0% found this document useful (0 votes)
122 views

CT Blowdown Philosophy

The document describes a water treatment process where cooling water (CW) is evaporated and makeup water (MU) is added. It calculates the total dissolved solids (TDS) concentration of the CW under different flow rates of evaporation, CW intake, blowdown, and MU to maintain a TDS of 400 ppm or reduce it to 390 ppm. It determines that using a blowdown flow rate of 11 L/s would reduce the TDS to 390 ppm, while a blowdown of 86 L/s would maintain 400 ppm TDS.

Uploaded by

zamijaka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
122 views

CT Blowdown Philosophy

The document describes a water treatment process where cooling water (CW) is evaporated and makeup water (MU) is added. It calculates the total dissolved solids (TDS) concentration of the CW under different flow rates of evaporation, CW intake, blowdown, and MU to maintain a TDS of 400 ppm or reduce it to 390 ppm. It determines that using a blowdown flow rate of 11 L/s would reduce the TDS to 390 ppm, while a blowdown of 86 L/s would maintain 400 ppm TDS.

Uploaded by

zamijaka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

Reduce to 390 ppm TDS CW from 400 ppm

Evap =
TDS =

CW =
TDS =

75 L/s
0 mg/L

5000 L/s
400 mg/L
2,000,000 mg/s

RCW =
TDS =

Maintain 400 ppm TDS CW


Evap =
TDS =

CW =
TDS =

5000 L/s
400 mg/L
2,000,000 mg/s

75 L/s
0 mg/L

RCW =
TDS =

BD =
TDS =

125 L/s
406 mg/L
50,761 mg/s

With blowdown :
CW =
TDS =

4925 L/s
406 mg/L
2,000,000 mg/s

Without blowdown :
CW =
TDS =
MU =
TDS =

4925 L/s
406 mg/L
2,000,000 mg/s

MU =
TDS =

200 L/s
10 mg/L
2000 mg/s

BD =
TDS =

11 L/s
406 mg/L
4,277 mg/s

TDS =

With blowdown :
CW =
TDS =

Without blowdown :
CW =

TDS =
MU =
TDS =
MU =
TDS =

86 L/s
50 mg/L
4277 mg/s

TDS =

With blowdown :
5000 L/s
1,951,239 mg/s
390

Without blowdown :
4925
2,000,000
75
2000

L/s
mg/s
L/s
mg/s

400.4

With blowdown :
5000 L/s
2,000,000 mg/s
400

Without blowdown :
4925 L/s

2,000,000 mg/s
75 L/s
4277 mg/s
400.86