Laminated Sheath XDRCU-ALT
XDRCU-ALT Single-core Cable for
220/127 (245) kV
with Copper wire screen and Aluminium laminated
sheath
Construction
*
*
*
Copper conductor, round stranded or segmented, optionally with longitudinal water
barrier
Inner semi-conductive layer firmly bonded to
the XLPE insulation
XLPE main insulation, cross-linked
Outer semi-conductive layer firmly bonded to
the XLPE insulation
Copper wire screen with semi-conductive
swelling tapes above and below as longitudinal water barrier
Aluminium foil, overlapped and glued as radial
diffusion barrier bonded to the oversheath
Thermoplastic oversheath as mechanical protection, optionally with semi-conductive
and/or flame-retardant layer
220/127 kV
Remarks
The inner semi-conductive layer, the XLPE main
insulation and the outer semi-conductive layer
are extruded in a single operation applying a dry
curing and a water or nitrogen cooling method.
Features
*
*
*
*
*
Low weight
Low losses
Low cost
Internationally proven design
Suitable for most applications
Standards
IEC 62067
ICEA S-108-720
AEIC CS9-06
Technical data
Conductor Outer diame- Cable weight AC resistance AC resistance
cross-section ter (approx.)
(approx.)
Reactance
Reactance
Capacitance Min. bending Max. pulling
radius
force
mm
mm
kg/m
m/km
m/km
m/km
m/km
F/km
mm
kN
400
500
630
800
1000
1200
1400
1600
2000
2500
96
97
97
101
104
108
111
115
119
126
12
13
14
16
18
20
22
25
29
34
61.6
48.9
39.0
31.9
27.0
20.4
17.8
16.0
13.4
11.5
60.2
47.0
36.5
28.8
23.2
20.1
17.4
15.5
12.8
10.8
148
141
132
126
120
115
111
110
107
104
234
227
218
209
201
194
188
185
180
173
0.124
0.136
0.156
0.173
0.193
0.220
0.239
0.249
0.263
0.287
2000
2000
2000
2100
2100
2200
2300
2300
2400
2600
24
30
38
48
60
72
84
96
120
150
Capacity
20130316-1
Subject to change without notice
Installation
Amb. temp.
Soil resist.
Load factor
Cross-section
mm
400
500
630
800
1000
1200
1400
1600
2000
2500
1.0
1.0
678
769
872
976
1072
1240
1333
1410
1540
1668
20 C
1.0 Km/W
35 C
in air
0.7
0.7
744
849
972
1098
1219
1397
1514
1610
1780
1954
802
915
1044
1176
1299
1510
1631
1729
1895
2064
862
989
1140
1296
1448
1670
1818
1937
2150
2374
818
942
1090
1245
1395
1647
1802
1924
2134
2365
899
1043
1221
1411
1602
1877
2072
2224
2497
2808
Calculation basis: Conductor temperature: 90C, Frequency: 50 Hz, Laying depth: 1200 mm, Phase distance at flat formation:
30 cm, Earthing method: Single-Point Bonding or Cross-bonding
Values apply for cables with rated voltages from 220 kV to 230 kV acc. to IEC 62067
HIGH VOLTAGE SYSTEMS
Phone +41 (0)56 460 3333
Fax +41 (0)56 460 3536
[email protected]