Derating Factor
Derating Factor
Method of
Laying
Basic ambient
temperatureoC
Layout of cable
In case of single core cable, three single core cable side
by side at a spacing of 2d
In air
40
Direct burial
25
Soil thermal
resistivity
120oC cm/W
DERATING FACTOR OF CURRENT CARRYING CAPACITY DUE TO GROUP INSTALLATION OF CABLES IN AIR.
Number of Cables Horizontally
Spacing
Number Vertically
1
7~20
8~20
S = d
1.00
0.85
0.80
0.70
0.70
0.70
0.60
0.60
0.56
0.53
0.51
0.50
S = 2d
1.00
0.95
0.95
0.90
0.80
0.90
0.90
0.85
0.73
0.72
0.71
0.70
S = 3d
1.00
1.00
1.00
0.95
0.95
0.95
0.90
Number Vertically
Number of Cables Horizontally
Spacing
9~10
11~12
13~15
16~19
20
S = d
0.48
0.41
0.37
0.34
0.32
0.31
0.30
0.30
0.30
0.30
0.30
S = 2d
0.80
0.80
0.68
0.66
0.65
0.65
0.64
0.63
0.62
0.61
0.60
S = 3d
0.85
0.85
In air
10
1.11
1.26
15
1.07
1.22
20
1.04
1.18
25
1.00
1.14
30
0.96
1.10
35
0.92
1.05
40
0.88
1.00
45
0.83
0.95
50
0.78
0.89
55
0.73
0.84
60
0.68
0.78
73