Technical Datasheet of Inergen System Pipes & Fittings: S.NO. Description

This technical datasheet provides specifications for pipes and fittings for an Inergen gas system. It specifies the following: 1. Carbon steel seamless galvanized pipes conforming to ASTM A106 Grade B, Schedule 160/80 will be used depending on flow calculations. 2. Forged steel fittings conforming to ASTM-105 and ANSI B-16.11 standards with a pressure rating of 3000# will be used upstream and downstream of pressure reducers depending on the pipe size. 3. Fittings will handle Inergen gas and will be inspected and tested according to an approved Quality Assurance Plan.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
219 views4 pages

Technical Datasheet of Inergen System Pipes & Fittings: S.NO. Description

This technical datasheet provides specifications for pipes and fittings for an Inergen gas system. It specifies the following: 1. Carbon steel seamless galvanized pipes conforming to ASTM A106 Grade B, Schedule 160/80 will be used depending on flow calculations. 2. Forged steel fittings conforming to ASTM-105 and ANSI B-16.11 standards with a pressure rating of 3000# will be used upstream and downstream of pressure reducers depending on the pipe size. 3. Fittings will handle Inergen gas and will be inspected and tested according to an approved Quality Assurance Plan.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

TECHNICAL DATASHEET OF INERGEN SYSTEM PIPES & FITTINGS

S.NO.
DESCRIPTION
1
MANUFACTURER - PIPES
2
MANUFACTURER - FITTINGS
3
FLUID TO BE HANDLED
PIPE & FITTINGS FOR INERGEN
4
SYSTEM
4.1

PIPES

4.2

FITTINGS (TEES, ELBOWS 1.5R &


REDUCERS)

4.2.1

UPSTREAM OF PRESSURE REDUCER


AS PER NFPA-2001, TABLE A4.2.3.1(a)
40NB & BELOW

50NB & ABOVE

4.2.2

DOWNSTREAM OF PRESSURE
REDUCER AS PER NFPA-2001, TABLE
A4.2.3.1(b)
40NB & BELOW
50NB & ABOVE

4.3

FLUID TO BE HANDLED
QUANTITY
Flanges

50NB & ABOVE

5
6

QUANTITY
FLUID TO BE HANDLED

PAINTING

8
9
10

DESIGN PRESSURE & TEMPERATURE


(UPSTREAM/Downstream)
BUSTING PRESSURE FOR ALL
FITTINGS
INSPECTION & TESTING

NERGEN SYSTEM PIPES & FITTINGS


SPECIFICATIONS

INERGEN GAS

Carbon Steel Seamless Galvanised Pipe Conforming


to ASTM A 106 Grade B, Schedule 160/80 (As per
flow calculation)

Forged Steel ASTM-105 (Galvanized) dimension


standard conforming to ANSI B-16.11, 3000#,
Socket Welded Fittings.
Forged steel ASTM-105 Conforming to ANSI B-16.11,
#3000, Galvanized butt welded fittings, or
Galvanized butt welded fittings confirming to ASTM
A 106 B, Grade-B Seamless pipe, Sch-160 for
Cylinder Mainfold & Diverter Manifold and Sch-80
for network piping.

Forged Steel ASTM-105 conforming to ANSI B-16.11,


3000# Galvanised Socket Welded Fittings.
Galvanised butt welded fitting conforming to ASTM
A234 Grade WPB, pressure equivalent to ASTM A
106 B, Grade B seamless pipe.
INERGEN GAS
As per approved drawing.
ASTM-105 or ASTM A 234 WPB, Dimensions /
Drilling as per ANSI B-16.5, 1500# WNRF for pipe
upstream of pressure reducer. Dimensions / Drilling
as per ANSI B 16.5. 900#/600# WNRF for pipe
downstream of pressure reducer.
As per approved drawing.
INERGEN GAS
Two coat of red oxide Primer and two coat of
synthetic enamel paint

200 Bar & 21 degree celcius Ambient temperature /


As per flow calculations
350kgf/cm2 (Minimum)