Aalborg Solutions
No. 3 August 2001
Oil contamination in marine boilers
Inadvertently mixing oil and water may lead to burnt down boilers. Aalborg Industries gives
advice on preventive maintenance and damage control when oil contamination is suspected.
General
of lime deposits if the contaminated
The isolating effect of oil deposits
An oil-fired steam boiler onboard a
feedwater is not treated sufficiently.
reduces heat transfer much more
ship is fed by returned, condensed
Also, make-up water bunkered a-
than e.g. a limestone scale layer
steam to replace the boiled off wa-
shore might contain humus particles
of equal thickness. To understand
ter as well as with stored make-up
and silica, forming heating surface
the mechanism, we have to focus
water to replace steam lost by con-
deposits when heated.
on the metal temperature as well
sumption, leakage or blow-down.
as the conductivity of the metal
The feedwater is normally treated
Oil as a contaminator
mechanically and chemically in
The most dangerous water contam-
order to suit the steaming process
ination, however, is heavy fuel oil
The conductivity of steel can be set
in the boiler and to ensure good
entering the steam or condensate
to 50 W/m2 C, scale having 2 W/m2
transfer of the heat input from the
from leaking tank coils or heat ex-
C and oil 0.1 W/m2 C. It follows
combustion process to the water.
changers. This kind of leakage in
that oil isolates 20 times as much
A closed cycle process would be
coil flanges or broken gaskets in
as scale, with the same thickness of
preferable in order to ensure a heat
plate heat exchangers frequently
deposit.
transfer of high efficiency, but for
occurs. If the problem is not observ-
investment reasons such systems are
ed in time, the boiler could be com-
The strength of the steel material
practically non-existent in todays
pletely destroyed due to overheat-
will be reduced with increased
auxiliary boiler installations.
ing of the furnace because of redu-
temperature. An example shows
ced water flow and minimised heat
that the material strength in an
transfer/cooling of the boiler tubes.
auxiliary boiler will be reduced to
Types of contamination
and the different types of deposits.
A ship contains heat exchangers for
1/3 of its original design value by
bunker fuel and cargo liquids, heat-
an oil deposit of only 0.5 mm
ing coils and seawater coolers. So
thickness. The steel material starts
when steam from the boiler and
scaling at the fireside, when it is
condensed steam circulate through
not cooled sufficiently and will
the ships system, it is almost inevit-
soon rupture with great damage
able that foreign substances like
as the consequence.
(See photos)
heavy fuel oil, lubricating oil and
First damage control action
(boiler)
seawater will influence the boiler
water quality due to leakage.
The first preventive action to be
A contamination could form depo-
taken when oil leakage into the
sits on the boiler tubes or furnace
feedwater system is suspected is to
walls that are swept by the flames
take a look in the cascade or hot-
on the opposite side.
well tanks. If oil is found in the last
compartment just before the water
With seawater it is well known that
chlorides will form a very hard layer
The result of oil contamination in an
oil-fired boiler.
enters the feedwater piping, it is
recommended to check whether a
dark oily film contaminates the
manhole door before opening up
First damage control action (ship)
boiler water level glasses inside.
the manhole for inspection. The
A careful examination and hydro-
If so, do not blow down the boiler
oil will now only cover the boiler
test of all suspected heating coils,
from the bottom; just surface blow
in the normal water level range
heaters or whatever is leaking in
several times. If you bottom blow
and can be manually removed.
the steam/condensate system. Be
the boiler, it will become totally
Hot or cold water high-pressure
aware that even when one leakage
covered in oil. The boiler should be
jet equipment together with oil
is found, there could be several
shut down and released from pres-
dispersive additives would be
more remaining. When it is assured
sure and the venting valve opened.
efficient for removal of the oil.
that no more leakage can be found,
In case the boiler is completely oily
the piping system, coils and heaters
Afterwards, the boiler can be
inside, the cleaning work could be
have to be cleaned of all remaining
drained slowly until water stops
turned over to a cleaning company
oil. The oil-fired boiler must not be
flowing from the loosened, upper
specialised in such work.
started up again until an oil-free
feedwater supply is guaranteed.
Temperature of furnace wall with sediments on water side
Preventive action
The feedwater/hotwell/cascade
If the waterside of a furnace wall
tanks have to have filters installed,
is fouled with e.g. carbonate,
filled with lofa sponges, coconut
silica, or oil film, the temperature
fibres or similar, which effectively
of the furnace wall increases due
take up small amounts of oil. The
to added thermal resistance.
filter inserts have to be exchanged
regularly according to demand. The
cascade tank can easily be equipped
with a continually measuring oil
detecting device which monitors if
oil is present in the condensate. By
Water
170C
7 bar(g)
locating the sensor in the cascade
Furnace
1200C
tank, it can be assured that oil is
detected before it enters the feedwater section, which means that no
Three examples are made to illustrate the increase in temperature of the furnace
part of the feedwater is being
wall when the waterside of the furnace is fouled with sediments of 2 mm carbo-
contaminated. Aalborg Industries
nate, 0.5 mm silica, or 0.5 mm oil film:
can supply standardised equipment
No sediment
2 mm carbonate
0.5 mm silica
0.5 mm oil film
a0 [W/(m2 x K)]
l1 [W/(m x K)]
10,000
10,000
10,000
10,000
1.72
0.172
0.10
l2 [W/(m x K)]
a3 [W/(m2 x K)]
38
38
38
38
145
145
145
145
0.5
0.5
S1 [mm]
S2 [mm]
T2 [C]
A more comprehensive system for
preventing oil from entering the
boiler would be to transmit a signal
to an air- or electrically operated
20
20
20
20
133
115
95.8
79.9
three-way valve switching over the
137
119
98.7
82.3
condensate flow to the bilge until
181.9
179.9
178.2
184
256
320
382
467
519
590
633
atotal[W/(m2 x K)]
Q [kW/m2]
T0 [C]
T1 [C]
fulfilling the above specifications.
the oil source is pinpointed and
eliminated. An investment in such
equipment pays off quickly because
In conclusion, the maximum temperature of the furnace wall is increased from
it prevents the boiler from serious
256C to 633C with an oil film of just 0.5 mm. Furthermore, the transferred heat
damage by burnt down tubes and
is reduced from 137 kW/m to just 82.3 kW/m , a reduction of 40%.
furnace room plates.
Aalborg Solutions is published by the Aalborg Industries After Sales and deals with operation
of steam and heating equipment. Ideas and suggestions for topics are most welcome.