Introduction
System Schematic
ADDRESSABLE SPUR CIRCUIT
LOOP 1
ADRRESSABLE
LOOP
CONVENTIONAL SOUNDERS
~
~
CONVENTIONAL
SOUNDERS
LOOPS 2-4
CF3000
MODBUS OUTPUT
TO BMS SYSTEM
CW9000
CTPR3000
EC200
NC
NC
SITE MONITOR
SYSTEM
SITE GRAPHICS
SYSTEM
EC700
EXT
24V
CFSFL01
LON-FO
BACNET OUTPUT
TO BMS SYSTEM
EC650
EXT
24V
ECO232
ECO232
NC
FIBRE OPTIC
LOCAL AREA NETWORK
NC
NC
EC400
CF1100/1200
EC400
UP TO MAX 126 NETWORK NODES
EXT
24V
EC540
CF3000
Introduction
Network Schematic
Max 126 nodes
Control Panels, Network Repeaters, Network Modules
Topology
Fire rated RS485 screened twisted pair, ie, Draka 910234
1000m cable max of copper network between boosters
Data Available
Panel Number, Loop Number, Device No. / Desc / type, Zone No. / desc
MODBUS OUTPUT
TO BMS SYSTEM
CF3000
CW9000
CTPR3000
EC200
NC
NC
SITE MONITOR
SYSTEM
SITE GRAPHICS
SYSTEM
EC700
EXT
24V
CFSFL01
LON-FO
BACNET OUTPUT
TO BMS SYSTEM
EC650
EXT
24V
ECO232
ECO232
NC
FIBRE OPTIC
LOCAL AREA NETWORK
NC
NC
EC400
CF1100/1200
EC400
UP TO MAX 126 NETWORK NODES
EXT
24V
EC540
CF3000
Introduction
Advanced Network Modules Range
NCDR
CFSFL01/02
LON (network) to BMS Gateway
EC650
LON (network) to RS232: Site Graphics & Site Monitor
EC200
LON (network) booster, splits network and resends data to increase range
ECO232
LON (network) to TCP/IP interface
EC540
LON (network) to Fibre Optic interface, max 15K FO length
EC400
Dual Redundancy Network Card (V2)
LON (network) to BACnet interface
EC700
BMS Gateway to ModBus interface
Standard Hardware
Standard Network Card Connections
Cable
Screening
Remove resistors at all network cards except the two ends
102 at each end = 51 across network
Ring Network
Resistor termination 102 (2 x 51 ) per card
Radial Network
Connect screen to ground at one end only
Termination
Enhanced fire rated data cable, Max 1000m length
Draka 910234 2 core twisted pair with screen
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
NETWORK
CONNECTIONS
A-X, B-Y
Y
X
B
IN
A
OUT
EC540 Booster:
treat the network either side as separate networks
TERMINATION
RESISTORS
RIBBON CABLE TO
CONTROL PANEL
Standard Hardware
Standard Network Termination
Radial Network
Remove resistors at all network cards except the two ends
102 at each end = 51 across network
PANEL 1 OF 4
PANEL 2 OF 4
102
PANEL 3 OF 4
NONE
PANEL 4 OF 4
NONE
102
Standard Hardware
Standard Network Termination
Radial Network with Booster
Remove resistors at all network cards except the two ends
102 at each end = 51 across network
PANEL 1 OF 4
PANEL 2 OF 4
PANEL 3 OF 4
EC540
BOOSTER
24V SUPPLY
102
NONE
102
102
TO NEXT
PANEL ETC
Standard Hardware
Standard Network Termination
Ring Network
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
PANEL 1 OF 4
PANEL 2 OF 4
51
PANEL 3 OF 4
NONE
PANEL 4 OF 4
NONE
NONE
Standard Hardware
Standard Network Termination
Resistor Termination on network card
Radial Network
102 (2 x 51 resistor)
To give 51 reading across network pair at any point
Remove resistors at all network cards except the two ends
102 at each end = 51 across network
Ring Network
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
51
A
B
51
All (102 )
A
B
51
51
LEAVE ALL
RESISTORS INTACT
One (51 )
None (no resistor)
A
B
A
O/C
CUT HERE TO REMOVE
FROM CIRCUIT
51
S/C
SOLDER LINK ACROSS
ONE RESISTOR
Terminal Mounted
102
SOME DEVICES MAY NOT HAVE
INBUILT RESISTORS
Advanced Hardware
NCDR: Network Card Dual Redundancy
Dual Network Channels
Cable
Enhanced fire rated data cable, Max 1000m length
Draka 910234 2 core twisted pair with screen
Screening
SCREEN
CONNECTIONS
Connect screen to ground at one end only
Termination
As per standard network card, but for each channel
NETWORK 2
CONNECTIONS
IN-OUT
NETWORK 1
CONNECTIONS
IN-OUT
OUT
IN
Y
X
B
OUT A
IN
TERMINATION
RESISTORS
RIBBON CABLE TO
CONTROL PANEL
Advanced Hardware
NCDR: Network Card Dual Redundancy
Dual Network Channels
Network 1 and Network 2
Automatic Switching in event of fault
Network Protocol V2 option must be selected
PANEL 1 OF 4
51
PANEL 2 OF 4
51
PANEL 3 OF 4
NONE
NETWORK CHANNEL 1
NETWORK CHANNEL 2
PANEL 4 OF 4
NONE
NONE
Advanced Hardware
CFSFL01/02: Lon (Network) to Fibre Optic Interface
Single or Dual Channel
Requires 2 for a dual network
Fibre
Single Mode x 2 (Tx & Rx)
9/125 micron
15Km max
SC Type connectors
24V DC
0V
FIBRE
CONNECTIONS
SCREEN
NETWORK A
NETWORK B
Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface
Single Channel network
Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
PANEL 3 OF 4
NONE
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
NONE
102
24V DC
Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface
Single Channel network
Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
NONE
PANEL 3 OF 4
24V DC
1021
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
24V DC
102
24V DC
Advanced Hardware
CFSFL02: Lon (Network) to Fibre Optic Interface
Dual Channel network
Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
24V DC
PANEL 3 OF 4
102
24V DC
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
102
24V DC
102
Advanced Hardware
CFSFL01/2: Lon (Network) to Fibre Optic Interface
Many possible combinations
PANEL 3 OF 7
102
PANEL 1 OF 7
PANEL 5 OF 7
102
PANEL 2 OF 7
PANEL 4 OF 7
PANEL 6 OF 6
PANEL 7 OF 7
24V DC
24V DC
24V DC
24V DC
24V DC
102
102
102
102
102
CFSFL01 or
CFSFL02
CFSFL02
CFSFL02
CFSFL02
CFSFL01 or
CFSFL02
2 x SINGLE MODE FIBRE
Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface
Network via PC network / internet / etc
Requires 2 for a dual network
Use Hyper Terminal for configuration
IP address
Inbuilt Web Server for IP configuration
IP address
Passwords
PROGRAMMING
NETWORK
CONNECTION
ETHERNET
CONNECTION
24V
DC
Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface
Requires fixed IP address
Useful for facilities management
PANEL 3 OF 3
24V DC
PANEL 1 OF 3
PANEL 2 OF 3
24V DC
NETWORK
NETWORK
Advanced Hardware
EC540: Lon (Network) Booster
Extend radial network length
Effectively splits a network into multiple networks
Requires 2 for a dual network
Max 5 per network
Any more may cause transmission delays
24V DC
NETWORK
CONNECTION
Advanced Hardware
EC540: Lon (Network) Booster
Radial Network
Terminate network either side of booster
PANEL 1 OF 3
PANEL 2 OF 3
PANEL 3 OF 3
24V DC
102
NONE
1000M MAX
102
102
102
1000M MAX
Advanced Hardware
EC0232: Lon (Network) to RS232 Interface
PC connection
No network address required
Versions
EC0232: Site Monitor, Site Graphics,
EC0232PAVA: EVAX HMX PAVA
EC0232PAVA3D: EVAX HMX PAVA 3 minute time delay
Advanced Hardware
EC0232: Lon (Network) to RS232 Interface
Typical Example
PANEL 1 OF 2
SITE GRAHICS OR
SITE MONITOR
PANEL 2 OF 2
EC0232
102
102
1000M MAX
Advanced Hardware
EC200: Lon (Network) to BMS Gateway
Translation for BMS connection
Requires EC700
Advanced Hardware
EC700: BMS Gateway to MODbus interface
Translation for BMS connection
Requires EC700
Verify requirement spec as protocol implementation may vary
Advanced Hardware
MODbus Interface
Typical Example
PANEL 1 OF 2
PANEL 2 OF 2
EC200
EC700
MODBUS
SYSTEM
102
102
1000M MAX
Advanced Hardware
EC650 to BACnet interface
Translation for BMS connection
Direct network connection
Verify requirement spec as protocol implementation may vary
Advanced Hardware
BACnet Interface
Typical Example
PANEL 1 OF 2
PANEL 2 OF 2
EC650
BACNET
SYSTEM
102
102
1000M MAX
Network
Standard Network Setup
At each control panel
Number of panels on network
Panel Address
E.g., Panel 1 of 4
Network Response (to commands received)
Silence
Reset
Evacuate
Fire
Fault
Pre Alarm
Network Filter
Select which Panels to respond to
Operation
Fault Finding a Network
Lon Network Error
Check panel address and totals settings
Check network termination
Check network cable insulation and continuity readings
Misc
Hard reset panel, then clear watchdog fault with soft reset
Generate fire or fault and check transmission and reset