The document summarizes test results for two dry type transformers with ratings of 2500 kVA, 11 KV/420V. Key tests included insulation resistance, magnetizing current, magnetic balance, vector group, voltage ratio, and winding resistance tests. Test results such as insulation resistances above minimum values and voltage and current measurements within expected ranges demonstrated that performance met specifications for both transformers.
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
357 views

Dry Type Transformer 1DAT01

The document summarizes test results for two dry type transformers with ratings of 2500 kVA, 11 KV/420V. Key tests included insulation resistance, magnetizing current, magnetic balance, vector group, voltage ratio, and winding resistance tests. Test results such as insulation resistances above minimum values and voltage and current measurements within expected ranges demonstrated that performance met specifications for both transformers.
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 6

TESTING PROTOCOL

2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

TEST REPORT FOR TRANSFORMER

Date: 06.05.2014

Plant

2X600 JINDAL INDIA THERMAL POWER


PROJECT,ANGUL,ORISSA

Location
System

LT Switchgear
Dry type Transformer-2DAT01

Specification
Make
Type of Cooling
Rating
Voltage
Amps
% Impedance
Vector Group
Frequency
Serial no.

BHEL
AN
2500kVA
11 KV
420V
131.22 A
3436.61 A

HV
HV
LV
HV
LV
10% is TOL

Tap NO
1
2
3
4
5

11550
11275
11000
10275
10450

420

Insulation Resistance:
Reference

Voltage Applied

1 Min Value

HV - Earth
LV - Earth
HV- LV

5000 V
500 V
5000 V

235 G
> 1 G
141 G

Magnetizing Current Test:


Applied Voltage in Volts

Measured Current in mA

1U1V

1V1W

1W1U

1U

1V

1W

412

412

411

18.2

15

11.5

412

408

407

17.8

16.5

12.3

415

413

411

17.6

13.3

11.1

409

405

404

20.3

17.3

12.7

410

406

403

19.3

17.4

13.5

Magnetic Balance Test HV SIDE:(Normal Tap-3)

M/s HVEPL
Signature
Name

LV (VOLTS)

Dyn11
50 Hz
2028727

Tap no

HV (VOLTS)

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

Applied terminal
1U1V
415
172.6
83.6

1U1V
1V1W
1W1U

Magnetic Balance Test LV SIDE:


Applied terminal
2U2N
2U2N
230
2V2N
115.9
2W2N
86.6

Measured Voltage in Volts


1V1W
308.1
411
333.9

1W1U
112.8
242.9
412

Measured Voltage in Volts


2V2N
138.2
234.4
136.0

2W2N
86.0
113.9
228.6

Vector Group Test: (1U,2U Shorted)


CONDITION
1. 1U1V=1U2N+1V2N
2. 1V2V=1V2W
3. 1W2V>1W2W
Phases
1U1V
1U2N
1V2N
1W2V
1W2W
1V2W
1V2V

M/s HVEPL
Signature
Name

Applied Voltage in volts


414
9.16
405
411
395
399
400

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

Voltage Ratio Test:

Tap No

Applied voltage in HV side


1U1V
1V1W
1W1U
412
412
411
412
408
407
413
408
409
409
405
404
410
406
403

1
2
3
4
5

Tap
No
1
2
3
4
5

2U2V
15.14
15.51
15.92
16.18
16.64

2V2W
15.12
15.44
15.81
16.04
16.53

Measured Voltage in LV side


2W2U
2U2N
2V2N
15.19
8.74
8.71
15.50
8.94
8.90
15.90
9.22
9.16
16.11
9.31
9.21
16.63
9.60
9.51

2W2N
8.70
8.85
9.10
9.16
9.49

Winding Resistance: (in m)

1UIV
315
305
294
290
285

HV Side
IVIW
315
306
295
290
285

IWIU
315
307
295
289
286

2U2N

0.19

LV Side
2V2N

0.19

2W2N

0.20

Remarks: Test Results found satisfactory.

M/s HVEPL
Signature
Name

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

TEST REPORT FOR TRANSFORMER

Date:07.05.2014

Plant

2X600 JINDAL INDIA THERMAL POWER


PROJECT,ANGUL,ORISSA

Location
System

LT Switchgear
Dry type Transformer-2DAT02

Specification
Make
Type of Cooling
Rating
Voltage
Amps
% Impedance
Vector Group
Frequency
Serial no.

BHEL
AN
2500kVA
11 KV
420V
131.22 A
3436.61 A

HV
HV
LV
HV
LV
10% is TOL

Tap NO
1
2
3
4
5

LV (VOLTS)

11550
11275
11000
10275
10450

420

Dyn11
50 Hz
2028728

Insulation Resistance:
Reference

Voltage Applied

1 Min Value

HV - Earth
LV - Earth
HV- LV

5000 V
500 V
5000 V

123 G
> 1 G
90 G

Magnetizing Current Test:


Applied Voltage in Volts
Tap no

Signature

Measured Current in mA

1U1V

1V1W

1W1U

1U

1V

1W

418

421

417

13.9

9.9

9.8

420

423

417

14.2

10.8

10.5

417

423

417

14.8

10.8

10.6

423

425

421

15.2

11.2

11.4

423

423

421

16.7

11.9

12.3

M/s HVEPL

Name

HV (VOLTS)

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

Magnetic Balance Test HV SIDE:(Normal Tap-3)


Applied terminal
Measured Voltage in Volts
1U1V
1V1W
1U1V
417
307.1
1V1W
211.7
421
1W1U
113.6
308.1

1W1U
111.8
211
417

Magnetic Balance Test LV SIDE:


Applied terminal
2U2N
2U2N
230.6
2V2N
114.5
2W2N
85.8

2W2N
87.0
115.6
230.7

Measured Voltage in Volts


2V2N
137.2
234.1
140.2

Vector Group Test: (1U,2U Shorted)


CONDITION
1. 1U1V=1U2N+1V2N
2. 1V2V=1V2W
3. 1W2V>1W2W
Phases
1U1V
1U2N
1V2N
1W2V
1W2W
1V2W
1V2V

M/s HVEPL
Signature
Name

Applied Voltage in volts


417
9.22
408
415
403
403
405

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
TRANSFORMER

Voltage Ratio Test:

Tap No

Applied voltage in HV side


1U1V
1V1W
1W1U
418
421
417
420
423
417
417
423
417
423
425
421
423
423
421

1
2
3
4
5

Tap
No
1
2
3
4
5

2U2V
15.44
15.91
15.98
16.81
17.19

2V2W
15.35
15.79
16.05
16.69
17.06

Measured Voltage in LV side


2W2U
2U2N
2V2N
15.36
8.83
8.87
15.75
9.08
9.11
16.02
9.20
9.27
16.68
9.58
9.63
17.05
9.83
9.83

2W2N
8.82
9.09
9.22
9.58
9.76

Winding Resistance: (in m)

1UIV
318
309
301
293
285

HV Side
IVIW
318
309
301
294
285

IWIU
317
309
301
293
284

2U2N

0.16

LV Side
2V2N

0.16

2W2N

0.17

Remarks: Test Results found satisfactory.

M/s HVEPL
Signature
Name

M/s VESPL

M/s BHEL

M/s JITPL