0% found this document useful (0 votes)
17 views

Testing Protocol: 2X600 MW Jitpl, Angule, Orissa

This document summarizes test results for the stator winding and rotor of a generator at the 2x600 MW Jindal India Thermal Power Project in Angul, Odisha. Insulation resistance tests on the stator winding found results between 840 megohms to 1.96 gigohms. Winding resistance was measured at 0.94 milliohms for each phase. Insulation resistance of the rotor was 741 megohms. Rotor winding resistances were also reported. An impedance test was performed and results were found satisfactory.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

Testing Protocol: 2X600 MW Jitpl, Angule, Orissa

This document summarizes test results for the stator winding and rotor of a generator at the 2x600 MW Jindal India Thermal Power Project in Angul, Odisha. Insulation resistance tests on the stator winding found results between 840 megohms to 1.96 gigohms. Winding resistance was measured at 0.94 milliohms for each phase. Insulation resistance of the rotor was 741 megohms. Rotor winding resistances were also reported. An impedance test was performed and results were found satisfactory.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

TESTING PROTOCOL

2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR

Plant

2X600 JINDAL INDIA THERMAL POWER


PROJECT,ANGUL,ORISSA

Location
System

TG BULIDING
GENERATOR Unit# 2

Date:19.08.2014

Specification
Nomenclature
Make

STATOR WINDING
BHEL

Insulation Resistance Test:(2500 V Megger)


Ref
U-Earth(V&W Earthed)
V-Earth(U&W Earthed)
W-Earth(U&V Earthed)

15 Sec
840 M
770 M
784 M

60 Sec
1.96 G
1.45G
1.57G

Winding Resistance:
Amp. Temp: 36.10C
Phase

Winding Resistance

U
V
W

0.94m
0.94m
0.94m

Remark: Test Result found satisfactory.

M/s HVEPL
Signature
Name

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR

Plant

2X600 JINDAL INDIA THERMAL POWER


PROJECT,ANGUL,ORISSA

Location
System

TG BULIDING
GENERATOR

Date:12.08.2014

Specification
Nomenclature
Make

ROTOR
BHEL

Insulation Resistance Test:(500 V Megger)


Ref
+ Ve to Body

IR Valve
741 M

Winding Resistance:
Reference

Winding Resistance (m)

1-3
2-4
1-4
2-3

71
69
68
66

M/s HVEPL
Signature
Name

M/s VESPL

M/s BHEL

M/s JITPL

TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR

Impedance Test:
Applied Voltage in Volts
5.12
10.40
15.26
20.72
25.46
30.66
35.73
40.2
45.3
51.1
60.4
65.8

Measured Current in A
1.85
3.73
5.49
7.33
8.91
10.64
12.28
13.98
15.58
17.45
20.4
22

Calculated Impedance
2.77
2.79
2.78
2.83
2.52
2.88
2.9
2.88
2.9
2.93
2.96
2.99

Remark: Test Result found satisfactory.