Cathodic Protection Rectifiers
Cathodic Protection Rectifiers
23478 -VOO-EYIO-OOO02-OI
m No.
BechtelCmofation
23A71t
SUPPLIERDOCUMENTREVIEW STATUS
RewsoandmsuhIL
.Rememdmsutmt
4Jq
R@w.#notqned
I STATUS
NO.
1 WJdcmayplumcd
2 a
WofkmYkm=d
MINYmtPIuc-4
Watimypruyad.
wbPC4bmWalIOM
0fdunge4mdrabd
.. ,
s
,.
..,;
cc
,
. .
.i.
,....
,.
,:~;;g$g
OP
,.
.,.
.,
.,
.,,.
.-,
!.
CAT
.
;.,
-.,
MADE
IN CANADA
Manual
Protection
staff
use the
in reliable
with
should
Rectifiers
as identified
years of experience
components,
with reasonable
RTS maintains
NUMBER
rectifier
by
case
it will impede
the case.
an engineering
consistent
that
RTS Cathodic
latest
It is recommended
on the unit.
Every effort
in the field.
so that
these
rectifiers
by
are of the
highest
quality
costs.
be specified
when
by serial number
requesting
information
only,
Therefore
on or ordering
the SERIAL
parts
for this
rectifier,
B. DELlVERY INSPECTION
If
damage
IMMEDIATELY.
damaged
Number,
has
occurred
in
If it is necessary
or missing
Purchase
Number
FILE
CLAIM
your supplier
be sure
components,
Order
shipment,
to contact
to
and Invoice
include
Number.
WITH
THE
CARRIER
or the manufacturer
ALL
information
concerning
such
that
as Serial
you obtain
service.
C. INSTALLATION
Proper
cathodic
1.
2.
rectifier
protection
installation
system.
procedures
These procedures
connections
to re-tighten
Select
the
mounting
accessibility,
proper
temperatures,
protection
and
site
to ensure
the integrity
of the
are as follows:
to make-sure
those which
for
the
importantly,
It is a good idea
carry electrical
rectifier;
shielding
ventilation,
most
paying
from
current.
special
sources
convenience
to
of
A.C.
attention
to
high
ambient
and
cathodic
connections.
3.
Mount
rectifier securely
4.
Have
electrical
are necessary
qualified
on mounting
electrician
make
A disconnect
switch
connections,
is required
following
ahead
the
of the A.C.
5.
BEFORE ENERGIZING,
ENSURE
CORRECT
to the structure
7.
BEFORE
ON D.C.
being protected
turning
on the
CONNECTIONS,
the lowest
setting
input
the output
fuse.
to prevent
breaker,
ensure
damage
the
moved
to bring output
should always
output.
to desired
negative
minutes
are at their
lowest
be made from
or prematurely
taps
to the rectifier
connecting
setting:
8.
POLARITY
blowing
moving
by
and repeat
as required
the
FINE adjustment
level.
If everything
one
until output
normal,
then
allow
proceed
to
9.
The Rectifier
should be operated
power
carrying
connections
may be warm,
10.
Air cooled
are
D.C, output
switch
current
and immediately
for about
in the connections.
feel
are overheating.
Shut the
all current
Connections
rectifiers
manufactured
vents
at the required
with
never
obstructed
openings
by plugged
top
for cooling,
and
screens
bottom.
or by
laying
the
rectifier
Periodically
monitor
level of cathodic
the
rectifier,
protection
re-adjusting
as necessary
to maintain
the
current required.
D. MAINTENANCE
C.P,
maintenance
conditions
rectifiers
have
is largely
which
1.
Excessive
Voltage
3.
Excessive
moving
of a preventative
will affect
2.
no
and therefore
(other that the meters),
primarily
three
Bear
in
mind
there
are
nature.
parts
component
temperatures.
output.
Meter
ammeter
accuracy
can be made
against an accurate
by measuring
the millivolt
voltmeter
meter.
A quick calibration
for
with
scale.
The
I(d.c, ) =
50
Where:
I(d.c.)
= Actual
E = Millivolt
I(shunt)
Meter
allowance
in amperes
D.C. output
= Shunt size(corresponds
accuracy
should
for temperature
be within
of 0.85%
2%
per 10 degrees
deflection,
of ammeter)
combined
C. for temperature
other
with
an
that
25
degrees C.
A periodic
functioning
meter.
check
properly.
This,
of rectifier
If an A.C.
of course,
conversion
wattmeter
efficiency
is unavailable,
is if no other electrical
if the rectifier
power
when
the A.C.
(in watts)
= 3600
KN
T
Where:
K = Watt-hour
N=
T=
meter constant
D.C. Power
Rectifier
Out x 100
A.C.
In
silicon
of VOLTS
efficiency
D.C. Power
For tap-adjusting
is the product
conversion
Power
D.C. x AMPERES
diode
D.C.
will be:
= % conversion
rectifiers,
efficiency
conversion
a properly functioning
efficiencies
rectifier.
is
watt-hour
of approximately
Maintenance
temperatures.
can
be the
Regular checks
Periodic
be undertaken.
best
deterrent
against
re-tightening
rectifier
failure
due to excessive
of electrical
connections
is good
source should
insurance
against
future trouble,
CAUTION: Hazardous voltages are present within the rectifier. ALWAYS interrupt
the A.C. power at the nearby disconnect. The rectifier A.C. breaker DOES NOT totally
remove all incoming A. C. power from the rectifier.
A temperature
These
temperatures.
The difference
between
should be subtracted
45 degrees
maintenance
temperatures
tool.
TEMPERATURE
COMPONENT
MEASUREMENT
Moulded
moulded
temperature
MAX
POINT
body
110 degrees
C,
stud
115 degrees
C.
Transformer
primary winding
160 degrees
C.
160 degrees
C.
80 degrees
C.
130 degrees
C,
Filter Choke
winding
Filter Capacitor
case
Output
Fuse
Current
Shunt
resistive element
75 degrees
C,
Electrical Corm.
bolt or screw
90 degrees
C.
Electrical Wiring
wiring harness
90 degrees
C,
against voltage
supplied
with
the
unit
electrical
equipment
Lightning
is intact. .
against
device
excessive
or component
(input breaker
failure.
Always
Keep - motor
and
power
the lightning
similar
surge
and surge
producing
possible.
lines wherever
protective
rectifier
Maintenance
outputs,
at time of
TEMPERATURE
mounting
protection
C.
TABLE
Silicon Diode
Maintenance
The following
COMPONENT
Bridge
preventative
or output
replace
when
output
requires
an over current
fuses with
the same
monitoring
situation
it is an indication
rating
and type.
of
rectifier
may arise.
If a
of overload
Check
the
time,
quality
failures
enable a potential
construction
and
will occasionally
preventative
maintenance
A good knowledge
happen.
will
reduce
of rectifier
rectifier
operation
will
equipment
Electronic
is essential
multimeter,
preferably
2.
Clamp-on
3.
Temperature
4,
Dummy
A.C. ammeter,
one which
can measure
up to 750
VAC
and
( Fluke 75 or 25)
Fluke 801-600
or Amprobe
ACD-I
1000
watt
capacity.
.
5.
Hand
tools.
1/4
nutdrivers;
- 3/4
socket screwdrivers;
6,
The majority
blown
fuses,
faulty
3/8
cathodic
of rectifier
loose
faulty
load connections,
to
determine
CAUTION:
the
rectifier.
Beware
[f doing
meters,
and lightning
of a faulty
should be followed
measurements,
1/4
#l,
- 1/2
S.A. E.
#2 and #2 long
terminals,
the
wrenches;
blade screwdrivers;
PROCEDURE:
follows
and 5/16
TROUBLE SHOOTING
components
S.A. E. combination
3/1 6, 1/4
cause
of
blown
M.O.V.
suppressors,
open circuits,
Visual inspection and smell can be
damage.
rectifier for the above faults.
by a systematic
non-operation.
work
on
electrical
a rectifier
voltages
other
input,
This
isolation
should
of various
rectifier
be conducted
as
of hazardous
any
circuit breaker.
and where
than
taking
they
are present
voltage
at the rectifier
or
in
current
disconnect,
not
1.
Check whether
A.C, voltage
it is the correct
2.
is present
line entering
If the
breaker
input
indicates
isolate
continues
bridge,
b)
to
trip
OFF
the rectifier.
Again
Provided
and that
input terminals
ON.
be experienced
if
Remove
a)
input rating.
at the rectifier
is a shorted
diode(s).
disconnected
energized,
this
usually
Proceed as follows;
by Coarse
energize
replace defective
when
the
breaker.
diode(s)
If the
in the stack.
breaker
Check
to
now
stack
and
(See #7 below)
from the A.C.
supply,
do an ohmmeter
check
between
ground lug and the load side(s) of the input breaker
Any detectable
resistance
will
(right side of CB1 on schematic).
indicate a primary to ground breakdown.
A Megger test instrument is
preferred
for
replacement
Visually
c)
this
test
if
Any
available.
fault
will
necessitate
of the transformer.
inspect
the
transformer
for any
signs
of burned
or shorted
windings.
Check for shorted
d)
3.
An
intermittent
A.C.
voltage
lightning arrestors.
reading
nearly
always
indicates
a loose
or burned
connection.
4.
Verify
there is transformer
secondary
voltage.
A measurement
5.
Verify
the COARSE
Measure
steps
output
20%
of the measurement
20%
of the voltage
step.
the A.C.
voltage
on schematic).
bars, otherwise
as being approximately
of each COARSE
MOVI
the D.C.
(item 4 above)
6.
to 1.6 times
of the voltage
It should
be the same
(same
as connection
as measured
across
points
of
the tap
7.
Conduct
a)
Disconnect
b)
and touch
250
Similarly,
range,
(negative
(Black)
points of MOVI
to 1000
lead to the
stack
on schematic).
diodes
A good
will give a
or short
terminal
a faulty
D3 and D4.
A.C.
An open
BEEP.
c)
NEGATIVE
(same as connection
the
terminal
diode.
Replace
tighten
faulty
diodes with
and polarity.
Recommended
torques
of voltage
NOTE:
With
no load,
potential
electronic
9,
10.
meter
Verify
meters
{ectifier
terminals
is present
in the wiring
may
the actual
read
D.C.
at
(or a
a static
voltage.
It
which
will
eliminate
the
false
reading
of
the
voltmeter,
and negative
If the voltage
electronic
may be necessary
lugs
positive
lugs.
a sensitive
which
output
at the D.C.
D.C. output
blown
are:
30 inch-pounds
Do not over-
output
terminals
but no
may indicate
readings
are correct
with
an electronic
meter.
Rectifier
Meter
11.
corrosive
are
H2S
environmentally
sealed
Their
switches
or
added
carefully
cost
placed
may
switches
save
future
be used
repair
contacts
to replace
work
and
down
of a suspect
normal
time.
types.
Jumpers
switch
will isolate
contacts.
Lightning
from
circuit
the
should
often a source
environments.
and checking
can be checked
with
for shorts
an ohmmeter.
by isolating
them
these should
Normally
F. SAFETY
Cathodic
unfamiliar
with
protection
rectifiers
the workings
do
of a unit.
electrical
few guidelines:
1.
When
approaching
a rectifier
to inspect
or repair,
always
remember
to touch
the case latch with the BACK of your hand first. If you feel any voltage
Tingle DO NOT grab the lock or latch with your hand as you may not be able
to let go,
You should turn off the A.C. power at the external disconnect
and
call an electrician.
2.
Understand
where
potential
them
bodily or
with tools.
3.
4.
5.
When taking
6.
Lock
out
energizing
on energized
equipment.
a supply
disconnect
or circuit
breaker
to
prevent
accidental
re-
of the circuit.
7.
Wear safety
8.
When
in doubt
technician
working
on
particular
or the factory.
any connection.
test
procedure,
contact
an
experienced
RECTIFIER SPECIFICATION
DIV.
CUSTOMER:
P. O.:
MODEL NO:
CSAYSE
SERIAL NO.:
A.C. VOLTS:
A.C. AMPS.:
60-12
115/230
9.5/4.75
QTY.
D.C. VOLTS:
D.C. AMPS :
DATE:
34704
60
12
PH.:
W.o.: 13339-1
CYCLES:
60
SINGLE
PART NUMBER
ITEM
C-972092
O/P CKTS:
V. A.: 1095
TAP-ADJUSTED
INPUT
TYPE:
DESCRIPTION
ENCLOSURE
A-1
STANDARD,
14 GAUGE
MILL
GALV.
STEEL,
CHASSIS
A-1
STANDARD
14 GAUGE
MILL
GALV.
STEEL,
WHITE
A-1
STANDARD
14 GAUGE
MILL
GALV.
STEEL,
WHITE
A-1
STANDARD,
1 -PR
PHENOLIC
MTG.
FRONT
TRANSFORMER
BKT.
PANEL
T-601
CT&D
RTS
NEMA
2-E
DIODE
BRIDGE
HEATSINK
#1024
35 MB60A
AC BREAKER
JAI-SD3ABOI
3.5/EQUlV.
VOLTS
9.75
5-FINE
WHITE
14.00
TAPS
F. S. D., /
60 RED LINE
YOKOGAWA
AMMETER
1
3/16
5-COARSE,
0-75
260-300-E50
1/1
XX,
RTS,
VOLTMETER
1
0-15
AMPERES
INTL.
RECTIFIER,
WAKEFIELD,
DAW-1015.O
ALUMINUM,
HEINEMANN,
10/5,0
600
BLACK
AMP.
SHUNT
15 AMPERE,
A.C.
ARRESTOR
SIOV-S20K250
SIEMENS,
130
VOLTS,
D.C.
ARRESTOR
SIOV-S20K130
SIEMENS,
130
VOLTS,
68 JOULE
SECONDARY
SIEMENS,
130
VOLTS,
68 JOULE
50 MV.
SIOV-S20KI
HOLLOWAY
30
TYPE
VOLTS
PIV.
ANODIZED
230VAC,
SURGE
SHEET
2-POLE
SW
130
JOULE
.
2
FUSE CLIPS
C-10,
PLATED,
FUSE
NON-1 5/Equivalent
EDISON,
15-AMPERE
RHEOSTAT
RHEOSTAT
RHI 50-1.0
MEMCOR,
KNOB
2514-010-017
MEMCOR
PLATE
A-1
DIALPLATE
RHEOSTAT
ILSCO
2491-020-001
1.0 OHM,
C. T.&D.
1/8
NKK
DPDT,
SWITCH
SWITCH
S-338 /EQUIV.
NKK
DPDT,
AMPERES
TERM.
1
2
BLOCK
BLOCK
BKT.
10-142,
150
WATT
AC
ALUMINUM
S-335 /EQUIV.
TERMINAL
2 FUSES
VOLTS
MEMCOR
STANDARD,
SWITCH
1
1
250
JONES
30 AMPERE,
66-X-0050
FOR El-225
AC TERMINAL
8-142,
JONES
30 AMPERE,
DC LUGS
XT #4
- #14,
ILSCO
PLATED,
300
#2 - VOLTS
- VOLTS
VAC,
& EI-300
300
VAC,
(1) POSITIVE
COARSE-FINE
TAPS
LAMINATION
C/VV
BARRIER
(1) NEGATIVE
II
NOTES:
1. RECTIFIER
EQUIPPED
AC WIRE SIZE: #
WITH
14 TEW
SINGLE
OUTPUT
CIRCUIT.
# 14 TEW
---
ANODE
LBI
MAIN
AC
TRANSFORMER
BREAKER
iNOTE
----------
21
~--1
1
I
1
1
;
TI
LI
336
1
VAC
PH.
NEUT
[
1
l,,
1,
1,2;
L.;
AC
T F
OUTPUT
FUSE
SECONDARY
SUROE
ARRESTOR
ARRESTOR
Ir
LI
1
1,
1
22
t,
VAC
PH.
I
1
1
1
{,
=ii~b
.--.!
---+1
I
1
4t
D3
O.c
SURGE
ARRESTOR
hA
D4
1
L------_.
D1ODE
BRIDGE
4SSEMBLY
GND
SI
%+
AMPERES
VOLTS
I
11
SURGE
A
,.
~;
L2
D2
II
230
!
01
SHUNT
G(-)
STRUCT
Y
$!,*
NOTES:
3.)
2 .)
CONSULT
SPEC1FICATION
SHEET
PART
NUMBERS
AND
OU4NT1T1ES
FOR
FOR
? t5
230
VAC
VAC
lNPUV.
INPUF
JUMPER
J.IMpER
FOR
1-2
2-3
13ET A1LLE0
c 3-4
ONLy.
TAP
m..
ADJUST,
Docummnt
ltB/230
.te:
VAC.
3-cIRCUIT
Number
UE
E? ST D.SCH
B
July
6.
1998
I S,r,. .t
3.
~
of