¥01 a3103NN0O [Moet] Bae | ae | aan [| 7S | vou | onttve
pannren auNSOTONS U3LIN/ BOWS /aaw woud 034
S1Nd3H9S NOLLNEIULSIG GvOT on aa
NOLO
PONIaTING / WTA “LoarOHdAPPENDIX - 5
ELECTRICAL SYMBOLS
“DESCRIPTION ©
Main Distribution Board (MOB)
‘Sub Main Distribution Board (SMDB)
Distribution Board (DB)
Air Circuit Breaker (ACB)
Moulded Case Circuit Breaker (MCCB)
Miniature Circuit Breaker (MCB)
Earth Leakage Circuit Breaker (ELCB)
Fuse
Link
kWh Meter (Direct reading type)
kWh Meter (CT operated type)
‘Switch Line (to connect up all outlets controlled by one si
itch)
Circuit Line (to connect up all outlets on the same circuit)
— —-— Skirting Trunking
Undertloor Trunking
13 A Switched socket outlet
20 A double pole switch with neon indicator
30 A double pole switch
a 15 A Switched socket outlet
By
a |
38«
Shaver Socket outlet to BS 3052
Combined mirror light with integral Shaver Socket outlet to
BS 3052
45 A Cooker control unit
Tungsten light fiting-ceiling mounted.
(fiting reference letter shall be shown in citcle and detailed in legend, to
sive load rating of light fiting and number of lamps).
Tungsten light fiting-wall mounted.
(fiting reference letter shall be shown in circle detailed in legend, to give
load rating of light fitting and number of lamps).
Fluorescent tube light fitting-ceiling mounted.
(fiting reference letter shall be shown in circle and detailed in legend, to
sive length of fitting and load rating plus the number of fluorescent tubes),
Fluorescent tube light ftting-wall mounted,
(fitting reference letter shall be shown in circle and detailed in legend, to
ive length of fitting and load rating plus the number of fluorescent tubes),
Lighting Switch - 1 WAY
Lighting Switch - 2 WAY
Lighting Switch - Intermediate way
Lighting Switch - Pull cord operated
Lighting Switch - Key operated
-39-" DESCRIPTION
ra Lighting switch - Weather proof type
e Clock outlet point
wa Exhaust Fan
Ceiling Fan Regulator
Low level cooker outlet connection unit
Earth Connection
e Time Switch
3 Photo Electric Cell
@ Bell Push
Bell (not associated with Fire Alarms)
+40APPENDIX - 6 (Clause 1.11 Section 1)
CONTRACTOR'S INSPECTION CERTIFICATE
1/ We certify that the Electrical Installation at
Project : Villa / Building /....
Consumer :
Application No. AIC No. :
Account No. / S. :
Drawing Approval Reference : HCS/ 19 Date
Connected Load kw. Max. Demand : kW
has been completed, inspected and tested in accordance with the DEWA / IEE Wiring Regulations
(latest edition) and that the results are as indicated below
ITEMS INSPECTED OR TESTED :
1. Type of L. V. distribution system : 1 Phase and / or
3- Phase
2.1. Over current protection is provided by :
+ Main circuits in MDB/s MCCB / Fuse /
~ Sub - circuits in SMDB / 5 MCCB / Fuse / MCB
-Final circuits in DB/s MCB /Fuse
2.2 Earth leakage protection is provided by
= BOF en «MA ELCB for 13 A socket-outlet &
Water heater / oo circuits Yes/No
= 30/100/ mA ELCB for Lighting’
ee : circuits : Yes/No
= 100/300/ MA ELCB / for AC
Equipment / Pumps / Machines 1... a : Yes/No
2.3. Earth leakage detection is provided by
30/100 mA ELS/ELR with Audio / Visual alarm for Essential
service equipment / : : Yes / No
3. Continuity of each earth continuity conductor is satisfactory. Yes/No
4, Insulation resistance of the fixed wiring installation with S00V
meggar in mega-ohms.
Continuity of ring circuit conductors is satistactory.
6. Polarity throughout the installation is correct and all single
pole devices for protection and switching are in the phase
Conductor only.
yes /No
Power Factor (P. F.) Correction Capacitors / Panel / s
installed, Yes/No
Min, Power factor of the wiring installation 7
Earth fault loop impedance is satisfactory Yes/No
Main earth electrode resistance in ohms
-41-Under Voltage relays with auto-reset timer for Air Conditioners/
Units fitted Yes/No
+ Auto-reset timer set at:
10. The operation of current operated earth leakage circuit breaker(s)
is checked and effective Yes/No
11. Barriers and enclosures for protection against electric shock in
Normal service are satistactory. Yes/No
12. lll flexible cords, switches, fuses, plugs and socket outlets are
in good serviceable condition except as noted below, (specify
under para 17) Yes/No
13. There is no sign of overloading of conductors or accessories
except as stated below, (specify under para 17 ). Yes/No
14. Apparatus tested [ includes/ [] does not include portable appliances.
15. We also confirm that the Main Distribution Board/s (MOBs) as noted below are fit to be energised
(LV MOBs connected directly to the Transtormer).
MoB (sis ): Yes/No Mos. (sis
Mos MOB... (sis.
(sis
16. _ In pursuance of this certification we undertake to carry out necessary tests in the wiring
installations carried out by us, after the electric supply is released, and rectify any defects if
found and/or when reported by the Owner/DEWA.
17. Comments and deviations, if any, from the wiring Regulations
Electrical wiring installations supervised and tested by
(Signature)
Name : Position
‘Company
P.O. Box Tel Fax
DEWA Wireman Competency Licence No.
[
{
Authorised Signature i
[
‘ {
(
Stamp ;
[
(
-42-APPENDIX - 7
A-TYPICAL ARRANGEMENT OF METERING CABINET ON COMPOUND WALL
160 cm MAX.
80cm MIN.
i, MINIMUM DIMENSIONS:
kWh Metering Rating of incomer breaker Dimensions inom
Type Reference in metering cabinet Als fc |.
7 GOA, 60A (1 - PHASE) 40_[ 60 | 20 | 20
2 40K, 608, 100A 40_| 60 | 20 | 20
3 125A, 160A 60 | 60 | 20 | 25
4 200A, 300A, 400A 0_[ 100 [25 | 30
ii, DESCRIPTION
4: Compound wall. T= 15/10 cm PVC pipe sleeve for
2: Weather proof (IP 55) metering service cable.
Cabet 8 18/10 cm PVC sleeve for load
3: Transparent viewing window. cable,
4 Hinged door with provision for wire S Conduit’s for earthing conductors
sealing & pad locking (ECC).
5: Cable (Gland) box. NOTE : All dimensions noted are in
&:- Position of incomer breaker. centimetres and not to scale
rt
-43-B-TYPICAL ARRANGEMENT OF kWh METERS IN ELECTRIC SERVICES ROOM
FLOOR LEVEL .
ji, DESCRIPTION :-
1» Main / Sub-main Distribution Board,
2» PVC/GS trunking
3- Non-combustible type board / plate for fixing kWh meters
4 kWh Meter.
5: Supply Cables.
NOTES =
a) All dimensions noted are in centimetres and not to scale.
b) Layout indicates only the minimum space, maximum number of rows and arrangement,
etc. of kWh meters.
©) Earthing details, outgoing circuits & conduit terminations, etc. are not indicated.
0) Refer to clause 3.2, 3.3 & 6.5 for regulations.
44+C-TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO. MDB
(MAX. 400 AMPS RATING)
‘YPICAL ELECTRICAL SERVICE ROOM WITH 1 NO.
MAX. 400 AMPS RATING
| TTT |
l
| OF + fle
Lt
1: Main Distribution Board.
2: PVC /GS trunking,
3: Non-combustible type board / plate for fixing kWh meters,
4: kWh Meters,
5: Exhaust fan (for non-air conditioned room),
6 Cable draw - pit
7:- Non-maintained, minimum 3 Hrs. rated, self contained emergency light.
8:- Light fitting
9:- Non-combustible door (Louvered type for non-air conditioned room).
NOTES =~
2) All dimensions noted are in centimetres and not to scale.
b) Only minimum dimension permitted for electrical room is shown in the layout. Each
electrical room shall be designed to accommodate the MDBs / SMDBs, kWh me!
etc, Prior approval shall be obtained for construction,
©) Reterto clause 3.2, 3.3 & 4.5 for regulations,
45 -D-TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO.
CUBICLE TYPE L. V. SWITCHBOARD / PANEL
DESCRIPTION :-
LV Switchboard / Panel.
Exhaust fan (for non-air conditioned room).
Non-maintained, minimum 3 Hrs. rated, self contained emergency light.
Light fitting
Non-combustible door (Louvered type for non-air conditioned room).
NOTES :-
a) All dimensions noted are in centimetres and not to scale.
b) Only the minimum clearance / space required on front, rear and sides of LV panel is
shown in the layout. Each electrical room shall be designed with adequate dimensions
to accomodate the MDBs / SMDBs, kWh Meters etc. Prior approval shall be obtained
for construction.
) The minimum clear space shown at the sides and rear of the panel is for switchboards
with rear access requirements only.
@) Referto clause 3.2 & 4.5 for regulations.
-46APPENDIX - 8
SELECTION OF CABLES
Recommended size of cables for use in fixed wiring installation,
for general purposes, and in normal situations, in the Emirate of Dubai
TABLE -1
Single - Core PVC insulated, non-armoured, Stranded copper Conductors
(BS 6004 & BS 6346)
Size of cables, in ‘concealed’ conduits Max. rating of Max. Load
x1C, 1 Phase! 3/4 x1 C, 3 Phase McBmcce eurrentidemand
(mm?) } ce (mm (A) os (a)
18 18 10 10
25 25 18 18
4 4 20 20
6 6 25 2s
6 10 30 30
10 16 40 40
16 25 50 50
2s 2s 60 60
35 50 80 80 |
70 100 100
: 9s 125 128
120 150 150
nnotes for Tables 1,2&3
Assess initial demand with safe diversity and anticipated demand in future, if any, as applicable to
individual circuits, for selection of cable size, breakers rating, etc,
Assess individual fault levels and select MCBS/MCCBs accordingly.
Refer to manutacturers catalogues and select MCBs/MCCBs, cable sizes, etc. for specific applica-
tions, considering inductive/capacitive loads, laying conditions, voltage drop, correction factors, ete.
Refer to Section 4, tor Regulations,
4a7-TABLE -2
Multi Core armoured PVC insulated, copper Conductors
(BS 6346)
Cable installed in normal situations McB/MCCB currentidemand
(mm?) (a) cay Ue
15 10 10
25 15 15,
4 20 20
6 30 30
10 40 40
16 50 50
25 60 60
35 80 80
50 100 100
70 128 128
95 160 160
120 180 180
150 200 200
185 250 250
240 300 300
300 350 350
400 400 400
bo
-48TABLE -3
Multi Core armoured XLPE insulated, copper Conductors
(BS 5467)
10 Table 1 for general notes
-49-APPENDIX -9
COLOUR IDENTIFICATION OF
FLEXIBLE CABLE CORE!
UNARMOURED, ARMOURED AND
S AND BARE CONDUCTORS
(Regulations 4.2.4 & 4.5.1)
Non - flexible cables and bare conductors
“ Funetion
Earth Continuity Conductor (ECC)
Neutral Conductor in 1 and 3-phase circuits (N)
Phase conductor in 1-phase circuits
Phase conductor in 3-phase circuits
R-phase
Y - phase
B - phase
Colour Identification
Green - and - Yellow
Black
Red
or
Red (R) / Yellow (Y) / Blue (B) as applicable
Flexible cables and Cores :
Function
Colour of Core
Live
Neutral
Earth
Brown
Blue
Green - and - Yellow
-50-APPENDIX - 10
‘SPECIFICATIONS OF MDBs/SMDBs
(Refer to clause 4.5.1) MDB/SMDB No. :
REFERENCE STANDARDS 8S EN 60439
8S 88, BS EN 60430-1, IEC 439-1 43
Il. RATING OF INCOMING SUPPLY 2008 [| 300 [ ) 400A 1]
BREAKER/ISOLATOR* Boa} 16004 [ j
(*On-load) BREAKER, i) ISOLATOR i)
I, CONSTRUCTION
1 Mounting Wall =[} Floor [J -Pedestal [
)
2 Degree of protection of the enclosure for Indoor.tP41/42 ()
installation Outdoor-IPSai55 )
“ 0
3. Painting/Finish (InternalExtemal) Stove enamelled (1 Epoxy]
Polyester [ IGananized [|
i
4 Front Cover (Neoprene) Hinged [ ] Bolted [ JPanellock [J]
Gasketted” ul
5 kWh Meter reading provision Glass Window [|] Gasketted t)
6 Cable Tray Top [1] Bottom (1
Top& Bottom —[ ]
7 Ventitation Louvres tl 1
& Sealing/pad locking provision Compliance with Regulation 3.3.10 1
IV. INTERNAL LAYOUT/ARRANGEMENT &
FAULT RATING
1 Segregation of lve parts: Barer (Shroud 1
Firmly secured [ ]
Incoming supply terminalstugs * Separately mounted &
Removable by tool 01
Busbar, ap-otf connections & terminals Barrier (1
(" Separate and independent of each other) Firmly secured i
* Separately mounted &
Removable by toot 0)
‘Neutral & Earth Bus-bars & Terminals ‘Separately mounted with adequate working
clearances'spacing from incoming supply
terminalstugs 0
2 Arrangement of bus-bar and tap-off
connections to outgoing circuit breakers Rigid, firmly secured, supported, direct
and as short as possible i)
Adequately sized )
Min. No.of bolted joints ul
3 Rating/size of phase & neutral bus-bars & Rated for max. 70 °C internal ambient,
terminals (at max. 50 °C ambient) consistent with the rated incoming
‘supply breaker/isolator {]
Tinned electrolytic Copper {1
-51-+52
4 Rating of Main incomer and Busbars OEWA’s l
+ Min fault rating 40kA 1
5 Min. & Max. rating of outgoing circuit t
breakers
Min, faut rating 35kA i i
6 Provision of min, working clearance/space 2008 3004 4008
for:
Incoming supply cable terminations
200A Incomers cms 25 {1 35 1 45 i
800/1600A incomer ms 75 1
Outgoing circu cables Withiwithout cable box 1
Adequate i
7 Provision ot supporsitacilty for Channels (1 Trunking [
dressing/clamping outgoing circuit cables (
Max. Height 2.0 M (From FFL) (
8 Operational accessiconvenience for From Outside of Hinged Door!
switchgear Bolted Cover i
lacoming supply circuit breakerisolator Restricted/Lockable i
Outgoing circuit breaker
9 Maintenance accessireplacement convenience Breaker [] ots rt
for switchgear components kWh Meter [1 Gland plate i
10 Provision for termination of Non-Ferrous glands plate i
Cu/XLPE/AWA(S.C.)
V. IDENTIFICATION
1 Rating of Incoming supply & Outgoing Circuit : Thermal i
breakers:- Discrimination
(vis-a-vis the rating speciied -Reterto approved Fault i
Single Line Diagram No.
)
Type of circuit breakers =
Incoming aca of] CCB [] FS
Outgoing meca [] FS [ jcumcca = [
2 Colour codes tor internal,
‘main circuits wiring
Phase Red / Yellow / Blue
Neutral Black
Earth Green and Yellow i
3. Terminal ferrules for controVauxiiary circuits - kWh Meter rt
Indicating Instruments i
Other (
4 Permanent labels, engraved, ‘rafolte’ or Board Designation |] Controls [
similar Circuit Designation [Indications [
Warning Notice's
Contd... 53/-x
VL EARTHING.
1 Rating/size of Eanh bus-bar & terminals
2 Earthing of conductive parts
3. Termination of ECCS
Vil. METERING
1. Standard indicating instruments,
2 KWH MetersiCTs
3 Wiring/Connections of CT Meter
4 Protection of CT meter wiring
(Allow 6 spare fuse cartridges in the MDB)
5 Mounting height from FFL.
6 Mounting (if door/cover mounted)
7
for Tariff Metering
VIIl, TESTSICERTIFICATION
1 Type Test
2 Routine Tests & Checks
Visual checks
Screwed/Bolted Connections
Operational checks
Dielectric test
Compliance with Regulation
Section - 5. {1
Adequate, consistent with the min.
fault rating specified under IV.4
and IV.5
Adequate No. & size to terminate
Main & Circuits ECCs
Enclosure
Hinged Door
Cable Glands
Copper lugs
Compliance with Regulation
Section - 3
Volt Meter with selector switch
Power Factor Meter
Ammeter
Current Transformers
Indicating Lamps
Tested & Calibrated in DEWA
‘Load’ side of Incoming
supply breaker
Curent Coit
Votage coil
Sealed type fuse”
Heat resistant’
High vottage grade (1
Max. 2 Mirs. C1 Min 0.8 Mt.
Hinged door mounted
Exclusive
Accuracy Class 0.25
Matching Ratio
As specified by the Consultants/Owner
Centiicate tor review/relerence
Compliance with specifications
Tightness
MechanicavElectrical
2500/2125V (85%)
]
1
1
]
]
REMARKS
-53-APPENDIX 11
SPECIFICATIONS OF DBs
(Reterto clause 4.5.2) DB No. :
REFERENCE STANDARDS.
RATING OF INCOMING SUPPLY
BREAKERIISOLATOR™
(Ontoag)
CONSTRUCTION
Mounting
Degree of protection of the enclosure for
Installation
Painting/Finish (InternavExternal)
Front Cover {*Neoprene)
Cable Tray/Conduit entry
Assembly
INTERNAL LAYOUT/ARRANGEMENT &
FAULT RATING
Segregation of live parts
Incoming supply terminals/lugs
Busbar, tap-off connections & terminals
( Separate and independent of each other)
Neutral & Earth Bus-bars & Terminals
Arrangement of bus-bar and tap-off
connections to outgoing circult
breakersiNeutral bus-bars
Rating'size of phase & neutral bus-bars &
terminals (at max. 50 *C ambient)
BS EN 60499, BS EN 60947, IEC 439.1 BS
4293, BS 1361 & BS 86
40d [} OAT 008
1258 [J
BREAKER i) isoLator
wail L 1 Pedestal
Surace {| ) Recessed
Indoor-IP 41/42
Outdoor-P54/55
Stove enamelled [ ] Epoxy
Polyester (} Galvanized
Hinged (] Bolted [JPanel lock
Gasketted”
Top [] Bottom
Top&Botom =}
Factory Assembled
Barrier {] Shroud
Firmly secured
* Separately mounted &
Removable by tool
Barrier
Firmly secured
* Separately mounted &
Removable by tool
Separately mounted with adequate working
clearancesispacing trom incoming supply
terminats/ugs & Outgoing terminals of
MCBSiFS
‘Segregated for each
Group of MCBs/TP ways
ELCB Section
Rigid, firmly secured, supported, direct
and as short as possible
‘Adequately sized
Min, No, of Bolted joints
Min. No. of looped Connections.
Rated for max. 70 °C internal ambient,
Consistent with the rated incoming
supply breakerlisolator
Tinned electrolytic Copper
Conta
54>Min. fault rating of circuit breakers
Provision of supporsitacily for dressing
clamping outgoing circuit cables
Operational access/convenience for
switchgear
Incoming supply circuit breakerisolator
Outgoing Circuit Breakers
Maintenance access/replacement convenience:
for switchgear components
Provision for termination of
PVCISWA/PVC/XLPE/SWA/PVC Cables
ELCBs/RCCBs
UN. Relays with auto-reset timer
IDENTIFICATION
Rating of Incoming supply & Outgoing Circuit
breakers:-
(vis-&-vis the rating specified - Refer to approved
Single Line Diagrarv/distribution Schedules)
Type of circuit breakers -
Incoming
Outgoing (C/L-Current Limit)
Colour codes for internal, main
circuits wiring
Phase
Neutral
Earth
Terminal ferrules for controVauxiliary circuits
Permanent labels, engraved, tratolite’ of
similar
1
Channels U1 Trunking
Max. Height 1.8 M (trom FFL)
From outside of Hinged Door!
Bolted Cover
Restrictedil ockable
Breaker/s
ELCBIs
Isolators
ULV. Relays:
Gland plate Cable gland
Window AC
Lighting
Others.
Split A/C
Small Power
Window AC
Others
Split A/C
Thermal
Discrimination
Isolator (] Mcce
cH cca } FIS
For general loads, Type ‘1/L"
For Motor load, Type '2/'G'
[ Je MccB
t) ca
Red / Yellow / Blue
Black
Green and Yellow
Indicating Instruments
Other
Board Designation
Controls,
Circuit Designation
Indications
Warning Notices
ELCBIULV. Relay Section
Conta
“55+
56vi
vu
va.
EARTHING
Rating/size of Earth bus-bar & terminal
Earthing of conductive parts,
Termination of ECCS
METERING
Standard indicating instruments
Mounting height from FFL,
Mounting {if door/cover mounted)
TESTS/CERTIFICATION
Type Test
Routine Tests & Checks
Visual checks
Compliance with Regulation
Section -§
Adequate, consistent with the min.
fault rating specifies
under 1v.6
Adequate No. & size to terminate
Main & Circuits ECCs
Enclosure
Hinged Door
Cable Glands
Copper tugs
Compliance with Regulations
Section «3
As specified by the Consultants!
Owner
Max. 2 Mtrs
Min, 0.8 Mtr
Hinged door mounted
As specified by the Consultants!
Owner
Certificate for reviewireference
Compliance with specifications
{1
Screwed/Bolted Connections Tightness 1
Operational checks MechanicalElectrical (1
Dielectric test 2500/2125V (85% 1
REMARKS.
-56APPENDIX - 12
EARTH CONTINUITY CONDUCTORS (ECCs)
&
EQUIPOTENTIAL BONDING CONDUCTORS
(not less than 6)
en ae ae :
oe 8 ae z ; ee
Gros sctonl ata ot | Minimum oss ech ae
i saa @eces Copper conductors) acy sere iding-conductors
S oe a Hees
Bee : : 4
16<8<35 16 10
s
S>35 4
(need not exceed 25)
» = Refer to section.5 for Regulations.
nin
-87-APPENDIX - 13
EARTH LEAKAGE PROTECTION
Recommended value of operating current of ELCB/RCCB in Consumer installations
Sr. Circuitequipment Rated operating .
No. apparatus Current (mA) ”
1. | 13 A-smitched socket outlets 30
2 | Water neaeriCoces 2
3.__| RelrigeratorWashing machine and similar apparatus 30
4. | Domestic water pumps 30
5. | Jacuzzi pumes 10
6 Under water ighting 10
7. | 1A switched socket outlets (general purpose) f 30
8. | General lighting He eH 30/100
8 Flood lighting 7 100/300
10. Window/Split type Air Conditioner 100
11. | Fan coilAir Handiing-units/VAV 100
12 Package type A/C unit ee 100/300
13. Chiller im 100-500-1000
14, | ttrigation pump 100
15. | Electric Cooker = | 100
16. | Industria! machine | 100/300
17 Elevators/Escalators | 300/500
18. | Neon sign | 300
Notes :-
1 Grouping of circuits under one ELCB/RCCB is permitted tor lighting circuits, general purpose
switched socket outlets, single phase equipmenvappliance, etc. In such cases maximum number
of circuits proposed under each group shall be suitably selected considering the type of project
such as Residential, Commercial, Industrial, etc. and the possible interruptions.
2 Wherever un-interrupted power supply is required for equipmenticircuits of fire protection,
drainage, etc. suitable earth leakage detection system with indication and/or alarm is permitted.
For industrial installations which are designed with co-ordinated operational system of plants and
machines, the earth leakage protection shall be suitably selected considering the safety and
operational requirements.
4 Reter to clause 5.4 for RegulationsAPPENDIX - 14
SPACING OF SUPPORTS FOR TRUNKING, CONDUITS AND CABLES
Recommended maximum spacing of Clips, Cleats, Saddles or supports
(Refer to section-6 for Regulations)
!
|
1. TRUNKING : }
Horizontal
Vertical
2. CONDUITS :
‘Spacing of support in cm
Horizontal |
Vertical
ARMOURED CABLES :
we ‘Max. spacing of support in cm
| 2 Overall dia.
exceeding 4cm
est of fievinn Overall dia,
Horizontal 35 60
Vertical 80 !APPENDIX - 15
NUMBER OF CABLES THAT MAY BE INSTALLED IN TRUNKING, CONDUITS AND TRAYS
(Refer to section-6 for Regulations)
1. TRUNKING:
‘Where single core insulated cables are installed in surface mounted metal or PVC trunking, the space {
shall normally not exceed 40 percent. Suitable correction factor shall be applied to the corresponding cu
carrying capacity, based on the number of circuits installed within the trunking
1. CONDUIT:
“2; Size‘of Conduit in mm
The size of conduits selected shall allow drawing the cables freely within, without damaging the insulatior
3. CABLE TRAY:
1. Where single core insulated & sheathed cables are installed in ventilated cable trays, the sum
combined cross - sectional area of all cables installed in the tray shall not exceed 50% of the in
cross sectional area of the cable tray. Suitable correction factor shall be applied to the correspo:
current carrying capacity based on number of circuits and method of installation (touching or spac:
2, Where multicore cables are installed in ventilated cable trays the sum of the diameters of all c:
installed shail not exceed 60% of the cable tray width and the cables shall be installed in a <
layer. Suitable corrector factor shall be applied to the corresponding current carrying capacity
on the number of cables and the method of installation (touching or spaced)
-60-APPENDIX - 16
DATA SCHEDULE FOR LV ELECTRICITY METERS AND CURRENT TRANSFORMERS
(Refer to section-3, for Regulations)
A. Electricity Meters
Type of Meters
Reference voltages & frequency
Accuracy Class
Meter Application Balin
Direct Metering on LV system 160A
Register
Type of register
No. of digits (drums)
Height of numerals
Rated primary Current
(only one is applicable)
Rated burden
| No. of Phases
| Accuracy Class
CT Application tem Rati
CT metering on LV system
Medium of installation
Size of Busbars (Primary)
| Bated Primary Current
a) 200A, 300A
b) 4008
c) 600A, 800A
) 12004, 16004
24004
Rated Secondary Current 5A
| Maximum primary voltage 600v
Rated Frequency 50 Hz
Induction type
Watthour Meter
Refer to clause 1.2,
Section 1
Roller cyclometer
(drum type register)
6 (minimum)
5 mm (minimum)
200A, 300A, 4004,
600A, 800A, 120A, or
24008
5VA
1
02s
Air
20mm x 10 mm
30 mm x 10 mm
50 mm x 10 mm
or 2 Nos. x
30 mm x 10 mm.
2.Nos. x 60 mm x 10 mm
2.Nos. x 80 mm x 10 mm
-61-