Application Guide AC Pilot Wire Relaying System SPD and SPA Relays
Application Guide AC Pilot Wire Relaying System SPD and SPA Relays
Application Guide
AC Pilot Wire Relaying System
SPD and SPA Relays
CONTENTS
Summary of Features.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description & Operating Principles-SPD Relay .......................
Settings & Characteristics ..........................................
Application ........................................................
Calculation of Settings .............................................
Ground Sensor Connection ........................................
Description & Operating Principles-SPA Relay .......................
Pilot Monitoring ...................................................
Transfer Tripping ..................................................
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection of Pilot Wires .............................................
Ground Potential Rise .............................................
Induced Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lightning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elements of Pilot Wire System .......................................
Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
3
4
4
6
10
11
13
13
14
15
16
17
17
19
20
20
23
APPLICATION GUIDE
AC PILOT WIRE RELAYING SYSTEM
SPD AND SPA RELAYS
INTRODUCTION
The Type SPD relay provides selective high-speed
clearing of all faults on a protected line, using a
pilot wire circuit to compare line currents at all terminals of the line. Simultaneous clearing at all
terminals minimizes damage, permits high-speed
reclosing and improves the transient stability of
the system.
The Type SPA static auxiliary relays provide continuous monitoring of the pilot wire circuit to detect
open, shorted, reversed or grounded pilot wires.
Models are also available to provide for transfer trip
in addition to the monitoring function.
-F-----PHASE SEIQUENCE
NETWORK
I
SATURATING
TRANSFORMER
I
II
RESTRAINT
C I R C U I T
1 PHASE SEQlJiiCE
PILOT WIRE
- - - - - -
RESTRAINT---?=
I-
C--_______D
INSULATING
TRANSFORMERS
SATURATING
TRANSFORMER
WIRE CURRENT)
SUMMATION
LEVEL
DETECTOR -
- OUTPUT
mation amplifier output is applied to the level detector, the operating point of which is determined
by the pickup biassetting. Thesummation amplifier,
level detector and timer determine whether the
operate quantity exceeds the restraint quantity by
more than the pickup bias setting for a time interval
longer than the timer setting. When this occurs the
5/5 timer will initiate a trip output. The timer designation 5/5 defines operate and reset times of 5
milliseconds.
n-
le
TO
CURRENT
TRANSFORMERS ,c
THREE
PHASE
PICKUP
AMPERES
TO
PILOT
WIRE
VOLTAGE
MEASURING
UNIT
CURRENT
MEASURING
UNIT
ISOLATION
TRANSFORMER
RESTRAINT
TAP
l
HI
_-
I
L____
I
i,
o
LO
I
I
RESTRAINT
t,
TARGET
AND
II
SUMMING
AMPLIFIER
DETECTOR
and the pilot wires disconnected at the relay terminals. With single-end feed and pilot wires connected to relays at both ends of a two terminal line,
the factors in the table would be doubled, neglecting
the effect of the pilot wires. The information in Table
I, as well as the effect of the pilot wires on relay
pickup, is discussed in more detail in the section on
APPLICATION.
Table I shows that the phase-to-phase tap position C provides the best sensitivity (lowest pickup)
for phase faults, and also the closest agreement
between the pickup currents for three-phase and
phase-to-phase faults. Since it is true in most cases
that the positiveand negativesequence impedances
are equal, fault current for a phase-to-phase fault
will be 86 percent of the current for a three-phase
fault at the same location and with the same system
conditions. Thus, use of the C tap assures that the
relay will operate for the minimum expected phaseto-phase fault if it operates for the minimum threephase fault at the same location.
If the three-phase pickup tap is set below maximum possible load with the C tap setting, the relay
may operate on some load conditions if the pilot
Table 1
Relay Pickup in Multiples of Three-Phase Pickup
Tap Setting*
Phase-Phase
*Available three-phase pickup taps are 4, 5,6, 7,8, 10 and 12 amperes. Relay pickup forsingle-end feed with the pilot wires disconnected from the relay terminals can be found by multiplying the three-phase current tap setting in amperes times the factor in the
table for the particular fault type and the phase-to-phase & ground tap settings.
**When the A tap is used the relay will not respond to balanced 3-phase faults.
#When the F ground tap is used the relay will not respond to the zero sequence component of fault current, but will respond to the
positive and negative sequence components, resulting in the pickup multiple shown in the table.
Refer to Instruction Book GEK-49794 and Apparatus Handbook Section 7278 for further information on the SPD relay.
GROUND
SENSOR CT
GROUND
SENSOR CT
PROTECTED LINE
_-----~
NETWORK
SATURATING
TRANSFORMER
c________s
INSULATING TRANSFORMERS
SATURATING
TRANSFORMER
Figure 5. Simplified Functional Diagram of the SPD Relay System With Ground
Sensor CT Connection for Resistance Grounded Systems
OPERATING TIMES
Pickup time of the Type SPD relay, expressed as a
multiple of pickup, is shown in Figure 6. With heavy
fault currents of four times pickup or more, the
pickup time will be 15 milliseconds or less.
Dropout time, expressed in terms of fault current
prior to the clearing of a fault as a multiple of relay
pickup, is shown in Figure 7.
10
1
J
1.5
I
2
Figure 6. Pickup Time of the SPD Relay Vs. Multiple of Pickup Current
50
40 B
5
0 30#
5
d
5
Ft
F
5 20 0
B
5
10
10
APPLICATION
The ac pilot wire system using the type SPD relay
provides selective high-speed protection for phase
and ground faults on two- or three-terminal lines of
short to medium length. The basic scheme requires
one SPD relay at each terminal of the protected
line and an interconnecting pilot wire pair. Application limitations and determination of relay settings
are discussed in the following paragraphs.
THE PILOT WIRES
The pilot is a twisted pair of wires connected between the two (or three) terminals of the protected
transmission line. The SPD circuit will impose no
more than 60 volts peak on the pilot pair, so the
insulation capability of the pilot should be based on
the maximum induced voltages that may occur in
the pilot circuit, with the proper protection installed.
(See section on protection of the pilot).
The limitation on pilot length is determined by
the acceptable magnitudes of the loop resistance
and the shunt capacitance. For two-terminal lines it
is recommended that the series resistance of the
pilot loop, including the neutralizing reactor windings if present, not exceed 2000 ohms and that the
shunt capacitance be less than 1.5 microfarads. For
three-terminal lines the pilot circuit must be in the
form of a T connection as shown in Figure 8. It is
recommended that the two-way resistance of each
STATION A
RELAYS
CENTER
TAP
STATION B
RELAYS
1
STATION
C RELAYS
10
PILOT WIRE
SECTION WHOSE
CAPACITANCE MAY
NOT BE INCLUDED IN
POWER LINE
PILOT
WIRE
TE
PILOT WIRE
TAP TO COMPLETE
TION
TAP TO COMPLETE
11
[]
lL
M
If the current tap T determined in B satisfies equation (3), proceed to step D below. If the selected
current tap T does not satisfy equation (3), the relay
as set may not detect the minimum three-phase fault
on the protected line. The user then has two options:
IT = m i n i m u m t h e o r e t i c a l t h r e e - p h a s e
pickup tap; use next higher available
three-phase pickup tap (T).
[_]
lF
MNP
(3)
where:
T = three-phase pickup tap setting (determined in B)
lF = minimum 3-phase fault current at fault
location, sum of contributions from all
terminals
P = factor from Figure 10 for total capacitance of pilot wire (near-end curve)
M = multiple for phase-to-phase tap (1.0 for
C tap)
N = number of line terminals
2.0
PICK UP
PER U N I T
PER RELAY
1.0
EQUALS 1333 TIMES
CAPACITANCE IN MFD)
.5
12
(4)
P = factor from Figure 10 for actual capacitance of pilot wire (use near-end
curve)
The three-phase pickup amperes tap, the phaseto-phase tap, the ground tap and the restraint tap
must be set in the same position in the relays at all
terminals of the protected line.
GROUND SENSOR CONNECTION
On applications where the required sensitivity on
single-phase-to-ground faults is not realized, the
ground sensor CT connection shown in Figure 5
should be considered. This condition will typically
be encountered on resistance grounded systems,
where the ground fault current is primarily determined by the grounding resistor. In such cases the
ground fault current is substantially less than the
Table II
SPA1 28
*Refer to Instruction Book GEK-65512 and Apparatus Handbook Section 7278 for further information on the SPA relays.
13
FEATURES
In the transmitting or sending end relays, solid
state detection circuits operate undercurrent (UC),
overcurrent (OC) and ground (GND) units, each with
output contacts and associated light emitting diode
(LED). In the receiving end relays the solid state
circuit operates an undercurrent unit with alarm
contacts and LED. Powerforthesolidstatedetection
circuits and monitoring current is provided by an
isolated dc power supply. This isolation of the dc
source prevents a ground in the battery supply from
beingreflectedintothepilotwirecircuitandpossibly
causing a misoperation of the SPD scheme.
PILOT MONITORING
A typical installation of the pilot monitoring
scheme is illustrated by the simplified functional
diagram in Figure 11. This scheme requires a transmitting end relay, model SPA11A, and a receiving
end relay, model SPA12A. The scheme operates by
circulating a low-level current of approximately
0.75 milliamperes dc through the pilot wire circuit.
This current is initiated by the power supply in the
transmitting end relay and circulates through the
relay circuit at the receiving end. It provides the
reference to determine whether the pilot circuit is
SPD
open or shorted. With normal pilot wires the undercurrent units in both the transmitting end and receiving end relays will be held in the operated position by the 0.75 ma circulating current. This normal
circulating current is not sufficient to cause operation of the overcurrent unit in the transmitting end
relay.
Since the transmitting and receiving end monitoring relays are effectively in series with the pilot
wire loop, it is necessary to provide a low-impedance
bypass for the ac current circulated between the
SPD relays at each end. This system-frequency
bypass is provided by capacitors mounted internally
in the SPA relays and connected in parallel with the
relay circuit, as shown in Figure 11.
OPEN PILOT
An open circuited pilot wire will cause the monitoring current to fall to zero. The undercurrent units
(UC) in both the transmitting and receiving end
relays will drop out, the UC contacts will close, and
the LED indicators for the UC function will light.
SHORTED PILOT
A shorted pilot loop will result in an increase in
the monitoring current at the transmitting end, and a
NEUTRALIZING
REACTOR
NEUTRALIZING
REACTOR
SPD
r
I
+
____
+
-_-----mm
J;--l
ISOLATION
7r
,I
_-----(IF LINE IS
THREE-TERMINAL)
SPAlPA
RECEIVING END
i 13-l
!
?-I
ALARM
BLOCK
SPD
SPAl2A
SPD
RECEIVING END
SPA11A
SENDING END
14
NEUTRALIZING
REACTOR
NEUTRALIZING
ISOLATION
u
l-l
1I
STATIC
,CTCPTlnU
iI
L---L_I
lmSAME CONNS. ASI
RIGHT HAND
I
T E R M I N A LI
(IF LINE IS
THREE-TERMINAL)
\
INITIATE
TRANS.
TRIP
BL;ICKTTRIP
SPD
SPA110
TRIP
SPA12B
15
THREE-TERMINAL LINES
Application of the monitoring/transfer trip
schemes to three-terminal lines is represented by
the dashed connections in Figures 11 and 12, which
show the addition of the third terminal. The only
difference in the circuit is that a link in the receiving
end relays must be placed in the three-terminal
position.
CHARACTERISTICS
Detection levels of the undercurrent units (UC) in
the transmit and receiving end relays are listed in
Table III:
Table Ill
UC Unit Detection Levels
Relay
Line
Terminals
UC Level
SPA1 1A or -B
0.53 ma or less
SPA11A
A or-B
0.43 ma or less
SPA1 2A or -B
0.53 ma or less
SPA12A
A or-B
0.21 ma or less
Table V
Transfer Trip Times
Pilot
Resistance
0 Ohms
2000 Ohms
Operate*
Time
Reset*
Time
4 cyc.
5 cyc.
6 Cyc.
6 Cyc.
*60 Hz base.
STATION A
I
I
I
I
RELAY
J CASE
r - - - - - - - l
I
PILOT
SHEATH
RELAY
CIRCUIT
PILOT
WIRES
17
4
POTENTliL OF
STATION GROUND MAT
I
VOLTAGE PROFILE IN
/ VICINITY OF SUBSTATION
On the other hand, a common mode voltage difference, as a the result of the station ground potential rise, will attempt to force current through
the two windings in the same direction and will
therefore be opposed by the magnetizing impedance of the neutralizing reactor. The capacitors
connected to ground at the midpoint of the SPD
insulating transformer and the stray capacitance to
ground of the pilot wires complete the path for the
reactor magnetizing current resulting from the potential difference between station ground and remote ground. Since most of the voltage drop from
this circulating magnetizing current will appear
across the reactor windings, the relays and pilot
connections on the station side of the reactor will
be elevated in potential to essentially the same level
as the station ground mat, as illustrated by the voltage profile in Figure 15.
A______&_
c REMOTE GROUND
POTENTIAL
The voltage profile also reveals that the neutralizing reactor itself and a section of the pilot wire cable
adjacent to the station may still be subjected to
excessive voltage stresses during a station ground
potential rise. For this reason a neutralizing reactor
that can withstand the full ground potential rise
NOTGROUNDED
NEUTRALIZING
REACTOR
l--P
SPA
,STATlON
.
.
REMOTE GROUND
POTENTIAL
VOLTAGE PROFILE
18
INDUCED VOLTAGES
MUTUAL
DRAINAGE
REACTOR
GAS TUBE
NEUTRALIZING
REACTOR
SPD
REMOTE
It- GROUND
\ PILOT WIRE
TO OTHER
TERMINAL
Figure 16. Typical Use of Mutual Drainage Reactor and Gas Tube
19
needed as typified by Figure 17. The protection provided by the arresters should coordinate with the
insulation withstand capability of the neutralizing
reactor and the pilot pair. It is essential that the
arresters reseal with nominal ac and dc currents
flowing in the pilot pair. It is for this reason that
lightning arresters rather than carbon blocks are
recommended. The arresters should be remotely
grounded outside the zone of influence so that they
do not operate on a ground potential rise, since the
neutralizing reactors protect against this condition.
LIGHTNING
Control equipment in substations is generally so
well shielded against severe voltage surges caused
by lightning that direct protection may not be necessary. The pilot wire system differs from other
control equipment in that it runs over a considerable
distance from one substation to another and hence
is exposed to lightning. Lightning induced voltages
may exceed the pilot insulation capability, and if this
is possible, lightning arrestors may be applied as
As shown in Figure 17, a gas tube is usually connected from wire to wire of the pilot pair when arresters are used. The purpose of this gas tube, which is
supplied with the neutralizing reactor, is to short
the two wires together should one arrester fire and
not the other. This will prevent a high voltage between the pilot pair which could cause a false trip
by the SPD relay during arrester discharge. It is
essential that the gas tube be left ungrounded so
that it does not provide a path to the ground.
STATION
GROUND
SHIELD
STATION
GROUND
SHIELD
GAS TUBE
r (NO GROUND) ,
1
NEUTRALIZING
REACTOR
PILOT
WIRES
NEUTRALIZING
REACTOR
rm
SPD
TL
SPD
LIGHTNING
ARRESTERS
El
SPA
ELEMENTS OF THE
PILOT WIRE SYSTEM
The elements of the ac wire pilot scheme and
their functions, which were discussed in detail in
earlier sections. are summarized in Table VI. As is
apparent from the table the major components of
the system, some of which are supplied by the user,
are the following:
1. Pilot wire relay, type SPD, and associated
equipment.
20
Table VI
Items Included in SPD Pilot Wire Scheme
ORDERED ITEM
INCLUDED
SPDllA
Test Switch
Ammeter & Transformer
FUNCTION
REMARKS
REQUIRED OR OPTIONAL
Required
SPA11A
Pilot Monitor
Transmit End
Optional
:AllB
Transmit End
Optional
SPAIZA
Pilot Monitor
Receive End
Optional
SPA128
Receive End
Optional
Neutralizing
Reactor
(0257A9787G3)
Required if calculations
indicate insulation
withstand capability
will be exceeded.
Optional
Or
21
SPD
Relay
Milliameter
Meter
Range-Changing
CT
Test
Switch
SPA Relay
(See Table II)
Figure 18
Mutual
Drainage
Reactor
Neutralizing
Reactor
Figure 19
22
Excitation
Assembly
BIBLIOGRAPHY
1. Committee Report, Application and Protection of Pilot Wire Circuits for Protective
Relaying. Sponsored by the Pilot Wire Subcommittee, AIEE Relays Committee, July,
1960 (Publication S-117).
2. Committee Report, The Isolation Concept for Protection of Wire Line Facilities Entering
Electric Power Stations. Sponsored by the Power System Communications Committee,
IEEE Power Engineering Society. IEEE Trans. (Power Apparatus & Systems) 1976,
pages 1216-33.
3. Committee Report, The Neutralizing Transformer Concept for Protection of Wire Line
Facilities Entering Electric Power Stations. Sponsored by Power System Communication Committee, IEEE Power Engineering Society. IEEE Trans. (Power Apparatus &
Systems) 1977, pages 1256-79.
4. A Guide for the Protection of Wire Line Communications Facilities Serving Electric
Power Stations, IEEE Standard 468 published 1980.
5. J. F. Laidig and F. P. Zuper, A Practical Ground Potential Rise Prediction Technique for
Power Stations. Presented at IEEE-PES Winter Meeting, 1979.
23
*(3RZHU0DQDJHPHQW
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222
Fax: (905) 201-2098
www.GEindustrial.com/pm