This document contains a conduit fill calculator that allows a user to enter cable information including outer diameter and quantity to calculate the total fill area for up to 10 cables. It then provides tables with trade size, inner diameter, area, and permissible fill area for various types of conduit to calculate the percentage fill. The summary entered cables with a total fill area of 0.29 square inches and found the percentage fill for a 1" rigid PVC conduit to be 34.79%, within the permissible limits.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100%(1)100% found this document useful (1 vote)
2K views
Conduit Fill Calc Latest
This document contains a conduit fill calculator that allows a user to enter cable information including outer diameter and quantity to calculate the total fill area for up to 10 cables. It then provides tables with trade size, inner diameter, area, and permissible fill area for various types of conduit to calculate the percentage fill. The summary entered cables with a total fill area of 0.29 square inches and found the percentage fill for a 1" rigid PVC conduit to be 34.79%, within the permissible limits.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6
Conduit Fill Calculator
Enter Cable ODs and Qty
Cable Information OD (in) Area Quantity Total Area Cable One 0.21 0.03 5 0.17 Cable Two 0.17 0.02 5 0.12 Cable Three 0 0 Cable Four 0 0 Cable Five 0 0 Cable Six 0 0 Cable Seven 0 0 Cable Eight 0 0 Cable Nine 0 0 Cable Ten 0 0 Total 10 0.29
NEC Chapter 9 Table 1
Number of Conductors Percentage 1 53.00% 2 31.00% over 2 40.00%