0% found this document useful (0 votes)
715 views28 pages

Cooper Networking Lon Rs232 Modbuse TCP Ip

The document provides information on networking fire alarm panels using a LON protocol. It describes the standard network hardware including cable, termination, and topology. Advanced hardware such as dual redundancy network cards, fibre optic interfaces, and gateways to other protocols are also covered. The networking of standard and advanced hardware in different configurations is demonstrated. Standard network setup and fault finding procedures are summarized.

Uploaded by

asifaliabid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
715 views28 pages

Cooper Networking Lon Rs232 Modbuse TCP Ip

The document provides information on networking fire alarm panels using a LON protocol. It describes the standard network hardware including cable, termination, and topology. Advanced hardware such as dual redundancy network cards, fibre optic interfaces, and gateways to other protocols are also covered. The networking of standard and advanced hardware in different configurations is demonstrated. Standard network setup and fault finding procedures are summarized.

Uploaded by

asifaliabid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 28

Introduction

System Schematic

ADDRESSABLE SPUR CIRCUIT

LOOP 1
ADRRESSABLE
LOOP

CONVENTIONAL SOUNDERS

~
~
CONVENTIONAL
SOUNDERS

LOOPS 2-4

CF3000

MODBUS OUTPUT
TO BMS SYSTEM

CW9000

CTPR3000

EC200

NC

NC

SITE MONITOR
SYSTEM

SITE GRAPHICS
SYSTEM

EC700

EXT
24V

CFSFL01

LON-FO

BACNET OUTPUT
TO BMS SYSTEM

EC650

EXT
24V

ECO232

ECO232

NC
FIBRE OPTIC

LOCAL AREA NETWORK


NC

NC
EC400

CF1100/1200

EC400

UP TO MAX 126 NETWORK NODES


EXT
24V
EC540

CF3000

Introduction
Network Schematic

Max 126 nodes

Control Panels, Network Repeaters, Network Modules

Topology

Fire rated RS485 screened twisted pair, ie, Draka 910234


1000m cable max of copper network between boosters

Data Available

Panel Number, Loop Number, Device No. / Desc / type, Zone No. / desc

MODBUS OUTPUT
TO BMS SYSTEM

CF3000

CW9000

CTPR3000

EC200

NC

NC

SITE MONITOR
SYSTEM

SITE GRAPHICS
SYSTEM

EC700

EXT
24V

CFSFL01

LON-FO

BACNET OUTPUT
TO BMS SYSTEM

EC650

EXT
24V

ECO232

ECO232

NC
FIBRE OPTIC

LOCAL AREA NETWORK


NC

NC
EC400

CF1100/1200

EC400

UP TO MAX 126 NETWORK NODES


EXT
24V
EC540

CF3000

Introduction
Advanced Network Modules Range
NCDR

CFSFL01/02

LON (network) to BMS Gateway

EC650

LON (network) to RS232: Site Graphics & Site Monitor

EC200

LON (network) booster, splits network and resends data to increase range

ECO232

LON (network) to TCP/IP interface

EC540

LON (network) to Fibre Optic interface, max 15K FO length

EC400

Dual Redundancy Network Card (V2)

LON (network) to BACnet interface

EC700

BMS Gateway to ModBus interface

Standard Hardware
Standard Network Card Connections

Cable

Screening

Remove resistors at all network cards except the two ends


102 at each end = 51 across network

Ring Network

Resistor termination 102 (2 x 51 ) per card

Radial Network

Connect screen to ground at one end only

Termination

Enhanced fire rated data cable, Max 1000m length


Draka 910234 2 core twisted pair with screen

Remove resistors at all network cards except one


Link out 1 resistor leaving 51 across network

NETWORK
CONNECTIONS
A-X, B-Y

Y
X
B
IN
A

OUT

EC540 Booster:

treat the network either side as separate networks


TERMINATION
RESISTORS

RIBBON CABLE TO
CONTROL PANEL

Standard Hardware
Standard Network Termination

Radial Network

Remove resistors at all network cards except the two ends


102 at each end = 51 across network

PANEL 1 OF 4

PANEL 2 OF 4

102

PANEL 3 OF 4

NONE

PANEL 4 OF 4

NONE

102

Standard Hardware
Standard Network Termination

Radial Network with Booster

Remove resistors at all network cards except the two ends


102 at each end = 51 across network

PANEL 1 OF 4

PANEL 2 OF 4

PANEL 3 OF 4
EC540
BOOSTER
24V SUPPLY

102

NONE

102

102

TO NEXT
PANEL ETC

Standard Hardware
Standard Network Termination

Ring Network

Remove resistors at all network cards except one


Link out 1 resistor leaving 51 across network

PANEL 1 OF 4

PANEL 2 OF 4

51

PANEL 3 OF 4

NONE

PANEL 4 OF 4

NONE

NONE

Standard Hardware
Standard Network Termination

Resistor Termination on network card

Radial Network

102 (2 x 51 resistor)
To give 51 reading across network pair at any point

Remove resistors at all network cards except the two ends


102 at each end = 51 across network

Ring Network

Remove resistors at all network cards except one


Link out 1 resistor leaving 51 across network

51
A
B
51

All (102 )
A
B

51
51
LEAVE ALL
RESISTORS INTACT

One (51 )

None (no resistor)


A
B

A
O/C
CUT HERE TO REMOVE
FROM CIRCUIT

51
S/C
SOLDER LINK ACROSS
ONE RESISTOR

Terminal Mounted
102

SOME DEVICES MAY NOT HAVE


INBUILT RESISTORS

Advanced Hardware
NCDR: Network Card Dual Redundancy
Dual Network Channels
Cable

Enhanced fire rated data cable, Max 1000m length


Draka 910234 2 core twisted pair with screen

Screening

SCREEN
CONNECTIONS

Connect screen to ground at one end only

Termination

As per standard network card, but for each channel

NETWORK 2
CONNECTIONS
IN-OUT

NETWORK 1
CONNECTIONS
IN-OUT

OUT
IN

Y
X
B
OUT A
IN

TERMINATION
RESISTORS

RIBBON CABLE TO
CONTROL PANEL

Advanced Hardware
NCDR: Network Card Dual Redundancy

Dual Network Channels

Network 1 and Network 2


Automatic Switching in event of fault
Network Protocol V2 option must be selected

PANEL 1 OF 4

51

PANEL 2 OF 4

51

PANEL 3 OF 4

NONE

NETWORK CHANNEL 1
NETWORK CHANNEL 2

PANEL 4 OF 4

NONE

NONE

Advanced Hardware
CFSFL01/02: Lon (Network) to Fibre Optic Interface

Single or Dual Channel

Requires 2 for a dual network

Fibre

Single Mode x 2 (Tx & Rx)


9/125 micron
15Km max
SC Type connectors

24V DC
0V
FIBRE
CONNECTIONS

SCREEN
NETWORK A
NETWORK B

Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface

Single Channel network

Radial, ring or part network


PANEL 1 OF 4

24V DC

PANEL 2 OF 4

102

PANEL 3 OF 4

NONE

2 x SINGLE MODE FIBRE

PANEL 4 OF 4

NONE

102

24V DC

Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface
Single Channel network
Radial, ring or part network
PANEL 1 OF 4

24V DC

PANEL 2 OF 4

102

NONE

PANEL 3 OF 4

24V DC

1021

2 x SINGLE MODE FIBRE

PANEL 4 OF 4

24V DC

102

24V DC

Advanced Hardware
CFSFL02: Lon (Network) to Fibre Optic Interface

Dual Channel network

Radial, ring or part network


PANEL 1 OF 4

24V DC

PANEL 2 OF 4

102

24V DC

PANEL 3 OF 4

102

24V DC

2 x SINGLE MODE FIBRE

PANEL 4 OF 4

102

24V DC

102

Advanced Hardware
CFSFL01/2: Lon (Network) to Fibre Optic Interface
Many possible combinations

PANEL 3 OF 7

102
PANEL 1 OF 7

PANEL 5 OF 7

102
PANEL 2 OF 7

PANEL 4 OF 7

PANEL 6 OF 6

PANEL 7 OF 7

24V DC

24V DC

24V DC

24V DC

24V DC

102

102

102

102

102

CFSFL01 or

CFSFL02

CFSFL02

CFSFL02

CFSFL02

CFSFL01 or
CFSFL02

2 x SINGLE MODE FIBRE

Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface
Network via PC network / internet / etc

Requires 2 for a dual network

Use Hyper Terminal for configuration

IP address

Inbuilt Web Server for IP configuration

IP address
Passwords

PROGRAMMING

NETWORK
CONNECTION

ETHERNET
CONNECTION

24V
DC

Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface

Requires fixed IP address

Useful for facilities management

PANEL 3 OF 3

24V DC

PANEL 1 OF 3

PANEL 2 OF 3

24V DC

NETWORK

NETWORK

Advanced Hardware
EC540: Lon (Network) Booster

Extend radial network length

Effectively splits a network into multiple networks

Requires 2 for a dual network

Max 5 per network

Any more may cause transmission delays

24V DC
NETWORK
CONNECTION

Advanced Hardware
EC540: Lon (Network) Booster

Radial Network

Terminate network either side of booster

PANEL 1 OF 3

PANEL 2 OF 3

PANEL 3 OF 3

24V DC
102

NONE

1000M MAX

102

102

102

1000M MAX

Advanced Hardware
EC0232: Lon (Network) to RS232 Interface

PC connection

No network address required

Versions

EC0232: Site Monitor, Site Graphics,


EC0232PAVA: EVAX HMX PAVA
EC0232PAVA3D: EVAX HMX PAVA 3 minute time delay

Advanced Hardware
EC0232: Lon (Network) to RS232 Interface

Typical Example

PANEL 1 OF 2

SITE GRAHICS OR
SITE MONITOR

PANEL 2 OF 2
EC0232

102

102

1000M MAX

Advanced Hardware
EC200: Lon (Network) to BMS Gateway

Translation for BMS connection

Requires EC700

Advanced Hardware
EC700: BMS Gateway to MODbus interface

Translation for BMS connection

Requires EC700

Verify requirement spec as protocol implementation may vary

Advanced Hardware
MODbus Interface

Typical Example

PANEL 1 OF 2

PANEL 2 OF 2
EC200

EC700
MODBUS
SYSTEM

102

102

1000M MAX

Advanced Hardware
EC650 to BACnet interface

Translation for BMS connection

Direct network connection

Verify requirement spec as protocol implementation may vary

Advanced Hardware
BACnet Interface

Typical Example

PANEL 1 OF 2

PANEL 2 OF 2
EC650
BACNET
SYSTEM
102

102

1000M MAX

Network
Standard Network Setup
At each control panel

Number of panels on network


Panel Address
E.g., Panel 1 of 4

Network Response (to commands received)

Silence
Reset
Evacuate
Fire
Fault
Pre Alarm

Network Filter

Select which Panels to respond to

Operation
Fault Finding a Network
Lon Network Error

Check panel address and totals settings


Check network termination
Check network cable insulation and continuity readings

Misc

Hard reset panel, then clear watchdog fault with soft reset
Generate fire or fault and check transmission and reset