Sound Noise Control
Sound Noise Control
3 1
C o n t r o l
Right to alterations reserved.
3 2
Noise Outlet
Usually a grille or a diffuser. Any opening acting as a terminal element on either an extract or supply system.
Background Noise
It is the irreducible noise level measured in the absence of any building occupants when all of known sound sources have been turned off.
3 3
Octave Bands
Subdivisions of the frequency range each identified by its mid (or centre) frequency. By international agreements these comprise 63, 125, 250, 500, 1k, 4k, and 8k Hz. and sometimes 31.5 Hz.
Breakout Noise
The transmission of fan or air system noise through duct walls.
Regenerated Noise
Noise in addition to that produced by the fan, caused by air passing over fixed duct elements such as blades on grilles, dampers, air turns, splitters in attenuators, etc.
Criteria
Noise levels which are subjectively or objectively acceptable in a given environment. The most commonly used criteria are Noise Criteria Curves (NC Levels), Noise Rating Curves(NR Levels) and dB(A).
Reverberant SPL
Noise which is transmitted by reflection off room surfaces.
Decibel (dB)
Commonly, the unit used to measure sound. It is used to quantify both sound pressure level and sound power level.
Reverberant Time
A measurement of the acoustic "reflectiveness" of a room.
Ductborne Noise
Noise which is transmitted along ductwork, botk upstream and downstream of a fan.
Frequency (Hz.)
The pitch of sound. The number of sound pressure waves arriving at a fixed point per second.
Insertion Loss
A measure of the noise reduction capability of an attenuator (sometimes of a partition) so named
3 4
Waves in air
We fire a starter's gun.
Waves in air
Sound waves spread out in the air, in all directions, in an increasing ball from the centre, i.e. the gun.
Wave in air
Kinetic energy is transmitted from molecule to molecule in the air. They bounce against each other, and move back and forwards. Energy spreads from the source.
Wave in air
If waves in air encounter a wall, they will be reflected at the same angle as they met the obstruction.
3 5
Waves in air
When sound waves depart from the source, the starter's gun, wave movement drops off and the sound becomes weaker and weaker until it can no longer be heard.
Wave in air
The energy which started the wave propagation, or the power needed to keep it going, is distributed across an increasing volume as the distance, the radius, increases.
The ball moves more slowly when it bounces back than when it hit the wall.
Right to alterations reserved.
1.0
Mineral W ool 100 m m
3 6
0.5
M
in
l ra
oo W
0 l5
m
er oo al W
l2
mm
Min
Soft c
on c arpet
Wind
oncre
te floo
ow gla
ss
0 125
a
Concrete
i=a+r = a i
250
500
1000 2000
4000 Hz
An open window can be said to have a = 1, all sound from the room which arrives at the window disappears out! In hard materials, such as concrete or marble surfaces, virtually no sound energy is absorbed, everything is reflected and the a value is near to zero. In rooms with hard surfaces, the sound bounces for a long time before it dies out. The room has a long reverberation time and we get a strong, unpleasant echo. The sound level caused by normal sound sources becomes high. In soft materials, such as thick mineral wool boards, the opposite happens. The a value is close to 1. Sometimes, excessively damped, soft rooms are unsuitable "You can't hear what you say". Avoid extremes - the reverberation time in a room should be chosen to suit the activities there.
Infra Sound
Ultra Sound
3 7
Audible Sound 20 Hz 20 000 Hz We perceive changes in sound frequency on a logarithmic scale, i.e. it is the relative frequency and not the difference in Hz which determines how a change in note is perceived. A doubling of frequency is perceived as being the same, irrespective of whether it is a change from 100 to 200 Hz, 1000 to 2000 Hz or 10 to 20 kHz.
Infra Sound
Ultra Sound
The characteristics of sound propagation are: frequency (f), which is measured in Hertz, Hz, (s-1), (and specifies the number of times a second that a new sound wave arrives). wave length (, "lambda"), which is measured in metres, m, (and specifies the distance between two similar points on the curve).
20
50
100
200
The logarithmic scale is usually sub-divided into octaves. i.e. in scales where the top note is twice the frequency of the bottom note. This has been customary in music for a long time.
and
speed of sound (c) which is measured in m/s, (and specifies the speed of movement of the sound wave). These three variables have the following relationship: c=f The speed of sound in air is also a function of pressure and temperature. At normal air pressure and + 20oC: c 340 m/s.
Infra Sound Audible Sound Logarithmic scale
20 50 100 200 500 1000 2000 5000 10000 20000 Hz
Ultra Sound
3 8
Ultra Sound
We react differently to two sounds which have the same sound pressure level and different frequencies.
16
31.5
16 Hz
Curves which describe how people normally perceive sounds of varying strength and frequency have been constructed through experiments on large numbers of volunteers. These so-called hearing level curves are designated by the sound pressure level for each curve at a frequency of 1 kHz. The unit used for the curves is the phon.
Sound pressure changes in the audible area can vary within very wide limits. Some sounds are so weak that we can not hear them. The so-called audible limit varies with frequency and is 20 mPa at about 1000 Hz. Other sounds are so loud that we risk hearing damage. The pain limit, the sound pressure which causes pain in your ears also varies with frequency, but is about 20 Pa at 1000 Hz. This means that it is a million times louder than the weakest sound we can perceive. We also perceive changes in sound pressure on a logarithmic scale. A sound level concept using the decibel (dB) as the unit, has been created to express comparable values.
Example:
The sound pressure level 70 dB at 50 Hz is normally perceived as being as loud as 50 dB at 1000 Hz.
3 9
Several methods are used to compare the disturbance caused by two different sounds, and where the perception of the ear to noise has been modelled.
The simplest way is to compare their "weighted" sound levels. The incoming sound is filtered in an electronic filter to reduce the components, mostly the low-frequency components, where the ear is not so sensitive, and amplify the components between 1 and 4 kHz, where we are most sensitive. Sound meters usually have three electronic filters, A-, Band C-filter. The A-filter is mostly used these days, where the result, the "weighted" sound level, is expressed in dB (A).
Attenuation dB (above 20 Pa)
0 -10 -20 -30 -40 -50 -60 2 31 5 63 102 2 125 250 5 500 103 1 2 2 5 4 8 104 16 2 Hz kHz
C B A
A C B
3 10
In order to effectively deal with each of the different sound sources and related sound paths associated with an HVAC system, the following design procedures are suggested : 1. Determine the design goal for HVAC system noise for each critical area according to its use and construction. Use Table 14 to specify the desirable NC levels.
9. Redesign the system, adding additional sound attenuation to the paths which contribute to the excessive sound pressure levels in the critical room.
10. Repeat steps 4 through 9 until the desired design goal is achieved.
11. Steps 3 through 10 must be repeated for every room that is to be analyzed.
2. Relative to equipment that radiates sound directly into a room, select equipment that will be quiet enough to meet the desired design goal.
12. Make sure that noise radiated by outdoor equipment will not disturb adjacent properties.
3. If central or roof-mounted mechanical equipment is used, complete an initial design and layout of the HVAC system, using acoustical treatment where it appears appropriate.
13. With respect to outdoor equipment, use barriers when noise associated with the equipment will disturb adjacent properties.
4. Starting at the fan, appropriately add the sound attenuations and sound power levels associated with the central fan, and duct elements between the central fan and the critical room to determine the corresponding sound pressure levels in the room. Be sure to investigate the supply and return air paths. Investigate possible duct sound breakout when central fans are adjacent to the critical room or roof-mounted fans are above the critical room.
14. If mechanical equipment is located on upper floors or is roof-mounted, vibration isolate all reciprocating and rotating equipment. It may be necessary to vibration isolate mechanical equipment that is located in the basement of the building.
5. If the mechanical equipment room is adjacent to the critical room, determine the sound pressure levels in the room associated with sound transmitted through the mechanical equipment room wall.
6. Add the sound pressure levels in the critical room that are associated with all of the sound paths between the mechanical equipment room or roof-mounted unit and the critical room.
7. Determine the correspondin NC level associated with the calculated total sound pressure levels in the critical room.
A sound analysis should be carried out starting from the fan or noise source having ducted connections to the room of interest. It is strongly recommend that sound level requirements for NC 30 or below be calculated out by Safid so as to ensure a complete check against noise criteria levels.
At low frequencies some of the sound power on reaching the critical noise outlet is reflected back along the duct. The degree of attenuation due to this phenomenon is dependent on frequency and the total area of the outlet. The attenuation from Table 6 is inserted in line c. The total duct attenuation is obtained from lines b and c and is inserted in line d. The Sound Power Level leaving the critical outlet is obtained from: e=a-d
3 11
Duct system between the fan and the critical noise outlet.
Select the most critical noise outlet in the duct system, normally the noise outlet nearest to the fan, and estimate the sound power reduction which occurs along the duct path to this outlet and the outlet itself. Using the following information assess the total duct attenuation. Straight unlined sheet metal ducts provide a degree of attenuation. This is frequency dependent and varies with the minimum duct dimension and duct length. Approximate attenuation of straigth unlined rectangular sheet metal ducts per meter run is shown in Table 2. To avoid noise breakout problems in the duct attenuation taken should be limited to approximately 15dB. Circular sheet metal duct attenuation shown in Table 3. Bends provide attenuation as shown in Tables 4 and 5. Duct and bend attenuation figures should be entered against lines b.
To estimate the Direct Sound Pressure Level. Calculate the percentage of the total sound leaving the critical noise outlet. This is approximately equal to the percentage of the fan air volume which passes through the critical outlet. Table 7 gives the factors to be inserted in line f. Estimate the distance between the nearest listening position and the critical outlet, and using Table 8, insert the distance factors in line g. Unless the specification states otherwise, the commonly applied distance is 1.5 meters. By examining the position of the nearest outlet in relation to the walls and ceiling of the room will affect the resultant sound pressure level, due to directivity. Select the location type (A, B, or C) using Table 9, which is closest to matching the position of the critical outlet in the room. Using the charts for the chosen location type and outlet area, insert the factors obtained in line h.
3 12
To estimate the Reverberant Sound Pressure Level. For the fan system in question, Calculate the percentage of the sound emerging from all the noise outlets in the room served by the fan. This approximates to the percentage of the fan air volume serving the room under investigation. Using Table 10 insert the factor in line k. The amount of reflection or absorption of the sound emerging from the noise outlets depends upon the volume and the reverberation time (which is a function of the amount of absorption) of the room. Table 11 and 12 give the factors related to these which are inserted in lines l and m respectively. The factors tabulated at each Octave Band in lines k,l and m are now added together in line n, to give the Total Reverberant Factors. The Reverberant sound Pressure level (line o) in the room is equal to the sum of the Sound Power Level leaving the Critical Outlet (line e) and the Total Reverberant Factors (line n). To arrive at the Combined Sound Pressure Level, it is necessary to logarithmically sum the Reverberant Sound Pressure Level and the Direct Sound Pressure Level. This can be simplified by using Table 13. The combined pressure level can then be entered in line p.
130 120 110 100 90 80 70 60 50 0.1 1.0 10 100 Volume flow cubic metres per second
Pa 3200 Pa 1600 a 800 P a 400 P a 200 P a 100 P 50 Pa a 251 P
3 13
Spectrum Correction
Octave Centre frequency, fm in Hz 63 Forward Curved Centrifugal Backward Curved Centrifugal Axial -2 -7 -5 125 -7 -8 -5 200 -12 -7 -6 500 -17 -12 -7 1k -22 -17 -8 2k -27 -22 -8 4k -32 -27 -14 8k -37 -32 -17
S
3 14
Table 3: Attenuation of straight unlined circular or round sheet metal ducts - dB/m
Duct Dimensions S in mm Octave Centre frequency, fm in Hz
63 000 - 180 181- 380 381 - 760 761 - 1520 0.03 0.03 0.02 0.01
Table 4: Attenuation of mitred bends without turning vanes or with short chord turning vanes (rectangular ducts) - dB
Minimum Duct Dimensions S in mm 000 - 200 201- 400 401 - 800 801 - 2000 Octave Centre frequency, fm in Hz
63 0 0 0 0
125 0 0 0 6
200 0 0 6 8
500 0 6 8 4
1k 6 8 4 3
2k 8 4 3 3
4k 4 3 3 3
8k 3 3 3 3
Table 5: Attenuation of radiussed bends or mitred bends with long chord turning vanes (circular or rectangular ducts) - dB
Minimum Duct Dimensions S in mm 000 - 250 251- 500 501 - 1000 1001 - 2000
63 0 0 0 0
125 0 0 0 1
200 0 0 1 2
500 0 1 2 3
1k 1 2 3 3
2k 2 3 3 3
4k 3 3 3 3
8k 3 3 3 3
125
15 14
250
500
1k
3
10 9
6 5 2
2 3 4 5
3 15
10
20
50
100
1.5
4 5 6 7 8 9
Direct Reverberant
Right to alterations reserved.
2 3 4 5
3 16
10
20
Type B
50
10 +6 +6 +6 +6 +7 +7 +7 +8
100
1000 +7 +7 +7 +8 +8 +8 +8
100
+7
+8
+9 +9
Type C
10
100 +3 +3
1000 +4
+4 +5 +6 +4 +5 +6 +6 +7 +8 +7 +8
+3 +4 +5 +5 +6 +7 +8
+3 +4 +5 +6 +7 +8
3 17
NC 15 20 25 20 - 25 25 - 30 20 - 25 30 - 35 35 35 - 40 35 - 45 30 - 40 20 - 30 30 - 35 35 - 40 40 - 45 35 - 40 40 - 45 25 - 30 30 - 35 35 35 - 45 25 - 30 25 - 35 30 - 35 35 - 45 40 - 50 55 25 - 30 25 - 35 35 - 40 35 - 45 45 - 50 45 - 55 50 - 65 25 30
3 18
3 19
Outlet reflection SWL leaving system Percentage leaving outlet Distance from outlet Directivity
cm2
c d e f g h i j k l m n o p q r s
Total direct factors (f + g + h) Direct SPL Percentage reaching room Room volume Reverberation time Total reverberant factors (k + l + m) Reverberant SPL Combined SPL Criterion Required insertion loss Selected insertion loss Selection Code: NC55 NR55 NC50 NR50 NC45 NR45 NC40 NR40 NC35 NR35 NC30 NR30 NC25 NR25 NC20 NR20 74 79 71 75 67 71 64 67 60 63 57 59 54 55 51 51 67 70 64 65 60 61 57 57 52 52 48 48 44 44 40 39 62 63 58 59 54 54 50 49 45 45 41 40 37 35 33 31 58 58 54 53 49 48 45 44 40 39 35 34 31 29 26 24 56 55 51 50 46 45 41 40 36 35 31 30 27 25 22 20 54 52 49 47 44 42 39 37 34 32 29 27 24 22 19 17 53 50 48 45 43 40 38 35 33 30 28 25 22 20 17 14 52 49 47 43 42 38 37 33 32 28 27 23 21 18 16 13
3 20
Plantroom
Fan
1 700x600 700x600 2 3 4 600x350 6 7 5 8
650x 300
10
VD
VD
11
VD
VD
Roomside Calculation
System Element Ref Type 1 Duct 2 Bend 3 Duct 4 Duct 5 Bend 6 Duct 7 Bend 8 Duct 9 Bend 10 Duct 11 Outlet W H Length/Type 700 600 2 metres 700 600 Radiused 700 600 5 metres 600 350 2 metres 600 350 Radiused 600 350 6 metres 600 350 Radiused 600 350 2 metres 350 350 Radiused 350 350 2 metres 2 slot diffuser 1200 mm long,
3 21
FAN DETAILS Type : Centrifugal Duty : 2.26 m3/s at 600 Pa. Sound Power Level at mid frequency Octave Bands Hz dB 63 86 125 91 250 87 500 92 1k 88 2k 88 4k 82 8k 74
: : :
300 m3 3m Slot diffuser 1200m long each slot 15mm wide each slot diffuser handles 0.195 m3/s
ROOM CRITERION NC 35 at 1.5 metres from the noise outlet. Office area
86 1 0 3 1 0 4 0 1 0 1 14 25 61
a b
3 22
Outlet reflection Total duct attenuation (b + c) SWL leaving system Percentage leaving outlet Distance from outlet Directivity Total direct factors (f + g + h) Direct SPL Percentage reaching room Room volume Reverberation time
c d e f g h i j k l m n o p q r s
8% 1.5 m Type C
-3 -11 0 -14 47 48
Total reverberant factors (k + l + m) Reverberant SPL Combined SPL Criterion Required insertion loss +3dB Selected insertion loss Selection Code: SA20-150 / 900L x 700W X 600H NC55 NR55 NC50 NR50 NC45 NR45 NC40 NR40 NC35 NR35 NC30 NR30 NC25 NR25 NC20 NR20 NC 35
60 0 8 74 79 71 75 67 71 64 67 60 63 57 59 54 55 51 51