Panel No: 1: EST3 Battery Calculations
Panel No: 1: EST3 Battery Calculations
10/1/2011
PANEL NO:
EST3 LRMs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Qty 1 1 1 1 x x x x x x x x x x x x x x x x x x x x x x x x x x x x
Standby Current (mA) 110 100 55 48 38 53 139 256 158 242 50 70 38 53 60 50 105 217 45 20 20 38 45 35 35 75 75 53
Alarm Current (mA) 145 110 55 48 38 53 158 294 177 261 50 70 52 53 95 330 110 217 45 20 20 38 45 1.25 2.3 4.98 5.24 147
3-CPU3 3-CPU1 3-RS485 3-RS232 3-LCD (with 3-CPU3) 3-LCD (with 3-CPU1 AND 3-CPU) 3-SSDC1(include full loop of devices) 3-SDDC1(include full loop of devices) 3-SSDC (include full loop of devices) 3-SDDC (include full loop of devices) 3-BPS/M 3-BBC/M 3-LCDXL (with 3-CPU3) 3-LCDXL (with 3-CPU1 AND 3-CPU) 3-MODCOM 3-IDC8/4 3-FIBA 3-FIBMB SMXLO OR SMXHI MMXVR LED Switch Modules (12leds) LED Switch Modules (24leds) 3-ASU 3-ZA20 3-ZA40 3-ZA90 3-ZA95 3-OPS 3-PPS/M Aux 2 circuits 3-ANNCPU1 3-ANNCPU3 LED Switch Modules (12leds) LED Switch Modules (24leds) 3-ANNSM 3-REMICx NSHM1 NSHM2
29 30 31 32 33 34 35 36
x x x x x x x x
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Note 1: Max total current = 7000mA, Note 2: Add 3-BPS/M OR 3-BBC/M to cater for power requirement of more than 7amps and up to max 28amps Note 3: 3-BBC/M has charging function and connects to a sets of battery (battery has to be same AH sizing as battery use in 3-PPS/M)
Totals =
567 24 13608
mA Stdby Hrs. +
mAh
Ah
22.40
0.63
FINAL AH REQUIREMENT
1.) Discharge Factor of Battery in Normal State = 0.90 2.) Discharge Factor of Battery in Alarm State = 0.80 3.) Aging Factor = 0.75 4.) Temp. Correction Factor = 0.90
PANEL NO:
EST3 LRMs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Qty 1 1 1 1 x x x x x x x x x x x x x x x x x x x x x x x x x x x x
Standby Current (mA) 110 100 55 48 38 53 139 256 158 242 50 70 38 53 60 50 105 217 45 20 20 38 45 35 35 75 75 53
Alarm Current (mA) 145 110 55 48 38 53 158 294 177 261 50 70 52 53 95 330 110 217 45 20 20 38 45 1.25 2.3 4.98 5.24 147
3-CPU3 3-CPU1 3-RS485 3-RS232 3-LCD (with 3-CPU3) 3-LCD (with 3-CPU1 AND 3-CPU) 3-SSDC1(include full loop of devices) 3-SDDC1(include full loop of devices) 3-SSDC (include full loop of devices) 3-SDDC (include full loop of devices) 3-BPS/M 3-BBC/M 3-LCDXL (with 3-CPU3) 3-LCDXL (with 3-CPU1 AND 3-CPU) 3-MODCOM 3-IDC8/4 3-FIBA 3-FIBMB SMXLO OR SMXHI MMXVR LED Switch Modules (12leds) LED Switch Modules (24leds) 3-ASU 3-ZA20 3-ZA40 3-ZA90 3-ZA95 3-OPS 3-PPS/M Aux 2 circuits 3-ANNCPU1 3-ANNCPU3 LED Switch Modules (12leds) LED Switch Modules (24leds) 3-ANNSM 3-REMICx NSHM1 NSHM2
29 30 31 32 33 34 35 36
x x x x x x x x
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Note 1: Max total current = 7000mA, Note 2: Add 3-BPS/M OR 3-BBC/M to cater for power requirement of more than 7amps and up to max 28amps
Totals =
507 24
mA Stdby Hrs.
580 30 0.5
Note 3: 3-BBC/M has charging function and connects to a sets of battery (battery has to be same AH sizing as battery use in 3-PPS/M)
12168
290
mAh
Ah
20.03
FINAL AH REQUIREMENT
0.54
1.) Discharge Factor of Battery in Normal State = 0.90 2.) Discharge Factor of Battery in Alarm State = 0.80 3.) Aging Factor = 0.75 4.) Temp. Correction Factor = 0.90
TOATL AH REQUIREMENT ( A + B )
25.71
OFFERED BATTERY : 26 AH
in Alarm Time
5 0.90
Battery Calculator Detect 3004 Quiecent Current Sr. No. 1 2 3 4 5 6 7 8 Item Description Model No. Quiecent Current Quantity mA 86 40 0.25 0.25 0.37 0.5 0 0 1 1 50 3 9 2 2 9 Total Quiecent Current 86 40 12.5 0.75 3.33 1 0 0
Fire Alarm Control Panel-up to 4 loops Loop interface active-2 loops Optical smoke detector Heat detector Push button detector,isolator Output module Hooter Response Indicator
Detect - 3004 DLI 3240P X1 PL 3200 O PL 3200 T PL 3300 MCP-kit OMS 3301 MASS MASS
143.58
Total Quiecent Current (In A) By Pass Time Requirement (In Hours) Total Alarm Current (In A)
0.144
24
0.77
5.67
FINAL AH REQUIREMENT
1.43
1.) Discharge Factor of Battery in Normal State 2.) Discharge Factor of Battery in Alarm State 3.) Aging Factor = 0.75 4.) Temp. Correction Factor = 0.90
8.88
OFFERED BATTERY : 10 AH
Alarm Current Alarm Current mA 146 140 5 5 5 5 125 2 Quantity 1 2 13 1 3 2 2 3 Total Alarm Current 146 280 65 5 15 10 250 6
771
Alarm Time (In Hours)
ge Factor X Ageing Factor X Temp. Corr. Factor 0.771 X 1 0.80 X 0.75 X 0.90
1.43
rge Factor of Battery in Normal State = 0.90 rge Factor of Battery in Alarm State = 0.80 Factor = 0.75 Correction Factor = 0.90
FFERED BATTERY : 10 AH
FFERED BATTERY : 10 AH