Wind Load Calculation + Design Criteria

This document summarizes the load calculations for the design of an aluminum roof sheet and supporting structure. It calculates dead loads from the roofing material and purlins of 7.06 kg/m2 and 4.71 kg/m2 respectively, for a total dead load of 11.77 kg/m2. Service loads are specified as 75 kg/m2. Wind load calculations are performed according to British standards, resulting in a peak wind load of 2.13 kN/m2 and minimum of -1.96 kN/m2 acting on the roof from different wind directions. Foundation design considers loads from walls and adjacent buildings.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
292 views

Wind Load Calculation + Design Criteria

This document summarizes the load calculations for the design of an aluminum roof sheet and supporting structure. It calculates dead loads from the roofing material and purlins of 7.06 kg/m2 and 4.71 kg/m2 respectively, for a total dead load of 11.77 kg/m2. Service loads are specified as 75 kg/m2. Wind load calculations are performed according to British standards, resulting in a peak wind load of 2.13 kN/m2 and minimum of -1.96 kN/m2 acting on the roof from different wind directions. Foundation design considers loads from walls and adjacent buildings.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Design weight of Aluminum Roof sheet covering = 1 x 1 x 0.0009 x 7850 = 7.

06 kg/m2
Weight of the purlins
Assume purlins is

(40+40+10+10+200) x 0.002 x 7850 = 4.71 kg/m2


Assume 4.71 kg/m2
Total load of vertical dead load = 11.77 kg/m2
Service Load
As per QATALUM standard SOW 1.1 is 75 kg/m2
Wind load calculation
As per British Standard
Clause 2.2.32

10.0000

10.7500

10.0281

10.0000

Figure 11 H= 10.75, B= 18m


H B consider building as one part

10 cation Qatar basic wind speed as per QCS = 28 m/s


Clause 2.2.22.2
Assuming that the topography is not considered significant
Sa = 1 + (0.001 x os) assume os = 10m
Sa= 1 + (0.001 x 10) 1.01
Clause: 2.2.2
Site wind speed vs = vb x sa x sd x ss x sp
Page1of7

Assuming sd=ss=sa=1
Vs= 33 x 1.01 = 33.33 m/sec
Clause 2.2.3 table 4
Effective wind speed Ve = vs x sb
Clause 2.2.3.3
He= 10.75m sd=1.85
Ve= 28 x 1.85=51.8 m/s
95= 0.613 x (ve)2 = 0.613 x (51.8)2/1000= 1.64kg/m2
PC= qs x cpe x ca

5.0

5.0

18.0

6.0

6.0

6.0

Roof Is designed As Monopitch Roof

Case (1) Loads on (+ x x)

Page2of7

0.82
roof
(-1.96)

1.39

D/h = 10/10= 1.0


CPC = + 0.85
CPi = -0.5 assume Ca = 1.0
Pe= 1.64 x 0.85 = 1.39 KN/m2
Pi= 1.64 x 0.5 = 0.82 KN/m2
Wind On The Roof
From Table 8
We Will take Zone B
Curved eaves r/b 0.05
Cpe = -1.2
Pei = 1.64x(-1.2)x1 = -1.96 kn/m2

Case (1)

Case (2) (-x+x)

Page3of7

2.13

roof (-1.1)

0.82

From table 5
Isolated zone (A)
Cpe = 1.3
Cpi = 0.85
Pe = 1.64 x1.3= 2.13 kn/m2
Pei = 1.64 x-0.8 = -1.312 kn/m2
From table 9
Load on the roof = 1.1 kn/m2
From table 18
Cpi first side -0.57
Cpe second side + 0.77

pi = 1.64 x(-0.57) = 0.94 kn/m2


pe = 1.64x0.77
= 0.97 kn/m2

Case (3) (-z+ z)

Page4of7

10.0

10.0

10.8

10.0

0.94 roof (-1.1)

Cpe = 1.3
Cpi = 0.5

1.26

pe = 1.64 x 1.3 =2.13 kn/m2 table 5 isolated


pei = 1.64x 0.5 = 0.82 kn/m2 table 5 isolated

Loads on roof
-1.1 kn / m2

Case (4) (+ z z)

Page5of7

1.26

Cpe = 1.3
Cpi = 0.5

10.0

10.0

10.8

10.0

roof (-1.1)

0.94

pe = 1.64 x 1.3 =2.13 kn/m2 table 5 isolated


pei = 1.64x 0.5 = 0.82 kn/m2 table 5 isolated

Loads on roof
-1.1 kn / m2

Foundation design
1- We take in our consideration the effect of the wall on the foundation 3,7,11,15
20.84 kn/m
2- All our design according to BRITISH standards

Page6of7

3- We take the load of the next building in our consideration 5 kn/m2 in foundation
1,13

Page7of7