The Basic Reed Switch
The Basic Reed Switch
MEDER electronic
(Figure #1. The basic hermetically sealed Form 1A (normally open) Reed Switch and its component makeup.)
A Reed Switch consists of two ferromagnetic blades (generally composed of iron and nickel) hermetically sealed in a glass capsule. The blades overlap internally in the glass capsule with a gap between them, and make contact with each other when in the presence of a suitable magnetic field. The contact area on both blades is plated or sputtered with a very hard metal, usually Rhodium or Ruthenium. These very hard metals give rise to the potential of very long life times if the contacts are not switched with heavy loads. The gas in the capsule usually consists of Nitrogen or some equivalent inert gas. Some Reed Switches, to increase their ability to switch and standoff high voltages, have an internal vacuum. The reed blades act as magnetic flux conductors when exposed to an external magnetic field from either a permanent magnet or an electromagnetic coil. Poles of opposite polarity are created and the contacts close when the magnetic force exceeds the spring force of the reed blades. As the external magnetic field is reduced so that the force between the reeds is less than the restoring force of the reed blades, the contacts open.
(Figure #2. The 1 Form C (single pole double throw) three leaded Reed Switch and its component makeup.)
The common blade (or armature blade), the only moving reed blade, is connected to the normally closed blade in the absence of a magnetic field. When a magnetic field of sufficient strength is present, the common blade swings over to the normally open blade. The normally open and normally closed blades always remain stationary. All three reed blades are ferromagnetic; however, the contact area of the normally closed contact is a non-magnetic metal which has been welded to the ferromagnetic blade. When exposed to a magnetic field, both the fixed reeds assume the same polarity, which is opposite that of the armature. The nonmagnetic metal interrupts the magnetic flux on the normally closed blade so that the armature sees an un-interrupted flux path to the normally open blade, and it is that which it seeks. Here the attractive force is of sufficient magnitude between the normally open and armature that the contacts close.
The Reed Switch described above is a 1 Form A (normally open (N.O.)or Single Pole Single Throw (SPST)) Reed Switch. Multiple switch usage in a given configuration is described as 2 Form A ( two normally open switches or Double Pole Single www.meder.com
28
MEDER electronic
To close Reed Switch contacts, two approaches are generally used. 1. The use of a permanent magnet (see Figure #3);
(Figure #3. The basic operation of a Reed Switch under the influence of the magnetic field of a permanent magnet. The polarization of the reed blades occurs in such a manner to offer an attractive force at the reed contacts.)
or 2. The use of a coil wound with copper insulated wire (see Figure #4).
(Figure #4. A Reed Switch sitting in a solenoid where the magnetic field is strongest in its center. Here the reed blades become polarized and an attractive force exists across the contacts.)
www.meder.com
Germany # ++49-(0)7733-94870, USA # 800-870-5385
29
MEDER electronic
Temperature (C)
(Figure #6. The Pull-in and Drop-out points will change with temperature at the rate of 0.4%/oC.)
Here, because the copper coil wire expands and contracts with temperature, the Pull-In or operate point will vary with temperature by 0.4% oC. Well designed relays usually take this parametric change into consideration in the design and specification.
Figure #5. For most accurate results, saturate the contacts with a magnetic field first, before testing for Pull-in and Drop-out.
www.meder.com
30
MEDER electronic
Drop-Out (DO) is described as that point where the contacts open and has similar characteristics as the Pull-In above. It is also described as release or resetvoltage current or AT.
Hysteresis exists between the Pull-In and DropOut and is usually described in the ratio DO/PI expressed in %. The hysteresis can vary depending upon the Reed Switch design, (see Figure #7), where variations in plating or sputtering thickness, blade stiffness, blade overlap, blade length, gap size, seal length, etc. will all influence this parameter. See Figure #29 for example of hysteresis when using a magnet to handle a Reed Switch.
Drop-out vs. Pull-in
(Figure #8. A representation of the bulk resistance and resistance across the contacts making up the contact resistance value in Ohms for a Reed Switch.)
40
30 20 10 0 0 10 20 30 40 50
Dynamic Contact Resistance (DCR) is a true measure of the disposition of the contacts. As already described, the contact resistance is mostly made up of bulk resistance or lead resistance. Measuring the resistance across the Reed Switch only gives gross indication that the contacts are functional. To give a better indication of the contacts functionality, one must look at the contacts under dynamic conditions. Opening and closing the contacts at frequencies in the range of 50 Hz to 200 Hz can reveal much more information. Switching 0.5 Volts or less with approximately 50 mA will allow enough voltage and current to detect potential problems. This testing can be carried out using an oscilloscope or may be easily digitized for more automatic testing. One should avoid test voltages greater than 0.5 Volts to avoid break-over. If a Reed Switch is not properly cleaned during its manufacture, potential nonconductive films may exist that may only be of the order of a few Angstroms thick. This extremely thin film will look like an open circuit if one is switching very low signals or in currentless closing of the Reed Switch (closing the contacts before any voltage or current is applied across the contacts). Using a higher voltage while testing the contact resistance, one might miss this potential quality problem. See Figure #9.
Drop-out (AT)
Pull-in (AT)
(Figure #7. The Pull-in and Drop-out ranges are shown. Note that variation in hysteresis is for low ampere turns (AT) is very small and increases with higher AT.)
Contact Resistance is the DC resistance generated by the reed blades (bulk resistance) and the resistance across the contact gap. Most of the contact resistance resides in the nickle / iron reed -8 blades. Their resistivity is 7.8 x 10 -m and -8 10.0 x 10 -m , respectively. These are relatively high when compared to the resistivity of copper, -8 which is 1.7 x 10 -m . Typical contact resistance for a Reed Switch is approximately 70 m, 10 to 25 m of which is the actual resistance across the contacts. In a Reed Relay, many times the relay pins will be nickel/iron improving the overall
www.meder.com
Germany # ++49-(0)7733-94870, USA # 800-870-5385
31
MEDER electronic
(Figure #9. A schematic diagram of a typical circuit used for measuring the dynamic contact resistance across the contacts of a Reed Switch.)
(Figure #10. A typical dynamic contact resistance portrayal showing the first closure, bouncing, dynamic noise and pattern generated by wavering contacts.)
Applying the frequency described above to a coil, the contacts will operate and close in approximately mA. The contacts may then bounce for about 100s and undergo a period of dynamic noise for as much as ms. This dynamic noise is generated by the contacts continuing to bounce but not opening, whereby the contact resistance varies widely where the force or pressure on the contacts varies harmonically, critically dampening in about ms or less. See Figure #10. Once this dynamic noise dissipates, the contacts will then undergo a wavering period. Here the contacts have closed, but will waver while closed for up to 1 ms or more. This wavering of the contacts in the coils magnetic field generates a current through the contacts. Once this effect dissipates the contacts enter their static condition.
Observing the electrical pattern produced by this dynamic test can reveal much about the quality of the Reed Switch. Generally speaking, once the coil voltage has been applied, the dynamic contact activity should settle down by 1 ms. If the contacts continue to bounce more than 250 s, the closing force may be weak, which may result in a shortened life, particularly if one is switching a load of any size. (See Figure #11)
www.meder.com
32
MEDER electronic
(Figure #11. A dynamic contact resistance pattern showing excessive contact bounce.)
(Figure #12. A dynamic contact resistance pattern portraying excessive dynamic noise indicating potential stressed or cracked glass seal.)
If the dynamic noise or the wavering contacts continue for periods longer than indicated, it may mean the Reed Switch seals are weak or perhaps overstressed. This could result in capsule cracking or breaking. Also, if the wavering produced has excessive amplitude, this could represent a condition of capsules having added stress which could produce leaking seals. In this case, outside air and moisture may seep into the capsule producing unwanted contamination on the contacts. See Figure #12 & Figure #13.
(Figure #13. A dynamic contact resistance pattern with indicated excessive contact wavering often indicates a stressed or cracked glass seal.)
www.meder.com
Germany # ++49-(0)7733-94870, USA # 800-870-5385
33
MEDER electronic
of operations depending on the amount of current switched. Most pressurized Reed Switches can not switch more than 250 Volts, principally because they can not break the arc occurring when one tries to open the contacts. Generally, switching above 250 Volts requires evacuated Reed Switches, where up to 10,000 Volts is possible. Switching below 5 Volts, no arcing occurs and therefore no blade wear occurs, extending Reed Switch lifetimes well into the billions of operations. Properly designed Reed Relays can switch and discern voltages as low as 10 nanoVolts.
Switching Current refers to that current measured in Amperes DC (peak AC), switched at the point of closure of the contacts. The higher the level of current the more sustained the arcing at opening and closing and therefore the shorter the life of the switch.
(Figure #14. A dynamic contact resistance pattern showing contact resistance changing in each successive operation indicating contact contamination.)
Any time long life, stable contact resistance, and fault free operation are conditions in your application, dynamically testing the contacts and having tight testing limits are a must.
Carry Current, also measured in Amperes DC (peak AC), is specified as the maximum current allowed when the contacts are already closed. Since the contacts are closed, much higher currents are allowed. No contact damage can occur, since the only time arcing occurs is during the opening and closing transitions. Surprisingly high pulsed currents can be specified over short durations when the contacts are closed. Conversely, unlike electromechanical armature style relays, the Reed Relay can switch or carry currents as low as femptoAmperes (10-15 Amperes).
Switching Voltage, usually specified as a maximum in units of Volts DC or Volts peak, is the maximum allowable voltage capable of being switched across the contacts. Switching voltages above the arcing potential can cause some metal transfer. The arc potential generally occurs over 5 Volts. Arcing is the chief cause of shorted life across the contacts. In the 5 V to 12 V range most contacts are capable of switching well into the tens of millions
Stray Capacitance measured in microFarads or Pico Farads is always present, to some degree, when switching any voltage and current. When switching a given voltage and current, the first 50 nanoSeconds are the most important. This is where the arcing will occur. If there is a significant amount (depending on the amount of voltage switched) of stray capacitance in the switching circuit, a much greater arc may occur, and thereby reducing life.
www.meder.com
34
MEDER electronic
When switching any sizable voltage, it is always a smart idea to place a fast current probe in the circuit to see exactly what one is switching in the first 50 nanoSeconds. Generally speaking, when switching voltages over 50 Volts, 50 picoFarads or more can be very significant to the expected life of the switch.
Common Mode Voltage is also another parameter that can have a significant effect on the life of a Reed Switch. Depending upon the circuit and the environment, common mode voltages can in effect, charge stray capacitances in the switching circuit and dramatically reduce Reed Switch life in an unexpected manner. Again, a fast current probe can reveal a startling voltage and current switched in that first 50 nanoSeconds, having no bearing on ones actual load. When line voltages are present in or near sensitive circuits, be cautious. Those voltages can be coupled into the circuit creating havoc with your life requirements. Typically, a faulty Reed Switch is blamed for this reduced life, when in actuality, it is a product of unforeseen conditions in the circuit.
Insulation Resistance is the measure of isolation across the contacts and is probably one of the most unique parameters that separate Reed Switches from all other switching devices. Typically, Reed Switches have insulation resistances averaging 1 x 1014 ohms. This isolation allows usage in extreme measurement conditions where leakage currents in the picoAmpere or femptoAmpere range would interfere with the measurements being taken. When testing semiconductors, one may have several gates in parallel where the switching devices have combined leakage currents that become significant in the test measurement circuit.
Switching Wattage is the combined voltage and current switched at the time of closure. Sometimes there is confusion with this parameter. For a given switch, with a switching rating of 200 Volts, 0.5 Amperes and 10 Watts, any voltage or current switched, when multiplied together, can not exceed 10 Watts. If you are switching 200 Volts, then you can only switch 50 milliAmperes. If you are switching 0.5 Amperes, then you can only switch 20 Volts. Breakdown Voltage (Dielectric Voltage) generally is higher than the switching voltage. Reed Switches stand off higher voltages because unlike the switching voltages, breaking the arc on opening is not a consideration. On larger evacuated Reed Switches, ratings as high as 15,000 Volts DC are not uncommon. Some smaller evacuated reeds can stand off up to 4000 Volts DC. Small
Dielectric Absorption describes the effect different dielectrics have on very small currents. Currents below 1 nanoAmpere are affected by the dielectrics tendency to slow or delay these currents. Depending upon how low a current one is measuring, these delays can be on the order of several seconds. MEDER engineers have designed Reed Relays and circuits to minimize dielectric absorption. For specific requirements call for applications help.
www.meder.com
Germany # ++49-(0)7733-94870, USA # 800-870-5385
35
MEDER electronic
Operate Time
0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0 0 10 20 30 40 50
Release Time is the time it takes for the contacts to open after the magnetic field is removed. In a relay, when the coil turns off, a large negative inductive pulse (kick) occurs causing the reed blades to open very rapidly. This release time may be in the order of 20 s to 50 s. If a diode is placed across the coil to remove this inductive voltage spike (which can be 100 Volts to 200 Volts), the contact opening time will slow to about 300 s. Some designers require the fast release time, but cannot have the high negative pulses potentially being coupled into sensitive digital circuity. So they add a 12 Volt to 24 Volt zener diode in series with a diode, all of which is in parallel across the coil. Here, when the coil is turned off, the voltage is allowed to go negative by the zener voltage value, which is sufficient to cause the contacts to open generally under 100 s. See Figure #16.
Release Time
(s) ( Release time
15
Pull-in (AT)
10
(Figure #15. A typical graph of the operate time for increasing Pull-in AT values. With higher Pull-in AT the Reed Switch gap increases taking a longer time for the contacts to close.)
0 0 10 20 30 40
Drop-out (AT)
(Figure #16. A graph of the release time for increasing Drop-out AT. With increasing Drop-out AT the restoring force increases causing even faster release time.)
www.meder.com
36
MEDER electronic
Resonant Frequency for a Reed Switch is that physical characteristic where all reed parameters may be affected at the exact resonance point of the Reed Switch. Reed capsules 20 mm long will typically resonate in the 1500 to 2000 Hz range; reed capsules on the order of 10 mm will resonate in the 7000 to 8000 range. Avoiding these specific resonance areas will insure a fault free environment for the Reed Switch. Parameters typically affected are the switching voltage and the breakdown voltage. See Figure #17.
Resonant Frequency
Cumulative frequency percen
0.2
90.1 80.1 70.1 60.1 50.1 40.1 30.1 20.1 10.1 0.1 6500
0.1
0 0 10 20 30 40
Pull-in AT
7000
7500
8000
8500
9000
(Figure #18. As the Pull-in AT increases its gap increases, therefore reducing the capacitance across the Reed Switch.)
(Figure #17. A depiction of a group of 10 mm Reed Switches and its resonant frequency distribution.)
www.meder.com
Germany # ++49-(0)7733-94870, USA # 800-870-5385
37