Testing Protocol: 2X600 MW Jitpl, Angule, Orissa
Testing Protocol: 2X600 MW Jitpl, Angule, Orissa
2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR
Plant
Location
System
TG BULIDING
GENERATOR Unit# 2
Date:19.08.2014
Specification
Nomenclature
Make
STATOR WINDING
BHEL
15 Sec
840 M
770 M
784 M
60 Sec
1.96 G
1.45G
1.57G
Winding Resistance:
Amp. Temp: 36.10C
Phase
Winding Resistance
U
V
W
0.94m
0.94m
0.94m
M/s HVEPL
Signature
Name
M/s VESPL
M/s BHEL
M/s JITPL
TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR
Plant
Location
System
TG BULIDING
GENERATOR
Date:12.08.2014
Specification
Nomenclature
Make
ROTOR
BHEL
IR Valve
741 M
Winding Resistance:
Reference
1-3
2-4
1-4
2-3
71
69
68
66
M/s HVEPL
Signature
Name
M/s VESPL
M/s BHEL
M/s JITPL
TESTING PROTOCOL
2X600 MW JITPL,ANGULE,ORISSA.
GENERATOR
Impedance Test:
Applied Voltage in Volts
5.12
10.40
15.26
20.72
25.46
30.66
35.73
40.2
45.3
51.1
60.4
65.8
Measured Current in A
1.85
3.73
5.49
7.33
8.91
10.64
12.28
13.98
15.58
17.45
20.4
22
Calculated Impedance
2.77
2.79
2.78
2.83
2.52
2.88
2.9
2.88
2.9
2.93
2.96
2.99
M/s HVEPL
Signature
Name
M/s VESPL
M/s BHEL
M/s JITPL