Lab3E6 - Series and Parallel Pump PDF
Lab3E6 - Series and Parallel Pump PDF
Pumps are used in almost all aspects of industry and engineering from feeds to reactors or
distillation columns in chemical engineering to pumping storm water in civil and environmental.
They are an integral part of engineering and an understanding of how they work is important for
any type of engineer.
Centrifugal pump is one of the most widely used pumps for transferring liquids. This is for a
number of reasons. Centrifugal pumps are very quiet in comparison to other pumps. They have a
relatively low operating and maintenance costs. Centrifugal pumps take up little floor space and
create a uniform, non-pulsating flow. This equipment illustrates the basic operation and
characteristics of centrifugal pumps. The equipment will explore flow rates and pressure head of
a single pump and of two identical pumps that are run in series or in parallel. In this equipment,
there are two pumps connected through a pipe work that allows for them to be operated
individually, in series or in parallel. When identical pumps are in series the pressure head is
doubled but the flow rate remains the same. This is useful when a high pressure is needed but
the same flow rate as of a single pump is sufficient. When pumps are run in parallel the flow is
increased and the pressure head produced is around the same as a single pump.
Pumps are devices that transfer mechanical energy from a prime mover into fluid energy to
produce the flow of liquids. There are two broad classifications of pumps: positive displacement
and dynamic. In the experiments, students are able to operate Horizontal Single Stage
Centrifugal Pump (PI) and (P2) in different arrangement-single, parallel and serial.
2.1 Dynamic Pumps
Dynamic pumps add energy to the fluid by the action of rotating blade, which increases the
velocity of the fluid. Figure 1 shows the construction features of a centrifugal pump, the most
Figure 3 Pump Head versus Flow rate Curves for Centrifugal Pump for water and for a more
viscous liquid
The maximum head produced by a centrifugal pump is called pump shutoff head because an
external system valve is closed and there is no flow. Notice from Figure 4 that as the external
system resistance decrease (which occurs when a system valve is opened more fully), the flow
rate increases at the expense of reduced pump head. Because the output
Flow rate changes significantly with external system resistance, centrifugal pumps are rarely
used in fluid power systems. Zero pump head exists if the pump discharge port were opened to
the atmosphere, such as whenfillingnearby open tank with water. The open tank represents
essentially zero resistance to flow for the pump. Figure 4 shows why centrifugal pumps are
desirable for pumping stations used for delivery water to homes and factories. The demand for
water may go to near zero during the evening and reach a peak during the daytime, but a
centrifugal pump can readily handle these large changes in water demand. Since there is a great
deal of clearance between the impeller and housing, centrifugal pumps are not self-priming,
unlike positive displacement pumps. Thus if a liquid being pumped from a reservoir located
below a centrifugal pump, priming is required. Priming is the prefilling of the pump housing and
inlet pipe with the liquid so that the pump can initially draw the liquid and pump efficiency.
Priming is required because there is too much clearance between the pump inlet and outlet ports
to seal against atmospheric pressure. Thus the displacement of a centrifugal Pump is not positive
where the same volume of liquid would be delivered per revolution of the driveshaft.
The lack of positive internal seal against leakage means that the centrifugal pump is not
forced to produce flow when there is a very large system resistance to flow. As system
resistance decrease, less of the fluid at the discharge port slips back into the clearance spaces
between the impeller and housing, resulting in an increase in flow. Slippage occurs because the
fluid follows the path of least resistance.
2.2.2 Performance Characteristic Curves for Centrifugal Pumps
When Centrifugal Pump manufacturers test their pumps, they typically produce (for a given
geometry and speed) performance curves of head, overall efficiency, and input shaft power
versus flow rate of the specified fluid. Figure 5 shows these three curves plotted on the same
graph. Note that as the flow rate increases from zero, the efficiency increases from zero until it
reaches maximum, and then it decreases as the maximum flow rate is approached. The point
where the maximum efficiency occurs is the best efficiency point (BEP), and the corresponding
flow rate is the design flow rate. When selecting a pump for a given application, it is usually
desirable to use a pump that will operate near its efficient point. Maximum efficiency values for
centrifugal pumps typically range from 60% to 80%.
2.3 Centrifugal pump connected in Parallel
If a single pump does not provide enough flow rate for a given application, connecting two
pumps in parallel as shown in Figure 4, can rectify the problem. The effective two-pump
performance curve is obtained by adding the flow rates of each pump at the same head. As
shown, when two pumps are connected in parallel, the operating points shift from A to B,
providing not only increased flow rate as required but also greater head. Figure 6 shows
identical pumps, but the pumps do not have to be the same.
: Clean
P1
Figure 7 Process Diagram for Serial / Parallel Pump Test Unit
3.2
Installation Procedures
2. Unpack the unit and place it on a table close to the single phase electrical supply.
3. Place the equipment on top of a table and level the equipment with the adjustable feet.
4. Inspect the all parts and instruments on the unit and make sure that it is in proper
condition.
5. Connect the equipment to the nearest power supply.
3.3
Commissioning Procedures
1. Install the equipment according to Section 3.1.
2. Make sure that all valves are initially closed.
3. Fill up the sump tank with clean water until the water level is sufficient to cover the
return flow pipe.
4. Then test the pumps according to Section 5.1.
5. Check that pumps, flow meter and the gauges are working properly. Identify any
leakage on the pipe line. Fix the leakage if there is any.
6. Turn off the pumps after the commissioning.
7. The unit is now ready for use.
4.0 PROCEDURES
4.1 General Start-up Procedures
Before conducting any experiment, it is necessary to do the following checking to avoid any
1. Make sure that the circulation tank is filled with water up to at least the end of the pipe
output is submerge with water.
5.
Turn on pump and slowly open V5 until maximum flow rate is achieved as shown in
Table 2.
Eto
1& 4
Valve 5
Pump ON
Pump 1
Procedures:
1. Follow the basic procedure as written in section 3.2.
2. Ensure that all setting follows the equipment set up.
3. Slowly open valve V5 until the flow rate reaches 20 LPM.
4. Observe the pressure reading on the pressure indicator. Record flow rate and pressure
value when stable condition is achieved.
5. Repeat observation by increasing the flow rate with increment by 10 LPM until the
flow rate reaches 90 LPM
1,3
Valve 5
Pump ON
Both Pump
Procedures:
1. Follow the basic procedure as written in section 3.2.
2. Ensure that all setting follows the equipment set up.
3. Slowly open valve V5 until the flow rate reaches 20 LPM.
4. Observe the pressure reading on the pressure indicator. Record flow rate and pressure
value when stable condition is achieved.
5. Repeat observation by increasing the flow rate with increment by 10 LPM until the
flow rate reaches 90 LPM
4.5 Experiment 3: Parallel Pump Operation
Objective: Parallel pump operation with variable flow rate
Table 5Equipment Set Up of Experiment 2
Fully Close valve Fully Open Valve Variable parameter
3
1,2 & 4
Pump ON
Valve 5
Both Pump
Procedures:
1. Follow the basic procedure as written in section 3.2.
2. Ensure that all setting follows the equipment set up.
3. Slowly open valve V5 until the flow rate reaches 40 LPM.
4. Observe the pressure reading on the pressure indicator. Record flow rate and pressure
value when stable condition is achieved.
5. Repeat observation by increasing the flow rate with increment by 20 LPM until the
flow rate reaches 180 LPM
5.0 RESULTS
2.92
1.05bar
1.04
1.03
bar
2.85
bar
1.02
02
1
.
2.79
2.70
01
2.60
2.50
sppgh
DP
Fg
mm
"
/
line
best
LPM
flow
of
fit
graph
rate
M3/g
4.75
2.92
1.03
4.63
2.85
1.03
4.50
2.79
4.33
2.69
1.02
4.16
2.60
1.01
2.48
1.00
3.97
Pressure Gauge 1
(PI1)kgf/cm2
1.04
Pressure Gauge 2
(PI2) kgf/cm2
3.04
Pressure Gauge 4
(PI4) kgf/cm2
2.99
04
2.98
2.93
1.04
2.93
2.88
1.03
1.02
1.01
1.00
1.00
=
2.85
2.78
2.70
2.60
2.50
2.73
2.65
2.80
2.56
2.45
i. A
ii. B
C
7.0 CONCLUSION
st
Edition,
ii.
st
.
Result Sample
20
30
40
50
60
70
80
90
20
30
40
50
60
70
80
90
Table 8 Result of Experiment 3
Rotamete r Pressure Gauge 1 (PI1) Pressure Gauge 2
(FI1) LPM
kgf/cm2
(PI2) kgf/cm2
40
60
80
Pressure Gauge 4
(PI4) kgf/cm2
100
120
140
160
180