ABB Isomax molded case circuit breakers are modern, innovative units designed after extensive analysis of the demands of todays market. These new units embody all the experience and advances derived from ABBs previous highly successful and acclaimed range of circuit breakers. ABB Isomax circuit breakers are designed for the total safety of both operators and systems. This complete and versatile series of circuit breakers can satisfy the most demanding system specications. ABB Isomax circuit breakers are ideal for all electrical power generation and distribution applications. The Isomax series maximizes safety and dependability for all power users. The new line is particularly suitable for applications involving special protection coordination needs and automated control systems. ABB Isomax units also satisfy the most demanding requirements for rated current and fault current levels. With the wide range of optional trip functions total system selectivity can be maximized. Continuous currents from 15A to 2500A Rated interrupting capacities from 14kA to 85kA (600VAC UL/CSA) Extended working life of all mechanical and electrical parts for continuity of operation Suitable for isolation applications UL/CSA 100% equipment rated versions
15
Derived versions
Circuit breakers with selective and nonselective residual current protection Switch disconnectors Circuit breakers for motor control with adjustable magnetic release Circuit breakers for machine tools Circuit breakers for direct current Fixed: all models Plug-in: up to S5 400A (IEC) Withdrawable: from S3 to S7 1200A (IEC) UL File #E93565 CSA File # LR90467
15.1
AC 1000 - 11/03
15
ax m s o Is CB MC
S1
S3B
S3
Circuit-breaker type Maximum frame continuous rated current Rated operational voltage Test voltage Rated impulse withstand voltage Poles Performance level UL/CSA short-circuit interrupting capacity UL 489, File # E93565 CSA, File # LR90467 IEC-947 rated ultimate short-circuit breaking capacity 240VAC 480VAC 600VAC 500VDC 600VDC 220/230VAC 380/400/415VAC 440VAC 500VAC 660/690VAC 40C 50/60 Hz 1 min. 50/60 Hz A V V kV No.
S1 100 277/480V 3000 6 3 N 50 203 40 25 16 12 in in No. ops./hour lbs 4.72 x 3.07 x 2.75 4.72 x 4.09 x 2.75 25,000 240 2.42
S3B 225 240 3000 6 2-3 B 150 50 150 6.70 x 4.13 x 4.07 6.70 x 5.51 x 4.07 25,000 240 6.75 N 65 25 14 35 20 65 35 30 25 14 H 100 50 14 50 35 100 65 50 40 18 6.70 x 4.13 x 4.07 6.70 x 5.51 x 4.07 25,000 120 6.75 150 600 3000 6 2-3-4 L 150 852 25 65 50 170 85 65 50 20
S3 225 480 3000 6 2-3-4 B 150 N 65 25 25 65 35 30 25 14 6.70 x 4.13 x 4.07 6.70 x 5.51 x 4.07 25,000 120 6.75 H L 100 150 50 65 35 50 100 170 65 85 50 65 40 50 18 20
kA RMS
1 1
Icu
kA RMS
Overcurrent trip unit/relays Thermal-magnetic Microprocessor-based Dialogue unit Interchangeability Version Terminals
1 For use with thermal-magnetic trip only: 500VDC, 2 poles in series 600 VDC, 3 poles in series 2 15-30A units are 65kA at 480VAC 3 15A units are 14kA at 480VAC
15.2
AC 1000 - 11/03
15
Is MC oma CB x s
S7 S8
S4
S5
S6
S6
S4 250 600 3000 8 2-3-4 N 65 25 18 65 35 30 25 14 H 150 65 22 150 65 50 40 18 10.0 x 4.13 x 4.07 10.0 x 5.51 x 4.07 25.000 120 8.8 L 200 100 35 200 100 80 50 20 N 65 35 22 35 50 65 35 30 25 20
S5 400 600 3000 8 2-3-4 H 150 65 22 50 20 100 65 50 40 25 10.00 x 5.51 x 4.07 10.00 x 7.24 x 4.07 20,000 120 11.0 L 200 100 35 65 35 200 100 80 65 30 N 65 50 25 35 50 65 35 30 25 20
S6 600 600 3000 8 2-3-4 H 150 65 35 50 20 100 65 50 40 25 10.55 x 8.27 x 4.07 10.55 x 11.0 x 4.07 20,000 120 21.0 L 200 100 42 65 35 200 100 80 65 35 N 65 50 25 35 50 65 35 30 25 20
S6 800 600 3000 8 2-3-4 H 150 65 35 50 100 65 50 40 25 14.25 x 8.27 x 4.07 14.25 x 11.0 x 4.07 20,000 120 22.0 L 200 100 42 65 200 100 80 65 35
S7 1200 600 3000 8 2-3-4 H 100 65 50 100 65 55 45 25 15.98 x 8.27 x 5.45 15.98 x 11.0 x 5.45 10,000 120 37.5
S8 1600/2000/2500 600 3000 8 3 V 125 100 85 120 120 100 70 50 15.75 x 15.98 x 9.25
15
10,000 20 135
1 For use with thermal-magnetic trip only: 500VDC, 2 poles in series 600 VDC, 3 poles in series
15.3
AC 1000 - 11/03
15
ax m s o Is CB MC
Improved use
General information
ABB Isomax circuit breakers from Model S4 to S8 and starting from 40A are provided with microprocessor based modular relays. These are available in two versions: ABB PR211: with overload and short-circuit protection ABB PR212: with overload protection, short-circuit protection, and ground fault protection. This version can also be tted with a dialog unit for connection to automation systems. These reliable and precise relays are unaffected by electromagnetic disturbances. Minimal response tolerances ensure high precision in discrimination computations. S1, S3 and selected versions of the S5 and S6 breakers are tted with thermal-magnetic trip releases. Flexible and modular construction simplify panel design and construction for: primary distribution (switchboards) motor control (MCC) secondary distribution (panelboards) panel builders (OEM & users) Standard modular dimensions Standard circuit breaker depths S3-S6 Assembly onto DIN prole up to 400 A Full range of accessories Standard front ange: - for DIN 45mm cut-outs on S3-S5 - for 105mm cut-outs on S3-S7. Handle operators: - ange type - variable depth rotary type - xed depth rotary type
Maximum versatility
ABB Isomax circuit breakers can be tted with a wide range of terminals for all types of connections. Modular design also makes installation and assembly extremely simple. The various terminal options can be tted in different combinations in the same unit (e.g. one type at the top and another at the bottom). This makes ABB Isomax circuit breakers easy to adapt to any installation.
15
Front Extended front CU front cable terminals (saddle type) CU/AL front cables (standard type)
CU rear cables Rear threaded Rear horizontal at bar Rear vertical at bar
15.4
AC 1000 - 11/03
15
Is MC oma CB x s
Simplied maintenance
Maintenance operations are kept to a minimum. All inspection can be performed quickly and easily. A dialog unit (optional) can be installed to store operational data for efcient maintenance scheduling. Reliability is ensured by the high quality of all materials and by advanced manufacturing in automated assembly systems capable of ensuring consistent product quality. Insulation distances are as required for both UL/CSA 600VAC approvals and also IEC-947 690VAC rating, which ensures safe insulation even under the severest operating conditions. Double insulation. The cover on S3 S7 encloses all electrical accessory cavities which are also completely separated from the power circuit. Moreover: positive operation to guarantee safe and reliable signalling. optional draw-out with closed-door racking-out for maximum operational safety. high and low terminal covers are available to increase operator protection level.
15
15.5
AC 1000 - 11/03
15
ax m s o Is CB MC
Versions Key
1 2 3 4 5 6 7 8
On request, IEC circuit breakers can be delivered in plug-in or withdrawable, two, three or four pole versions. Units are normally provided with front or rear terminals. Fixed parts are always manufactured to IP20 protection. See Accessories section for details of other optional accessories.
3
Terminals Fixed contacts Arcing chamber Moving contacts Operating mechanism Microprocessor based solid-state relay Closed door isolation device Plug-in connector for auxiliary circuits
2 4
15
8 7
15.6
AC 1000 - 11/03
15
Is MC oma CB x s
Operating lever Overcurrent relay adjustments Closed door racking-in and racking-out device 4 Rotary handle operating mechanism 5 Standard front ange (105 mm/4.13" high). Available for circuit-breakers S3 S7 6 Flange (45 mm/1.77" high) for installation of circuit breakers behind standard IEC doors. Available for circuit-breakers up to S5 frame 7 Direct acting motor operator S3 S5 8 Stored energy motor operator S6 S7 9 Shunt trip device 10 Undervoltage release 11 Auxiliary contact switch for circuit breaker position indication
6 4
1 7 2 5
15
10
11
15.7
AC 1000 - 11/03
15
ax m s o Is CB MC
Combinations of terminals Connection type
All circuit breaker bus terminations are made of silver-plated copper. Terminals can be provided in different combinations (e.g. one type at the top and another type at the bottom). Various connection schemes are available making ABB Isomax circuit breakers easily adapted to any installation requirements. In particular, this exceptional versatility makes
Circuit-breaker F
Front bar P W F
S1 S3 S4 S5 S6 S7 S8
Key: F = Fixed P = Plug-in
W = Withdrawable
= Optional terminals
=Standard connections
15
Circuit-breaker F
S1 S3 S4 S5 S6 S7 S8
Key: F = Fixed P = Plug-in
W = Withdrawable
= Optional terminals
15.8
AC 1000 - 11/03
15
Is MC oma CB x s
Double insulation
The double insulation technique involves the total separation of the power and auxiliary circuits, and is a characteristic of all Isomax breakers, from size S3 to S7. The housing of each electrical accessory is completely segregated from the power circuit, thus avoiding all risk of contact with the active parts and hence improving operator safety conditions in plant management and inspection. In addition, the insulation of the internal active parts, in terms of both the thickness of the materials and the distances, is superior to that required by the IEC Standards and complies with American usage.
Positive operation
The operating lever always indicates the exact position of the moving contacts in the circuit-breaker, thus guaranteeing safe and reliable indication (I = Closed; O = Open; yellow line = Open due to tripping of releases). The operating mechanism of the circuit-breaker is trip-free, independently of the pressure on the lever or the speed of operation. Tripping of the releases automatically opens the moving contacts; to close them again, the operating mechanism has to be reset by pushing the operating lever from the intermediate position fully down to the lower limit of the open position. In the plug-in or withdrawable circuit breakers, the mobile part can only be detached from the xed part when the circuit-breaker is open (i.e. moving contacts separate from xed contacts).
15
Selectivity
The complete range of releases available makes it possible to coordinate protection functions using current-type, time-type, energytype or residual-current selectivity chains. This makes it possible to isolate only those zones affected by faults, ensuring maximum operating continuity. Circuit-breakers in category B are available from 400 A upwards. (IEC 947-2)
Inspection
A direct check can be made on the state of the internal parts and active components when the circuit-breaker is out of service. Access can be gained to the arcing chambers and xed and moving contacts simply by removing the cover of the circuit-breaker. The operation, made easier by the limited number of components, reduces maintenance times and guarantees a higher level of safety.
15.9
AC 1000 - 11/03
15
ax m s o Is CB MC
Isolation behavior
In the open position, the circuit-breaker guarantees the isolation of the circuit in accordance with IEC 947-2 specications. In the IEC withdrawable or plug-in versions, the power and auxiliary circuits are isolated in the racked out or removed positions, thus guaranteeing that no parts are live. In these conditions, using suitable connectors, blank tests can be conducted, with the operations on the circuit-breaker being carried out in complete safety. The redundant insulation distances guarantee the absence of leakage currents and dielectric strength in the event of any overvoltages across the input and output.
15
Electromagnetic compatibility
With the use of the PR211/P microprocessor-based overcurrent releases and the RC211 and RC212 electronic residual current releases, slow non-operation is guaranteed, even in the presence of interference caused by electronic equipment, atmospheric disturbance or discharges of an electrical nature. Furthermore, the appliances do not generate interference with other electronic equipment in the vacinity. This is in accordance with IEC 947-2 Addendum F, IEC 1000-4, EN 61000-4, EN 50081-2, European Directive No. 49/12-12-1992 specications on electromagnetic compatibility EMC.
Tropicalization
The Isomax series of circuit-breakers and accessories comply with the strictest regulations on use in hot-damp saline climates (in conformity with climatographic chart No. 8 of the IEC 721-2-1 specications), thanks to: insulating cases made of berglass-reinforced synthetic resins corrosion-resistant treatment on all main metal parts (environment C UNI 3564-65) Fe/Zn 12 galvanizing (UNI ISO 2081), protected by a conversion layer composed mainly of chromates (UNI ISO 4520).
15.10
AC 1000 - 11/03
15
Is MC oma CB x s
Protection classes
Various measures have been incorporated in Isomax S circuit-breakers to achieve IP20 protection for the xed, plug-in and withdrawable versions of the circuit-breaker, excluding the terminals, and IP 30 for the front parts of circuit-breakers installed in switchboards. The xed parts are always IP20 protection grade. IP54 protection can be achieved for circuit-breakers installed in switchboards by using doormounted crank handle operating mechanisms and special insulating gaskets that can be ordered separately.
15
Resistance to vibration
The circuit-breakers are unaffected by vibrations generated mechanically or by electromagnetic effects, in compliance with the IEC 68-2-6 standards and the strictest regulations set by the most important classication organizations: RINA DET Norske Veritas Lloyd's Register of Shipping Germanischer Lloyd Bureau Veritas
Installation positions
The circuit-breakers can be installed in any position with no variations to their rated characteristics. In compliance with UL and IEC 947-2 standards, Isomax S circuitbreakers can be powered from either their top or bottom terminals, without affecting operation. They can be installed in switchboards, mounted directly on the base plate or on DIN channels up to size S5.
15.11
AC 1000 - 11/03
15
ax m s o Is CB MC
Table of power losses
Dissipated power (W) Setting In (A)
R15 R20 R25 R30 R40 R50 R60 R70 R80 R90 R100 R125 R150 R175 R200 R225 R300 R400 R600 R800 In = 100 In = 150 In = 250 In = 300 In = 400 In = 600 In = 800 In = 1000 In = 1200 In = 1600 In = 2000 In = 2500
15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 225 300 400 600 800 100 150 250 300 400 600 800 1000 1200 1600 2000 2500
11.8 10.8 12 16.9 15.1 16.4 14.4 15.8 17.9 21.9 21 18.5 40.5 35.9 36 55
13 11.9 13.2 18.5 16.6 18 16 18.8 21 26 25 26 52 40 46 67 52.7 66.4 79 96 83 93.2 5.2 13 40 8 19 55 40 60 57 90 63 96 104 125 102 151 140 203 41 64 100 106 119
15 400Hz response
Breaker frame Breaker rating Thermal amperes Minimum Maximum Fixed Magnetic rating Minimum Maximum
400Hz response
Thermal magnetic releases 1 Breaker frame S5N S6N Breaker rating 300 400 600 800 Thermal Amperes Minimum Maximum 0.7 189 252 378 504 1.0 270 360 540 720 Magnetic rating Set @ 5lm only 2250 3000 4500 6000
S1
1000 1000 1000 1000 1000 1000 1200 1400 1600 1800 2000 850 850 850 850 850 850 850 1020 1190 1360 1530 1700 1360 1605 1640 1875 2138 2400
S3
15.12
AC 1000 - 11/03
Protective releases
15
Is MC oma CB x s
S3 150 S3 225
Fixed thermal
+
Fixed magnetic
S1 100, S3 100
R15 R20 R25 R30 R35 R40 R45 R50 R60 R70 R80 R90 R100 R125 R150 R175 R200 R225 R300 R400 R600 R800
18 24 30 35 41 47 53 59 71 83 94 106 118 148 177 207 236 266 345 465 690 965
17 22 28 33 39 44 50 56 67 78 90 101 112 140 168 196 224 252 328 442 656 90
16 21 27 32 37 42 48 53 64 74 85 95 106 133 159 186 212 239 314 420 628 855
15 20 25 30 35 40 45 50 60 70 80 90 100 125 150 175 200 225 300 400 600 800
15
15.13
AC 1000 - 11/03
15
ax m s o Is CB MC
S1, 100 R15-R30
10000 2000 1000 200 100 t [s] 20 10
2000 1000
200 100
20 t [s] 10
2 1
2 1
R20 R25
R40
0.01 0.1
1 x Ith
10
100
2000 1000
15
200 100
0.01 0.1
1 x Ith
10
100
15.14
AC 1000 - 11/03
15
Is MC oma CB x s
S3, R20-R30
10000
2000 1000
2000 1000
200 100
200 100
t [s]
20 10
t [s]
20 10
2 1
2 1
0,1
1 x Ith
10
100
S3, R35-R50
10000
S3, R50-R100
10000
2000 1000
2000 1000
15
200 100
200 100
20 t [s] 10
20 10 t [s] 2 1
2 1
0.1
0.1
0.01
0.01 0.1
0.1 1 x Ith 10 100
1 x Ith
10
100
15.15
AC 1000 - 11/03
15
ax m s o Is CB MC
S3, R125-R225 10X Im
10000 2000 1000 200 100 20 10 t [s] 2 1
2000 1000
200 100
20 10 t [s] 2 1
0.1
0.1
0.01 0.1
15
15.16
AC 1000 - 11/03
Protective releases Specic let-through energy I2t curves S3 TM - Ith = 15A 225A, 480VAC
15
Is MC oma CB x s
225A 200A 175A 150A 125A 100A 90A 80A
I 2t [(kA)2s ] 10
10 -1
15A
15
10 -2 1
Key Is = Prospective short-circuit symmetrical current I2t = Specic let-through energy at the voltages shown
10
10 2
10 3 Is [kA]
15.17
AC 1000 - 11/03
15
ax m s o Is CB MC
They are available in two versions:
Microprocessor based overcurrent relays for alternating current for S4, S5, S6 and S7 circuit-breakers
The microprocessor based overcurrent relays (actual RMS) for Isomax S circuitbreakers offer a wide range of current and trip time settings. PR211/P with overcurrent protection L and instant short circuit protection I. Available with functions L, I, or L+I. L function includes adjustable long-time pick-up and long-time delay. PR212/P with overcurrent protection L, selective short circuit protection S, instant short circuit protection I and ground fault protection G. Available with functions L+S+I or L+S+I+G. Functions S, I and G can be excluded manually by means of the trip current threshold selector (OFF position). In its most complete conguration, i.e. with functions L+S+I+G, the PR212/P relay can be combined, on request, with the following units:
Note
The K and T units are always external. Other important features of the microprocessor based relays are as follows: protection of neutral with programmable automatic adjustment, executed by the manufacturer, to 50% (standard) or 100% (on request) of the current value selected for the phases. The optional version has no code in this catalog; reliable operation also when one phase only is live; individual and simultaneous adjustment on the three phases and neutral; no need for auxiliary supply; trip specications not affected by the ambient temperature; consistency of specications and reliability including in contaminated environments; signalling of tripped relay (available for all versions) by means of voltage-free contact for 24 V d.c. or a.c. circuits maximum 3 W. Circuit-breaker rated current change according to ambient temperature. The tripping characteristics of Isomax S4 S8 with electronic trip units are unaffected by ambient temperatures from -25C to +70C.
The dialog unit is external for circuit breakers S4 and S5 and is located inside the The external dialog unit is connected by means of a cable for supply and communication with the PR212/P protection relay. The standard version of the dialog interface has the following specications: hardware: EIA RS485 serial transmission line communication protocol: ABB Modbus transmission speed: 150 19200 baud (bit/s).
15.18
AC 1000 - 11/03
Protective releases Microprocessor based overcurrent relays, PR211 for S4, S5, S6 & S7 breakers
Protective functions and set values
Protection against Trip Symbol
15
Is MC oma CB x s
Overload Short-circuit
L I
PR211
5
Key
1 2 3 4 5 Dip-switch for function L setting (I1) Dip-switch for function I setting (I3) Rated current of current transformers 15 V d.c. input for release functioning check Function L trip time setting dip switch (T1)
15
Rated and setting currents
Circuit-breaker Iu-A Current transformer In-A L (I1) A (0.4 1 x In) Functions I (I3) A (1.5 12 x In)
S4 S5 S6 S7
40 100 100 250 120 300 160 400 240 600 320 800 400 1000 480 1200
150 1200 375 3000 450 3600 600 4800 900 7200 1200 9600 1000 12,000 1800 14,400
15.19
AC 1000 - 11/03
15
ax m s o Is CB MC
Function L - I
15
Key
In = Rated current of current transformers t = Tripping time
15.20
AC 1000 - 11/03
Protective releases Microprocessor based overcurrent relays, PR212 Protection functions and set values, S4 S8
Protection functions and set values
Protection against Overload Short-circuit Short circuit
15
Is MC oma CB x s
Earth fault
Trip Symbol Set values (manual adjustment in steps Set values (electronic adjustment)
Inverse or denite short delay S I2 = 1-2-3-4-6-8-10 OFF x In t2 = 4 curves A D I2 = 1 10 OFF x In t2 = 0.05 0.5
I3 = 1.5-12 OFF x In
PR212
8 2
Key
1 2 3 4 5 6 7 8 9 10 Function L setting dip-switch (I1)
4 4b
Function L trip time setting dip-switch (t1) Function S setting dip-switch (I2) Function S trip time setting dip-switch (t2) Function I setting dip-switch (I3) Function G setting dip-switch (I4) Function G trip time setting dip-switch (t4) Rated current of current transformers 15 V d.c. input for release functioning check Socket for connecting SACE PR010/T test unit
15
1 S8 it = 0.2 - 0.4
15.21
AC 1000 - 11/03
15
ax m s o Is CB MC
Rated and setting currents
Circuit breaker Iu
S4 S5 S6 S7
40 100 100 250 120 300 160 400 240 600 320 800 400 1000 480 1200 640 1600 800 2000 1000 2500
100 .1000 250 .2500 300 .3000 400 .4000 600 .6000 800 .8000 1000 .10,000 1200 .12,000 1600 .16,000 2000 .20,000 2500 .25,000
150 1200 375 3000 450 3600 600 4800 900 7200 1200 9600 1500 12,000 1800 14,400 2400 19,200 3000 24,000 3750 30,000
20 100 50 250 60 300 80 400 120 600 160 800 200 1000 240 1200 320 640 400 800 500 1000
S8
1600 2500
2000 2500
Key
Iu In I1 I2 I3 I4 = = = = = = Rated uninterrupted current of circuit-breaker Rated current of current transformers Current setting value for relay overload protection Current setting value for relay short-circuit selective protection Current setting value for relay instantaneous short-circuit protection Current setting value for earth fault protection
15
15.22
AC 1000 - 11/03
15
Is MC oma CB x s
15
Key
In t = = Rated current of current transformers Tripping time
15.23
AC 1000 - 11/03
15
ax m s o Is CB MC
Function L - S - I
15
Key
In t = = Rated current of current transformers Tripping time
15.24
AC 1000 - 11/03
15
Is MC oma CB x s
15
Key
In t = = Rated current of current transformers Tripping time
15.25
AC 1000 - 11/03
15
ax m s o Is CB MC
208V Horsepower per NEC 430-50 230V 460V
Magnetic trip 1/2 1/2 3/4 3/4 1 1 1/2 1/2 1 1/2 3/4 2 3/4 3 1 1 3 1 1/2 5 1 1/2 2 2 3 3 7 1/2 10 5 5 15 15 7 1/2 7 1/2 20 10 10 30 25 30 40 15 15 40 20 20 60 50 25 25 60 30 30 75 100 75 50 25 20 10 5 7 1/2 1 1/2 2 0.9 1.1 1.3 1.6 1.7 2.1 2.2 2.4 2.7 3 3.2 3.4 3.5 3.9 4.2 4.6 4.8 6 6.1 6.6 6.8 7.5 7.6 9 9.6 10.6 11 14 15.2 16.7 17 21 22 24.2 27 28 30.8 32 34 40 41 42 46.2 52 54 59.4 62 65 68 74.8 77 80 88 96 99 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 S3 3 3 3 3 3 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 25 25 25 25 25 25 25 25 25 25 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 150 150 150 150 150 150
1300 1100 900 800 700 1000 900 800 700 700 600 600 1100 1000 1000 900 800 700 700 600 600 1300 1300 1100 1000 900 900 700 700 600 600 1000 900 800 700 700 600 600 600 1000 1000 1000 900 800 700 700 600 600 600 800 800 800 700 600 600
2000 1600 1400 1100 1100 1400 1400 1300 1100 1000 900 900 1700 1500 1400 1300 1300 1000 1000 900 900 2000 2000 1700 1600 1400 1400 1000 1000 900 900 1400 1400 1200 1100 1100 1000 900 900 1500 1500 1400 1300 1200 1100 1000 100 900 900 1200 1200 1100 1000 900 900
2700 2200 1800 1500 1400 1900 1800 1700 1500 1300 1300 1200 2300 2100 1900 1700 1700 1300 1300 1200 1200 2700 2600 2200 2100 1900 1800 1400 1300 1200 1200 1900 1800 1700 1500 1400 1300 1300 1200 2000 2000 1900 1700 1500 1500 1300 1300 1200 1200 1600 1600 1500 1400 1300 1200
3400 3700 2300 1900 1800 2400 2300 2100 1900 1700 1600 1500 2900 2600 2400 2200 2100 1700 1600 1500 1500 3300 3300 2800 2600 2400 2300 1800 1600 1500 1500 2400 2300 2100 1900 1800 1600 1600 1500 2500 2400 2400 2200 1200 1900 1700 1600 1500 1500 2000 1900 1900 1700 1600 1500
4000 3300 2800 2300 2100 2900 2700 2500 2200 2000 1900 1800 3400 3100 2900 2600 2500 2000 2000 1800 1800 4000 3900 3300 3100 2800 2700 2100 2000 1800 1800 2800 2700 2500 2200 2100 1900 1900 1800 3000 2900 2900 2600 2300 2200 2000 1900 1800 1800
15
15.26
AC 1000 - 11/03
15
Is MC oma CB x s
10X % 12X %
Electronic trip 40 40 100 125 50 50 150 60 125 60 150 75 75 200 250 100 100 300 250 125 350 125 150 300 400 150 450 350 500 400 200 450 200 500 104 114 124 125 130 143 144 154 156 169 180 192 211 240 242 248 273 289 302 312 336 343 360 361 362 396 412 414 472 477 480 515 528 590 S4 S4 S4 S4 S4 S4 S4 S4 S4 S4 S5 S5 S5 S5 S5 S5 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S6 S7 250 250 250 250 250 250 250 250 250 250 400 400 400 400 400 400 600 600 600 600 600 600 600 600 600 600 800 800 800 800 800 800 800 1000
350 350 300 300 300 250 250 250 250 200 350 300 300 250 250 250 350 300 300 300 250 250 250 250 250 250 300 300 250 250 250 250 250 250
500 450 400 400 400 350 350 300 300 300 450 400 400 350 350 300 450 400 400 400 350 350 350 350 300 300 400 400 350 350 350 300 300 350
1000 900 800 800 800 700 700 600 600 600 900 800 800 700 700 600 900 800 800 800 700 700 700 700 600 600 800 800 700 700 700 600 600 700
1400 1300 1200 1200 1200 1000 1000 1000 1000 900 1300 1300 1100 1000 1000 1000 1300 1200 1200 1200 1100 1100 1000 1000 900 900 1200 1200 1000 1000 1000 900 900 1000
1900 1800 1600 1600 1500 1400 1400 1300 1300 1200 1800 1700 1500 1300 1300 1300 1800 1700 1600 1500 1400 1400 1300 1300 1300 1200 1600 1600 1400 1300 1300 1200 1200 1400
2400 2200 2000 2000 1900 1700 1700 1600 1600 1500 2200 2100 1900 1700 1700 1600 2200 2100 2000 1900 1800 1700 1700 1700 1600 1500 1900 1900 1700 1700 1700 1600 1500 1700
2900 2600 2400 2400 2300 2100 2100 1900 1900 1800 2700 2500 2300 2000 2000 1900 2600 2500 2400 2300 2100 2100 2000 2000 1900 1800 2300 2300 2000 2000 2000 1900 1800 2000
15
15.27
AC 1000 - 11/03
15
ax m s o Is CB MC
Notes
15
15.28
AC 1000 - 11/03
15
Is MC oma CB x s
S4 N 250 B W - 2 xxx
Number of poles
-2 = -4 = None = 2 pole 4 pole 3 pole
Type connectors
W = None
15
Current rating
015 = 250 = 400 = 1200 = 15A 250A 400A 1200A
Frame size
S1= S3 = S4 = S5 = 100A 150 / 225A 250A 400A S6 = 600 / 800A S7 = 1200A
1 Consult ABB for factory installed accessories. 2 Consult ABB for availability.
15.29
AC 1000 - 11/03
15
ax m s o Is CB MC
S1
General
The S1 breaker family ranges from 15 through 100 amperes. The S1 trip mechanisms are non-interchangeable and use sensitive electromagnetic relays for overcurrent trip protection. Heat sensitive bimetals are used for thermal rating of the breaker. Lugs are included with the S1 breaker.
240VAC 277/480VAC
Number of poles
The S1 is available in three pole or four pole versions. The four pole version is IEC only. For price estimate of a four pole device, add 35% to list price of selected version three pole breaker, contact ABB Control for details.
Accessory mounting 1
Shunt trips or undervoltage releases mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S1 family are suitable for reverse feed applications.
15 100A
S1N
Breaker IC at 480 VAC Rating Magnetic 3 pole catalog number List price
14kA
15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A
500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A
S1N015TL S1N020TL S1N025TL S1N030TL S1N040TL S1N050TL S1N060TL S1N070TL S1N080TL S1N090TL S1N100TL
$ 392
15
S1N
20kA
392
459
15.30
AC 1000 - 11/03
Discount schedule S1
15
Is MC oma CB x s
Standard S3 package includes complete circuit breaker and mounting hardware. Order cable lugs as a separate item, standard copper/ aluminum (Cu/Al) lugs are no charge when ordered with breaker.
HxWxD 6.70" x 4.13" x 4.07"
S3B
General
The S3 breaker family ranges from 15 through 225 amperes. The S3 trip mechanisms are non-interchangeable and use sensitive electromagnetic relays for overcurrent trip protection. Heat sensitive bimetals are used for thermal overcurrent protection. Short circuit current protection begins at 10 times the thermal rating of the breaker and uses a magnetic coil principle.
Versions
To meet all application needs, the S3 is available in various versions: T =Thermal-magnetic Q =100% UL rated D = Molded case switch M = Magnetic only (MCP) G = 3X Mag (100 - 225A 3-pole only)
65 25 14 35 20
100 50 14 50 35
150 85 1 25 65 50
Performance level
Each version is also available in different maximum fault interrupting levels B = 240VAC N = Normal H = High L = Extra high
Number of poles
In UL/CSA form, the S3 is available in two pole or three pole versions, both with the same dimensions. A four pole version is also available in UL/ IEC form. For price estimate, add 35% to list price of selected version three pole breaker, contact ABB Control for details.
65 35 30 25 14 35 20
100 65 50 40 18 50 35
170 85 65 50 20 65 50
Accessory mounting
Internal accessories are UL/CSA approved for both factory or eld installation. Accessories require control cable connectors. Shunt trips or UVR's mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
15
Reverse feeding
All versions of the S3 family are suitable for reverse feed applications.
Discount schedule S3
15.31
AC 1000 - 11/03
15
ax m s o Is CB MC
S3B
Breaker IC at 240VAC
Rating
S3B
150kA
$ 460
$ 590
S3N
Breaker IC at 480VAC Rating Magnetic trip 2 pole, 480VAC/500VDC catalog number List price 3 pole, 600VAC/DC catalog number List price
S3N
25kA
15A 20A 25A 30A 35A 40A 50A 60A 70A 80A 90A 100A 125A 150A 175A1 200A1 225A1
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3N015TW-2 S3N020TW-2 S3N025TW-2 S3N030TW-2 S3N035TW-2 S3N040TW-2 S3N050TW-2 S3N060TW-2 S3N070TW-2 S3N080TW-2 S3N090TW-2 S3N100TW-2 S3N125TW-2 S3N150TW-2 S3N175TW-2 S3N200TW-2 S3N225TW-2
$ 316
S3N015TW S3N020TW S3N025TW S3N030TW S3N035TW S3N040TW S3N050TW S3N060TW S3N070TW S3N080TW S3N090TW S3N100TW S3N125TW S3N150TW S3N175TW S3N200TW S3N225TW
$ 413
407
504
911
1131
S3H
Breaker IC at 480VAC Rating Magnetic trip 2 pole, 480VAC/500VDC catalog number List price 3 pole, 600VAC/DC catalog number List price
S3H
50kA
15A 20A 25A 30A 35A 40A 50A 60A 70A 80A 90A 100A 125A 150A 175A1 200A1 225A1
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3H015TW-2 S3H020TW-2 S3H025TW-2 S3H030TW-2 S3H035TW-2 S3H040TW-2 S3H050TW-2 S3H060TW-2 S3H070TW-2 S3H080TW-2 S3H090TW-2 S3H100TW-2 S3H125TW-2 S3H150TW-2 S3H175TW-2 S3H200TW-2 S3H225TW-2
$ 527
S3H015TW S3H020TW S3H025TW S3H030TW S3H035TW S3H040TW S3H050TW S3H060TW S3H070TW S3H080TW S3H090TW S3H100TW S3H125TW S3H150TW S3H175TW S3H200TW S3H225TW
$ 619
617
702
15
1376
1586
S3L
Breaker IC at 480VAC Rating Magnetic trip 2 pole, 480VAC/500VDC catalog number List price 3 pole, 600VAC/DC catalog number List price
65k
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3L015TW-2 S3L020TW-2 S3L025TW-2 S3L030TW-2 S3L035TW-2 S3L040TW-2 S3L050TW-2 S3L060TW-2 S3L070TW-2 S3L080TW-2 S3L090TW-2 S3L100TW-2 S3L125TW-2 S3L150TW-2 S3L175TW-2 S3L200TW-2 S3L225TW-2
$ 634
S3L015TW S3L020TW S3L025TW S3L030TW S3L035TW S3L040TW S3L050TW S3L060TW S3L070TW S3L080TW S3L090TW S3L100TW S3L125TW S3L150TW S3L175TW S3L200TW S3L225TW
$ 824
634
824
S3L
85kA
816 1818
1010 2260
65kA
1818
2260
1 480VAC maximum
15.32
AC 1000 - 11/03
Discount schedule S3
15
Is MC oma CB x s
List price
S3NQ
25kA
15A 20A 25A 30A 35A 40A 50A 60A 70A 80A 90A 100A 125A 150A 175A1 200A1 225A1
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3NQ015TW S3NQ020TW S3NQ025TW S3NQ030TW S3NQ035TW S3NQ040TW S3NQ050TW S3NQ060TW S3NQ070TW S3NQ080TW S3NQ090TW S3NQ100TW S3NQ125TW S3NQ150TW S3NQ175TW S3NQ200TW S3NQ225TW
$ 459
560
1257
S3HQ
Breaker IC at 480VAC Rating Magnetic trip 3 pole catalog number List price
S3HQ
50kA
15A 20A 25A 30A 35A 40A 50A 60A 70A 80A 90A 100A 125A 150A 175A1 200A1 225A1
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3HQ015TW S3HQ020TW S3HQ025TW S3HQ030TW S3HQ035TW S3HQ040TW S3HQ050TW S3HQ060TW S3HQ070TW S3HQ080TW S3HQ090TW S3HQ100TW S3HQ125TW S3HQ150TW S3HQ175TW S3HQ200TW S3HQ225TW
$ 688
780
1762
15
S3LQ
Breaker IC at 480VAC Rating Magnetic trip 3 pole catalog number List price
65kA
500A 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
S3LQ015TW S3LQ020TW S3LQ025TW S3LQ030TW S3LQ035TW S3LQ040TW S3LQ050TW S3LQ060TW S3LQ070TW S3LQ080TW S3LQ090TW S3LQ100TW S3LQ125TW S3LQ150TW S3LQ175TW S3LQ200TW S3LQ225TW
$ 916
S3LQ
85kA
1123
2511
Note: When applied correctly, UL tested 100% equipment rated breakers may be applied at full rating rather than on the sizing rules of the NEC where breakers and cable are sized based on actual continuous load current divided by 80%. This 100% rating can save the user the cost of larger cable or bus bar. Please consult the NEC for details and other design factors needed for this application.
1 480VAC maximum
Discount schedule S3
15.33
AC 1000 - 11/03
15
ax m s o Is CB MC
Magnetic only (MCP)
Type
S3 150/225A, 600VAC
Magnetic only circuit breakers are instantaneous trip only devices which are Underwriters Laboratories Recognized. MCPs must be used with some other device that will provide overload protection.
Interruption capacity Amps Magnetic trip 3 pole catalog number List price
3 5 10 25
S3N
Type
Interruption capacity
Amps
Magnetic trip
List price
240VAC 480VAC 600VAC 240VAC 480VAC 600VAC 240VAC 480VAC 600VAC 480VAC
50kA 25kA 10kA 50kA 25kA 10kA 150kA 85kA 25kA 65kA
3 5 10
12 36 20 60 40 120
25
100 300
S3L025MW
S3L
800 2400
S3B-D
225
2250A
S3B225DW
$ 410
15
S3H-D
150 225 2
1500A 2250A
S3H150DW S3H225DW
892 1254
Withstand rating
600VAC
6.5kA
Connection options
Type Wire range Amps Set of 2 catalog number List price Set of 3 catalog number List price
CU/AL front lugs CU/AL front lugs CU/ALfront lugs CU/AL front lugs
$4 4 4 10
$6 6 6 15
30 46
1 Suggested lugs for circuit breaker up to amps shown. Cable size and type determine maximum amperage. 2 480VAC maximum. 3 With fuse or MCCB protected circuit.
15.34
AC 1000 - 11/03
Discount schedule SM S3 MCPs only Discount schedule S3 Circuit breakers Discount schedule SA Lugs
15
Is MC oma CB x s
Standard S4 package includes complete circuit breaker and mounting hardware. Order cable lugs or other connection scheme as a separate item.
S4
General
The S4 breaker family is a 250A frame utilizing a microprocessor based overcurrent protective trip system. In the 250A version, the trip unit is adjustable from 100A up to 250A without the addition of any parts or rating plugs. As standard, the S4 includes adjustable long time function for overload protection and adjustable instantaneous function for short circuit protection.
Versions
To meet all application needs, the S4 is available in various versions: B = Adjustment LI C = Adjustment LSI E = Adjustment LSIG Q = 100% UL rated D = Molded case switch M = Magnetic only (MCP)
65 25 18
150 65 22
200 100 35
Trip functions
These tripping functions are available: L = Long time S = Short time I = Instantaneous G = Ground fault
65 35 30 25 18
150 65 50 40 22
200 100 80 65 30
Performance level
Each version is also available in different maximum fault interrupting levels: N = Normal H = High L = Extra high
Number of poles
In UL/CSA form, the S4 is available in two pole or three pole versions, both with the same dimensions. A four pole version is also available in UL/IEC form. For price estimate, add 35% to list price of selected version three pole breaker, contact ABB Control for details.
15
Accessory mounting
Internal accessories are UL/CSA approved for both factory or eld installation. Accessories require control cable connectors. Shunt trips or UVR's mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S4 family are suitable for reverse feed applications.
Discount schedule S4
15.35
AC 1000 - 11/03
15
ax m s o Is CB MC
Breaker IC at 480VAC
The S4 breaker family uses two available microprocessor based internal trip units. The standard PR211 trip unit includes adjustments for long time current pick-up and instantaneous current trip point.
S4N
25kA
S4H
65kA
S4L
100kA
S4N
25kA
S4H
65kA
S4L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
0.5 50 125
0.6 60 150
0.7 70 175
0.8 80 200
0.9 90 225
0.95 95 237
15.36
AC 1000 - 11/03
Discount schedule S4
15
Is MC oma CB x s
NEC for details and other design factors needed for this application.
Trip type Adjustment 3 pole catalog number List price
S4N
25kA
S4H
65kA
S4L
100kA
S4N
25kA
S4H
65kA
S4L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
Discount schedule S4
15.37
AC 1000 - 11/03
15
ax m s o Is CB MC
Magnetic only (MCP)
Type Amps
S4 250A, 600VAC
All S4 magnetic only breakers utilize the electronic PR211 trip unit with an adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs are 600VAC rated.
Interruption capacity Adjustment range 2 pole 600VAC catalog number List price 3 pole 600VAC catalog number List price
S4N
150 1200A 375 3000A 150 1200A 375 3000A 150 1200A 375 3000A
$ 1073
$ 1347
S4H
2572
3030
S4L
3159
3950
S4H-D
250
3000A
S4H250DW
$ 1215
100 250
K4NCT-100 K4NCT-250
$ 250
Connection options
Type Wire range Amps Set of 2 catalog number List price Set of 3 catalog number List price
CU/AL front lugs CU/AL front lugs CU/AL front lugs CU/AL front lugs
$4 4 10 20
$6 6 15 30
15
CU front lugs (saddle) CU rear lugs Extended front bar 14AWG 250kcmil 6AWG 250kcmil 250 250 250
30 46
1 Suggested lugs for a circuit breaker up to the amps shown. Cable size and type determine maximum amperage. 2 With fuse or MCCB protected circuit.
15.38
AC 1000 - 11/03
15
Is MC oma CB x s
Standard S5 package includes complete circuit breaker and mounting hardware. Order cable lugs or other connection scheme as a separate item.
(a) With K5TF cable lugs, breaker is 10.0" tall. (b) With K5TG cable lugs, terminal covers are provided and breaker is 13.62" tall.
HxWxD 10.0" x 5.51" x 4.07" (a) 13.62" x 5.51" x 4.07" (b)
S5
General
The S5 breaker family is a 400A frame utilizing a microprocessor-based overcurrent protective trip system. In the 400A version, the trip unit is adjustable from 160A up to 400A without the addition of any parts or rating plugs. As standard the S5 includes adjustable long time function for overload protection and adjustable instantaneous function for short circuit protection.
65 35 22 35 20
150 65 22 50 35
200 100 35 65 50
Versions
To meet all application needs, the S5 is available in various versions: B = Adjustment LI C = Adjustment LSI E = Adjustment LSIG Q = 100% UL rated D = Molded case switch M = Magnetic only (MCP) T = Thermal magnetic G = 2.5 Mag ( 3-pole only)
65 35 30 25 20
100 65 50 40 25
200 100 80 65 30
Trip functions
These tripping functions are available: L = Long time S = Short time I = Instantaneous G = Ground fault
Performance level
Each version is also available in different maximum fault interrupting levels N = Normal H = High L = Extra high
15
Number of poles
In UL/CSA version, the S5 is available in two pole or three pole version, both with the same dimensions. A four pole version is also available in UL/IEC form. For price estimate, add 35% to list price of selected version three pole breaker, contact ABB Control for details.
Accessory mounting
Internal accessories are UL/CSA approved for both factory or eld installation. Accessories require control cable connectors. Shunt trips or UVR's mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S5 family are suitable for reverse feed applications.
Discount schedule S5
15.39
AC 1000 - 11/03
15
ax m s o Is CB MC
Breaker IC at 480VAC
The S5 breaker family uses two available microprocessor based internal trip units. The standard PR211 trip unit includes adjustments for long time current pick-up and instantaneous current trip point.
S5N
35kA
S5H
65kA
S5L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
0.5 200
0.6 240
0.7 280
0.8 320
0.9 360
0.95 380
1.0 400
Setting Amps
15
Breaker
IC at 500VDC
Rating
Magnetic trip
List price
List price
300A (210 300A) 400A (280 400A) 300A (210 300A) 400A (280 400A) 300A (210 300A) 400A (280 400A)
15.40
AC 1000 - 11/03
Discount schedule S5
15
Is MC oma CB x s
3 pole, 600VAC catalog number List price
rating can save the user the cost of larger cable or bus bar. Please consult the NEC for details and other design factors needed for this application.
S5N
35kA
S5H
65kA
S5L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
Discount schedule S5
15.41
AC 1000 - 11/03
15
ax m s o Is CB MC
Magnetic only (MCP)
Type Amps
S5 400A, 600VAC
All S5 magnetic only breakers utilize the electronic PR211 trip unit with an adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCP's are 600VAC rated.
Interruption capacity
Adjustment range
List price
List price
S5N
400
240 VAC 480VAC 600VAC 240VAC 480VAC 600VAC 240VAC 480VAC 600VAC
600 4800A
S5N400MW-2
$ 1798
S5N400MW
$ 2151
S5H
400
600 4800A
S5H400MW-2
3285
S5H400MW
3654
S5L
400
600 4800A
S5L400MW-2
3945
S5L400MW
4733
S5H-D
400A
5000A
S5H400DW
$ 1994
400
K5NCT-400
$ 250
Connection options
Type Wire range Amps2 Set of 2 catalog number List price Set of 3 catalog number List price
300 400
K5TF-2 K5TG-21
$ 30
K5TF K5TG1
Set of 6 catalog number
$ 45
15
90 114
1 Including lug cover. 2 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage. 3 With fuse or MCCB protected circuit.
15.42
AC 1000 - 11/03
15
Is MC oma CB x s
Standard S6 package includes complete circuit breaker and mounting hardware. Order cable lugs or other connection scheme as a separate item.
(a) With K6TH cable lugs breaker is 10.55" tall. (b) With K6TJ cable lugs, terminal covers are provided and breaker is 14.25" tall.
General
The S6 breaker family is an 800A frame with a 600A and 800A version, both utilizing a microprocessor based overcurrent protective trip system. Both versions are adjustable from 40% to 100% of rating without the addition of any parts or rating plugs. As standard, the S6 includes adjustable long time function for overload protection and adjustable instantaneous function for short circuit protection.
65 50 25 35 20
150 65 35 50 25
200 100 42 65 50
Versions
To meet all application needs, the S6 is available in various versions: B = Adjustment LI C = Adjustment LSI E = Adjustment LSIG Q = 100% UL rated D = Molded case switch M = Magnetic only (MCP) T = Thermal magnetic G = 2.5 Mag (3-pole only)
Trip functions
These tripping functions are available: L = Long time I = Instantaneous S = Short time G = Ground fault
65 35 30 25 20
100 65 50 40 25
200 100 80 65 35
Performance level
Each version is also available in different maximum fault interrupting levels N = Normal H = High L = Extra high
15
Number of poles
In UL/CSA version, the S6 is available as in two pole or three pole version, both with the same dimensions. A four pole version is also available in UL/IEC form. For price estimate, add 35% to list price of selected version three pole breaker, contact ABB Control for details.
Accessory mounting
Internal accessories are UL/CSA approved for both factory or eld installation. Accessories require control cable connectors. Shunt trips or UVR's mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S6 family are suitable for reverse feed applications.
Rating
Magnetic trip
S6N600GW S6N800GW
3 pole, 600 Amp thermal magnetic, Im=2.5 x Ith 3 pole, 800 Amp thermal magnetic, Im=2.5 x Ith
1500A 2000A
Discount schedule S6
15.43
AC 1000 - 11/03
15
ax m s o Is CB MC
Breaker IC at 480VAC
S6 600A / 800A, 600 VAC Electronic and thermal magnetic trip type
The optional PR212 trip unit includes adjustments for long time current pick-up/ delay, short time pick-up/delay, I2t (on/off), instantaneous current trip point and further optional ground fault protection.
The S6 breaker family uses two available microprocessor based internal trip units. The standard PR211 trip unit includes adjustments for long time current pick-up and instantaneous current trip point.
S6N
50kA
S6H
65kA
S6L
100kA
S6N
50kA
S6H
65kA
S6L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
600A (420 600A) 800A (560 800A) 600A (420 600A) 800A (560 800A) 600A (420 600A) 800A (560 800A)
15.44
AC 1000 - 11/03
Discount schedule S6
15
Is MC oma CB x s
3 pole 600VAC catalog number List price
rating can save the user the cost of larger cable or bus bar. Please consult the NEC for details and other design factors needed for this application.
S6N
50kA
S6H
65kA
S6L
100kA
S6N
50kA
S6H
65kA
S6L
100kA
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
Discount schedule S6
15.45
AC 1000 - 11/03
15
ax m s o Is CB MC
Magnetic only (MCP)
Type Amps
S6 600A / 800A
All S6 magnetic only breakers utilize the electronic PR211 trip unit with an adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs are 600VAC rated.
Interruption capacity Adjustment range 2 pole 600VAC catalog number List price 3 pole 600VAC catalog number List price
S6N
900 7200A 1200 9600A 900 7200A 1200 9600A 900 7200A 1200 9600A
S6H
S6L
S6H-D
600VAC
600 800
K6NCT-600 K6NCT-800
$ 250
Connection options
Type Wire range Amps2 Set of 2 catalog number List price Set of 3 catalog number List price
15
600 800
K6TH-2 1 K6TJ-2
$ 50 90
K6TH K6TJ 1
Set of 6 catalog number
$ 75 135
CU rear lugs CU rear lugs Extended front bar Extended front bar
1 Includes lug cover. 2 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage. 3 With fuse or MCCB protected circuit.
15.46
AC 1000 - 11/03
15
Is MC oma CB x s
Standard S7 package includes complete circuit breaker and mounting hardware. Order cable lugs or other connection scheme as a separate item.
General
The S7 breaker family is a 1200A frame utilizing a microprocessor based overcurrent protective trip system. In the 1200A version, the trip unit is adjustable from 480A up to 1200A without the addition of any parts or rating plugs. As standard, the S7 includes adjustable long time function for overload protection and adjustable instantaneous function for short circuit protection.
Versions
To meet all application needs, the S7 is available in various versions: B = Adjustment LI C = Adjustment LSI E = Adjustment LSIG Q = 100% UL rated D = Molded case switch M = Magnetic only (MCP)
100 65 50
Trip functions
These tripping functions are available: L = Long time S = Short time I = Instantaneous G = Ground fault
100 65 55 45 25
200 100 80 70 35
Performance level
Each version is also available in different maximum fault interrupting levels H = High L = Extra high (IEC only)
Number of poles
In UL/CSA version, the S7 is available as in two pole or three pole version, both with the same dimensions. A four pole version is also available in a UL/IEC form. For price estimate, add 35% to list price of selected three pole, contact ABB Control.
15
Accessory mounting
Internal accessories are UL/CSA approved for both factory or eld installation. Accessories require control cable connectors. Shunt trips or UVR's mount in the left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S7 family are suitable for reverse feed applications.
1 Consult factory
Discount schedule S7
15.47
AC 1000 - 11/03
15
ax m s o Is CB MC
Breaker IC at 480VAC
The S7 breaker family uses two available microprocessor based internal trip units. The standard PR211 trip unit includes adjustments for long time current pick-up and instantaneous current trip point.
S7H
65kA
LI LSI LSIG
S7H1000BW-2 S7H1000CW-2
$ 6959 8039
S7H
65kA
LI LSI LSIG
S7H1200BW-2 S7H1200CW-2
$ 6959 8039
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
1 Consult factory.
15.48
AC 1000 - 11/03
Discount schedule S7
15
Is MC oma CB x s
rating can save the user the cost of larger cable or bus bar. Please consult the NEC for details and other design factors needed for this application.
Trip type Adjustment 3 pole catalog number List price
S7H
65kA
LI LSI LSIG
S7H
65kA
LI LSI LSIG
Trip settings
Adjustment Trip function Range Individual settings
L S I G
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating A-B-C-D
15
1 Consult factory.
Discount schedule S7
15.49
AC 1000 - 11/03
15
ax m s o Is CB MC
Magnetic only (MCP)
Type Amps
S7 1200A, 600V
All S7 magnetic only breakers utilize the electronic PR211 trip unit with an adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs are 600VAC rated.
Interruption capacity Adjustment range 2 pole catalog number List price 3 pole catalog number List price
S7H
1000 1200
S7H1000MW-2 S7H1200MW-2
$ 6959
S7H1000MW S7H1200MW
$ 7724
S7H-D
20,000A 20,000A
$ 7300
Withstand rating
1000 1200
K7NCT-1000 K7NCT-1200
$ 250
Connection options
Type Wire range Amps 1 Set of 2 catalog number List price Set of 3 catalog number List price
1200
K7TK-2
$ 120
K7TK
Set of 6 catalog number
$ 180
1200
K7ET-1250
240
15
1 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage. 2 With fuse or MCCB protected circuit.
15.50
AC 1000 - 11/03
15
Is MC oma CB x s
S8V
16
E W X
Closing coil
1 - 480VAC 2 - 240VAC 3 - 208VAC 4 - 120VAC 5 - 250VDC 6 - 125VDC 7 - 48VDC 8 - 24VAC/VDC 0 - None
X
15
UV release Motor
2 - 240,208VAC/250VDC 4 - 120VAC/125VDC 7 - 48VDC 8 - 24 30 VAC/VDC 0 - None 1 - 480VAC 2 - 240VAC 4 - 120VAC 5 - 250VDC 6 - 125VDC 7 - 48VDC 8 - 24VDC 0 - None
Frame size
Current rating
16 - 1600A 20 - 2000A 25 - 2500A
Trip
C - LSI E - LSIG M-I D - Molded case switch
Contacts
A B P 0 Aux switches Trip Signal Both None
Shunt trip
1 - 480VAC 2 - 240,208VAC/250VDC 3 - 24VAC/30VDC 4 - 120VAC/125VDC 7 - 48VAC/48VDC 8 - 24VDC 0 - None
Connection scheme
WR L D E S V H J M-
Without connectors Rear connectors, line & load Cable terminals, line & load Rear connectors, line side only Rear connectors, load side only Cable terminals, line side only Cable terminals, load side only Cable terminals, line side; rear connectors, load side Rear connectors, line side; cable terminals, load side K8TM lugs, line and load side
Accessories
D - Locking button device (open) L - Key lock (open) X - None
15.51
AC 1000 - 11/03
15
ax m s o Is CB MC
15.75" 15.98" Approximate dimensions 9.25"
Trip functions
L S I G Long time pick-up and delay Short time pick-up and delay Instantaneous trip Ground fault pick-up and delay
1600A
Catalog number List price
2000A
Catalog number List price
2500A
Catalog number List price
S8V
100kA
PR212
125 100 85 25
Trip settings
Adjustment Trip function Range Individual settings
L S I
Long time pick-up Long time delay Short time pick-up Short time delay Instantaneous trip Ground fault Ground fault delay
0.4 1.0 3.0 18 sec. 1.0 10.0 0.05 0.5 sec. 1.5 12.0 0.2 1.0 0.1 0.8 sec.
0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212 A-B-C-D Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating A - B - C - D (I2t On-Off) 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating Off-0.2-0.3-0.4 x Frame rating A-B-C-D
15
S8VQ16CW S8VQ16EW
$ 13,168 15,231
S8VQ20CW S8VQ20EW
$ 15,148 17,390
Three pole breakers are listed and approved for use in two pole applications with center-pole not connected. 2 Applies to MCS only.
15.52
AC 1000 - 11/03
Discount schedule S8
15
Is MC oma CB x s
Accessory type Voltage Rating
Closing coil
Required for closing breaker electrically, the coil voltage must be specied at the time of order entry.
Closing coil
480VAC 240VAC 208VAC 120VAC 250VDC 125VDC 48VDC 24VAC/VDC 240,208VAC & 250VDC 120VAC/125VDC 48VDC 24 30VAC/VDC 480VAC 240,208VAC & 250VDC 24VAC/30VDC 120VAC/125VDC 48VAC/48VDC 24VDC 480VAC 240VAC 120VAC 250VDC 125VDC 48VDC 24VDC 2A/1B 1A/1B 2A/1B Aux & 1A/1B Trip
1 2 3 4 5 6 7 8 2 4 7 8 1 2 3 4 7 8 1 2 4 5 6 7 8 A B P
$ 575
100VA/120Watts 30VA (12 Watts/ 10VA (4 Watts) 10A Max. 0.3A Max. 0.15A Max 30VA / 40VA
3217
Closing coil
Shunt trip
518 MS8
Stored energy
1000
230
0.05s
0.035s
9.0s
Undervoltage release
518
Aux. contacts Trip signal Combo. aux. & trip contacts Padlockable button cover (open) Key lock (open)
D L
144 155
15
$ 888
Door ange
Item Catalog number List price
Face plate
K8FP
$ 25
Discount schedule SA
15.53
AC 1000 - 11/03
15
ax m s o Is CB MC
K1S4
48VAC/60VDC 220/250VAC 24 30VAC 110 130VAC 250VDC 110VDC 48VDC 24VDC 220VDC
S1 S2 S3 S4 S5 S6 S7 S8 S9
$ 212
$ 197
For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole mounted and can not be used with undervoltage releases. All shunt trips are approved for use in ground fault systems. Shunt trips must be ordered with correct connector.
All
Included
K2C-SU
$ 15
24, 120, 240, 480VAC ~ 50/60 Hz 24, 48, 125, 250VDC 100VA~/120W Instananeous duty
S1 with K1S4
Price
U1 U2 U3 U4 U6 U7 U8 U9
$ 212
$ 197
15
Will trip circuit breaker when connected voltage drops to 35 70% of undervoltage release voltage rating. Will allow circuit breaker to close (ON) when voltage is approximately 85% of rated voltage. All undervoltage releases are left pole mounted and can not be used with shunt trips. Undervoltage releases must be ordered with correct connector.
All
Included
K2C-SU
$ 15
24, 120, 240, 480VAC ~ 50/60 Hz 24, 48, 125, 250VDC 6VA~/3W Continuous duty
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format. 2 Not UL approved for eld installation.
15.54
AC 1000 - 11/03
Discount schedule SA
15
Is MC oma CB x s
List price
S1 S2 S4 S7 S8 S9
$ 430
$ 415
24VDC 120VAC
SA SB
$ 430
K5SA K5SB
K7SA K7SB
$ 415
For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole mounted and can not be used with UVRs. Except for 12VDC, all shunt trips are approved for use in GF systems. Shunt trips must be ordered with correct connector.
All All
included included
K6C-SU K6C-SUP
K7C-SU K7C-SUP
$ 15
Electrical specications shunt trips (standard) V For S3-S5 P For S6-S7 24, 120, 240, 480VAC ~ 50/60 Hz 12, 24, 48, 125, 250 VDC 100 VA~/120W Instantaneous duty 150 VA~/150W
Undervoltage releases
Factory installation K5U1 Voltage Catalog number sufx 1 List price adder Field installation Catalog numbers S3 S4 S5 S6 S7 List price
15
U1 U2 U4 U3 U5 U6 U7 U8
$ 430
$ 415
Will trip CB when connected voltage drops to 35-70% of UVR voltage rating. Will allow CB to close (ON) when voltage is approximately 85% of rated voltage. All UVRs are left pole mounted and can not be used with shunt trips. UVRs must be ordered with correct connector.
All All
included included
K6C-SU K6C-SUP
K7C-SU K7C-SUP
$ 15
Electrical specications UVR & low power shunt trips V For S3-S5 P For S6-S7 24, 120, 240, 480 VAC ~ 50/60 Hz 24, 48, 125, 250 VDC 6 VA~/3W Continuous duty 10 VA~/4W
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
Discount schedule SA
15.55
AC 1000 - 11/03
15
ax m s o Is CB MC
S1 with auxiliaries
2 Form Cs 1 BA & 1 C
A BA
$ 190
K1AS K1BA
$ 175
The auxiliary contacts are accessory contacts for the indication of circuit breaker open-closed or tripped. Bell alarm contacts (B.A.) can be used to indicate circuit breaker tripping. All contacts are right pole mounted
All
Included
K2C-AB
$ 15
30 VDC 127 VDC 220 VAC N.O. = contact is open as circuit breaker is open N.C. = contact is closed when circuit breaker is open B.A. = will open/close only when circuit breaker trips
4A 4A 4A
K5AS
Auxiliary contacts S3 S7
Factory installation Contacts Catalog number sufx 1 List price adder S3 S4 S5 Field installation Catalog numbers S6 S7 List price
A BA BA3
$ 275 365
K5AS K5BA
$ 260 350
The auxiliary contacts are accessory contacts for the indication of circuit breaker open-closed or tripped. Bell alarm contacts (B.A.) can be used to indicate circuit breaker tripping. All contacts are right pole mounted.
K6C-ABP
15
All All
included included
K6C-AB K6C-ABP
K7C-AB K7C-ABP
$ 15
125 VDC 250 VDC 250 VAC N.O. = contact is open as circuit breaker is open N.C. = contact is closed when circuit breaker is open B.A. = will open/close only when circuit breaker trips
0.3 A 0.15 A 6A
S5 with K6C-AB
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format. 2 Not UL approved for eld installation.
15.56
AC 1000 - 11/03
Discount schedule SA
15
Is MC oma CB x s
Catalog number S3 S4 S5 List price
$ 678
K5M2
For remote control of circuit breaker opening and closing. Complete with manual operating lever, padlock device and emergency opening push-button. When ordering the connector always specify type and version of the circuit-breaker. The following options are also available: key lock for open position key lock for open position of two or more circuit breakers (using the same key for groups of circuit breakers)
All All
K6C-M K6C-MP
$ 15
120, 240VAC ~ 50/60 Hz 24, 48, 125, 250 VDC 500 VA~/500W 350 VA~/500W 0.1 s 0.1 s
$ 2407
Stored-energy motor operator with springs automatically pre-loaded by motor. Complete with shunt opening and closing release, and compartment door ange. When ordering the connector always specify type and version of the circuit-breaker. The following options are also available: key lock for open position key lock for open position of two or more circuit-breakers (using the same key for groups of circuit-breakers).
15
All All
K6C-M K6C-MP
K7C-M K7C-MP
$ 15
Electrical specications V P inrush P normal Close time Open time Reset time 120, 240 VAC ~ 50/60 Hz 24, 48, 125, 250 VDC 660 VA~/600W 180 VA~/180W 0.09 s 1.2 s 2.0 s
S7 with K7M4
Discount schedule SA
15.57
AC 1000 - 11/03
15
ax m s o Is CB MC
K4TB
S3 S3 S4 S3 S4 S3 S4 S5 S4 S5 S5 S6 S6 S7
14AWG 14AWG 2AWG 4AWG 6AWG 250kcmil (2) 3/0 (2) 250kcmil (3) 2/0 (4) 4/0
2AWG 1/0 4/0 300kcmil 350kcmil 500kcmil 250kcmil 500kcmil 400kcmil 500kcmil
K3TA-2 K4TB-2 K4TC-2 K4TD-2 K4TE-2 K5TF-2 K5TG-22 K6TH-2 K6TJ-22 K7TK-2
$4 4 4 10 20 30 30 50 90 120
K3TA K4TB K4TC K4TD K4TE K5TF K5TG2 K6TH K6TJ2 K7TK
$6 6 6 15 30 45 45 75 135 180
Standard cable lugs, for use on line and load side of circuit breaker. Suitable for use with Cu or Al. Special versions available with taps and screws for control wire connection. Note: S6 and S7 lugs are Al9Cu (90C); all others Al7Cu (75C).
K4ET-250
S3 S4 S3 S4 S3 S4 S5 S4 S5 S5 S6 S6 S7
14AWG 2AWG 4AWG 6AWG 250kcmil (2) 3/0 (2) 250kcmil (3) 2/0 (4) 4/0
$8 8 14 24 34 34 54 94 124
$ 12 12 21 36 51 51 81 141 186
S3 S4 S5 S6 S6 S7
For adding onto standard circuit breaker front terminals, extending available connection area for user termination. Suitable for spaded cable or bus connection. S3 S5 include terminal covers.
15
K4TER
S3 S4 250 14AWG 250kcmil K4TES $ 30 S5 400 250kcmil 500kcmil K5TGS 90 These special non-aluminum cable lugs are for use with copper cable. Lugs are intended for use with copper cable or where non-aluminum connectors are required (marine, salt or corrosive environments).
S3 S4 S5 S6 S6
6AWG 250kcmil 250kcmil 500kcmil (2) 2/0 350kcmil (3) 250kcmil 350kcmil
$ 30 90 150 170
For use where cable connection from the back-rear of the breaker is desired.
S3 S4 S5
250 400
K4TN K5TGD
$ 125 240
1 Suggested lugs for circuit breaker up to amps shown. Cable size and type determine maximum amperes. 2 Includes required lug covers.
15.58
AC 1000 - 11/03
Discount schedule SA
15
Is MC oma CB x s
List price
S3 S4 S5 S6 S7
Mounts directly onto breaker. Includes door interlock to prevent CB door opening while CB is in ON position. Padlock provision included to padlock CB in open position. Can also be key locked with optional cylinder lock assembly. Door interlock bracket must be ordered separately, if required. See page 15.62.
K5RH
S1
K2VD-M
OHB45J10 OHG45J10 OHB65J10 OHG65J10 OHB95J10 OHG95J10 OHB125J10 OHG125J10 OHB175J10 OHG175J10
(1.8) (1.8) (2.6) (2.6) (3.7) (3.7) (4.9) (4.9) (6.9) (6.9)
$ 70
OHB65J10
49 80 80
80 90 100
Pistol type 4, 4X
OHB95J10 Frame Catalog number mechanism List price Shaft catalog number (length in inches) List price Handle catalog number (length in inches) List price
S1
K2VD-M
OHB45L10 OHG45L10 OHB65L10 OHG65L10 OHB95L10 OHG95L10 OHB125L10 OHG125L10 OHB175L10 OHG175L10
(1.8) (1.8) (2.6) (2.6) (3.7) (3.7) (4.9) (4.9) (6.9) (6.9)
$ 110
S3S4S5 K5VD-M
OHB125J10
49 80 80
S6 S7
K6VD-M K7VD-M
$ 59 49 80 80
K5VD-S12 K7VD-S20
$ 24 27
$ 25 25 28 28
15
S3 S4 S5
K5VD-LSS
$ 25
Discount schedule SH
15.59
AC 1000 - 11/03
15
ax m s o Is CB MC
S1
$ 240 248 255 280 288 295 240 248 255 280 288 295 240 248 255 280 288 295 240 248 255 280 288 295 523 531 538 563 571 578
K2FHD-M
$ 128
K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22 K7FHD-S12 K7FHD-S17 K7FHD-S22
12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5 12 17 22.5
$ 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34 19 27 34
K7FHD-HS12
$ 93
K7FHD-HS4
133
S3
K7FHD-HS12
93
K3FHD-M
128
K7FHD-HS4
133
S4
K7FHD-HS12
93
K4FHD-M
128
K7FHD-HS4
133
K7FHD-HS12
S5
K7FHD-HS12
93
K5FHD-M
128
K7FHD-HS4
133
S6
K7FHD-HS12
93
K6FHD-M
411
K7FHD-HS4
133
Available as complete kits including ange handle, shaft and breaker operating mechanism. Mechanism mounts directly onto breaker and shaft can be cut to the desired length for the breaker enclosure. Door is interlocked with the handle when the breaker is in the closed (ON) position; handles include interlock defeater for emergency override. Handle can be padlocked in the open (OFF) position. Can be eld converted for left hand mounting.
15
Item
Catalog number
List price
Door hardware kit, right hand, 2 point latch for enclosures less than 40 inches high Roller for 3 point latch, add to FH-DHK
FH-DHK FH-3RL
$ 150 30
Enclosure depths
Minimum
Breaker Depth (inches)
S1 S3 - S5 S6 Maximum
For maximum depth, add 4 inches to the shaft length
8 10 11
15.60
AC 1000 - 11/03
Discount schedule SH
15
Is MC oma CB x s
List price
K2FHDC-M K2FHDC-M K4FPM K4FPM K5FPM K5FPM K6FPM K6FPM K7FPM K7FPM
$ 198 198 110 110 128 128 220 220 220 220
K6FHDC-036 K6FHDC-060 K6FHDC-036 K6FHDC-060 K5C036 K5C048 K5C060 K5C072 K5C084 K5C096 K5C108 K5C120 K7C048 K7C060 K7C072 K7C084 K70096 K7C120
36(91cm) 60(152cm) 36(91cm) 60(152cm) 36 (91cm) 48 (122cm) 60 (152cm) 72 (183cm) 84 (213cm) 96 (244cm) 108" (274cm) 120" (305cm) 48 (122cm) 60 (152cm) 72 (183cm) 84 (213cm) 96 (244cm) 120 (305cm)
$ 114 146 114 146 114 146 160 175 204 221 238 256 190 220 256 270 320 350
K7FHD-HS12 K7FHD-HS4 K5FCH K5FCH4 K5FCH K5FCH4 K7FCH K7FCH4 K7FCH K7FCH4
Notes: For complete assembly; mechanism, cable and handle are required. All cables mount onto the right side of the breaker. Handle can be mounted on the right or left side.
Door hardware kit, right hand, 2 point latch for enclosures less than 40 inches high Door hardware kit, right hand, 3 point latch for enclosures 40 inches high or greater
KDH2R KDH3R
$ 200 225
Enclosure depths
Minimum
Breaker Depth (inches)
S1 - S6 S7 Maximum
Maximum depth is determined by cable length.
8 10
15
Discount schedule SH
15.61
AC 1000 - 11/03
15
ax m s o Is CB MC
K5LD
External accessories S1 S7
Front locking device
Item Catalog number List price
S1 S3 S4 S5 S6 S7 S3 S4 S5 S6 S7
$ 14 14 16 20 14 16 20
Mounts directly onto front of CB. Includes padlock device for locking CB in open position. Can be used as a manual handle block, with padlock or with optional key lock accessory. Optional door interlock kit that will prevent CB door from opening while CB is in the closed (ON) position.
Bracket
K7DB
$5
Key locks
Catalog number Accessory Keys S3 S4 S5 S6 S7 List price
Electric operator
K7KL
$ 25
Keyed cylinder locks are available for mounting onto Isomax electric operators, rotary handle mechanisms and front locking devices. Key locks can be for one individual circuit breaker (different keys in each order) or for two circuit breakers using the same key.
S1 S3 S4 S5 S6 S7
$8 8 12 18 40
$ 16 16 24 32
Both high and low types are available for xed circuit-breakers. Covers provide IP40 degree of protection for xed mounted circuit breakers. Lug covers are required and included as standard with S5 400A and S6 800A cable lug kits. Covers up to S6 can be sealed with lug cover seal shown in next section.
15
K6LCH
K6LC-S
$5
K6LC-S
S1 S3 S4 S5
$ 11 24 26 38
Kit consists of mounting bracket to x S3-S5 breakers onto 75mm DIN rail (EN 50023 rail) and includes 45mm high front face plate to match up with miniature circuit breakers and manual motor starters. S1 breaker mounts on 35mm DIN rail.
S3 S4 S5 S6 S7
K3DMB
Provides for mounting of two similar breakers on a single mounting plate. CBs are interlocked via a walking beam type interlock, preventing breakers from being ON or closed at the same type. Both breakers can be OFF or tripped. MIP is available in two versions, one with breakers mounted horizontally and then also a version for vertical mounting of breakers.
1 Required for drawout breakers.
15.62
AC 1000 - 11/03
Discount schedule SA
Accessories S1 S7 IEC
Rear connected stud kits1
For breakers Max. amps
15
Is MC oma CB x s
Set of 6 catalog number List price
Plug-in (3 pole)1
Movable kit Frame Movable List price Separate kits xed and movable Fixed base kit Front bus List price Rear conn. List price Complete plug-in kits Includes both xed and movable portion Front bus List price Rear conn. List price
S1 S3 S4 S5
Rear plug-in & drawout circuit breakers
Draw-out (3 pole) 13
Movable kit Frame Movable List price Separate kits xed and movable Fixed base kit Front bus List price Rear conn. List price Complete draw-out kits Includes both xed and movable portion Front bus List price Rear conn. List price
K7TUT
Movable kit = parts needed to modify standard CB to movable type. Fixed base kit = x mount onto panel. Ext Fr bus = xed base with line and load side extended front bus connectors. (FF) Rear Conn. = xed base with line and load side rear bus connectors. (FR) Complete kit = includes all parts required for plug-in or draw-out connection; does not include CB. Plug-in = open breaker can be physically removed from xed base without disconnecting cable or bus from xed base. (P) Draw-out = also known as withdrawable, breaker can be removed from xed base via a through the door crank. Includes ON, TEST and OFF position. (W)
15
Draw-out crank
Isomax frames Catalog number List price
S1 S7
K7WCR
$ 20
S3 S4 S5
$ 72 72 86
S4 S5 S6 S7
K7TUT
$ 210
Isomax hand-held test kit is used to both test and exercise microprocessor trip units in breakers S4 through S7. Unit includes test forks that insert into the test plugs on all Isomax microprocessor trip units. Tester generates 15VDC signal that performs diagnostic on electronic trip functions and will conrm test by tripping the CB. Will not test S3 nor any molded case switch versions.
1 IEC ratings only. 2 Front cable connection. 3 Requires front locking device to prevent drawout while breaker is closed.
Discount schedule SA
15.63
AC 1000 - 11/03
15
ax m s o Is CB MC
Notes
15
15.64
AC 1000 - 11/03
15
Is MC oma CB x s
Description Type 1
General purpose indoor enclosure intended for use in normal environments to provide a degree of protection against contact with enclosed equipment. Sheet steel, surface mount. Breaker is front-operable and can be padlocked via front hasp. Available through 2500A, 600VAC UL Listed for use as service entrance equipment (SUSE), per UL le E116374.
Type 7/9
Cast from copper-free aluminum (max. 0.025 copper content) Stainless steel shotblasted or sandblasted natural nish Standard conduit openings in top and bottom Breaker is operated from front handle and can be padlocked NEC Class I Groups D, Div. 1 & 2 NEC Class II Groups E, F & G, Div 1 & 2 NEC Class III External machined ange joint design Integral cast mounting feet Machined ange for ease of hinge installation Ground lug Cast mounting pan bosses All enclosures suitable for drilling & tapping UL panel listed per UL File # E183868
15
Type 3R/12
Type 3R is intended for outdoor use providing protection against rain, sleet or snow. Type 12 is for use in indoor atmospheres to provide a degree of protection against circulating dust, lint, sawdust, falling dirt and dripping non-corrosive liquids. Surface-mounted, sheet steel enclosure. Breaker can be operated via separately ordered handle mechanism; door is interlocked with mechanism. Available through 2500A, 600VAC. UL Listed for use as service entrance equipment (SUSE), per UL le E116374.
15.65
AC 1000 - 11/03
15
ax m s o Is CB MC
NEMA designation Breaker type
S3E-1
S4E-3R12 3
Enclosures (Price does not include circuit breaker; order as a separate item.) 4
Enclosure maximum rating AL cables CU cables Approximate dimensions1 H x W x D (inches) Catalog number List price
Type 1
S1 S22 S3 S4 S5 S6 S7 S8 S1 S2 2 S3 S4 S5 S6 S7 S8
100A 125A 150A 225A 400A 800A 1000A 2500A 100A 125A 150A 225A 400A 800A 1000A 2500A
100A 125A 225A 250A 400A 800A 1200A 2500A 100A 125A 225A 250A 400A 800A 1200A 2500A
14 x 10 x 3.1 16 x 11 x 3.1 22 x 12 x 4.5 30 x 17.5 x 4.5 30 x 17.5 x 4.5 44 x 22 x 6 44 x 22 x 6 88 x 36 x 24 14 x 10 x 8.8 16 x 11 x 8 22 x 12 x 9 30 x 17.5 x 9 30 x 17.5 x 9 44 x 22 x 11 44 x 22 x 11 88 x 36 x 24
S1E-1 S2E-1 S3E-1 S4E-1 S5E-1 S6E-1 S7E-1 S8ES250-1 S1E-3R12 S2E-3R12 S3E-3R12 S4E-3R12 S5E-3R12 S6E-3R12 S7E-3R12 S8ES250-3R12
$ 200 200 235 305 305 685 685 5285 305 305 395 575 575 905 905 5285
Type 3R/123
Neutral kits
Breaker type Neutral cable capacity and wire range Neutral kit catalog number List price
S1 S2
Neutral #14-1/0 Bonding Lug #14-1/0 Neutral #6-250 kcmil Bonding Lug #14-1/0 Neutral #6-250 kcmil Bonding Lug #14-1/0 kcmil Neutral (2) #6-250 kcmil Bonding Lug #14-1/0 kcmil Neutral (2) #2-600 kcmil Bonding Lug #6-250 kcmil Neutral (4) #2-600 kcmil Bonding Lug #6-250 kcmil Neutral (6) #1/0-750 kcmil Bonding Lug (2) #2-600 kcmil
15
S3 S4 S5 S6 S7 S8
NOTE: The list price adder for factory installation of an enclosed circuit breaker is 50% of the enclosure list price.
1 2 3 4
Enclosures may not meet size requirement for UL 100% rated breakers. Not UL approved. Variable depth rotary handle must be ordered separately (S1 - S7). Consult ABB for breakers installed in enclosures.
15.66
AC 1000 - 11/03
Discount schedule SE
15
Is MC oma CB x s
Enclosure max. rating Approximate dimensions H x W x D (inches) Catalog number sufx List price adder
Explosion-proof enclosures (Price does not include circuit breaker; order as a separate item for factory assembly.)
NEMA designation Breaker type
Type 7/9
S3 S3 S4 S5 S6 S6 S7
Cu only 100A Cu only 225A Cu only 250A Cu only 400A Cu only 600A Cu only 800A Cu only 1200A
7 7 7 7 7 7 7
S5N400BW7
To order a breaker in an explosion-proof enclosure, add the sufx "7" to the end of the catalog number and add the list price adder to the list price of the breaker. Example: S5N400BW7 S5N400BW breaker............... $ 2151 Explosion proof enclosure ........ 6600 Total ....................................... $ 8751
Additional options
NEMA 4XStainless steel boltsCaptive boltsDrain NEMA designation Breaker type Enclosure max. rating Cat. no. adder List price adder Cat. no. adder List price adder Cat. no. adder List price adder Cat. no. adder List price adder
Type 7/9
S3 S3 S4 S5 S6 S6 S7
Cu only 100A Cu only 225A Cu only 250A Cu only 400A Cu only 600A Cu only 800A Cu only 1200A
-X -X -X -X -X -X -X
-S -S -S -S -S -S -S
$ 20 25 45 60 60 60 80
-B -B -B -B -B -B -B
-D -D -D -D -D -D -D
$ 110
To add additional options, simply add the sufx to the end of the catalog number. Example: S5N400BW7XSD S5N400BW breaker............... $ 2151 Explosion proof enclosure ........ 6600 NEMA 4X .................................... 175 Stainless steel bolts...................... 60 Drain ........................................... 110 Total ....................................... $ 9096
S4 N 250 B W 7 - 2 xxx
Frame size S3 = 150 / 225A S4 = 250A S5 = 400A S6 = 600 / 800A S7 = 1200A Interrupting rating class B = Basic (240VAC) N = Normal H = High L = Extra high D = Special molded case switch Accessories (added in alpha-numeric order) A = Auxiliary switch B = Captive bolts BA = Bell alarm BA3 = Bell alarm (S6/S7 only) D = Breather/drain H = Fixed rotary handle mounted on CB S_ = Shunt trip with voltage code S = Stainless steel bolts U_ = Undervoltage release with voltage code X = NEMA 7/9/4X Number of poles -2 = 2 pole -4 = 4 pole None = 3 pole
15
Current rating 015 = 15A 250 = 250A 400 = 400A 600 = 600A 800 = 800A 1200 = 1200A
Trip unit function B = LI C = LSI D = Molded case switch (MCS) E = LSIG T = Thermal-magnetic
F H J K M
= = = = =
Discount schedule SE
15.67
AC 1000 - 11/03
15
ax m s o Is CB MC
NEMA 1
B
F 4-MTG. HOLES C E
A 14.0
355.6
B 10.0
254.0
C 2.85
72.39
D 11.0
279.4
E 7.0
177.8
F .312
7.93
16.0
406.5
11.0
280.0
2.85
72.5
13.0
330.0
8.0
203.0
.312
7.93
22.0
559.0
12.0
305.0
4.25
108.0
19.0
482.0
9.0
229.0
.312
7.93
30.0
762.0
17.5
444.5
4.25
108.0
27.0
686.0
14.5
368.5
.312
7.93
30.0
762.0
17.5
444.5
4.25
108.0
27.0
686.0
14.5
368.5
.312
7.93
44.0
1118.0
22.0
559.0
5.75
146.0
41.0
1041.5
19.0
483.0
.312
7.93
44.0
1118.0
22.0
559.0
5.75
146.0
41.0
1041.5
19.0
483.0
.312
7.93
FRONT VIEW
SIDE VIEW
SECTION
F 4-MTG. HOLES
NEMA 3R, 12
15
DANGER
HAZARDOUS VOLTAGES ARE LOCATED INSIDE HAZARD OF ELECTRICAL SHOCK OR BURN DISCONNECT POWER BEFORE WORKING ON THIS EQUIPMENT Y 6917 1000-061
SACE S5
D
on
off
FRONT VIEW
SIDE VIEW
SECTION
A 16.0
406.5
B 11.0
280.0
C 8.8
224.0
D 14.5
368.5
E 9.5
242.0
F 0.50
13.7
22.0
559.0
12.0
305.0
8.8
224.0
20.5
520.5
10.5
267.0
0.50
13.7
30.0
762.0
17.5
444.5
8.8
224.0
28.5
724.0
16.0
406.5
0.50
13.7
30.0
762.0
17.5
444.5
8.8
224.0
28.5
724.0
16.0
406.5
0.50
13.7
44.0
1118.0
22.0
559.0
10.8
274.5
42.5
1080.0
20.5
521.0
0.50
13.7
44.0
1118.0
22.0
559.0
10.8
274.5
42.5
1080.0
20.5
521.0
0.50
13.7
15.68
AC 1000 - 11/03
15
Is MC oma CB x s
35.1
892
2.0
51
35.8
909
24.0
610
LEFT 3.6
91
RIGHT 16.2
411
23.8
605
FRONT 2.0
51
3.8
97
TOP VIEW ENCLOSURE ROOF (SOLID REMOVABLE ROOF PANEL) 35.79 (OVER ALL)
909
87.4
2220
4.53
115
26.73
679
4.53 REAR
115
4.00
102
5.00
127
3.36
85
13.8
351
15.09
383
23.80
605
RIGHT 3.36
85
3.9 5.20
99 132
1.5
38
15
15.69
AC 1000 - 11/03
15
ax m s o Is CB MC
NEMA 7 & 9
K A
J F D
Breaker type S3 60A S3 100A S3 225A S4 250A S5 400A S6 600A S6 800A S7 1200A
A 9.25
235.0
B 14.25
362.0
C 9.00
228.6
D 10.00
254.0
E 7.5
190.5
F 9.13
231.9
G 3/8
9.5
H 2.50
63.5
J 1.50
38.1
K 10.25
260.4
9.25
235.0
16.25
412.8
9.00
228.6
10.00
254.0
9.50
241.3
9.13
231.9
3/8
9.5
2.50
63.5
2.00
50.8
10.25
260.4
10.38
263.7
21.63
549.4
9.00
228.6
11.00
279.4
14.50
368.3
9.75
247.7
3/8
9.5
2.75
69.9
2.50
50.8
11.25
285.8
15
16.25
412.75
24.25
616.0
10.00
254.0
18.00
457.2
14.38
365.3
15.75
400.0
1/2
12.7
3.25
82.6
2.50
50.8
17.25
438.2
16.25
412.75
28.25
717.6
11.00
279.4
18.00
457.2
18.38
466.9
15.75
400.0
1/2
12.7
3.63
92.2
3.00
76.2
17.25
438.2
16.25
412.75
34.25
889.0
11.00
279.4
18.00
457.2
23.00
584.2
15.75
400.0
1/2
12.7
4.50
114.3
4.00
101.6
17.25
438.2
16.25
412.75
40.25
1041.4
13.50
244.6
18.00
457.2
29.00
736.6
15.75
400.0
1/2
12.7
4.50
114.3
4.00
101.6
17.25
438.2
16.25
412.75
50.25
1298.7
13.50
295.4
18.00
457.2
39.00
990.6
15.75
400.0
5/8
13
4.50
114.3
4.00
101.6
17.25
438.2
15.70
AC 1000 - 11/03
Technical data
15
Is MC oma CB x s
60 C (140 F) Types TW UF 75 C (167 F) Types RH, RHW THHW THW THWN XHHW USE 90 C (194 F) Types TBS SA, SIS THHN THHW THW-2, THWN-2 RHH, RHW-2 USE-2 XHH, XHHW XHHW-2, ZW-2 Size AWG kcmil Aluminum or copper-clad
Copper
18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000
20 25 30 40 55 70 85 95 110 125 145 165 195 215 240 260 280 320 355 385 400 410 435 455 495 520 545 560
20 25 35 50 65 85 100 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545 590 625 650 665
14 18 25 30 40 55 75 95 110 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615 665 705 735 750
20 25 30 40 55 65 75 85 100 115 130 150 170 190 210 225 260 285 310 320 330 355 375 405 435 455 470
20 30 40 50 65 75 90 100 120 135 155 180 205 230 250 270 310 340 375 385 395 425 445 485 520 545 560
25 35 45 60 75 85 100 115 135 150 175 205 230 255 280 305 350 385 420 435 450 480 500 545 585 615 630
12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000
15
Unless otherwise specically permitted elsewhere, the overcurrent protection for conductor types marked with a star () shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 20 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
Correction factors Ambient temperature C For ambient temperatures other than 30 C (86 F) multiply the allowable ampacities shown above by the appropriate factor shown below. Ambient temperature F
21 25 26 30 31 35 36 40 41 45 46 50 51 55 56 60 61 70 71 80
1.04 1.00 .96 .91 .87 .82 .76 .71 .58 .41
1.05 1.00 .96 .91 .87 .82 .71 .71 .58 .41
15.71
AC 1000 - 11/03
15
ax m s o Is CB MC
1 Opening release
Externial Circuit
+ ~
SO
+ ~
SO
A4 Conn. X1 1 C1 1 D1
Q/0
Internal Circuit
YO
YU
C2 Conn. X1
Externial Circuit
D2 2
A4
15
Legend
- Figure number of diagram A4 - Example switchgear and connections for control and signalling, ouside the circuit-breaker Q/0 - Auxiliary contacts of the circuit-breaker SO - Pushbutton or contact for opening the circuit-breaker
Incompatibility: The circuits indicated in the following figures cannot be powered simultaneously on the same circuit-breaker: 1-4-5-6 2-3 Availability: Connectors X1 and X2 are only supplied to order for circuit breakers S1 -S2. Notes: ( * A ) The undervoltage release is powered from upstream circuit-breaker or by an independent power supply: closing of the circuit-breaker is only allowed when the release is energized (the closing lock is implemented mechanically).
15.72
AC 1000 - 11/03
15
Is MC oma CB x s
Externial Circuit
+ ~
SO
+ ~
SO
+ ~
SO
A4 Conn. X1 C1 Term. XV C1 C1 D1 D1 D1 D1 D1 D1
Q/0
Internal Circuit
YO
YU
YU
Term. XV C2 Conn. X1
C2 D2 C2
D2 D2 D2
D2
D2
Externial Circuit
~ ~ ~ ~ ~ +
A4
Legend
-
Incompatibility:
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit-breaker: 1-4-5-6 2-3
15
A4 - Example switchgear and connections for control and signalling, ouside the circuit-breaker Q/0 - Auxiliary contacts of the circuit-breaker SO - Pushbutton or contact for opening the circuitbreaker
Availability:
Connectors X1 and X2 are only supplied to order for circuit breakers S1 -S2.
Notes:
( * A ) The undervoltage release is powered from upstream of the circuit-breaker or by an independent power supply: closing of the circuitbreaker is only allowed when the release is energised (the closing lock is implemented mechanically).
15.73
AC 1000 - 11/03
15
ax m s o Is CB MC
Externial Circuit
+ ~
SO2 SC
A4 Conn. X2 U6 Term. XV U6 U8 U8 U1 U1 U2 U2
Internal Circuit
S1
M
S2
A1 Term. XV U5 Conn. X2
Externial Circuit
U5
A4
+ ~ Legend
15
OFigure number of diagram A1 - Applications of the circuit-breaker A4 - Example switchgear and connections for control and signalling, ouside the circuit-breaker MFor S6 -S7: motor for opening the circuit-breaker and loading the closing springs of the circuitbreaker S2 - For S3 - S4 - S5: safety contact operated by: - key lock (if mounted) - padlock device - local control Allen key SC - Pushbutton or contact for closing the circuit-breaker. For circuit breakers S3 - S4 -S5, the operating mechanism must have a time of not less than 100ms S02 - Pushbutton or contact for opening the circuit-breaker. For circuit breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100 ms (see instructions for resetting the circuit-breaker after the releases have tripped.
S1 - For S3 - S4 - S5: position contact operated by a circuit-breaker cam for S6 - S7: contact controlled by the motor operated cam: closes when the circuit-breaker reaches it's closed positon and opens when the circuitbreaker reaches its open position (doesn't switch when the circuit breaker goes into its tripped position)
15.74
AC 1000 - 11/03
15
Is MC oma CB x s
SO2 X2 XV SY XV X2 96 2 1 95 A1 A1 A3 A1 A3 A3 U1 U1 U1
Externial Circuit
+ ~
SC SO1
S3
Internal Circuit
M
KO KO
YC S2 S1
A2 Term. XV U2 Conn. X2
Externial Circuit
U2
U2
A4
+ ~
Legend
OFigure number of diagram SO1 Pushbutton or contact for opening the circuit breaker S02 - For circuit breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100ms (see instructions for resetting the circuit breaker after the releases have tripped) SY - Contact for electrical signalling of circuit breaker open due to tripping of thermomagnetic releases, YO, YO1, YU (tripped position) KO - For S6 - S7: opening and spring-loading relay with held position make contact, released by a cam of the motor operator when the circuit breaker reaches its open position and the closing springs have been loaded MS2 - For S3 - S4 - S5: safety contact operated by: - key lock (if mounted - padlock device - local control Allen key SC - Pushbutton or contact for closing the circuit breaker. For circuit breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100ms For S6 - S7: motor for opening the circuit breaker and loading the closing springs of the circuit breaker
15
A1 - Applications of the circuit-breaker A2 - Applications of the motor operators A4 - Example switchgear and connections for control and signalling, outside the circuit breaker S1 - For S3 - S4 - S5: position contact operated by a circuit breaker cam for S6 - S7: contact controlled by the motor operated cam: closes when the circuit breaker reaches its closed position and opens when the circuit breaker reaches its open position (doesn't switch when the circuit breaker goes into its tripped position)
X1 - Connectors for the auxiliary circuits of the circuit breaker X2 - For circuit breakers S1 - S2 supplied for order only XV - Terminal block for accessories YC - Closing release
15.75
AC 1000 - 11/03
15
ax m s o Is CB MC
Auxiliary switch
Two change-over contacts, for electrical signalling of circuitbreaker open/close
Bell alarm
One changed-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to triping of thermomagnetic releases YO, YO1, YU ( tripped position )
Externial Circuit
A4 Conn. X2 12 6 14 7 22 3 24 4 12 6 14 7 96 3 98 4
Internal Circuit
Q/1
Q/2
Q/1
SY
11 Conn. X2. 5
21 2
11 5
95 2
15
O-
Externial Circuit
A4
Legend
Figure number of diagram
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker Q/1...2 Auxiliary contacts of the circuit breaker
SY - Contact for electrical signalling of circuit breaker open due to tripping of thermomagnetic releases YO, YO1, YU (tripped position)
15.76
AC 1000 - 11/03
15
Is MC oma CB x s
Bell alarm
One changed-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to triping of thermomagnetic releases YO, YO1, YU ( tripped position ) 12 12 14 14 96 96 98 98
11
Auxiliary switch
Two change-over contacts, for electrical signalling of circuitbreaker open/close
Externial Circuit
A4 Conn. X2 12 Term. XV 12 14 14 22 22 24 24
Internal Circuit
Q/1
Q/2
Q/1
SY Term. XV 11 Conn. X2 11 1 95 11 95
1 21
1 11 21
Externial Circuit
A4
Legend
OFigure number of diagram
15
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker Q/1...2 Auxiliary contacts of the circuit breaker
SY - Contact for electrical signalling of circuit breaker open due to tripping of thermomagnetic releases YO, YO1, YU (tripped position)
15.77
AC 1000 - 11/03
15
ax m s o Is CB MC
Term. X6 Term. X5
X3 XO
Externial Circuit
A4
1 1 3
Internal Circuit
K51 YO1 XO X3
4 4
4
Term. X5 Term. X6
Externial Circuit
A4
15
OFigure number of diagram
Legend
Incompatibility:
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit breaker: 11 - 12 - 13 41 - 42 - 43 - 44
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker K51/YO1 - Electrical signalling of alarm for release YO1 tripped due to overcurrent or "trip test" X3 - Connectors for the circuits of the microprocessorbased overcurrent release (with plug in or withdrawable circuit breakers, the connectors are pulled out at the same time as the circuit breaker XO - Connector for the opening solenoid YO1
Availability:
Connectors X1 and X2 are only supplied to order for circuit breakers S1 - S2.
Notes:
(*C) The electrical signalling contact for the microprocessorbased overcurrent release, shown in Fig. 41, has the following electrical characteristics: rated voltage = 24V breaking capacity (resistive load = 3 W/VA) maximum interrupted current = 0.5A For S4 - S5 available with PR212/P release only
15.78
AC 1000 - 11/03
15
Is MC oma CB x s
96 96
Externial Circuit
A4 Conn. X2 12 Term. XV 12 24 24
Internal Circuit
Q/1
Q/2
SY Term. XV 11 Conn. X2 11 1 95 23 95
1 23
Externial Circuit
A4
Legend
OFigure number of diagram
15
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker Q/1...2 Auxiliary contacts of the circuit breaker
SY - Contact for electrical signalling of circuit breaker open due to tripping of thermomagnetic releases YO, YO1, YU (tripped position)
15.79
AC 1000 - 11/03
15
ax m s o Is CB MC
First circuitbreaker position contact, for electrical signalling of racked put or removed
Second circuitbreaker position contact, for electrical signalling of racked out or removed
Externial Circuit
A4
Term. XV
Internal Circuit
S75I/1
S75I/2
S75S/1
S75S/2
Term. XV
15
Legend
OFigure number of diagram
Externial Circuit
A4
Incompatibility
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit breaker: 20 - 21 - 31, 22 - 32, 23 - 33, 24 - 34, 25 - 35
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker S75I/1...5 - Contacts for electrical signalling of circuit breaker in inserted position (only for plug in or withdrawable circuit breakers, see Note D.) S75S/1...5 - Contacts for electrical signalling of circuit breaker in removed or racked out position (only for plug in or withdrawable circuit breakers, see Note D.)
Notes
(*D) The circuit breaker can be mounted with position contacts S75I and S75S in any combination up to a maximum of: Total of 2 contacts for S3 Total of 3 contacts for S4, S5 Total of 5 contacts for S6, S7
15.80
AC 1000 - 11/03
15
Is MC oma CB x s
First circuitbreaker position contact, for electrical signalling of racked put or removed Second circuitbreaker position contact, for electrical signalling of racked out of removed Third circuitbreaker position contact, for electrical signalling of racked out or removed
Externial Circuit
A4
Term. XV
Internal Circuit
S75I/1
S75I/2
S75I/3
S75S/1
S75S/2
S75S/3
Term. XV
Externial Circuit
A4
Legend
OFigure number of diagram
15
Incompatibility
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit breaker: 20 - 21 - 31, 22 - 32, 23 - 33, 24 - 34, 25 - 35
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker S75I/1...5 - Contacts for electrical signalling of circuit breaker in inserted position (only for plug in or withdrawable circuit breakers, see Note D.) S75S/1...5 - Contacts for electrical signalling of circuit breaker in removed or racked out position (only for plug in or withdrawable circuit breakers, see Note D.)
Notes
(*D) The circuit breaker can be mounted with position contacts S75I and S75S in any combination up to a maximum of: Total of 2 contacts for S3 Total of 3 contacts for S4, S5 Total of 5 contacts for S6, S7
15.81
AC 1000 - 11/03
15
ax m s o Is CB MC
21
First circuit-breaker position contact, for electrical signalling of inserted
Externial Circuit
A4 Term. XV 4 2 4 2 4 2 4 2 4 2 2 4 2 4 2 4 2 4 2 4
Internal Circuit
S75I/1
S75I/2
S75I/3
S75I/4
S75I/5
S75S/1
S75S/2
S75S/3
S75S/4
S75S/5
Term. XV
Externial Circuit
A4
15
O-
Legend
Figure number of diagram
Incompatibility
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit breaker: 20 - 21 - 31, 22 - 32, 23 - 33, 24 - 34, 25 - 35
A4 - Example switchgear and connections for control and signalling, outside the circuit breaker S75I/1...5 - Contacts for electrical signalling of circuit breaker in inserted position (only for plug in or withdrawable circuit breakers, see Note D.) S75S/1...5 - Contacts for electrical signalling of circuit breaker in removed or racked out position (only for plug in or withdrawable circuit breakers, see Note D.)
Notes
(*D) The circuit breaker can be mounted with position contacts S75I and S75S in any combination up to a maximum of: Total of 2 contacts for S3 Total of 3 contacts for S4, S5 Total of 5 contacts for S6, S7
15.82
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
Y
3.58
91
3.07
78
2.80 1
71
0.06
1.5
0.98
25
0.98
25
6 0.63
16.0
5 4.72
120
3.78
96
X
10.5 5x11
1.77
45
X
1.89
48
C L
2 0.63
16.0
0.12
3
C L
3.58
91
C L 0.98
25
3.29
83.5
15
2.44
62
3.94
100
2.52
64
R - 0.06
X
3.35
85
1.5
2.09
53
0.16
4
6-32 LEGEND 1-FRONT TERMINALS FOR CABLE OR FOR FLAT BAR 2-MOUNTING ON CHANNEL TO DIN EN 50022 (OPTIONAL) 3-COMPARTMENT DOOR SHEET STEEL DRILLING FOR FIXING THE FLANGE 4-MOUNTING ON SHEET STEEL 5-FLANGE FOR THE COMPARTMENT DOOR 6-INSULATING BARRIER
15.83
AC 1000 - 11/03
15
ax m s o Is CB MC
101.5
Inches
[Millimeters]
Y 4.00 4.61
117 105
4.13 1.38
35
0.98
25
18x18
1.38
35
0.39
10 73.75
2.90
4.13
105
87.25
3.44 6.34
161
X 5.63
143
6.69
170
C L
1.81 0.53
13.5 46
2 0.12
3 103.5
Y 4.07 0.08
2
C L
4 4.41
112
C L
5 Y
3.15
80
5.59
142
2.82
71.75
1.38
35
X X
4.41
112
5.47
139
0.28
7
15
10-24 Y Y 10-24 6
LEGEND 1-FRONT TERMINALS FOR CABLE CONNECTION 2-REAR TERMINALS FOR CABLE CONNECTION 3-FLANGE FOR THE COMPARTMENT DOOR 4-COMPARTMENT DOOR SHEET STEEL DRILLING FOR FIXING THE FLANGE 5-MOUNTING ON SHEET STEEL 6-MOUNTING ON SHEET STEEL WITH REAR CABLE TERMINALS 7-HIGH TERMINAL COVERS WITH IP 20 PROTECTION DEGREE 8-TIGHTENING TORQUE 17.70 lb-in
3.73
94.75
7.28
185
FIGURE A B 1.38
35
LUG KIT CAT. NO. K3TA, K3TA-2 K4TB, K4TB-2 K4TC, K4TC-2 K4TD, K4TD-2
WIRE RANGE 14AWG - 2AWG 14AWG - 1/0 2AWG - 4/0 4AWG - 300kcmil
MOUNTING TORQUE 120 lb-in 120 lb-in 150 lb-in 150 lb-in
1.38
35
C R - 0.59
15
15.84
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
Y 4.61
117 105
8 0.98
25
101.5
4.00
1 1.38
35
4.13 1.38
35
18x18
0.43
11
4.22
107.25
107.25
4.93
4.13 8.58
218 105
6.34
161
10.00
254
C L
7 0.53
13.5 1.81 46
2 0.12
3 103.5
4.07
0.08
2
C L
4 4.41
112
C L
Y
3.15
80
5.59
142 105.25
4.14
1.38
35
10-24
4.41
112
X 0.28
8.42
214
5 LEGEND
15
Y 6
1-FRONT TERMINALS FOR CABLE CONNECTION 2-REAR TERMINALS FOR CABLE CONNECTION 3-FLANGE FOR THE COMPARTMENT DOOR 4-COMPARTMENT DOOR SHEET STEEL DRILLING FOR FIXING THE FLANGE 5-MOUNTING ON SHEET STEEL 6-MOUNTING ON SHEET STEEL REAR CABLE TERMINALS 7-HIGH TERMINAL COVERS WITH IP 20 PROTECTION DEGREE 8-TIGHTENING TORQUE 17.70 lb-in 5.04
128.25
10.24
260
LUG KIT CAT. NO. K4TB, K4TB-2 K4TC, K4TC-2 K4TD, K4TD-2 K4TE, K4TE-2
MOUNTING TORQUE 120 lb-in 150 lb-in 150 lb-in 150 lb-in
1.38
35
C R - 0.59
15
15.85
AC 1000 - 11/03
15
ax m s o Is CB MC
4.00
101.5
Inches
[Millimeters]
5.51
140
4.61 1 1.72
43.75 117
8 0.98
25
4.13
105
24x24 0.43
11
1.72
43.75
107.25
4.22
107.25
4.93
8.58
218
4.13
105
6.34
161
C L
10.00
254
C L
0.53
13.5
1.81
46
2 0.12
3 107
4.21
103.5
C L
135
C L
Y
4 4.41
112
3.15
80
105.25
4.14
1.72
10-24 5.59
142
43.75
8.42
214
4.41
112
X 0.28
7
15
Y
Y LEGEND R - 0.79
20
1.72 10.71
272 43.75 134.25
5.29
1-FRONT TERMINALS FOR CABLE CONNECTION 2-REAR TERMINALS FOR CABLE CONNECTION 3-FLANGE FOR THE COMPARTMENT DOOR 4-COMPARTMENT DOOR SHEET STEEL DRILLING FOR FIXING THE FLANGE 5-MOUNTING ON SHEET STEEL 6-MOUNTING ON SHEET STEEL REAR CABLE TERMINALS 7-HIGH TERMINAL COVERS WITH IP 20 PROTECTION DEGREE 8-TIGHTENING TORQUE 17.70 lb-in
"G" WIRE RANGE 250 - 500 kcmil 3/0 - 250 kcmil (2) WIRE TORQUE 375 lb-in 275 lb-in MOUNTING TORQUE 175 lb-in 175 lb-in WIRE SCREW SIZE 3/8 5/16
15.86
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
Y 8.27
210
1.85
47
101.5
4.00
5.51
140
1.26
32
21.5
2.76
70
2.76
70
111.75
4.34
125.25
4.93
10.56 4.13
105
6.34
161
9.49
241
268
C L
C L
0.47
12
5.98
152
2 0.12
3
0.77
19.5
1.85 47 0.83
21
103.5
4.07
7 0.08
2
C L
C L
Y 4 Y 4.53 Y
115
109.75
4.32
10-24 2.76 X X
5.59
142
4.41
112
X 0.28
7
X 9.33
237
70
Y 5.79
147
15
LEGEND Y 1-FRONT TERMINALS FOR CABLE PROTECTION 2-REAR TERMINALS FOR CABLE CONNECTION 3-FLANGE FOR THE COMPARTMENT DOOR 4-COMPARTMENT DOOR SHEET STEEL DRILLING TEMPLATE 5-MOUNTING ON SHEET STEEL 6-MOUNTING ON SHEET STEEL REAR CABLE TERMINALS 7-HIGH TERMINAL COVERS WITH IP 20 PROTECTION DEGREE 8-TIGHTENING TORQUE 17.70 lb-in
141.75
5.58
3.38
85.75
3.38
85.75
R - 0.85
21.5
11.85
301
10-24 "H" FIGURE H Y J LUG KIT CAT. NO. K6TH, K6TH-2 K6TJ, K6TJ-2 LUG NO. D2957 D2958 TEMP. 90 C 90 C "J" WIRE RANGE 250 - 500 kcmil (2) 2/0 - 400 kcmil (3) WIRE TORQUE 275 lb-in 375 lb-in WIRE MOUNTING SCREW TORQUE SIZE 85 lb-in 110 lb-in 5/16 3/8
15.87
AC 1000 - 11/03
15
ax m s o Is CB MC
2.24
57 78
Inches
[Millimeters]
3.82 3.07 97
21.4 1 0.28
7
Y 5.51 2.76
70 152
1.50
38
2.76
70
1.46
37
1.20
30.5
2 8.54 6.97
177 217
X 12.83
326
4.13 C L
105
15.98 X 406
6.34 C 161 L
1.46
37
5 5.45
138.5
0.28
7
5.51
140
8.27
210
0.12
3
140.5 146.5
C L 0.08
2
C L Y
Y Y 4.53
115
4.41
112
X 0.28
7
15
5.79 Y
147
14.88 X
378
LEGEND 1-FRONT TERMINALS FOR CABLE CONNECTION 2-FLANGE FOR THE COMPARTMENT DOOR 3-COMPARTMENT DOOR SHEET STEEL DRILLING TEMPLATE 4-MOUNTING ON SHEET STEEL 5-TIGHTENING TORQUE 17.70 lb-in
10-24
"K" LUG KIT CAT. NO. K7TK, K7TK-2 WIRE TORQUE 375 lb-in MOUNTING TORQUE 375 lb-in WIRE SCREW SIZE 3/8
FIGURE K
TEMP. 90 C
15.88
AC 1000 - 11/03
00.00
00.00
Inches
[Millimeters]
15
Is MC oma CB x s
15.98
406
9.25
235
14.96
380
5.65
141
15.17
305.3
1.77
45
2.17
55.2
0.79
20
0.51
13
0.83
21.1
2.84
72.1
4.72
120
4.72
120
20.47
520
15.75
400
12.32 BKR
313
BKR
C L
C L
11.02
280
0.35D
9
0.79
20
1.57 40 0.55D
14
2.56
65
3.15 0.79
20
1.57
40
80
BREAKER BKR.
C L
C L
5.65
143.5
C L
380
324
C L
0.79
20
327
15
13.43
341
13.54
344
TYP 2
0.20
5
4.72
120
1600A LUG
2500A LUG
FIGURE L M
TEMP. 90 C 90 C
WIRE RANGE 1/0 - 750 kcmil (4) 1/0 - 750 kcmil (6)
WIRE SCREW SIZE 1/2 1/2 ( 2500A LUGS SHOWN ON BREAKER ) "L" "M"
NOTE: Lugs are interchangeable and may be ordered as required by the installed wire gauge.
15.89
AC 1000 - 11/03
15
ax m s o Is CB MC
K2VD-M
Inches
[Millimeters]
6.61 / 11.81
168 / 300
2.68
68
3.64 93
SHAFT 4.7
119.5
C L
0.10
2.5 1.85
47
2.56
65
2.09
53.0
0.20 D
K2VD-H 5.0
"X"
1.65
42
0.27
6.8
1.30 D 45
33.0
15
C L
0.10
1.77
45
2.66
67.5
2.5
2.09
53.0
0.20 D
OHB65_10 5.0
"X"
0.27
2.56
65
6.8
1.22 D 45
31.0
15.90
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
C L
1.02
26.0
C L
4.13
105.0
0.394 SQ
10 SQ
SACE S5
0.45
11.5
4.13
105.0
off
1.81
46.0
"X"
0.61
15.5
1.36
34.5 on
1.06
27.0
2 0.59
15.0 S3
2.13
54.0
1.30 DIA.
33.0 DIA
1.67
42.5
S5 W LUG COVER
5.75
146.0
TO BASE OF BREAKER
15
1 4.13 0.394 SQ
10 SQ 105.0
C L
1.02
26.0
2.09
53.0
4.13
105.0
0.20 D
5.0
"X"
0.45
11.5
1.22 D
31.0
0.61
15.5
45 2 1.77
45.0
1.67
42.5
S4
15.91
AC 1000 - 11/03
15
ax m s o Is CB MC
Inches
[Millimeters]
C L
8.27
1 0.394 SQ
10 SQ
210.0
5.51
140.0
4.13
105.0 SACE S7
C L
1.63
41.5
4.13
105.0
off
1.81 1.10
28.0 46.0
1.06 2 0.89
22.6
5.51 1.36
34.5 140.0 on
"X"
1.30 DIA
33.0 DIA
27.0
2.12
54.0
1.67
42.5
0.59
15.0 on
1.95
49.5
S7 =6.78
172.3
TO BASE OF BREAKER
C L
15
8.27
210.0
5.51
140.0
C L
1.63
41.5
0.394 SQ
10 SQ
2.09
53.0
0.20 D
5.0
1.10
28.0
5.51
140.0
45
1.22 D
31.0
"X"
0.89
22.6
1.77
45.0
4.91
125.0
1.67
42.5
2
on
6.89
175.0
S6 W LUG COVER S7
S6 =5.41
137.3
S7 =6.78
172.3
TO BASE OF BREAKER
15.92
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
OPTIONAL FLANGE DRILLING 1.00
0.56
"B"
1.30 K G
"X" MAY DRILL & TAP FOR 10-32, FLATHEAD SCREW IF THE MECHANISM IS TO BE MOUNTED ALONE.
NOTES: 1. " A " DIM. IS THE WIRING BENDING SPACE AS REQUIRED BY THE NATIONAL ELECTRIC CODE. 2. " B " DIM. IS 2.340 in. IF ENCLOSURE DOES NOT HAVE A SAFETY DOOR INTERLOCK, AND 1.500 in. IF IT DOES HAVE A SAFETY DOOR INTERLOCK.
15
E 3.94 3.94 5.47 8.43 8.43 9.33 F 4.72 4.72 6.69 10.00 10.00 10.55 G 2.53 2.53 2.64 2.64 3.16 4.41 H 3.07 3.54 4.13 4.13 5.51 8.27 J 4.89 4.89 5.31 5.31 6.69 10.36 K 1.97 1.97 2.73 4.22 4.22 4.66 L -.97 -.97 -.59 +.76 +.76 +1.61
FRAME S1 S2 S3 S4 S5 S6
15.93
AC 1000 - 11/03
15
ax m s o Is CB MC
S1, S2 = 3.54
90
Inches
[Millimeters]
S3, S4 = 4.13
105
S5 = 5.51
140
SACE S3
3.00
76
S1, S2 = 4.72
120
S1, S2 = 4.14
105
S3 = 6.69
170
S4, S5 = 10.00
254
S1, S2 = 4.89
124
S3, S4 = 5.31
135
S5 = 6.69
170
15
1.07
27
S1, S2 = 4.04
103
S3, S4 = 5.02
128
1.83 Min
46
S5 = 6.40
163
15.94
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
S3, S4 = 4.13
105
S5 = 5.51
140
SACE S3
ON
OFF
S3 = 6.69
170
S4, S5 = 10.00
254
OFF
5.65
143.5
5.37
136
S3, S4 = 6.75
171.5
15
S5 = 8.13
206.5
0.51
13
DOOR CATCH
S3, S4 = 6.24
158.5
S5 = 7.62
193.5
15.95
AC 1000 - 11/03
15
ax m s o Is CB MC
Inches
[Millimeters]
ENCLOSURE
FLANGE DRILLING
C L
1.00 MIN.
0.56
2.438
2.88 4.69
C L
DOOR INTERLOCK BRACKET
0.50
2.406
15
DRILL & TAP 1/4-20 HOLE 4 PLACES
NOTES: 1. " A " DIM. IS THE WIRING BENDING SPACE AS REQUIRED BY THE NATIONAL ELECTRIC CODE. 2. THE MINIMUM BEND RADIUS OF THE CABLE IS 3 INCHES.
15.96
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
FLANGE DRILLING 1.00 MIN. 0.56
ENCLOSURE
"A" 1.38
4.14
C L
2.88 4.69
C L
BREAKER MECHANISM
2.406
BREAKER OUTLINE
15
5.49 DRILL & TAP 1/4-20 HOLE 4 PLACES NOTES: 1. " A " DIM. IS THE WIRING BENDING SPACE AS REQUIRED BY THE NATIONAL ELECTRIC CODE. 2. THE MINIMUM BEND RADIUS OF THE CABLE IS 3 INCHES.
15.97
AC 1000 - 11/03
15
ax m s o Is CB MC
Inches
[Millimeters]
ENCLOSURE
"A" 1.72
FLANGE DRILLING
1.00 MIN.
4.14
C L
2.88 4.69
C L
BREAKER MECHANISM
2.406
BREAKER OUTLINE
15
NOTES: 1. " A " DIM. IS THE WIRING BENDING SPACE AS REQUIRED BY THE NATIONAL ELECTRIC CODE. 2. THE MINIMUM BEND RADIUS OF THE CABLE IS 3 INCHES.
15.98
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
8.27
210
S6 = 10.56
268
S7 = 15.98
406
ON
OFF
OFF
6.89
175
S6 = 7.41
188.2
S7 = 8.15
207
11.67
296.4
15
0.67
17
11.00
279.4
15.99
AC 1000 - 11/03
15
ax m s o Is CB MC
K5RH
Inches
[Millimeters]
4.13
105.0 SACE S5
C L
2.10
53.5
4.20
107.0
4.13
105.0
off
"X"
4.20
107.0
on
S3
1.36
34.5
S4
7.11
180.5
TO BASE OF BREAKER
C L
8.27
15
210.0
C L
5.51
140.0 SACE S7
2.50
off 63.5
K6RH / K7RH
5.51
140.0
5.60
142.0
"X"
5.60
on 142.0
1.33
33.8
1.61
41.0
S7 = 6.78
172.3
S6 = 7.02
178.3
S7 = 8.40
213.3
TO BASE OF BREAKER
15.100
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
C
2.10
53.5
Locking device, S3 - S5
C
5.51
L
140
4.13
105
SACE S5 SACE S5
L
4.20
107
on K5LD 0.24
6
1.06
27
4.13
105
"X"
off 4.20
107
1.67
42.5
S4
Locking device, S6 - S7
8.27
210
15
CL
5.51
140
CL
SACE S7
2.50
63.5
5.60
142
K6LD / K7LD
5.51
140
on
"X"
5.60
142
off
1.67
42.5
15.101
AC 1000 - 11/03
15
ax m s o Is CB MC
Electrical operator, S3 - S5
Inches
[Millimeters]
5.51
140
L
105
4.80 122
4.13
SACE S5
C 2.10
53.5
L
4.20
107
4.13 K5M_
105
Auto Manual
"X"
4.20
107
S4
Electrical operator, S6 - S7
4.67 118.6 8.27
210
SACE S7
15
5.51 140 7.62
193.5
CL
10.71
272
on
K6M_ K7M_
"X"
5.6
142
off
3.87
98.3
CL
S6 W LUG COVER
15.102
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
C
S3/S5
S6/S7
S3/S5
S6/S7
CL
G
K_MI-H
15
K L
FRAME S3 S4 S5 S6 S7
A 4.08 103.5 4.08 103.5 4.08 103.5 4.07 103.5 5.53 140.5
F 5.31 135 6.83 173.5 6.83 173.5 7.38 187.5 8.86 225
G 10.43 265 13.78 350 13.78 350 14.76 375 17.72 450
H 4.57 116 6.14 156 6.14 156 6.89 175 8.27 210
J 8.96 227.5 12.40 315 12.40 315 13.78 350 16.54 420
K 12.76 324 12.76 324 15.85 402.5 20.67 525 21.65 550
L 13.78 350 13.78 350 16.93 430 25.60 650 25.98 660
15.103
AC 1000 - 11/03
15
ax m s o Is CB MC
Inches
[Millimeters]
C A B D
CL
E
L M K_MI-V
L G
CL
H
15
K
FRAME S3
A 4.07 103.5
C 7.08 180 7.08 180 8.67 180 12.20 310 13.39 340
D 6.20 157.5 6.20 157.5 7.91 201 11.02 280 12.40 315
E 4.49 114 5.12 130 5.12 130 5.81 147.5 5.12 14.43
F 6.00 152.5 7.81 198.5 7.81 198.5 8.82 224 11.26 286
G 22.76 578 29.53 750 29.53 750 32.28 820 43.31 1100
H 13.78 350 19.29 490 19.29 490 20.67 525 34.45 875
J 6.20 157.5 7.70 195.5 7.70 195.5 8.82 224 11.26 286
S4 S5
S6 S7
15.104
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
3.58
91
2.99
76
4.84
123
1.57
40
0.39
10
3.07
78
0.09
2.5
0.06
1.5 2 max
2 4.02
102
4.88
124
6.44
163
C L
C L
3.78
96
1.77
45
1.54
39
1.97
50
2.76
70
1
Y
2 2.95
75
C L
2.05
52
3.58
91
C L
1.97
50
0.98
25 Y
R - 0.51
13
3.31
84
2.48
63
5.67
144
1.02
26
0.22
5.5 X X
4.02 1.38
102 35 2.36 60 max
M8
2.59
65.5
15
0.98
25
0.98
25
M4 4.5
0.18
C L
0.16
4 Y
LEGEND 1-PLUG IN BASE 2-FLANGE FOR THE COMPARTMENT DOOR 3-MOUNTING SCREWS FOR PLUG IN BASE ON PLATE 4-MOUNTING HOLES FOR PLUG IN BASE ON CHANNEL 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TERMINAL COVERS (SEPERATE ITEM) 8-SEALING SCREWS (OPTIONAL) 2.52
64 X R 1.5 X
0.06
2.09
53
3.39
86
3.29
83.5
15.105
AC 1000 - 11/03
15
ax m s o Is CB MC
1.10
28
Inches
[Millimeters]
4.84
123 10.5x11
3.58
91
3.07 0.06
1.5 : -2 78 Y
0.09
2.5
2 4.88
124
6.42
163
3 1.97
50
C L
3.78 96 X 1.77
45
2.76
70
1
Y
1.65
42
2.95
75
C L
2.05
52
3.58
91
1.97
50
C L
25 Y
0.98 6 0.18
M4 4.5
15
5.67
144 X
7 3.31
84
0.22
5.5 X
1.38 2.36
35 60 max
0.98
25
0.98
25
0.16
4
C L
Y
0.06 2.52
64 X R 1.5 X
2.09
53
3.39
Y LEGEND 1-PLUG IN BASE 2-FLANGE FOR THE COMPARTMENT DOOR 3-MOUNTING SCREWS FOR PLUG IN BASE ON PLATE 4-MOUNTING HOLES FOR PLUG IN BASE ON CHANNEL 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TERMINAL COVERS (SEPERATE ITEM) 8-SEALING SCREWS (OPTIONAL) Y 86
3.29
83.5
15.106
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
4.61 4.13
105 117
6.89 5.63
143 175
1.22
31
3.53
89.75
2.90
73.75
6.34
161
3.31
84
4.13 X
105
C L
0.11
3
3 6.02
153
C L
0.08
2
6.16
156.5
7.27
184.55
5 (M12)
C L
3.94
100
Y 1.38
35
1.89
48
1.38
35
R - 0.55
14
C L
2.90
73.75
15
5.63 2.06
52.25 143
3.94
100
Y 5 4.41
112
0.20
5 (M4)
3.15
80
5.59
142
0.98
25
X
45
4.41
112
1.77
45
1.77 Y
0.28
7
LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TIGHTENING TORQUE 9.7 lb-in
15.107
AC 1000 - 11/03
15
ax m s o Is CB MC
0.12 1
3
Inches
[Millimeters]
Y 1.22
31
0.19
5
2 0.39
10
4.60
117
4.13
105
4.22
107.25
6.89
175
3.53
89.75
6.34
4.13
105
C L
8.27
210
=
X
161
7 6.02
153 156.5
0.39
10
0.79
20
0.32
8.2
1.38
35
1.38
35
6.16
184.55
7.27
C L C L
Y 5 4 3.15
80
Y 4.41
112
15
X
2.06
52.25
5.59
142
3.94
100
4.41
112
=
X 0.28
7
0.20
5 (M4)
0.98
25
Y LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TIGHTENING TORQUE 9.7 lb-in
1.77
45
15.108
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
7 3.27
83
1.08
27.5
Y
2.91 74 4.13 105 3.78 96
1 4
1.22
31
73.75
2.90 X 5.63
143
X 161
C L
C L
4.13
105
X 0.22 0.07
5.5 1.75
1.38
35
1.38
35
2 3.31
84
6.57
167
Y Y
0.079
2 5 (M12)
7.48
190
7.70
195.5
3.94
100
0.16 1.89
48 4
80
C L
Y
5.31 135
C L
Y 1.38
35
1.38
35
2.48
63 1.77 45
5 for 7
0.28
15
6 R - 0.55
14 2.85 72.5
2.90
73.75
2.06
52.25
5.63
143
X 0.20
5 (M4)
3.94
100
X
4.96 126 0.63 16
3.70 94
0.98
25
5 Y
R min. 200
1.77
45
1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in
15.109
AC 1000 - 11/03
15
ax m s o Is CB MC
2.91
74
Inches
[Millimeters]
Y 3.78
96
1.08 4
27.5
0.19
5
1.22 0.12
31 3
0.39
10
4.13
105
107.25
4.22
89.75
6.34
161
8.27
210
4.13
105
X
5.5
X 0.22 0.07
1.75
0.39
10
0.79
20
0.32
8.2
6.57
167
1.38
35
1.38
35
0.079
2
7.48
190
3.31
84
7.70
195.5
0.16
4
Y 80 6
C L
2.06
52.25
Y 3.94
100 5 (M4)
X 0.20
5.31
135
2.48
63
1.77
15
0.98
25
45
5 for 7
0.28
2.85
72.5
1.07 3.70
94 27.25
1.77
45
5.59
142
4.96
126
0.63
16
3.19 LEGEND 4.92 1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in
125 81
5 Y
R min. 200
15.110
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
Y 4.13
105
3.27
83
1 1.22
31
10.20
259
5.03
127.75
5.03
127.75
7 8.58
218
4.13
105
6.34
161
6.02
153
4.61
117
6.16
156.5
7.27
184.5
Y 1.38
35
1.38
35
5 (M12) 3.23
82
6 R - 0.55
14
3.94
100
1.89
48
4.22
107.25 65.75
2.59
5.31
135
8.58
218
X 5
Y 4.41
112
15
5 (M4)
3.15
80
5.59
142
X 2.76
70
4.41
112
Y LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TIGHTENING TORQUE 9.7 lb-in
15.111
AC 1000 - 11/03
15
ax m s o Is CB MC
1 5.54
140.75
Inches
[Millimeters]
Y 4.06 3 2
117
0.39
10
4.13
105
4
140.75
5.54
10.20
259
11.20
285
127.75
5.03
11.22
285
4.13
105
6.34
161
0.39
31 5 10
0.79
20
0.32
8.2
0.12
3
1.22
0.19
1.38
35
1.38
35
6.02
153 156.5
6.16 7.27
184.5
5 4.41
112
3.15
80
15
65.75
2.59
3.23
82
5.59
142
5.31
135
4.41
112
0.20
5 (M4)
0.28
7
Y LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3- FRONT TERMINAL 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING TIGHTENING TORQUE 9.7 lb-in
15.112
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
3.27
83
2.91
74
Y 4.13
105
3.78
96
1.22 1.08
27.5
31
5.03
127.75
10.20
259
6.34
161
5.03
127.75
X 4.13 105
5.5 1.75
8.58
218
0.22 0.07 8
1.38
35
1.38
35
6.57 3.31
84
7.48
190
167
0.12
3
Y 1.38
35
1.38
35
7.70
195.5
5 (M12) 3.94
100
0.16
4
1.89
48
80
Y 3.23
82
5.31
135
6 R - 0.55
14
2.48
63 1.77 45
15
0.28
5 for 7
2.85
72.5
4.22
107.25
2.59
65.75
1.07
27.25
135
5.31
8.58
218
3.70
94
=
5.59 142
X 4.96
126
0.63
=
16
5 (M4)
3.19
81
4.92 5 2.76
70 125
LEGEND 1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in
R min. 200 Y
15.113
AC 1000 - 11/03
15
ax m s o Is CB MC
0.39
10
Inches
[Millimeters]
Y 4.13
105
4 1.08
27.5 140.75 127.75
0.19 2 3
5
1.22
31
0.12
3
5.54
5.03 7
10.20
259
13.15
334
6.34
161
X 4.13 105
5.5
X 0.22 0.07
1.75
0.39
10
0.79
20
0.32
8.2
1.38
35
1.38
35
3.31 2.91
74 84
6.57
167
3.78
96
0.079
2
7.48
190
7.70
195.5
Y 6 0.16
4
2.59
65.75
3.23
82
80 X
5.31
135
15
5 (M4) Y 5.31
135
2.48
63
1.77
45
0.28
5 for 7
LEGEND 2.85 1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in
72.5
1.07 3.70
94
27.25
5.59 4.96
126 142
0.63
=
16
3.19
81
4.92 5
125
R min. 200
15.114
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
Y 5.51
140
3.31
84
4.61
117
1.34
34
127.75 107.75
5.03
4.22
10.20
259
7 8.58
218
4.13 X
105
6.34
161
6.02
153 156.5
6.16 7.27
184.5
0.12
3
Y 1.72
43.75
1.72
43.75
4.53
115
3 4.25
108 M16
6
R - 0.71
18
2.28
58
4.22
107.25
2.59
65.75
5.31
135
8.58
218
15
Y
5 (M4)
4.41
112
3.15
80
5.59 3.44
87.5 142
Y
LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TIGHTENING TORQUE 17.7 lb-in
4.41
112
15.115
AC 1000 - 11/03
15
ax m s o Is CB MC
1
Inches
[Millimeters]
Y 5.51
140
0.52 2
14
3.78
117
150.75
5.94
12.01
305
127.75
5.03
10.20
259
4.13
105
6.34
161
0.12
3
0.52 1.22
31
0.98
25 43.75
0.39
10
0.24
6
14
1.73
43.75
1.73
6.02
153 156.5
Y 5 4.41
112
6.16 7.27
184.5
3.15
80
15
65.75
2.59
4.53
115
5.59
142 X
5.31
135
4.41
112
0.20
5 (M4)
LEGEND 1-PLUG IN BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-TIGHTENING TORQUE 17.7 lb-in
15.116
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
2 1 3.31 1.34
34 84
Y 2.91
74
3.78
96
= 5.03
127.75
5.51
140
= 4
1.08
27.5
10.20
259
4.22
107.25
6.34
161
8.58
218
0.07
1.75
43.75
1.72
1.72
43.75 101.5
6.57 7.70
190
7.48
167
0.12
3
4.00
195.5
Y 1.72
43.75
1.72
43.75
0.16
4
M16
80
4.25
108
2.28
58
Y 5.31
135
2.48
63
1.77 4.53
115 45
0.28
5 for 7
15
1.07
27.25
6 R - 0.71
18
2.85
72.5
3.70
94 142
=
5.59
4.22
107.25
4.96
126
0.63
2.59
65.75
5.31
135
8.58
218
X 3.19
81
5 (M4)
4.92 5
125
1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FRONT FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in
16
15.117
AC 1000 - 11/03
15
ax m s o Is CB MC
0.52
14
Inches
[Millimeters]
Y 5.51
140
= 1.08
27.5
0.24 2 3
6
1.22 0.12
31 3
4 5.03
150.75
1 7
12.01
305
6.34
161
4.13
105 5.5
X 0.22 0.07
1.75
0.52
14
0.98
25
6.57
167
1.72 Y
43.75 96
10
43.75
0.079 3.78
101.5 2
7.48
190
4.00
7.70
195.5
0.16 4 Y 6 80
2.59
65.75
4.53
115
5.31 X
135
X Y 5.31
135 5 (M4)
15
2.48
63
1.77
45
0.28
5 for 7
Y
72.5
3.70
94
=
5.59
142
2.85
1.07
27.25
LEGEND 1- WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-COMPARTMENT DOOR FLANGE 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 9.7 lb-in 5
4.96
126
0.63
3.19
81
4.92
125
R min. 200 Y
15.118
AC 1000 - 11/03
16
Inches
[Millimeters]
15
Is MC oma CB x s
0.08
2
Y 8.27
210 91.5
7.48
190
6.57 5.16
131 167
3.60 5.51
140
2.38
60.5
0.79
20
0.12
3
5.24
133
7.72
196
3.52 4.80
122
0.57
14.5
2.28
58
89.5
X 5.51
140
0.22
5.5
8.19 5.71
145 208
11.61
295
10.75
273
1.08
27.5
1.57
40
0.55
14
123.5
4.86
136.5
5.37
0.16
4
80
2.76
70
2.76
70
Y Y 8.43
214
Y 6.69
170
15
3.17
80.5
0.28 1.77
45 7 for 7
3.06
77.5
6 1.79
45.5
5.51
140
3.54 2.26
57.5 90
0.35
9
=
6.97
177
X 4.72
120
X 6.34
161
1.54
3.41
86.5
8.5 ( M8 )
3.06
77.5
0.77
19.75
5 LEGEND Y 6.40
3.98
101
0.63
16
162.5 1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR THE FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 79.7 lb-in
4.76
121
R min.200 Y
39
15.119
AC 1000 - 11/03
15
ax m s o Is CB MC
0.78
20
Inches
[Millimeters]
Y 8.27
210
5.51
140
0.39
10
1.22
31
0.12
3
3 1
6.22
158
5.24
133
7.72
196
4.80
122
0.57
14.5
2.28
58
13.58
345
X 5.51
140
X 0.22
5.5
5.71
145
11.61
295
10.75
273
6.57 1.57
40
0.08
2
167
0.78
20
7.48
190 195.5
2.76
70
2.76
70
7.70
3.60
91.5
5.16
131
0.16
4
123.5
4.86 Y Y 8.43
214
136.5
5.37 80
15
3.06
77.5
6 1.79
45.5
Y 5.51
140
6.69
170
3.17
80.5
0.28 1.77
45 7 for 7
2.26
57.5
X 4.72
120
3.41
86.5
3.54
90
0.35
9
=
6.97
177
X
8.5 ( M8 )
3.06
77.5
6.34
161
1.54
LEGEND
Y 0.77
19.75
1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR THE FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 79.7 lb-in
5 6.40
162.5
3.98
101
0.63
16
4.76
121
R min.200 Y
15.120
AC 1000 - 11/03
39
Inches
[Millimeters]
15
Is MC oma CB x s
4.25
108
1.08 Y 8.27
210 27.5
0.12
3
0.55
14
5.51
140
0.87
22
4 8.32
211.25
0.87
22
7.72
196
143.25
5.64
0.32
8.25 15.99 406
6.30
160 max
X 5.51
140
5.5
0.22
270
X 10.63
1.97
50
0.43
11
3.60
91.5
5.16
131
8.58 0.08
218 241.5 2
4.86
123.5
5.37 Y
136.5
9.51
9.72
247
0.63
16
0.16
4
3 80
2.76
70
2.76 Y Y
70
Y 6.69
170
15
3.17
80.5
0.28 1.77
45 7 for 7
120.5
4.74
8.43
214
1.79
68.25
0.35 9
6.97
177
3.64
92.5
4.72 X 2.99
76 120
X 0.77
19.75
5
8.5 ( M8 )
3.98
101
0.63
16
6.40
162.5
4.76 4.74
120.5
5.51
140
121
LEGEND 1-WITHDRAWABLE BASE Y 2-MOVING PART FITTED WITH TERMINAL COVERS 3-REAR TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 79.7 lb-in
R min.200
1.54 39
15.121
AC 1000 - 11/03
15
ax m s o Is CB MC
0.55
14
Inches
[Millimeters]
0.08
2
9.51
241.5
Y 8.27
210
8.60
218.5
5.51
140
0.63
16
1.22
31 0.12 3
0.87
22
211.25 278.25
8.32
7 4
10.95
15.99
406
7.72
196
21.26
540
0.32
8.25
6.30 X X X 5.51
140
5.5
0.22
160 max
1.08
27.5
11
0.43
0.87 22
1.97 50
9.72
247
2.76
70
2.76
70
3.60
91.5 123.5
5.16
131 136.5
0.16
4
4.86 Y Y
5.37
80
15
120.5 68.25
4.74
8.43
214
Y 6.69
170
1.79
3.17
80.5
0.28 1.77
7 for 7 45
6 3.64
92.5
4.72 X 2.99
76 120
0.35 9
6.97
177
8.5 ( M8 )
120.5
4.74
5.51
140
19.75
0.77
5
162.5
3.98
101
0.63
16
6.40
LEGEND 1-WITHDRAWABLE BASE 2-MOVING PART FITTED WITH TERMINAL COVERS 3-FRONT TERMINALS 4-FLANGE FOR THE COMPARTMENT DOOR 5-MOUNTING HOLES FOR FLANGE 6-MOUNTING HOLES FOR SHEET STEEL MOUNTING 7-COMPARTMENT DOOR INTERLOCK 8-TIGHTENING TORQUE 79.7 lb-in
4.76
121
R min.200 Y
15.122
AC 1000 - 11/03
1.54 39
Inches
[Millimeters]
15
Is MC oma CB x s
4.13
105
1.08
27.5
0.08
2
10.61
269.5
Y 2.28
58 1
4.13
105
6.34
161
Y 4.61
117
3 4.41
112
3.15
80
15
LEGEND 5.59 1-FLANGE FOR THE COMPARTMENT DOOR 2-PLUG FOR MOTOR OPERATOR 3-DRILLING TEMPLATE
142
4.41
112
0.28
7
15.123
AC 1000 - 11/03
15
ax m s o Is CB MC
Y 2.91
74
Inches
[Millimeters]
1.08 3.78
96 27.5
0.08
2
10.61
269.5
4.13
105
3.31
84
6.34
161
4.13
105
X 0.20
5
Y 6.57
167
Y 5.31
135
2.48
63
15
1.07 LEGEND 1-MOUNTING HOLES FOR FRONT FLANGE 2-FLANGE FOR THE COMPARTMENT DOOR X 4.96
126 27.25
3.70 Y
94
5.59
142
0.63
16
3.19
81
4.92
125
R min. 200
15.124
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
5.51
140
1.08
27.5
0.08
2
10.61
269.5
1 2.97
75.5
6.34
161
4.13
105
Y 4.61
117
3 4.41
112
3.15
80
15
LEGEND 1-FLANGE FOR THE COMPARTMENT DOOR 2-PLUG FOR MOTOR OPERATOR 3-DRILLING TEMPLATE
5.59
142
4.41
112
0.28
7
15.125
AC 1000 - 11/03
15
ax m s o Is CB MC
Y 2.91
74
Inches
[Millimeters]
3.78
96
1.08
27.5
5.51 =
140
= 4.00
101.5
0.08
2
10.61
269.5
X 6.34
161
4.13
105
X 0.20
5
6.57
167
5.31
135
2.48
63
15
1.07 LEGEND 1-MOUNTING HOLES FOR FRONT FLANGE 2-FLANGE FOR THE COMPARTMENT DOOR X 4.96
126
3.70 Y
94
27.25
5.59
142
0.63
16
3.19
81
4.92
125
R min. 200
15.126
AC 1000 - 11/03
Inches
[Millimeters]
15
Is MC oma CB x s
X
Y 8.76 3.60
91.5 222.5
1.08
27.5
186.5
7.34
13.31 10.63
270 338
4.80
122
117.5
4.62
5.51
140
0.93
23.5
0.08 2 9.74
247.5
Y 3.20 0.31
7 for 8 81.25
3.20
81.25
0.77
19.75
15
R8 12.56
319
2.84
72.25
X 3.96
100.5
X 4.25
108
6.28
159.5
0.90
22.75
6.85
174
4.80 R.min,=200 Y
122
15.127
AC 1000 - 11/03
15
ax m s o Is CB MC
Y
91.5
Inches
[Millimeters]
1.08
27.5
8.76
222.5
3.60
0.28
7
7.48
190
8.32
211.25
10.63
270
13.30
338
4.49
114
5.51
140
0.93
23.5
0.08 2 11.63
295.5
Y 3.20 0.31
7 for 8 81.25
3.20
81.25
0.77
19.75
15
11.97
304
R8 12.56
319
2.84
72.25
X 6.28 3.82
97
4.11
104.5
159.5
0.90
22.75
6.85
174
4.80 R.min,=200 Y
122
15.128
AC 1000 - 11/03
15
T MC max CB s
Introduction
ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high performance, versatility and standardization in a range of molded case circuit breakers. The ABB Tmax has been developed to complement the performance-proven Isomax line of circuit breakers. This new breaker, with a range up to 225A, has several very big features that go along with its very small size: Double insulation this construction characteristic allows for the UL Listed eld installation of internal accessories without exposure to the power poles. Positive operation all molded case breakers from ABB ensure that the toggle indicates the precise position of the moving contacts. This guarantees safe and reliable signaling by the device. Installation Tmax T1, T2 and T3 can be installed in panels and switchboards in either the horizontal or vertical planes while being fed from either end without any derating of their performance characteristics. Range of accessories in the pursuit of standardization, all Tmax internal and external accessories can be utilized across the entire range from 10A to 225A. Interrupt ratings from 22kAIC at 480VAC up to 65kAIC. Standard depth all three frames are 2.76 inches deep UL Listed and IEC rated for global application and acceptance. The ABB Tmax has the performance and accessories to satisfy all industry requirements in the 480VAC to 500VDC ranges. A single pole molded case version is available for the rst time. Standardized sizing and accessories make it easy to design and install these items in all applications.
15
Derived versions
T2 circuit breakers with LS/I electronic trip units Switch disconnectors in T1 and T3 frames Circuit breakers for motor circuit protection (MCPs) Circuit breakers for direct current
15.129
AC 1000 - 11/03
15
ax Tm CBs MC
T1
T2
T3
Circuit-breaker type Maximum frame continuous rated current Rated operational voltage Test voltage Rated impulse withstand voltage Poles Performance level UL/CSA short-circuit interrupting capacity UL 489, File #E93565 CSA, File #LR90467 IEC-947 rated ultimate short circuit breaking capacity 240VAC kA RMS 277VAC kA RMS 480VAC kA RMS 250VDC 1 kA RMS 500VDC 1 kA RMS 220/230VAC 300/400/415VAC 440VAC 500VAC 660/690VAC kA RMS kA RMS kA RMS kA RMS kA RMS 40C 50/60 Hz 1 min. 50/60 Hz A V V kV No. B (1P) 18 25
T1 100 480 3000 6 1-3 N 50 22 25 25 50 36 22 15 6 in in No. ops./hour lbs 5.12 x 3.00 x 2.76 5.12 x 4.00 x 2.76 25,000 240 1.98 S 65 35 85 50 45 30 7
T2 100 480 3000 6 2-3-4 H 100 65 100 70 55 36 8 5.12 x 3.54 x 2.76 5.12 x 4.72 x 2.76 25,000 240 2.43 N 50 25 25 35 50 36 25 20 5
T3 225 480 3000 6 2-3-4 S 65 35 25 35 85 50 40 30 8 5.9 x 4.13 x 2.76 5.9 x 5.51 x 2.76 25,000 120 4.63
Icu
Overcurrent trip unit/relays Thermal-magnetic Microprocessor-based Version Terminals Fixed front or rear Plug-in front or rear (IEC)
1 For use with thermal-magnetic trip only: 250VDC, 2 poles in series 500 VDC, 3 poles in series
15.130
AC 1000 - 11/03
15
T MC max CB s
T3 H 080 T W - 2 xxx
Number of poles
-2 = 2 pole -4 = 4 pole None = 3 pole
Type connectors
W = None L = Lugs included
Current rating
015 = 080 = 100 = 225 = 15A 80A 100A 225A
15
Frame size
T1 = 100A T2 = 100A T3 = 225A
15.131
AC 1000 - 11/03
15
ax Tm CBs MC
T1
General
The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection. Thermal overload protection is provided by heat sensitive bimetals. Short circuit protection for the breaker is accomplished using a precise magnetic coil. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits.
10 18
50 14 22 25 25
Versions
The T1 frame is available in two versions: T = Thermal-magnetic, xed D = Molded case switch
Performance levels
The T1 breaker has two performance levels available: B = 277V Single pole N = 480V Three pole
230V 415V 440V 500V 690V 250VDC 2 pole series 500VDC 3 pole series
25
50 36 22 15 6 36 36
Number of poles
The UL/CSA version of the T1 is available in single, three and four pole versions. IEC versions of the T1 are also available with the same dimensions up to 160 amperes.
Accessory mounting
The T1 frame is double insulated allowing for UL/CSA factory or eld installation of internal accessories. No extra control cables are required for eld installation. Shunt trips or UVRs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity.
15
Reverse feeding
All versions of the T1 family are suitable for reverse feed applications.
15.132
AC 1000 - 11/03
15
T MC max CB s
$ 402 402 402 402 402 402 402 479 479 479 479
14kA
15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A
1000A 1000A 1000A 1000A 1000A 1500A 1500A 1500A 1500A 1500A 1500A
T1N015TL1 T1N020TL T1N025TL T1N030TL T1N040TL T1N050TL T1N060TL T1N070TL T1N080TL T1N090TL T1N100TL
T1N
22kA
T1B
18kA
15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A
1000A 1000A 1000A 1000A 1000A 1500A 1500A 1500A 1500A 1500A 1500A
T1B015TL-1 T1B020TL-1 T1B025TL-1 T1B030TL-1 T1B040TL-1 T1B050TL-1 T1B060TL-1 T1B070TL-1 T1B080TL-1 T1B090TL-1 T1B100TL-1
$ 230 230 230 230 230 230 230 262 262 262 262
T1-D
240V, 50kA
100A
1000A
T1N100DL
$ 431
15
15.133
AC 1000 - 11/03
15
ax Tm CBs MC
T2
General
The T2 breaker family ranges from 10 through 100 amperes. The T2 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection as well as a version with microprocessor-based electronic trip unit. Thermal overload protection is provided by heat sensitive bimetals. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits.
240VAC 480VAC
15 100A 15 100A
65 35
100 65
Versions
The T2 frame is available in four versions: T = Thermal-magnetic, xed B = Adjustable LS/I electronic M = Magnetic only (MCP) E5 = Electronic instantaneous only (MCP)
230V 415V 440V 500V 690V 250VDC 2 pole series 500VDC 3 pole series
85 50 45 30 7 50 50
100 70 55 36 8 70 70
Trip functions
These tripping functions are available: L = Long time S = Short time I - Instantaneous
Performance levels
The T2 breaker has two performance levels available: S = Standard H = High
Number of poles
The UL/CSA version of the T2 is available in two, three and four pole versions. IEC
15 versions of the T2 are also available with the same dimensions up to 160 amperes.
Accessory mounting
The T2 frame is double insulated allowing for UL/CSA factory or eld installation of internal accessories. No extra control cables are required for eld installation. Shunt trips or UVRs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity.
Reverse feeding
All versions of the T2 family are suitable for reverse feed applications.
15.134
AC 1000 - 11/03
15
T MC max CB s
List price
T2S
35kA
15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A
500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A
T2S015TW-2 T2S020TW-2 T2S025TW-2 T2S030TW-2 T2S040TW-2 T2S050TW-2 T2S060TW-2 T2S070TW-2 T2S080TW-2 T2S090TW-2 T2S100TW-2
T2S015TW T2S020TW T2S025TW T2S030TW T2S040TW T2S050TW T2S060TW T2S070TW T2S080TW T2S090TW T2S100TW
$ 575 575 575 575 575 575 575 661 661 661 661
Breaker
IC at 480VAC
Rating
Magnetic trip
List price
T2H
65kA
15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A
500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A
T2H015TW-2 T2H020TW-2 T2H025TW-2 T2H030TW-2 T2H040TW-2 T2H050TW-2 T2H060TW-2 T2H070TW-2 T2H080TW-2 T2H090TW-2 T2H100TW-2
T2H015TW T2H020TW T2H025TW T2H030TW T2H040TW T2H050TW T2H060TW T2H070TW T2H080TW T2H090TW T2H100TW
$ 785 785 785 785 785 785 785 961 961 961 961
T2S
35kA
PR221DS-LS/I
T2H
65kA
PR221DS-LS/I
15
T2S
35kA
Mag only
120 - 240 300 - 600 600 1200 120 - 240 300 - 600 600 1200
T2H
65kA
Mag only
T2H
65kA
Instantaneous only
T2S
35kA
Instantaneous only
15.135
AC 1000 - 11/03
15
ax Tm CBs MC
T3
General
The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection. Thermal overload protection is provided by heat sensitive bimetals. Short circuit protection begins at 10 times the thermal rating of the breaker using a precise magnetic coil. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits.
50 25 25 25
65 35 35 35
Versions
The T3 frame is available in three versions: T = Thermal-magnetic, xed M = Magnetic only (MCP) D = Molded case switch
230V 415V 440V 500V 690V 250VDC 2 pole series 500VDC 3 pole series
50 36 25 20 5 36 36
85 50 40 30 8 50 50
Performance levels
The T3 breaker has two performance levels available: N = Normal S = Standard
Number of poles
The UL/CSA version of the T3 is available in two, three and four pole versions. IEC versions of the T3 are also available with the same dimensions up to 250 amperes.
Accessory mounting
15
The T3 frame is double insulated allowing for UL/CSA factory or eld installation of internal accessories. No extra control cables are required for eld installation. Shunt trips or UVRs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity.
Reverse feeding
All versions of the T3 family are suitable for reverse feed applications.
15.136
AC 1000 - 11/03
15
T MC max CB s
$ 406 489 489 489 489 1034 1034 1034 1034 1034
List price
T3N
25kA
60A 70A 80A 90A 100A 125A 150A 175A 200A 225A
600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
T3N060TW T3N070TW T3N080TW T3N090TW T3N100TW T3N125TW T3N150TW T3N175TW T3N200TW T3N225TW
Breaker
IC at 480VAC
Rating
Magnetic trip
T3S
35kA
60A 70A 80A 90A 100A 125A 150A 175A 200A 225A
600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A
T3S060TW T3S070TW T3S080TW T3S090TW T3S100TW T3S125TW T3S150TW T3S175TW T3S200TW T3S225TW
$ 523 641 641 641 641 1430 1430 1430 1430 1430
T3S
35kA
Mag only
T3S-D
150A 225A
1500A 2250A
T3S150DW T3S225DW
$ 714 1003
15
15.137
AC 1000 - 11/03
15
ax Tm CBs MC
KT3S4
Accessories Electrical
Shunt trips
Factory installation Voltage Catalog number sufx 1 List price adder Field installation Catalog number T1 T3 List price
480 500VAC 220/250VAC/DC 380 440VAC 110 125VAC/DC 48 60VAC/DC 24 30VAC/DC 12VDC
S1 S2 S3 S4 S7 S8 S9
$ 324
$ 298
For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole mounted and can not be used with undervoltage releases. All shunt trips are approved for use in ground fault systems.
Electrical specications
Voltage 24, 120, 240 48 - 60 480 - 500 AC VA 50 60 55 DC Watts 50 60
Undervoltage releases
Factory installation Voltage Catalog number sufx 1 List price adder Field installation Catalog number T1 T3 List
Price
T1 with KT3S4
480 500VAC 220 250VAC/DC 380 440VAC 110 125VAC/DC 60VAC/DC 48VAC/DC 24 30VAC/DC
U1 U2 U3 U4 U5 U7 U8
$ 324
$ 298
Will trip circuit breaker when connected voltage drops to 35 70% of undervoltage release voltage rating. Will allow circuit breaker to close (ON) when voltage is approximately 85% of rated voltage. All undervoltage releases are left pole mounted and can not be used with shunt trips.
Electrical specications
Voltage 24 48 - 60 120 220 - 250 480 - 500 AC VA 1.5 1 2 2.5 4 DC Watts 1.5 1 2 2.5
KT3U2
15
Auxiliary contacts T1 - T3
Factory installation Contacts Catalog number sufx List price adder Field installation Catalog number List Price
1 Form C + 1 BA 3 Form C + 1 BA
A A3
$ 205 262
KT3AS KT3AS3
$ 190 247
Motor operators
Field installation Voltage Catalog number List Price
T1 with K3TAS
KT3M1 KT3M2
$ 645
Electrical specications
Voltage range Inrush power
2500VA / 1000W
KT3M1 1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
15.138
AC 1000 - 11/03
Accessories Mechanical
Direct mount rotary operator handle
Catalog number
15
T MC max CB s
List price
KT3RH
$ 146
Locking device
Catalog number List price
Locking device
OHB65J6
KT3LD
$ 21
Lugs
For breakers Amps Wire size Set of 2 catalog number List price Set of 3 catalog number List price Set of 4 catalog number List price
KT2100-2
$6
$9 9 9 12 18
$ 12 12 12 18 24
T3
T2 T3
KT3LD
100 225
KT2EF-3 KT3EF-3
$ 26 33
KT2EF-4 KT3EF-4
$ 35 44
15
Rear terminals
Set of 3 For breakers Amps Catalog number List price adder Set of 4 Catalog number List Price
T2 T3
100 225
KT2R-3 KT3R-3
$ 78 98
KT2R-4 KT3R-4
$ 105 131
KT3100-3
OHB 65 J 6
Color
B =Black Y =Red/Yellow
KT2EF-3
KT2R-3
15.139
AC 1000 - 11/03
15
ax Tm CBs MC
KT2DIN
Accessories Mechanical
DIN Rail mounting kits 35mm DIN
For breakers Catalog number List price
T1 / T2 T3
KT2DIN KT3DIN
$ 33 41
T1 T2 T3
High Prole For breakers
$ 35 40 50
List price
$ 47 54 68
List Price
$ 37 43 53
$ 50 58 72
T2 3-Pole T3 3-Pole
KT2PMK KT3PMK
$ 171 190
KT2PFF KT3PFF
$ 238 264
Fixed parts accept the same cable and rear terminal kits as the circuit breakers.
T1 T3
KT1HTC-3
KT3MIF2
$ 452
KT3MIF3
$ 904
15
KT2PMK
KT3MIF2
15.140
AC 1000 - 11/03
15
T MC max CB s
Tmax T1 100 TMF In = 80 ... 100A
t [s ] 10 4 10 3 10 2 10
10 3
10 2
10
10 -1
40A 60A 30A 70A 50A 25A 20A 15A
10 -1
90A 100A 80A
10 -2
10 -2 10 -1 1 10 10 2 x In
10 -1
10
10 2 x In
103
10 3
15
102
10 2
10
10
1
60 100A
10-1
40A 50A 35A 30A 25A 20A 15A
10 -1
10 -2 10 -1 1 10 10 2 x In
15.141
AC 1000 - 11/03
15
ax Tm CBs MC
Tmax T2 100 PR221DS-LS, function L-I
t [s] 104
L
1.5
t [s]
104
I
103
103
B
1
B A
102
102
10 102
10 102
10-1
10-1
10-2
10-2
L
0.4 1 1
0.4-0.44-0.48-0.52-0.56-0.60-0.64-0.680.72-0.76-0.80-0.84-0.88-0.92-0.96-1
10 3
103
1.5
15
10 2
B A
B A
102
10
C B
S
10 2
10
12
10 -1
10-1
10 -2
10-2
10 -3 10 -1 1 10 x In 10 -1 1 10 Iu [kA]
15.142
AC 1000 - 11/03
15
T MC max CB s
Tmax T3 225 TMF In = 125 ... 225A
t [s] 104 103 102
103
102
10
10
1
60100A
1
125225A
10-1
10-1
15
15.143
AC 1000 - 11/03
15
ax Tm CBs MC
Tmax T1 and T1 1P
In [A] 15 20 25 30 40 50 60 70 80 90 100 50 F / 10 C 18 24 29 35 47 60 71 83 94 106 121 50 F / 10 C 18 24 30 35 40 46 56 71 83 96 109 115 50 F / 10 C 70 82 92 104 117 145 175 205 236 264
68 F / 20 C 17 22 28 34 45 57 68 79 90 101 114 68 F / 20 C 17 23 28 33 39 44 54 68 79 91 103 110 68 F / 20 C 67 78 88 100 112 139 167 195 224 251
104 F / 40 C 15 20 25 30 40 50 60 70 80 90 100 104 F / 40 C 15 20 25 30 35 40 50 60 70 80 90 100 104 F / 40 C 60 70 80 90 100 125 150 175 200 225
Tmax T2
In [A] 15 20 25 30 35 40 50 60 70 80 90 100
Tmax T3
In [A] 60 70 80 90 100 125 150 175 200 225
15
15.144
AC 1000 - 11/03
15
T MC max CB s
T1 Single pole
15
83
T2 2 & 3 pole
30
90 30
78 70
9.38
65
181
130
17
76.2
15.145
AC 1000 - 11/03
15
ax Tm CBs MC
T3 2 & 3 pole
Approximate dimensions T3
15
15.146
AC 1000 - 11/03