This certificate summarizes test results for 3 ring type current transformers with a ratio of 200/5A. Routine tests were performed to check polarity, withstand voltages between primary/secondary and earth, inter-turn insulation, ratio and phase angle error, and composite errors. All tests found results within specified limits, certifying the transformers meet ISS: 2705-1992 standards.

Uploaded by

naveenbansal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views1 page

Alpha Electro Control Devices

This certificate summarizes test results for 3 ring type current transformers with a ratio of 200/5A. Routine tests were performed to check polarity, withstand voltages between primary/secondary and earth, inter-turn insulation, ratio and phase angle error, and composite errors. All tests found results within specified limits, certifying the transformers meet ISS: 2705-1992 standards.

Uploaded by

naveenbansal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

ALPHA ELECTRO CONTROL DEVICES

270 Dhakka, Near Kingsway Camp, Delhi:-110009


CURRENT TRANSFORMERS TEST CERTIFICATE
CT TESTED: Measuring/Protection
CT TYPE : Ring Type Insulation CT
SPECIFICATION:
System Voltage: 660V/250V
Frequency : 50HZ
Ratio : 200/5A
Burden : 5/10/15
Accuracy Class: 1.0/5.0/0.5/5P10/PS/10P10/5P20/X
Quantity : Nos.3
This is to than certify that current Transformers bearing serial Nos. given
Above have been manufactured strictly in accordance with specification: ISS: 2705-1992 to which then
confirm and following are the routine test performed.
1. POLARITY TEST: Cheeked as per Terminal marking.
2. HIGH VOLTAGE POWER FREQUENCY ONE MINUTE WITIISTAND TEST:
(1) Withstood 3KV between Primary to Secondary and earth
(2) Withstood 3KV between Secondary to Primary and earth
3. INTER TURN INSULATION TEST: Conducted as per ISS/BSS and test was satisfactory.
4. RATIO &PHASE ANGLE ERROR TEST: Tested as per ISS/BSS and the result found within
Limits specified therein.
5. COMPOSITE ERROR TESTS: Tested as per ISS/BSS and the result found within
Limits specified therein FOR PROTECTION CLASS CTS.
Customer..
Customer order no.
Works Order No..
This is to certify that above transformers has been tested by us.


Date:.. Testing Engineer