02 - Non-Dir Over Current
02 - Non-Dir Over Current
F1
F2
F3
Co-ordinate protection so that relay nearest to fault operates first Minimise system disruption due to the fault
Fuses
IFA approx 2 x IFB Limited sensitivity to earth faults Single phasing Fixed characteristic Need replacing following fault clearance
Tripping Methods
51
Trip Coil IF
51
-
IF
Capacitor discharge trip used with static relays where no secure DC supply is available
51
DC BATTERY
Overcurrent Protection
50
IF2
50
IF1
Current settings chosen so that relay closest to fault operates Problem Relies on there being a difference in fault level between the two relay locations Cannot discriminate if IF1 = IF2
TIME
TOP
Applied Current
51
0.9 sec
51
0.5 sec
Operating time is independent of current Relay closest to fault has shortest operating time Problem Longest operating time is at the source where fault level is highest
Applied Current
Current setting via plug bridge Time multiplier setting via disc movement Single characteristic Consider 2 ph & EF or 3 ph plus additional EF relay
INST t I > Is
0.05 0 0 0 0 0 0 1 1 1
No Ph+ In Vx Hz V
Is = x Is
Is = RESET
x Is
x t =
x t =
LT1
t
S1 V1 E1
0 0 0 0 0 0
1 2 4 8 10
INST =
x Is
1 2 4 8 10
INST =
x Is
Electronic, multi characteristic Fine settings, wide range Integral instantaneous elements
I>1 I>2
Time
I>3 I>4
Current
Multiple characteristics and stages Current settings in primary or secondary values Additional protection elements
Co-ordination
IF1
T
Other relays must have adequate additional operating time to prevent them operating Current setting chosen to allow FLC Consider worst case conditions, operating modes and current flows
IS2 IS1
10
E
1
D C B
0.1
0.01
Current (A)
FLB
FLC
FLD
SI VI EI
t =
0.14
(I0.02 -1)
Operating Time (s)
100
t = 13.5
(I -1)
10
LTI SI
t =
80
(I2 -1)
1
VI EI
LTI t = 120 (I - 1)
0.1 1
10
100
100
10
0.1 1
Set just above full load current allow 10% tolerance Allow relay to reset if fault is cleared by downstream device consider pickup/drop off ratio (reset ratio) relay must fully reset with full load current flowing PU/DO for static/numerical = 95% PU/DO for EM relay = 90% e.g for numerical relay, Is = 1.1 x IFL/0.95
R1
R2
IF1
Operating time difference between two devices to ensure that downstream device will clear fault before upstream device trips Must include breaker opening time allowance for errors relay overshoot time safety margin
GRADING MARGIN
R1
R2
Traditional breaker op time relay overshoot allow. For errors safety margin Total Calculate using formula 0.1 0.05 0.15 0.1 0.4s
Grading Margin = 0.4Tf + 0.15s over whole characteristic Assume fuse minimum operating time = 0.01s Use EI or VI curve to grade with fuse Current setting of relay should be 3-4 x rating of fuse to ensure co-ordination
Overcurrent Protection
Grading Margin - relay with upstream fuse
Tf Tr
I FMAX
1.175Tr
Allowance for CT and relay error
0.1
CB
0.1
Safety margin
0.6Tf
Allowance for fuse error (fast)
or Tf = 2Tr + 0.33s
Used to adjust the operating time of an inverse characteristic Not a time setting but a multiplier Calculate TMS to give desired operating time in accordance with the grading margin
10
Calculate relay operating time required, Treq consider grading margin fault level Calculate op time of inverse characteristic with TMS = 1, T1 TMS = Treq /T1
Calculate required operating current Calculate required grading margin Calculate required operating time Select characteristic Calculate required TMS Draw characteristic, check grading over whole curve Grading curves should be drawn to a common voltage base to aid comparison
200/5
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
Grade relay B with relay A Co-ordinate at max fault level seen by both relays = 1400A Assume grading margin of 0.4s
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
Relay B is set to 200A primary, 5A secondary Relay A set to 100A If (1400A) = PSM of 14 relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13 (I0.02 -1) (140.02 -1) Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s Relay A uses SI curve so relay B should also use SI curve
B Is = 5 Amp
Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s Relay A uses SI curve so relay B should also use SI curve Relay B set to 200A If (1400A) = PSM of 7 relay B OP time TMS = 1 = 0.14 x TMS = 0.14 = 3.52s (I0.02 -1) (70.02 -1) Required TMS = Required Op time = 0.53 = 0.15 Op time TMS=1 3.52 Set relay B to 200A, TMS = 0.15, SI
350MVA
CTZ61
(Open)
MCCB 27MVA
1 2 3 4 F
Fuse Load
K 20MVA
ZA2118B
TX damage
MCCB (cold)
Fuse
Very inverse
Relay 2
10kA
1000kA
350MVA
KCEG 142
ACB
2
(Open)
ACB
1 2 3 4 F
MCCB 27MVA
Fuse Load
K 20MVA
ZA2120C
100S
Fuse
TX damage
MCCB (cold)
Relay 3
Relay 2
Relay 4
10kA
1000kA
Overcurrent Protection
Blocked OC Schemes
R1
IF1
M
ZA2135
(Transient backfeed ?)
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio = 3 :1
A phase-phase fault on one side of transformer produces 2-1-1 distribution on other side Use an overcurrent element in each phase (cover the 2x phase) 2 & EF relays can be used provided fault current > 4x setting
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio = 3 :1
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
51 HV
51 LV
Grade HV relay with respect to 2-1-1 for - fault Not only at max fault level
86.6%If3 If3
Fast clearance of faults ensure good operation factor, If >> Is (5 x ?) Current setting must be co-ordinated to prevent overtripping Used to provide fast tripping on HV side of transformers Used on feeders with Auto Reclose, prevents transient faults becoming permanent AR ensures healthy feeders are re-energised Consider operation due to DC offset - transient overreach
Overcurrent Protection
Instantaneous OC on Transformer Feeders
HV2
HV1
LV
Set HV inst 130% IfLV Stable for inrush No operation for LV fault Fast operation for HV fault Reduces op times required of upstream relays
IF(LV)
IF(HV)
CURRENT
1.3IF(LV)
Earthfault Protection
Earth fault current may be limited Sensitivity and speed requirements may not be met by overcurrent relays Use dedicated EF protection relays Connect to measure residual (zero sequence) current Can be set to values less than full load current Co-ordinate as for OC elements May not be possible to provide co-ordination with fuses
Overcurrent Protection
Earth Fault Relay Connection - 3 Wire System
E/F
OC
OC
OC
E/F
OC
OC
Overcurrent Protection
Earth Fault Relay Connection - 4 Wire System
E/F
OC
OC
OC
E/F
OC
OC
OC
Independent of neutral current but must use 3 OC relays for phase to neutral faults
Solid earth 30% Ifull load adequate Resistance earth setting w.r.t earth fault level special considerations for impedance earthing - directional?
For low settings cannot use residual connection, use dedicated CT Advisable to use core balance CT CT ratio related to earth fault current not line current Relays tuned to system frequency to reject 3rd harmonic
NO OPERATION
OPERATION
Need to take care with core balance CT and armoured cables Sheath acts as earth return path Must account for earth current path in connections - insulate cable gland
E/F