Setting Calculation Protocol For IDMT Over Current Relay

This document provides the setting calculation protocol for IDMT overcurrent and earth fault relay settings for a typical outgoing feeder. It details the general data, fault data, CT data, and calculations to determine the plus setting multiplier (PSM), time multiplier setting (TMS), and final adopted settings for the overcurrent and earth fault elements. The settings have been coordinated with the downstream and upstream sides.

Uploaded by

rajinipre-1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
648 views

Setting Calculation Protocol For IDMT Over Current Relay

This document provides the setting calculation protocol for IDMT overcurrent and earth fault relay settings for a typical outgoing feeder. It details the general data, fault data, CT data, and calculations to determine the plus setting multiplier (PSM), time multiplier setting (TMS), and final adopted settings for the overcurrent and earth fault elements. The settings have been coordinated with the downstream and upstream sides.

Uploaded by

rajinipre-1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Overcurrent Relay Settings


Station:
Contract:
Consultant:
Contractor:
Feeder ID:

Outgoing Feeder (Typical)

Relay:

Relay Type:

Numerical

Relay Model:

Delta

Relay Make:

VATECH

CT Ratio

Prim. Current

Sec. Current

Burden, VA

Class

Rct

600/400/1

100

15 - 10

5P15

Fault Current, If

L-L Fault

L-G Fault

CT Data:

Fault Data:

6975

Min. Fault Current, A

699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C


General Data:
Overload Current:

75.6

PMS (Plug Multiplier Setting):

(125% of Full load current of Protected Object)

0.756

Curve Selected:

Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


[(PSM)0.02 - 1]:

1.48 sec

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated
Current/PMS)]

1.09

92.26

Assuming Prot. Op. time, sec:


(0.3sec)

0.1 sec

Grading Margin (0.3sec)

0.5 sec

Hence TMS: ('= (0.3+0) / (Result


from Eq.1)

.........Eq. 3

0.5

Operating time at TMS 0.125, sec


'=0.14*0.125/[(PSM)0.02 - 1]:

0.739 sec

Operating time at TMS 0.2, sec


'=0.14*0.2/[(PSM)0.02 - 1]:

0.296 sec

PMS:

0.756

TMS:

0.5

High Set
(I>>):
Is settings co-ordinated with downstream side:

273240108.xls/IDMT OC-Outgoing

.........Eq. 2

0.406

Final TMS set at:

Adopted Settings:

.........Eq. 1

(for Sample)

10xIn
Yes/No

1/3

ADDC Testing and Protection Section


Is settings co-ordinated with upstream side:

273240108.xls/IDMT OC-Outgoing

Yes/No

2/3

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Earth Fault Relay Settings


Station:
Contract:
Consultant:
Contractor:
Feeder ID:

Outgoing Feeder (Typical)

Relay:

Relay Type:

Numerical

Relay Model:

Delta

Relay Make:

VATECH

CT Ratio

Prim. Current

Sec. Current

Burden, VA

Class

Rct

600/400/1

100

15 - 10

5P15

Fault Current, If

L-L Fault

L-G Fault

CT Data:

Fault Data:

6975

Min. Fault Current, A

699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C


General Data:
Earth Fault Current:

0.189

PMS (Plug Multiplier Setting):

0.189

Curve Selected:

Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


[(PSM)0.02 - 1]:

1.87 sec

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated
Current/PMS)]

.........Eq. 2

0.1 sec

Grading Margin (0.3sec)

0 sec

Hence TMS: ('= (0.3+0) / (Result


from Eq.1)

0.054

Final TMS set at:

.........Eq. 3

0.2

Operating time at TMS 0.2, sec


'=0.14*0.2/[(PSM)0.02 - 1]:

0.374 sec

PMS:

0.189

TMS:

0.2

High Set
(I0>>):

8xIn

Is settings co-ordinated with downstream side:

Yes/No

Is settings co-ordinated with upstream side:

Yes/No

273240108.xls/IDMT EF-Outgoing

.........Eq. 1

1.07

37.03

Assuming Prot. Op. time, sec:


(0.3sec)

Adopted Settings:

(25% of OC PMS)

3/3