9968specification For Elasomeric Cables - 1
9968specification For Elasomeric Cables - 1
( Reaffirmed 1999 )
( First Revision )
Third Reprirlt NOVEMBER 1997
UDC
Copyright 1989
BUREAU
MANAK
OF
BHAVAN,
INDIAN
STANDARDS
ZAFAR MARG
Gr 5
May 1989
Indian Standard
(First Revision )
0. FOREWORD
insulation, conductor, test for cables. sheath and methods of
0.1 This Indian Standard (Part 1) ( First Revision )
was adopted by the Bureau of Indian Standards on 2.5 August 1388, after the draft finalized by the Power Cables Sectional Committee had been approved by the Electrotechnical Division Council. 0.2 This standard was originally published in 1981. This revision has been brought out to take into account the experience gained since then. The opportunity has also been utilized to align the format of this specification with other specifications for different types of cables and to make reference to latest Indian Standards on
0.3 For the purpose of deciding whether a particular requirement of this st.andard is complied with, the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS : 2-1960*. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard. *Rules for rounding off numerical values ( revised
).
SECTION 1. SCOPE
GENERAL
standard specifies the requirements of elastomeric insulated cables for fixed wiring, flexible cables and flexible cords for electric power and lighting for operation at voltages up to and including 1 100 volts. 1.2 The following types of cables and cords are covered in this standard. 1.2.1 Cables for Fixed Wiring a) Braided and compounded/varnished, b) Elastomer sheathed ( normal duty ), and c) Elastomer sheathed ( normal earth continuity conductor. 1.2.2 Flexible Cables a) Braided and varnished, and b) Elastomer sheathed ( heavy duty ). 1.2.3 Flexible Cords a) Braided b) Elastomer sheathed ( normal duty ),
1
1.1 This
c) Unkinkable flexible cords - braided compounded ( workshop type ), and d) Unkinkable flexible cords compounded.
and
braided and
1.3 The cables covered in this standard are suitable for use on single-phase or three-phase ( earthed or unearthed ) system for rated voltages up to and including 1 100 volts. These cables may be used on dc system for rated voltages up to and including 1 500 volts to earth. 1.4 The cables covered in this standard are suitable for use where the combination of ambient temperature and temperature rise due to load results in conductor temperature not exceeding the following:
Type of Insulation Normal Continuous Operation Short-Circuit Condition
duty ) with
Insulation for general service Heat resisting insulation Silicone rubber insulation
facturer on all finished cable lengths demonstrate the integrity of the cable.
to
2. TERMINOLOGY 2.0 For the purpose of this standard, the definitions given in IS : 1885 ( Part 32 )-1971* shall apply, in addition to the following.
2.1 Routine Tests Tests made
2.2 Type Tests - Tests required to be made before supply on a general commercial basis a type of cable in order to demonstrate satisfactory performance characteristics to meet the intended application.
NOTE-These tests are of such a nature that, after they have been made, they need not be repeated unless changes are made in the cable materials or design which characteristics. might change the performance
*Electrotechnical
conductors and
vocabulary : Part
for electricity
accessories
2.3 Acceptance Tests - Tests carried out on samples taken from a lot for the purpose of acceptance of the lot.
MATERIALS 6. FILLERS
SECTION
3. CONDUCTOR 3.1 Copper Conductor - The conductor shall be tinned annealed copper wires complying with the requirements of IS : 8130-1984*.
NOTE - The use of plain copper conductor is also p&missible for cables with silicone rubber insulation.
6.1 The fillers shall be of natural or synthetic fibres or elastomer. The filler material shall be suitable for the operating temperature and compatible with the insulating material. 7. BRAID 7.1 Textile Braid - The textile braid shall consist of textile material ( natural or synthetic ), such as cotton, artificial silk mercerized or rayon ( excluding jute or hemp ). 7.2 Glass Braid - The glass braid shall consist of glass fibre yarn of suitable quality. 8. SHEATH 8.1 General Service Insulated Cables and Flexible Cords 8.1.1 Cables for Fixed Wiring and Flexible The sheath shall consist of elastomeric compound complying with the requirements of Type SE 1 of IS : 638O-1984*.
Cords -
3.2 Aluminium Conductor - The conductor shall be composed of aluminium wires complying with the requirements of IS : 8130-1984*. 3.3 A separator tape made of suitable material may be applied over the conductor. 4. INSULATION 4.1 Insulation for General Service - The insulation shall be of elastomer compound conforming to Type IE 1 of IS : 6380-1984t. 4.2 Heat Resisting Insulation - The insulation shall be of elastomer compound conforming to Type 1E 2 of IS : 6380-19847. 4.3 Silicone Rubber Insulation - The insulation shall be of silicone rubber conforming to Type IE 5 of IS : 6380-1984t. 5. TAPE
5.1 Proofed Tape - The proofed tape shall be closely woven textile, without selvedge, proofed on one side with rubber. The thickness of tape should be approximately 0.15 mm.
sheath shall 8.1.2 Flexible Cables - The consist of elastomeric compound complying with the requirements of Type SE 2 of IS : 63801984*.
8.2 Heat Resisting Insulated Cables
5.2 Polyethylene Terephthaiate ( PETP ) Tape or Plastic Tape or Any Other Suitable Tape - The should be O-012 5 mm thickness of tape ( minimum ). 5.3 Glass Tape suitable quality. The glass tape shall be of
8.2.1 Cables for Fixed Wiring and Flexible The sheath shall consist of elastomeric compound complying with the requirements of Type SE 3 of IS : 6380-1984*.
Cords -
8.2.2 Flexible Cables -The sheath shall consist of elastomeric compound complying with the requirements of Type SE 4 of IS : 6380-1984*.
*Specification for elastomeric insulation of electric cables (first revision ). and sheath
*Specification for conductors for insulated electric cables and flexible cords (first revision ). tSpecitication for elastomeric insulation and sheath of electric cables ( jirsr revisron ).
9.1 Preservative Compound - Preservative compound shall be free from deleterious action on any part of the cable.
SECTION 10. CONDUCTOR 10.1 Cables for Fixed Wiring -
Varnish shall be compatible with the operating temperature of the cable and It shall applied to prevent fraying of glass yarn. be free from deleterious action on any part of the cable.
3 CONSTRUCTION
12. INSULATION 12.1 The conductor, with or without separator, shall be provided with insulation in accordance with respective tables.
of conductor as follows:
8130-1984* )
12.2 Thickness of Insulation - The average thickness of the insulation shall be not less than the nominal value ( tl ) specified in respective tables. 12.3 Tolerance on Thickness of lusulation ( tl ) The smallest of the measured values of thickness of insulation shall not fall below the nominal value ( tl ) specified in respective tables by more than 0.1 mm + 0.1 fi. 12.4 Application of Insulation - The insulation shall be so applied that it fits closely on the conductor ( with or without separator ) but shall not adhere to it. The insulation, unless applied by the extrusion, shall be applied in two or more layers. 13. CORE IDENTIFICATION 13.1 The cores shall be identified either by colours or number in accordance with 13.2 using any one of the following methods: a) Numbered tapes, insulation,
1 and 1.5
10 and above
shall be circular.
10.1.2 The earth continuity conductor shall be constructed from same material as main conductor. 10.2 Flexible Cables and Cords formation shall be according IS : 8130-1984*.
11. SEPARATOR
TAPB
11.1 The separator tape may be applied over the conductor as mentioned in the respective tables.
*Specification for conductors for insulated cables and flexible cords (firsf revision ). electric
b) Coloured
c) Coloured tape, and d) Numbers printed on cores. 13.2 The colour given below: or number scheme shall be as
Numbers of Cores
Single
Rigid Cables
Flexible Cables
Flexible Cords
Numbers
Red, black, white, yellow or blue Red and black Red, yellow and blue Red, yellow, blue and black
-
Red, black. white, yellow or blue Red and black Red, yellow and blue Red, yellow, blue and green Red, yellow, blue, black and green
Red, black. white, yellow or blue Red and black Red. black and green* Red, yellow blue and green* -
_ 192 1, 2, 3 1, 2, 3, 4 1,2,3,4,5
IS : 9968 ( Part 1) - 1988 13.2.1 When numerals are used for identification, these shall appear at intervals of not greater than 150 mm. 18. BINDER TAPE
14. TAPE 14.1 Proofed tape or PETP tape or plastic tape or any other suitable tape may be applied over insulation as mentioned in the respective tables. The tape, when provided, shall be applied with an overlap. 15. BRAIDING braiding, as required in the respective tables, shall be applied reasonably close, but not so tight as to damage the insulation. 16. COMPOUNDING AND VARNJSHING
15.1 The
18.1 The proofed tape or glass tape or PETP tape or plastic tape or any other suitable tape over laid up cores shall be applied as required in the respective tables with an overlap. 19. SHEATH 19.1 The sheath shall be applied by extrusion, wherever required, in the respective tables. 19.2 Thickness of Sheath - The average thickness of the sheath shall be not less than the nominal value ( ts ) specified in respective tables. 19.3 Tolerance on Thickness of Sheath -- The smallest of the measured values of thickness of sheath shall not fall below the nominal value ( r8 ) specified in respective tables by more than 0.2 mm + 0.2 ta.
19.4 Colour - The colour of the sheath shall be black, unless any other is agreed between the purchaser and the supplier.
16.1 The compounding or varnishing shall be provided as required in the respective tables. 17. LAYING UP OF CORES 17.1 Jn case of twin and multicore circular cables and cords, the cores shall be laid together with a suitable right hand lay. Fillers in inteistices may be used to provide reasonable circularity of laid up cable. 17.1.1 The values of lay for flexible cables and cords shall be maximum 18 times the pitch circle diameter.
SECTION 21. CLASSIFICATION
20. OVERALL DJAMETER 20.1 Overall diameter of flexible cords shall not exceed the values given in the appropriate tables.
4 TESTS
OF TESTS
(1)
(2)
(3)
(1)
Persulphate test ( for copper ) Annealmg test ( for copper ) Tensile test ( for aluminium ) Wrapping test ( for aluminium ) Conductor resistante test Test for thickness of insulation and sheath and overall diameter ( where specified
IS: 8130-19s4t IS : 8130-19847 IS: 8130-1S4t IS : 8130-1984~ IS : 8130-1984t 12, 19, 21 and Tables 1 to 10 )
4 1 2 3 5 6
Physical tests for insulation and sheath ( as applicable ): a) Tensile strength and IS : 6380-1984* elongation at break b) Ageing in air oven IS : 6380-1984 c) Ageing in air bomb IS : 6380-1984 d) ;t_;g in oxygen IS : 6380-1984* e) Hot set f) Oil resistance g) Tear resistance Insulation resistance High voltage ( water immersion ) test Flammability test ( applicable to cables finished with SE 3 and SE 4 sheaths only ) Water absorption test ( for insulation as applicable ) IS : 6380-1984 IS : 6380-1984 IS : 6380-1984* IS : 6380-1984* 22.2 22.3
7 11 56 16 30 31 17 43 45 53
IS : 6380-1984*
28
l Me!hods of test for cables. Vpecification for conductors for insuIated cables and flexible cords (first revision ).
electric
insulation
and sheath
following
shall
b) Tensile t,est ( for aluminium ); cl Wrapping test ( for aluminium ); d) Conductor resistance test; e) Test for thickness of insulation and sheath,
and overall diameter ( where specified );
and elongation of insulation and sheath; set test for insulation ( where applicable );
at break
and sheath
21.3 Routine Tests - The following shall constitute the routine tests: a) Conductor resistance test, and b) High voltage test or spark test. 22. DETAILS
22.1 General OF TEST
6 kV ( rms ) within 10 seconds and held at this value for 5 minutes. If the sample this test, one more sample shall be to this test which shall pass. Xest on Completed Cables ( Acceptance and Routine Test ) - This test shall be carried out between conductors or between conductor and screen/armour. The test voltage shall be 3 kV ac ( rms ) or 7.2 kV dc. The test shall be carried out at room temperature and the time of application shall be 5 minutes. No failure of insulation shall occur. 22.2.2.1 Single-core cables shall be immersed in water at ambient temperature one hour before the test and the test voltage shall be applied between conductor and water. In case of singlecore, braided and compounded, and braided and varnished cables, the core shall be subjected to spark test according to IS : 10810 (Part 44 )1984*. 22.2.3 Spark Test ( Routine Test ) - Spark test may be applied as an alternative to the high voltage test specified at 22.2.2. It shall be made at the core stage during manufacture of cables and the potential difference between the electrode and the conductor shall be as specified below:
Nominal Thickness of Insulation Test Voltage
Unless otherwise stated in this the tests shall be carried out in standard. accordance with appropriate part of IS : 10810*, taking into account additional information given in this standard. 22.2 High Voltage Test
22.2.1 Water Immer$ion Test ( Type lest ) -
kV(rms)
The core( s ) shall be carefully removed from a sample approximately 3 metres long taken from the finished cable or cord. They shall be so immersed in a water bath at room temperature that their ends protrude at least 200 mm above the water level. After 24 hours, an ac voltage of 3 kV ( rms ) shall be applied between conductor and water. This voltage shall be ___-~*Methods of test for cables.
22.3 Flammability Test - Period of burning after removal of the flame shall not exceed 60 seconds and the unaffected ( uncharred ) portion from the lower edge of the top clamp shall be at least 50 mm.
*Methods of
IDENTIFICATION,
PACKING
23.1 Manufacturers Identification - The manufacturer shall be identified throughout the length of the cable by means of a tape bearing the manufacturers name or trade-mark, or by marmfacturers name or trade-mark being printed. indented or embossed on the cable or cord. In case, none of these methods can be employed, or if the purchaser so desires, colour identification threads in accordance with a scheme to be approved by the Bureau of Indian Standards shall be employed. The printing, 5
indentation or embossing shall be done on sheathed cables. The distance between any two consecutive printings, indentations or embossings shall be not more than 1 metre. 23.2 Cable Identification - Cables or cords shall be identified throughout the length of the cable or cords by the legends shown below, either printed or indented or embossed on the cable.
Type of Cable Insulation Legend
HR 90 HR 150
IS:9968(Partl)-1988
bearing manufacturers name NOTE 1 - Single or trade-mark and the legends mentioned above, if
provided, shall also be acceptable ments of 23.1 and 23.2. NOTE 2- No legend is purpose rubber insulation.
required
4 Type of cable and voltage trade; 4 Number of cores: cross-sectional area 9 Nominal
conductor;
of
the
23.3 Cable
Code - The following code shall be used for designating the cable:
Constituent Aluminium conductor Elastomer insulation Braiding, compounding or varnishing Elastomer sheath Earth continuity conductor
conductor material NOTE - When code letter is required for conductor. 24. PACKING
f) Cable code; f?) Length of the cable on the drum/reel/coil; h) Number of lengths on the reel, drum or
coil ( if more than one ); of arrow );
j) Direction
and
AND MARKING
24.1 The cables and cords shall be either wound on drums ( see IS : 1041%1982* ) or reels or
supplied in coils and packed. 24.2 The cable shall contain the following information either stencilled on the drum or contained in a label attached to it: a) Reference to this Tndian Standard, for example, #Ref IS : 9968 ( Part 1 ); b) Manufacturers name, brand name or trade-mark; *Specification for drums for electric cables.
TABLE 1 ELASTOMER INSULATED SINGLE-CORE TAPED OR UNTAPED TEXTILE BRAIDED AND COMPOUNDED CABLES (Chses Construction 11.1, 12, 14.1, 15.1 and 16.1) annealed copper or aluminium conductor ( 3 and 10.1 ) separator tape( 5) with tape (3.3 ) ( 4.1 ) service insulation
TABLE 2 ELASTOMER INSULATED SINGLECORE, CIRCULAR, TWIN-CORE, THREECORE AND FOUR-CORE ELASTOMER SHEATHED CABLES (Claftses Construction 11.1, 12, 14.1, 18.1 and 19) conductor b) Optional annealed copper or aluminium ( 3 and 10.1 ) separator tape ( 3.3)
: a) Tinned
: a) Tinned
e) Textile braiding ( 7.1 ) f) Textile braiding shall be treated preservative compound ( 9 ) NOMINAL CROSS-SECTIONAL
AREA OF CONDUCTOR
c) Insulation : 1) General service elastomeric ( 4.1 ) or 2) Heat resisting elastomer ( 4.2 ) d) Optional Sitlgle-Core Cables proofed tape ( 5 )
mm 1 ;:; 6 10 16 55 50
e) General service sheath e) 2, 3 and 4 core cables laid up ( 17.1 ) ( 8.1.1 ) in case of general service insulation and heat resisting f) OPtional fillers ( 6.1 ) sheathh!z;2*1 ) i? ease g) Optional binder tape ( 5 ) of reslstlna insulation h) General service sheath (8.1.1 ) in case of general service insulation and heat resisting sheath ( 8.2.1 ) in case of heat resisting insulation
TABLE 3 ELASTOMER INSULATED, FLAT TWINCORE CABLES ( WITH AND WITHOUT ECC ) AND FLAT THREE-CORE ( WITHOUT ECC) ELASTOMER SHEATHED CABLES ( CIuuses 11.1, 12 and 19) Construction annealed copper or aluminium conductor ( 3 and 10.1) b) Optional separator tape ( 3.3 ) c) General service elastomeric insulation ( 4.1) Cables Without ECC Cable with ECC
: a) Tinned
SHEATH THICKNESS CROSSSECTIONAL OF INSU- ~----h------7 ThreeTwinLATlON SingleARBAOP Core Core Core CONDUCTOR (tt)
FourCore mm 11 1.1 1-l l-2 1.3 14 1.5 17 l-8 2.0 2.1 2.4 2.5 2.7 2.9 3.2 3.5 3.8 -
mmn 1 15 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
mm
1'0 1.0 1.0 1'0 1'0
mm I0 1.0 1.0 10 1.0 11 1-l 12 1.2 13 14 14 15 1.6 1.7 18 19 2.0 2.2 2.3
mm 10 1.0 1.1 I.2 l-2 13 1.4 I.5 I.6 1.8 1.9 2-l 2.2 2.4 2.6 28 3.0 3.2 -
mm 10 11 1.1 12 12 14 I.4 l-6 1.7 1.8 2.0 2.2 2.3 2.5 2.7 3.0 3.2 3.4 -
1.2 12 1.4 14 1.6 1.6 1.8 18 2.0 2.2 2.4 2.6 2.8 3.0 3.0
d) Two or three insulated d) Two insulated cores laid cores laid side by side side by side ; the earth so as to form flat twin continuity conductor (bare or flat three as the case centrally placed between may be; optional woccores in the same plane) ming or filling ( 6.1) e) Elastomeric sheath ( 8 ) e) Elastomeric sheath ( 8 )
NOMINAL CROSSSECTIONAL AREAOP CONDUCTOR NOMINAL THICKNESS OF TNSULATION
TwinCore
Flat ThreeCore
( tl)
TABLE 4
ELASTOMER INSULATED, SINGLE-CORE, TWIN-CORE, THREE-CORE AND GLASS FIBRE BRAIDED AND VARNISHED CABLES, AND CORDS ( Clauses 11.1, 12, 15.1 und 16.1 )
FOUR-CORE
Construction
conductor for cables for fixed wiring and tinned annealed copper for flexible cables and cords ( 3,10.1 and 10.2 ) b) Optional separator tape ( 3.3 ) c) Silicone rubber insulation ( 4.3 ) 2-, 3- and I-Core Cables d) 2, 3 and 4 cores laid up ( 17.1) with optional ( 6.1 ) e) Glass braid ( 7.2 ) g) Treated with sultable varnish (9.2 )
NOMINAL THICKNESS OF INSULATION (r, ) ---h---_-----~ c---Cables for Flexible Cables Fixed Wiring and Cords
Single-Core Cubfes d) Glass braid ( 7.2 ) e) Treated with suitable varnish ( 9.2 )
fillers
AREA OF
I .o
;:2 12 1.2 ;:6 for cables with silicone rubber insulation.
: a) Tinned annealed
copper conductor ( 3 and 10.2 ) b) Optional separator tape ( 3.3 ) c) insulation: 1) General service elastomeric ( 4.1). or 2) Heat resisting elastomeric ( 4.2 ) d) Optional tape ( 5 ) Single-Core Cables 2-, 3-, 4- and j-Core Cubles e) 2, 3, 4 and 5 cores laid up ( 17.1 ) optional fillers ( 6.1 ) f) Optional binder tape ( 5 ) g) Heavy dutysheath ( 8.1.2) in case of general purpose rubber insulation and heavy duty HOFR sheath ( 8.2.2 ) in case of heat resisting rubber insulation
e) Heavy duty sheath (8.1.2) in case of general purpose rubbd insulation and heavyduty HOFR sheath ( 8.2.2 ) in case of heat resisting rubber insulation
mm
1.0 ;:;
z: :x
::
l-4
;:6
16 I.8 1:; 22 2.4 2-6 28 30 3-o
NOMINAL THICKNESSOF SHEATH( td ) _--____A ----P----T S%zeTwinFourThreeCore Core Core Core mm mm mm mm 2.5 16 20 21 2.7 2.4 25 ;:; 2.7 $49 5:; 2.0 33 2.2 3.5 3.4 3.7 24 3.6 ;:; 2.6 3.7 2.8 4.0 4.3 3.0 41 45 4.3 33:; 4.8 4.5 5.5 48 ::; 5.1 35 5.8 38 54 40 41
TABLE 6
ELASTOMER INSULATED, SINGLE-CORE, CIRCULAR-TWIN CORE, THREE-CORE FOUR-CORE ELASTOMER SHEATHED FLEXIBLE CORDS
AND
Construction
( &uses 11.1, 12, 18.1 and 19 ) annealed copper conductor ( 3 and 10.2 ) b) Optional separator tape ( 3.3 ) c) Insulation: 1) General service elastomeric ( 4.1), or 2) Heat resisting elastomeric ( 4.2 ) d) Optional tape ( 5 ) Single-Core Cords 2-, 3- and I-Core Cords e) General service sheath ( 8.1.1) in case of general e) 2, 3 and 4 cores laid up ( 17.1 ) optional fillers ( 6.1 ) service insulation and heat resisting sheath ( 8.2.1) f) Optional tape (5) in case of heat resisting insulation g) General service sheath (8.1.1 ) in case of general service insulation and heat resisting sheath (8.2.1 ) in case of heat resisting insulation
: a) Tinned
NOMINALTHICKNESSOF SHEATH NOMINAL NOMINAL CROSS-SEC- THICKNESS r ---------o~-*-------~ ThreeTIONALAREA OF INSULA- SingleCore Core Core OF CONDUC- TION ( tl ) TOR (4) (5j (3) (2) (1) mm mm mm mm mm1 0.5 0.75 :.5 2-5 4 10 ;:o 10 10 1.0 10 1.0 1.0 1.0 ;I; ;:; 1.2 10 1.0 1.0 ;:: 12
OVERALLDIAMETER MUX r--- __---h_------~ ThreeSingleTwoCore Core Core (7) mm 70 7.2 74 7.7 8.2 88 (81 mm 11.7 12.2 126 13.2 142 15.7 (9 mm 12.5 13.c 13.4 ;5:; 167
TABLE 7 ELASTOMER INSULATED TEXTILE BRAIDED, SlNGLE AND TWISTED TWIN FLEXlBLE CORDS ( Clurtses 11.1, 12 and 15.1 ) Construction
TABLE 9 ELASTOMER INSULATED TWIN-CORE OR THREE-CORE UNKINKABLE FLEXIBLE CORDS ( WORKSHOP TYPE) (Clnuses 11.1, 12.1, 15.1, 16.1 and 18.1 ) Construction
: a) Tinned
: a) Tinned
copper
conductor
copper
conductor
tape ( 3.3 )
c) General service elastomeric insulation ( 4.1 ) 4 Two or three cores shall be twisted together ( 17.1 ) e) Optional fillers ( 6.1 ) f) Binder tape ( 18.1 ) 9) Textile h) Textile
NOMINALCROSSSECTIONALAREA OFCONDUCTOR
silk mercerized
e) In case of twisted twin flexible cord, two such braided cores shall be twisted together ( 17.1 )
NOMINALCROSSSECTIONAL AKEA OFCONDUCTOR NOMINALTHICKNESSOF INSLJLATI~N(~~) OVERALLDIAMETER OFEACH BRAIDED CORE, Max
mm 4.9 5.1 53 56 60 mm
0'5 o-75 1 i.5 25 4
TION ( f, ) mm
10 10
Core mm
9.2 9.6
Core
mm 9.0
I0 10 10 I0
TABLE 8 ELASTOMER
TABLE 10 ELASTOhll<R INSLILATED. TWIN-CORE OR THREE-CORE INKINKAB1.E FLEXIBLE CORDS ( DOMESTIC TYPE )
Construction
: a) Tinned
a)
copper
conductors
b) Optional
service elastomeric
c) General service elastomeric insulation ( 4.1 ) d) Two or three cores shall be twisted together ( 17.1 ) e) Optional fillers ( 6.1 ) silk mercerized
OVERALL NOMINAL CRoss-
d) Two or three cores shall be twisted together ( 17 1 ) with fillers of natural or synthetic tibres (6.1 ) e) Elastomeric
sheath ( 8.1.1 )
being
semi-
mm 1.0 1.0
1.0
DIAMETER,Afr/.r r___h_-~ TwoThreeCore Core mm mm 8.3 8.7 9.1 9.7 105 117 90 9.5 99 105 11.3 126
SECTIONA L
INillL4-
_-._~ ThreeCore
ARIY=%
mm*
TK)\ ( r,)
m 111
Core mm
1.5 2.5 4
15 15 I.5 1.5 15 15
IS:!9968(Partl)-1988
OF CABLES
A-2.2.1 In order to ensure the randomness of selection, procedure given in IS : 49051968* may be followed.
a consignment, the cables of the same under essentially similar size manufactured conditions of production shall be grouped together to constitute a lot. A-2. SCALE OF SAMPLING A-2.1 Samples shall be taken and tested from each lot for ascertaining the conformity of the lot to the requirements of the specification. A-2.2 The number of samples to be selected shall depend on co1 1 and 2 as indicated below. These samples shall be taken at random: No. of Drums/Coils/
Reels in the Lot No. qf Drums/ Coils/Reels to be Taken as Sample (n) (2) 3 Permissible No. of Defectives I:; 0
A-3. NUMBER OF TESTS AND CRITERION FOR CONFORMITY A-3.1 Suitable lengths oftest samples shall be taken from each of the drums selected. These test samples shall be subiected to each of the acceptance tests ( see 21.2 ). A test sample is called defective if it fails in any one of the acceptance tests. If the number of defectives is. less than or equal to the corresponding permissible number given in co1 3 under A-2.2, the lot shall be declared as conforming to the requirements of acceptance tests; otherwise not.
{Y,
up
25
8 ::
0 :
*Methods for random sampling.
10
Bureau of Indian Standards BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote harmonious development of the activities of standardizaticur, marking and quality certification of goods and attending to connected matters in the country. Copyright No part of these publications may be reproduced in any form BIS has the copyright of all its publications. without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publication), BIS. Review of Indian Standards Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of BIS Handbook and Standards Monthly Additions.
BUREAU Headquarters:
OF INDIAN
STANDARDS Telegrams: Manaksanstha (Common to all offices) Telephone 323 76 17,323 38 41 337 84 99,337 337 86 26,337 85 61 91 20
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telephones: 323 0131,323 33 75,323 94 02 Regional Offices: Central Eastern Northern Southern Western Branches
: Manak Bhavan, 9 Bahadur Shah Zafar Marg
CALCUTTA
: SCO.335336,
: Manakalaya,
: AHMADABAD.
BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW. NAGPUR. PATNA. PUNE. THIRUVANANTHAPURAM.
Printed by Reprography Unit, BIS, New Delhi
AhIBN~ltdENT NO.
TO
APRIL 1991
UP TO AND
First Revision )
Insert the following clause after 2.3: when required,
2.4 Optional Tests - Special tests to be carried out, by agreement between the purchaser and the supplier. ( Page 5, ciause 21.3 ) 21.4 Optional Tests a) Flexing Insert the following
The following
shall constitute
test for cords for use with electric irons. Insert the following clause after 22.3: Irons see
Cords
Insert
Appendix
B at the
CAPPENDIX ( Clause22.4 )
IRONS
B-l The part of the iron comprising the cable entry fitted with the cord guard and the flexible cable or cord for which the iron is designed, is fixed to the oscillating member of an apparatus similar to that shown in Fig. 1. B-2 The sample is to the outer surface when the oscillating cable or cord, where so mounted that the axis of oscillation is tangential of the part in which the cord guard is secured, and member is at the middle of its travel, the axis of the it leaves the cord guard, is vertical.
B-3 A load having a mass equal to that of the iron but not less than 2 kg or more than 6 kg is attached to the cable or cord. 1
yx%//
[SAMPLE
OSCILLATION-/
II
III
306 mm
FIG. 1
FLEXING
TESTAPPARATUS
B-4 The oscillating member is moved backwards and forwards through an angle of 90 ( 45 on either side of the vertical ), number of ffexings, the sample is turned through 90 about the centre line of the cord guard. B-5 After the test, the cord guard shall not have worked loose and neither the cord guard nor the flexible cable or cord shall show any damage within the meaning of this specification except that and give then 10 percent of the total number of conductor strands may have been broken. NOTE - A flexing is one movement
either backward or forward.
( ETD 09 ) 2