EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm)
EA DUCT 200x150 Total Length Location Ref Drawing No Air Qty (Lps) 126 : Roof Floor :TX/8/17 (Toilet Extract Fan)
Eq. length 3 20
Pr. Drop (Pa/m) 1.545 1.545
Total Pr. Drop (Pa) 4.635 30.90 35.54 10.66 15 35
Remarks
3 4
Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser
TOTAL
131.73
EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm) EA DUCT 250x200 Total Length Location Ref Drawing No Air Qty (Lps) 240 : Roof Floor :KX/8/11 (Kitchen Extract Fan)
Eq. length 3 25
Pr. Drop (Pa/m) 1.435 1.435
Total Pr. Drop (Pa) 4.305 35.88 40.18 12.05 15 35
Remarks
3 4 5
Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser Kitchen Hood TOTAL
Details Not Available 142.41