0% found this document useful (0 votes)
350 views

01-Data Sheet Fire Alarm System

This document provides specifications for a fire alarm system for a new office building in Cilegon, Banten, Indonesia. It includes details on the fire detection and notification devices, such as 117 smoke detectors, 117 heat detectors, 10 break glass alarms, 10 fire alarm bells, 9 beacon lights. It also specifies the operating voltages, temperatures and humidity ranges for the devices, as well as their locations, materials, and dimensions. The vendor is instructed to complete the specification and provide a certificate of compliance.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
350 views

01-Data Sheet Fire Alarm System

This document provides specifications for a fire alarm system for a new office building in Cilegon, Banten, Indonesia. It includes details on the fire detection and notification devices, such as 117 smoke detectors, 117 heat detectors, 10 break glass alarms, 10 fire alarm bells, 9 beacon lights. It also specifies the operating voltages, temperatures and humidity ranges for the devices, as well as their locations, materials, and dimensions. The vendor is instructed to complete the specification and provide a certificate of compliance.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

DR OFFICE BUILDING OF PBS & PPBS

DEPARTMENT OF PT.KS
DATA SHEET

ENGINEERING & CONTRUCTION


PT. KRAKATAU ENGINEERING

Job. No.
: 3557
Doc. No.
:
3557-05-DS-001
Rev.
:0
Page
: 1 OF 3
: 18/03/11
Date

DATA SHEET
FOR
FIRE ALARM SYSTEM

PROJECT
OWNER
LOCATION

0
Rev.

: DR OFFICE BUILDING OF PBS & PPBS DEPARTMENT


: PT. KRAKATAU STEEL
: CILEGON - BANTEN

FOR APPROVAL
DESCRIPTION

Date

Prepared

PT. KRAKATAU ENGINEERING

Checked

Approved

DR OFFICE BUILDING OF PBS & PPBS


DEPARTMENT OF PT.KS
DATA SHEET

ENGINEERING & CONTRUCTION


PT. KRAKATAU ENGINEERING

Revision historical sheet


REV. NO.

DATE

DESCRIPTION

PT. KRAKATAU ENGINEERING

Job. No. : 3557


Doc. No. :
3557-05-DS-001
Rev.
:0
Page
: 2 OF 3
: 18/03/11
Date

FIRE ALARM SYSTEM DATA SHEET

ENGINEERING & CONTRUCTION


PT. KRAKATAU ENGINEERING

GENERAL

SMOKE DETEKTOR

PROJECT TITLE
CLIENT
PACKAGE
LOCATION
JOB NO.
Tag. No.

Foundation Design

Fire Alarm System

Function

Fire Alarm detection and monitoring

Case & Color

Mfr Std

Type

Conventional (4 Zone)

Quantity

1 Unit

Type

Ionization (Indoor)

Operating Voltage

24 Vdc

Material

White Polycarbonate

Operating Temperature Range

0C - 38C

Operating Humidity Range

0%-95%RH No-Condensating

Dimention

4 inch ( Diameter )

Input Terminal
Led Indicator

HEAT DETECTOR

FIRE ALAM BELL

BEACON LAMP

Notes

1.5 mm (Min)
Normal

Off

Alarm
Quantity

Blinking
117 Unit

Type

Fixed-temperature (Indoor)

Operating Voltage

24 Vdc

Material

White Polycarbonate

Operating Temperature Range

0C - 38C

Operating Humidity Range

0%-95%RH No-Condensating

Thermal Sensor

57.2 C

Dimention

4 Inch ( Diameter )

Input Terminal
Led Indicator

BREAK GLASS ALARM

: DR OFFICE BUILDING OF PBS &PPBS DEPARTMENT


: PT. KRAKATAU STEEL
: INSTRUMENT
: CILEGON-BANTEN
: 3557

1.5 mm (Min)
Normal

Off

Alarm

Blinking

Quantity

7 Unit

Type

Push button Operational

Operating Voltage

24 Vdc

Material

Metal

Push Button Enclosure

Glass

Colour

Red

Input Terminal
Quantity

1.5 mm (Min)
10 Unit

Type

Vibration Bell (Indoor)

Gong Size

6 Inch

Operating Voltage

220 Vac / 24 Vdc

Sound Level

76 - 94 dB

Tone

Continued

Input Terminal

2.5 mm (Min)

Housing

Heavy duty die cast

Colour
Quantity

Red
9 Unit

Type

Beacon lamp (Indoor)

Size

5 Inch

Operating Voltage

220 Vac / 24 Vdc

Input Terminal

2.5 mm (Min)

Lens Colour

Red

Light Mode
Quantity

Blinking
4 Unit

: - The Vendor shall complete this specification


- Delivery c/w Standard Certificate

PAGE 3 OF 3
REV

DATE

17/03/2011

PREP. BY

ELV

CHECK BY PEN
APP. BY

M.AG

You might also like