ESP Calculation For EXTRACT FANS 4STAR

This document contains two summaries of external static pressure calculations for ductwork systems in an MSE Hotel project. The first is for a 126 Lps toilet extract fan system with a total pressure drop of 131.73 Pa. The second is for a 240 Lps kitchen extract fan system with a total pressure drop of 142.41 Pa, though some details are not available. Both calculations include pressure drops from straight duct sections, fittings, dampers and diffusers.

Uploaded by

zfrl
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
3K views3 pages

ESP Calculation For EXTRACT FANS 4STAR

This document contains two summaries of external static pressure calculations for ductwork systems in an MSE Hotel project. The first is for a 126 Lps toilet extract fan system with a total pressure drop of 131.73 Pa. The second is for a 240 Lps kitchen extract fan system with a total pressure drop of 142.41 Pa, though some details are not available. Both calculations include pressure drops from straight duct sections, fittings, dampers and diffusers.

Uploaded by

zfrl
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm)

EA DUCT 200x150 Total Length Location Ref Drawing No Air Qty (Lps) 126 : Roof Floor :TX/8/17 (Toilet Extract Fan)

Eq. length 3 20

Pr. Drop (Pa/m) 1.545 1.545

Total Pr. Drop (Pa) 4.635 30.90 35.54 10.66 15 35

Remarks

3 4

Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser

TOTAL

131.73

EXTERNAL STATIC PRESSURE CALCULATION Project Job No Date : Rev Sl No 1 2 : MSE Hotel :24/06/2013 :0 Rectangular Duct Size (mm) EA DUCT 250x200 Total Length Location Ref Drawing No Air Qty (Lps) 240 : Roof Floor :KX/8/11 (Kitchen Extract Fan)

Eq. length 3 25

Pr. Drop (Pa/m) 1.435 1.435

Total Pr. Drop (Pa) 4.305 35.88 40.18 12.05 15 35

Remarks

3 4 5

Sub Total Add 30 % for fittings like Elbows, collars, vanes etc Fire Damper Diffuser Kitchen Hood TOTAL

Details Not Available 142.41