100% found this document useful (1 vote)
2K views9 pages

Tan Delta Test For Power Transformers

The document describes procedures for performing a tan delta test on power transformers to measure insulation dissipation factor. Key steps include short-circuiting windings, ensuring proper temperature and cleaning, applying voltage between combinations of HV, LV, and earth connections, and using an Omicron instrument to obtain tan delta results between 0.2616 and 0.4983 for the different winding combinations of a 100MVA, 33kV/220kV transformer.

Uploaded by

Bashir Ahmad
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views9 pages

Tan Delta Test For Power Transformers

The document describes procedures for performing a tan delta test on power transformers to measure insulation dissipation factor. Key steps include short-circuiting windings, ensuring proper temperature and cleaning, applying voltage between combinations of HV, LV, and earth connections, and using an Omicron instrument to obtain tan delta results between 0.2616 and 0.4983 for the different winding combinations of a 100MVA, 33kV/220kV transformer.

Uploaded by

Bashir Ahmad
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 9

TAN DELTA TEST FOR POWER TRANSFORMERS

TAN DELTA(INSULATION DISSIPATION FACTOR)


Tan delta is the insulation power factor & is equal to the ratio of power dissipated in the insulation in watts to the product of effective voltage & current in volt ampere when tested under sinusoidal voltage.

PROCEDURE
All windings immersed in insulating liquid. All windings shortcircuited using bare braided jumper such that jumper shall not be allowed to sag. All bushings in place. Temperature of winding & insulation liquid near to the reference temperature(27 degree). All bushings cleaned properly. Transformer earthed properly.

Neutral,star point of 3 phase winding connected to other bushing of that winding by means of short jumper. Tan delta is then tested between below combinations, a. HV to EARTH b. LV to EARTH c. HV to LV.

TEST SETUP
TRANSFORMER SPECIFICATONS
RATING-100 MVA VOLTAGE CLASS-33KV/220KV Yyn-0 COOLING-OFAF INSTRUMENT MAKE-OMICRON

APPLIED VOLTAGE-10KV

LV TO EARTH TESTING

HV TO EARTH TESTING

LV-HV TESTING

TAN-DELTA TEST RESULTS


WINDING LV TO EARTH HV TO EARTH LV TO HV TAN-DELTA 0.4702 0.4983 0.2616