The document is a tutorial on electrical engineering that contains 4 problems and their answers regarding transformer parameters and efficiency calculations. Problem 1 involves calculating the parameters of the equivalent circuit for a 1kVA transformer from open and short circuit test results. Problem 2 calculates the efficiency of the same transformer at various loads and power factors. Problem 3 estimates the efficiency of a 1kVA transformer at full load with a power factor of 0.9, given its maximum efficiency of 92% at 76% load and unity power factor. Problem 4 calculates the daily average efficiency of a 5kVA transformer with given core and load losses, operating under varying load conditions throughout the day.
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
30 views
Indian Institute of Technology Indore: Department of Electrical Engineering
The document is a tutorial on electrical engineering that contains 4 problems and their answers regarding transformer parameters and efficiency calculations. Problem 1 involves calculating the parameters of the equivalent circuit for a 1kVA transformer from open and short circuit test results. Problem 2 calculates the efficiency of the same transformer at various loads and power factors. Problem 3 estimates the efficiency of a 1kVA transformer at full load with a power factor of 0.9, given its maximum efficiency of 92% at 76% load and unity power factor. Problem 4 calculates the daily average efficiency of a 5kVA transformer with given core and load losses, operating under varying load conditions throughout the day.
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1
INDIAN INSTITUTE OF TECHNOLOGY INDORE
DEPARTMENT OF ELECTRICAL ENGINEERING
TUTORIAL NO. 8
COURSE NAME: Introduction to Electrical Systems 2nd Year B. Tech. (Electrical Engineering) COURSE CODE: EE 205 DATE: 10-10-2014
1. A 1kVA, 125/250V, 50 Hz, single phase transformer gave the following test result: Open circuit test (on LV side): 125V, 0.42 A, 34 W Short circuit test (on HV side): 22V, 4A, 60 W Compute the parameters of the approximate equivalent circuit referred to HV side and LV side. Also draw the equivalent circuit referred to the LV side. Ans: LV side: 459.57, 390.625 , 15 , 16.093 and 22 HV side: 114.88 , 97.65 , 3.75 , 4.023 and 5.5
2. For the same transformer as mentioned in problem 1, calculate its efficiency at a. Full load of unity p.f. b. Half load of unity p.f. c. Full load of 0.8 p.f. lag d. 2/3 rd of full load and 0.8 p.f.lag e. Calculate the load current at which maximum efficiency occurs f. Calculate the kVA load at which maximum efficiency occurs and also the value of max. efficiency at unity p.f. Ans: 91.407%, 91.07%, 89.48%, 89.78%, 3.011 A, 0.752 kVA and 91.715%
3. A 1kVA, 250/250V, 50 Hz, single phase transformer has maximum efficiency of 92 % when delivering 76% of its rated output at unity pf. Estimate its efficiency when delivering its full load output at p.f. of 0.9 lag. Ans: 90.896 %
4. A 5 kVA, single phase transformer has a core loss of 35 W and full load ohmic loss of 85 W. The daily variation of load on the transformer is as follows: 6 A.M. to 10 A.M.: 4 kW at 0.85 p.f 10 A.M. to 5 P.M. : 2.2 kW at unity p.f 5 P.M. to 12 P.M. : 3.5 kW at 0.7 p.f 12 P.M. to 6 A.M. : no load Ans: 96.79 %