Measurements Lab Manual
Measurements Lab Manual
PROCEDURE:
STANDARDIZATION:
1. Connections are made as per the Circuit diagram.
2. Keep the function knob of the potentiometer at STD position. Switch ON the RPS(1) and adjust
to 2 volts.
3. Adjust the slide contact and slide wire of the potentiometer to read standard cell voltage (1.08V).
4. Press the galvano key on the potentiometer and adjust the coarse and fine rheostat until the spot
reflecting galvanometer gives null deflection. This completes standardization of
galvanometer.Once standardization is done the position of R1 & R2 should not be changed
PMMC AMMETER:
1 Ammeter to be calibrated is connected in series with variable resistor R & standard resistance S
2 The standard resistance should of such a magnitude that current passed through it doesnt exceed
range of potentiometer
3 V.R box is used in parallel to potentiometer to reduce voltage to the range of potentiometer
4. Keep the rheostat at maximum position and change the function knob to E1 position. Switch on
RPS(2) and apply 30 volts.
5 Vary the rheostat gradually and adjust suitable current.
6. Press the galvano key on the potentiometer and adjust the slide contact and slide wire until the
spot reflecting galvanometer gives the null deflection.
7. Note down the readings of ammeter, voltmeter, and potentiometer slide contact and slide wire
readings.
8. Repeat the steps 5 to7 for different values of current.
9 Vary the rheostat to maximum position, reduce the voltage of RPS and RPS to zero. Switch off the
supply.
10 Draw the graph between Load current (vs) % Error.
TABULAR FORM:
FOR VOLTMETER:
S.No Voltmeter
reading(V) , Vtrue
E2 value(V) Vact=(R1+R2/R2)
*E2
%error
100
V
V V
true
true act
FOR AMMETER:
S.No Ammeter
reading(A)
E2 value(V) Iact=E/R %error
Itrue
100
I
I I
true
true act
CALCULATION :
CALIBRATION OF AMMETER:
Iact = Ammeter reading
Itrue =
ce resis dard S
box ratio volt of Ratio volt Fine volt Coarse
tan tan
) ( +
% error =
100
I
I I
true
true act
PRECAUTIONS :
1. Connect the circuit without loose connections.
2. Dont vary the coarse and fine pots, after standardization.
3. After connecting the unknown voltage, Dont press the final button of Galvanometer directly.
4. Operate the selector switch (P1) ad, slide wire (P2) very smoothly.
5. Take care about current rating which choosing the standard rheostat in calibration of ammeter
experiment.
6. Connect the unknown voltage directly to the test terminals, if it has less than 1.5V.
7. Since DC Crompton potentiometer measures upto1.86V adjust the voltage at E2 should not exceed
this value while doing the experiment.
RESULT :
The calibration of PMMC Voltmeter and Ammeter is done using Crompton DC potentiometer. The
calibration curves for voltmeter and ammeter are drawn.
QUESTIONS:
1. What do you mean by a potentiometer?
2. What are the types of potentiometer?
3. What is the working principle of a potentiometer?
4. What is standardization of potentiometer?
5. What is the purpose of connecting a standard battery in the circuit?
6. Application of dc potentiometer?
7. What do you mean by calibration curve of the ammeter?
8. What do you mean by a volt-ratio box?
9. What are the types of AC potentiometer?
10. What are the practical applications of ac potentiometer?
Calibration of PMMC Ammeter & Voltmeter using cromptons DC potentio meter:
Calibration of Voltmeter:
%Error= (Vact-Vtrue) / Vact *100
Vact =R1+R2 / R2 *E2
Vtrue = Voltmeter reading (v)
Vact = (1+2 / 2) * 5
=7.5V
Vtrue=0.25+51mv
=0.301V
% Error=(7.5-0.301/0.301 ) *100
=23.9%
Calibration of Ammeter:
%Error= (Iact-Itrue) / Iact *100
Iact =E/R
Itrue = Ammeter reading (A)
Iact = E/R=5/2
=2.5A
Itrue= 0.1 amps
% Error=(2.5-0.1/0.1 ) *100
=24%
EXPERIMENT NO.4
KELVINS DOUBLE BRIDGE
AIM :
To determine the low resistance by setting up Kelvins double bridge.
APPARATUS REQUIRED :
Sl. NO. NAME TYPE RANGE QTY.
1 Kelvins double bridge kit 1 no
2. Galvanometer 1 no.
3. Rheostat. 5A,50 OHM 1 no.
4. DMM DIGITAL 1 no.
5. Patch cards/ Connecting wires 1set.
6 RPS DC 2V 1 no
CIRCUIT DIAGRAM:
THEORY :
X is the unknown resistance to be measured.
S is the standard resistance.
The ratio of Q/q must be equal to M/m under balance conditions; there is no current through
galvanometer G. The first of ratio arms is Q and M. The second set of ratio arms of m is used to connect the
galvanometer to a point at the appropriate potential b/w point e and f to eliminate the effect of connecting
lead of resistance r between then the unknown resistance X and standard resistance S.
If
S
M
Q
thenX ,
m
M
p
Q
PROCEDURE :
1. Short the terminals which are marked +c,-c & +p , -p.
2. Calibrate the Kelvins double bridge by turning the zero adjusting knob until galvanometer
indicates zero.
3. During calibration remaining knobs should be kept at zero position.
4. Now short terminals +p,+c and p,-c. connect unknown specimen resistance between +p and p
terminals.
5. Now adjust the main dial ,slide wire and multiplier until the galvanometer indicates zero position.
6. Note down the readings of main dial slide wire and multiplier.
OBSERVATIONS :
S.No. Specimen type (OR) standard
or known
un Resistance or practical
1.
2.
3.
4.
SAMPLE CALCULATIONS :
Unknown resistance = multiplier *(main dial reading + slide wire reading)
PRECAUTIONS :
1. Galvanometer should always be connected to protective resistance to prevent damage to
galvanometer.
2. Changes in Q and q should be made immediately to bring the pointer of galvanometer back to
within scale to prevent damage.
3. Resistance r should be in the maximum position to start with and adjusted later if necessary to get
large deflection.
RESULT :
The unknown resistances of earth wires, having different parameters, are measured by using Kelvins
double bridge.
QUESTIONS:
1. Classify resistance?
2. Examples of high resistance?
3. What are the methods employed in measuring low resistances?
4. Which is the most accurate method to measure the low resistances? State the reason?
5. Kelvin double bridge is a modified version of ?
6. What is the main problem in measuring low resistances?
7. How do we measure high resistances?
8. Practical methods to measure earth resistance?
9. What are the quantities that are measured by ac bridges?
KELVINS DOUBLE BRIDGE CALCULATIONS:
Unknown resistance = multiplier * (main dial reading + slide wire reading)
Unknown resistance = 100 *(0.1+ (15*0.01))
= 11.5
Known resistance = 14
Tolerance = Known resistance - Unknown resistance
= 14 - 11.5
Tolerance = 2.5
EXPERIMENT NO. 5
CT TESTING BY SILSBEES METHOD
AIM:
To measure the % ratio error and phase angle error of given CT by Silsbees method.
APPARATUS:
SL.
NO.
NAME TYPE RANGE QUANTITY
1. CT Precision (Standard) 5/5 1 no.
2. CT Commercial 5/5 1 no.
3. Voltmeter MI 300 V 1 no.s
4. Ammeter MI 10A 2 no.
5. Wattmeter Electrodynamometer
Type LPF
10A, 600V 2no.
6 Connecting wires 1 set
7 Rheostat 50 Ohms, 5A
8 Loading Burden Rheostat 50 Ohms, 5A 1 no
9 Phase-shifting transformer 3 Ohms, 420V, 10A 1 no
10 Single Phase supply AC 230V, 10A 1no.
CIRCUIT DIAGRAM:
THEORY :
Methods of experiment testing instrument transformers i.e., finding their ratio and phase angle errors may
be broadly classified into two groups. Absolute methods and comparison methods each of these test
methods can be classified according to measurement technique employed as Deflecting methods and Null-
methods.
Silsbees method is a comparison method. There are two types of Silsbees methods deflectional
and here the ratio and phase angle of the test transformer are determined, in term of a standard transformers
having the same nominal ratio.
The two transformers are connected with their primaries in series. An adjustable burden is put in
the secondary circuit of the transformers under test. An ammeter is included in the secondary circuit of the
standard transformers so that the current may be set to the desired value. W1 is a wattmeter whose current
coil is connected to carry the secondary current of the standard transformers. The current coil of wattmeter
W2 carries a current which is the difference between the secondary currents of the standard and test
transformers. The voltage circuits of the wattmeters lies their pressure coils are supplied in parallel from a
phase shifting transformer at a constant voltage V.
PROCEDURE:
1. Connections are made as per circuit diagram.
2. Switch on the supply and by using single phase variac and rheostat adjust primary
current to some value say 3 A.
3. By varying the phase shifting transformer the phase of the voltage is so adjusted that wattmeter
W1 reads maximum value (Phase condition).
4. Now note down the readings of all meters. The readings of wattmeter in phase condition are taken
as W1p and W2p
5. Again vary the phase shifting transformer so that the wattmeter W1 reads zero value (90 phase
shift Quadrature condition).
6. At this instant also note down all the meter readings and the wattmeter readings are taken as W1q
and W2q.
7. % Ratio error and phase angle error are calculated by using the formulae given below.
TABULATION:
S.No. Ammeter
Reading
I1(Amps)
Ammeter
Reading
I2(Amps)
W1p
(Watts)
W2p
(Watts)
W1q
(Watts)
W2q
(Watts)
Rs =I1/I2
% Ratio error (Rx) = Rs {(W2p / W1p) +1}
Phase angle error (x) = W2q/ (W1p W2p) + s
FORMULAE USED :
Nominal ratio of standard CT = 10/5 = 2
Phase angle error of standard CT = 5
+
ss
s x
I V
W
R R
1
0
1
% ratio error =
x
s
R
R R
Phase angle error for CT under test
1
1
]
1
,
_
1
1
]
1
180
2
0
ss
s x
I V
W
PRECAUTIONS :
1. Take care, while varying the phase angle with phase shifting transformer.
2 Avoid lose connections.
3 Meter readings should not exceed their ratings.
4. Take readings without error.
5 Keep variac at their minimum position initially
6 Vary the variac such that the current and voltage are within the rated value
7 Live terminals should not be touched.
8 If any wattmeter reads, reading, change either current coil or pressure coil connections.
9 Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
10 Load current should not exceed rated current value.
11 Load should be varied very smoothly.
RESULT :
The current transformer is tested by using Silsbees method and, the ratio and phase angle errors are
calculated.
QUESTIONS:
1 How types of Silsbees methods ? And what are those ?
2 Silsbees methods----------- method
3 What is Burden of transformer?
4 Define (C.T&P.T) A. Transformation ratio
B. Turns ratio
C .Nominal ratio
D .RCF
5 Comparison between C.T & P.T
EXPERIMENT NO.6
A. MEASUREMENT OF CAPACITANCE BY SCHERING BRIDGE
AIM : To find the capacitance of unknown capacitor using Schering bridge.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1 Schering bridge circuit 1 no
2. Head phones 1 no.
3. Decade capacitance box 1 no.
4. DMM digital 1 no.
5. Patch cards 1set
6 RPS 230v 1 no
7 Galvanometer 1 no
CIRCUIT DIAGRAM:
THEORY:
The Schering bridge is very widely used for the measurement of capacitance, dielectric loss and power
factor of capacitors. The advantage of using this bridge is that it can be employed in both low voltage and
high voltage measurements.
From the circuit :
C1 is the unknown capacitance and
R1 is a resistance representing its loss component
C2 is a standard air capacitor and it is loss free
R3 & R4 are non-inductive standard resistors.
R3 is fixed and R4 is variable
C4 is a variable capacitors.
The detector may be a head phone or vibration galvanometer
E is a low voltage a.c. source r 230v,50hz,supply
The bridge is balanced by adjusting
C4 and R4
At balance, we have V1 = V2 & V3 = V4
4 2 4 3 1 3
2 1
1 1
& ,
1
1 2 ,
1
Z I V R I V
jwc
V
jwc
r V
1
]
1
1
]
1
+
Where Z4 =
1 4 4
4
4
1
4
4
1
4
+
+
1
]
1
C jwR
R
jwc
R
jwc
R
Or V4 =
4 4
4 2
1
1
C jwR
R
+
11
,
_
1
]
1
+
2
2
1
1
1 1
jwc
I
jwc
r
. (1) and
I1R3 =
4 4
4 2
1 C jwR
R I
+
.. (2)
From (1) & (2)
3
1
1
1
R
jwC
r +
=
) )( (
1
4 2
4 4
R jwc
C jwR +
or
,
_
,
_
+
4 4
4
1
1
1
R jwC
R
jwg
r
= R3
1
]
1
2
1
jwc
Simplifying, r1R4 -
1
4
wC
jR
=
2
4 4 3
C
C R R
-
2
3
wC
R
j
Equating real and imaginary parts
Separately, we get :
r1R4=
2
4 4 3
C
C R R
& C1= Cx =(R4/R3) x C2
NOTE: C1 =Cx1= Cx2=
C2=Cs1=Cs2=.
PROCEDURE :
1. Connections are made as per the circuit diagram.
2. Connect the unknown capacitance Cx between the terminals A & D.
3. Switch on the supply and vary the Resistance knob (R1) until minimum sound is obtained from the
loud speaker.
4. Switch off the supply and measure the Resistance (R1) between C & B by using DMM.
5. Repeat the above steps for different values of capacitance & tabulate the readings.
6. Switch off the supply.
PRECAUTIONS :
1. Avoid loose connections.
2. Resistance should be varied very smoothly.
3. Switch off the supply when the resistance R1 is measured.
FORMULA USED:
r1R4=
2
4 4 3
C
C R R
& C1= Cx =(R4/R3) x C2
NOTE: the value of unknown capacitors is
C = 0.01F
0.02 F
0.03 F
0.04 f
s.no Cs (known
capacitance)
R4 R3 Cx=CsR4/R3
QUESTIONS:
1. What do you mean by high voltage Schering Bridge?
2. State some of the errors that occur in bridge measurements?
3. Anderson Bridge is a modified version of __________
4. In Anderson Bridge the self inductance is measured in comparison with ___________
5. What are the resistors need to be adjusted to get the balance
6. At what condition the galvanometer detector will be replaced by the head phone.
7. Schering bridge is used for the measurement of ______________
8. What is meant by loss angle ?
9. Why we are doing electrostatic shielding for high voltage Schering bridge?
10. What are the elements need to be adjusted to obtain balance in Schering bridge?
RESULT : the value of unknown capacitance is calculated by using Schering bridge
. MEASUREMENT OF CAPACITANCE BY SCHERING BRIDGE
Schering Bridge
At balance condition V
1
=V
2
& V
3
=V
4
Here V
1
= (r
1
+ (1/jC
1
))
V
2
= (1/jC
2
)
V
3
= I
1
R
3
V
4
= I
2
Z
4
Where Z
4
= (R4 (1/jC
4
))/ (R
4
+ (1/jC
4
)) = (R
4
/ jR
4
C
4
)
Therefore V
4
= (I
2
R
4
)
/( jR
4
C
4
)
At balance V
1
=V
2
i.e., (r
1
+ (1/jC
1
)) = (1/jC
2
) (1)
V
3
= V
4
i.e., I
1
R
3
= (I
2
R
4
)
/( jR
4
C
4
)..(2)
From equation (1) & (2)
V
1
/V
3
= V
2
/V
4
(r
1
+ (1/jC
1
))/ (R
4
/ jR
4
C
4
) = (R
3
/ jC
2
)
By equating real & imaginary parts we get,
r
1
R
4
= (R
3
R
4
C
4
)/ C
2
and C
1
= C
x
= (R
4
C
2
)/ R
3
Calculation:
By taking C
2
value as 0.1f
We get R
4
= 10.3 k
R
3
= 560m
C
x
= (R
4
C
2
)/ R
3
Then, C
x
= (10.3 k*0.1f)/ 560m
= 1.83pf
B. MEASUREMENT OF INDUCTANCE BY ANDERSONS BRIDGE
AIM : To find the unknown inductance of a coil or inductor using Andersons bridge.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1 Andersons bridge circuit 1 no
2. Head phones 1 no.
3. Decade inductance box 1 no.
4. DMM DIGITAL 1 no.
5. Patch cards 1set
6 RPS 230 1 no
7 Galvanometer 1 no
CIRCUIT DIAGRAM:
THEORY :
Andersons bridge is a modification of the Maxwells inductance capacitance bridge. In this method, the
self-inductance is measured in terms of a standard capacitor. This method is applicable for precise
measurement of self-inductance over a very wide range of values.
Figure shows the connections and the phasor diagram of the bridge for balanced conditions:
Let L1 = Self-inductance to be measure
R1 = resistance of self-inductor,
r1 = resistance connected in series with self-inductor,
r, R2, R3, R4 = known non-inductive resistances, and
C = fixed standard capacitor.
At balance, I1 = I3 and I2 = Ic + I4
Now I1R3 = Lc x
C j
1
Ic = I1jCR3.
Writing the other balance equations
I1 (r1+R1+jL1) = I2 R2 + Icr and Ic
,
_
+
C j
r
1
= (I2 Ic) R4.
Substituting the value of Ic in the above equations, we have
I1(r1+R1+jL1) = I2R2+I1jC R3r
Or
I1(r+R1+jL1-jCR3r) = I2R2 (i)
and
jCR3 I1
,
_
+
C j
r
1
= (I2 IjCR3)R4 or I1(jCR3r + jCR3R4 +R3) = I2R4 (ii)
From Eqns. (i) and (ii), we obtain
I1 (r1 + R1 + jl1 jCR3r) = I1
,
_
+ +
2 3
4
3 2
4
3 2
R CR j
R
r R CR j
R
R R
and L1 = C
4
3
R
R
[r(R4 + R2) + R2R4]
An examination of balance equations reveals that to obtain easy convergence of balance, alternate
adjustments of r1 and should be done as they appear in only one of the two balance equations.
ADVANTAGES:
1. In case adjustments are carried out by manipulating control over r1 and r, they become independent of
each other. This is a marked superiority over sliding balance conditions met with low Q coils when
measuring axwells bridge. A study of convergence conditions would reveal that it is much easier to
obtain balance in the case of Andersons bridge than in Maxwells bridge for low Q-coils.
2. A fixed capacitor can be used instead of a variable capacitor as in the case of Maxwells bridge.
3. This bridge may be used for accurate determination of capacitance in terms of inductance.
DISADVANTAGES:
1. The Andersons bridge is more complex than its prototype Maxwells bridge. The Andersons bridge
has more parts and is more complicated to set up and manipulate. The balance equations are not simple
and in fact are much more tedious.
2. An additional junction point increases the difficulty of shielding the bridge.
Considering the above complications of the Andersons bridge, in all the cases where a variable capacitor is
permissible the more simple Maxwells bridge is used instead of Andersons bridge.
PROCEDURE :
1. Connections are made as per the circuit diagram with an audio oscillator and head phones
connected to proper terminals of the Andersons bridge.
2. Connect the unknown inductor L as shown in the circuit diagram.
3. Switch on the supply and select a certain value of C say 0.01 F.
4. Adjust R1and r1alternately till the head phones give minimum or no sound.
5. Note down the values of S, M and C at this balanced condition.
6. Repeat steps (4) and (5) for the same inductance by selecting different value of C.
7. Repeat the above steps for different values of unknown inductance.
8. Switch off the supply.
NOTE :
1. The value of C is so chosen that there is sufficient adjustment available in the value of M.
2. When C is small, M will be large.
3. The bridge is useful for measuring small values of inductor such as 50, 100, 150 and 200 mH.
Note the value of unknown inductances
1. 10mH
2. 100mH
CALCULATION :
L value is calculated by the given formula.
L1 = C
4
3
R
R
[r1(R4+ R2) + R2R4]
R1 =
1
4
3 2
r
R
R R
S.NO C(KNOWM
CAPACITANCE)
r1 R1 R2 R3 R4 L1
RESULT :
The value of unknown inductance is calculated by using Anderson Bridge
QUESTIONS:
1. What do you mean by high voltage Schering Bridge?
2. State some of the errors that occur in bridge measurements?
3. Anderson Bridge is a modified version of __________
4. In Anderson Bridge the self inductance is measured in comparison with ___________
5. What are the resistors need to be adjusted to get the balance
6. At what condition the galvanometer detector will be replaced by the head phone.
7. Schering bridge is used for the measurement of ______________
8. What is meant by loss angle ?
9. Why we are doing electrostatic shielding for high voltage Schering bridge?
10. What are the elements need to be adjusted to obtain balance in Schering bridge?
B. MEASUREMENT OF INDUCTANCE BY ANDERSONS BRIDGE
ANDERSONS BRIDGE
At balance condition I
1
=I
3
I
2
= I
C
+I
4
Here I
C
= I
1
jR
3
C
From the circuit balance equations are
I
1
(r
1
+ R
1
+jL
1
) = I
2
R
3
+ I
C
r
I
C
(r+ (1/jC)) = (I
2
- I
C
) R
4
By substituting of the value of I
C
in the above equation we get,
I
1
(r
1
+ R
1
+jL
1
- jCR
3
r) = I
2
R
2
......... (1)
I
1
(jCR
3
r+ jCR
3
R
4
+ R
3
) = I
2
R
4
.........(2)
From equation (1) & (2)
I
1
(r
1
+ R
1
+jL
1
- jCR
3
r) = I
1
((R
3
R
2
/R
4
)+( jCR
3
R
2
r /R
4
)+ jCR
3
R
2
)
By equating real & imaginary parts we get,
R
1
=
1
4
3 2
r
R
R R
and L
1
= C
4
3
R
R
[r1(R4+ R
2
) + R
2
R
4
]
Calculation:
In Andersons Bridge we have to calculate the unknown inductance value by using the
formula
L
1
=C
4
3
R
R
[r
1
(R
4
+ R
2
) + R
2
R
4
]
By taking C value as 0.02f
We get R
2
= 0.13 k
R
3
= 0.06 k
R
4
= 0.11 k
r
1
= 0.2 k
By using the above formula we get the value of inductance
i.e., L
1
= (0.02f *(0.2 k (0.11 k+0.13 k) + 0.13 k * 0.11 k))/ 0.11 k
= 0.56mh
EXPERIMENT NO.7
MEASUREMENT OF 3-PHASE REACTIVE POWER WITH SINGLE PHASE WATTMETER
AIM : To measure the 3-Phase reactive power using single wattmeter.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1. Wattmeter Dynamometer type, LPF 10A, 300V 1 no.
2. Voltmeter MI 300 V 1 no.
3. Ammeter MI 10A 1 no.
4. 3 Phase variable inductive load 0-10A, 230 V, 6-steps
50, 15A
1no.
5 Three Phase Variac 415/0-470V, 15A 1 no
6 Connecting wires 1 set
CIRCUIT DIAGRAM:
THEORY :
The basic principle used for measuring active as well as reactive power in an a.c. circuit is the
Blondels theorem.
If a network is supplied through n conductors, the total power is measured by summing the
readings of n wattmeters is in each line and the corresponding voltage element is connected between the
line and a common point.
If the common point is located on one of the lines, then the power may be measured by (n-1)
wattmeters.
One wattmeter method can be used for the measurement of power but this method is applicable
only for balanced loads the current coil is connected in one of the lines and one end of the pressure coil to
some line, other end being connected alternatively to other two lines.
In case of balanced three phase circuits it is simple to use a single wattmeter to read reactive
power the current coil of the wattmeter is connected in one line and pressure coil is connected across other
two lines.
Reading of wattmeter = ) 90 cos(
2 13
+ I V
= ) 90 cos( 3 + VI
=
sin VI 3
Q = 3 VI sin = ( ) 3 x reading of wattmeter.
Phase angle =
,
_
P
Q
1
tan
.
PROCEDURE :
1. Connections are made as per the circuit diagram.
2. Keep the 3-Phase variac to minimum or zero output position. Close the TPST switch and
gradually vary the variac until the rated voltage of 415V is applied.
3. Note down the readings of all the indicating instruments at no-load position.
4. Apply the load in steps by varying the 3-phase inductive load upto the rated current (10Amps) and
notedown the readings of instruments in each step.
5. Vary the load gradually to no-load position, vary the 3-phase variac to minimum or zero output
position and open the TPST switch.
6. Calculate the three phase reactive power.
TABULAR FORM:
S.N
o.
Voltmeter
reading
V(volts)
Ammeter
reading
I(Amps)
Wattmeter
reading W
(watts)
Three phase reactive power
Q= 3 *W
(VAR)
sin= Q/ 3 VI
PRECAUTIONS :
1. Keep the 3-phase variac in zero position initially.
2. Keep inductive load at no-load position initially.
3. Live terminals should not be touched.
4. Connect the circuit without any loose connection.
5. If any wattmeter reads, reading, change either current coil or pressure coil connections.
6. Take all meter readings without parallel error.
7. Load current should not exceed rated current value.
8 Vary the variac such that the current and voltage are within the rated value
9. Meter readings should not exceed their ratings.
10 Load should be varied very smoothly.
11 Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
RESULT : Reactive power absorbed by the inductive load is calculated & tabulated for various loading
conditions.
QUESTIONS:
1. How do you measure power ?
2. State the difference between wattmeter and an energy meter?
3. Types of wattmeters?
4. Which types of wattmeter is widely used?
5. How is the controlling torque obtained?
6. What are the errors in dynamometer type wattmeters? State a few.
7. How many wattmeters do we require to measure 3-phase power?
8. What is reactive power ? State the formula.
9. How many wattmeters are required to measure 3-phase reactive power?
10. How do we minimize the errors due to eddy currents in wattmeters?
Measurement of 3-phase reactive power with single phase wattmeter calculations:
When the load is balanced,
Total power is P = 3*(Wattmeter reading)
i.e., P = 3*Vph*Iph cos
Hence one wattmeter issued to measure the single phase power & then it is to be multiplied
by 3
Q = 3VIsin
Q = 3 *(Wattmeter reading)
Calculation:
Take the voltage, ammeter reading and wattmeter reading from the circuit
V = 300 v
I = 2 amp
W = 480 watts
Then 3- reactive power is
Q = 3 *W VAR
i.e., Q = 3 * 480 = 831.2 VAR
and sin = /( 3VI )
i.e., sin = 831.2/ ( 3*300*2) = 0.799
EXPERIMENT NO.8
MEASUREMENT OF PARAMETERS OF CHOKE COIL USING 3VOLTMETERS &
3AMMETERS METHOD
AIM : To obtain the parameters (R, X, L,Z, power and PF)of given choke coil using 3 Voltmeter and 3
Ammeter methods.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1. Choke coil 230 V, 10 A 1 no.
2. .Regulated D.C
Power supply
(0-30V) 1 no.
3. Voltmeter MI 300 V 3 no.
4. Ammeter MI 10A 4 no.
5. Rheostat 50, 15A 1no.
6 Single Phase Variac AC 0-270V, 10A 1 no
7 Connecting wires 1 set
CIRCUIT DIAGRAM:
THEORY :
An inductive transducer works on the principle of variation of inductance using multiple coils.
The coils that are being used need to be evaluated and their parameters so defined such that the use of their
parameters may be regarded as constant and accurate.
Thus emphasis need to be laid upon the method of measurement of inductance of choke coil by using 3
voltmeter meter method and 3 ammeter method.
For 3-Voltmeter method:
cos 2
3 2
2
3
2
2
2
1
V V V V V +
cos =
) 2 (
3 2
2
3
2
2
2
1
V V
V V V
, but cos =
2 / 1 2 2
] ) 2 ( [ fL r
r
+
[ ]
2 / 1
2 2
3 2
2
3
2
2
2
1
) 2 (
) 2 (
fL r
r
V V
V V V
+
( )
2
2
3
2
2
2
1
2
3
2
2 2 2 2
V V V
V V 4
r ) fL 2 ( r
+
( )
2
2
2
3
2
2
2
1
2 2
3
2
2 2
4
) 2 ( r
V V V
r V V
fL
L
( )
2
2
2
3
2
2
2
1
2 2
3
2
2
r
V V V
r V V 4
f 2
1
;
[ ]
2 / 1
2 2
) 2 ( fL r
r
+
[ ]
2 / 1
2 2
3 2
2
3
2
2
2
1
) 2 (
2
fL r
r
I I
I I I
+
( )
2
2
2
3
2
2
2
1
2
3
2
2
2
4
2
1
r
I I I
I I r
f
L
Hence by using the above formulae we can calculate the inductance of a choke coil.
PROCEDURE :
3 Voltmeter method
1. Connections are made as per the circuit diagram.
2. Keep the variac in minimum position and close the DPST switch.
3. Vary the variac gradually in steps up to rated current capacity of conductor that used for coil or up
to voltage less than rated voltage indicated by voltmeter1
4. Note down the readings of meters in each step. Tabulate the readings as per tabular form1
5. Gradually vary the variac to minimum position and open the DPST switch.
6 Now calculate the parameters of the choke coil.
3 Ammeter method
1. Connections are made as per the circuit diagram.
2. Keep the variac in minimum position and close the DPST switch.
3. Vary the variac gradually in steps upto the rated voltage (230V).OR Apply current less than
(500mA) indicated by ammeter 2
4. Note down the readings of 3 Ammeters in each step. Tabulate the readings as per tabular form 2
5. Gradually change the variac to minimum position and open the DPST switch.
6. Now calculate the parameters of the choke coil.
MEASUREMENTS OF RESISTANCE OF CHOKE COIL:
1. Make the connection as per the circuit diagram.
2. Keep the variac in minimum position and close the DPST switch.
3. Vary the variac gradually in steps say 10V,15V and 20V
4 Note down the ammeter readings . Tabulate the readings as per tabular form 3
5 Calculate resistance values R10v, R15v, R20v and take average of 3 resistance values as resistance
of choke coil.
TABLE 1
S.NO V1 V2 V3 IL P coso ZL RL XL L
TABLE 2
S.NO V I1 I2 I3 P COSO ZL RL XL L
PRECAUTIONS :
1 Measure the exact magnitude of external rheostat.
2 Avoid lose connections.
3 Take readings without parllox error.
4 Keep variac at their minimum position initially
5 Vary the variac such that the current and voltage are within the rated value
6 Meter readings should not exceed their ratings.
7 Live terminals should not be touched.
8 If any wattmeter reads zero (or negative) reading, change either current coil or pressure coil
connections.
9 Load current should not exceed rated current value.
10 Load should be varied very smoothly.
11 Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
RESULT :
The experiment is conducted by 3-voltmeter and 3-ammeter methods and inductance of the given choke
coil is calculated
QUESTIONS:
1. What are the choke coil parameters?
2. What is the function of choke?
3. What are the methods are there to find choke coil parameters?
4. What are the methods are there to find choke coil parameters?
5. Which method is very important for finding the choke coil parameters?
Measurement Of Parameters Of Choke Coil Using 3voltmeters & 3ammeters Method
calculations:
For 3-ph Voltmeter method
V
1
2
= V
2
2
+V
3
2
- 2 V
2
V
3
cos
Cos = (V
1
2
= V
2
2
+V
3
2
)/(- 2 V
2
V
3
)
But Cos = r/(r
2
+(2fL)
2
)
1/2
So that (V
1
2
-V
2
2
-V
3
2
)/ (- 2 V
2
V
3
) = r/(r
2
+(2fL)
2
)
1/2
By solving we get L = (1/2f) * ((4 V
2
2
V
3
2
r
2
)/ (V
1
2
-V
2
2
-V
3
2
)) - r
2
Calculation:
At on load
i.e., I
L
= 1 amp
V
2
= 100 v
V
3
= 106 v
P = 230 watts
Cos = 0.9
Therefore V
1
2
= V
2
2
+V
3
2
- 2 V
2
V
3
cos = 220 v
L = (1/2f) * ((4 V
2
2
V
3
2
r
2
)/ (V
1
2
-V
2
2
-V
3
2
)) - r
2
Here f = 50Hz
L =(1/2f) * ((4 I
2
2
I
3
2
r
2
)/ (I
1
2
-I
2
2
-I
3
2
)) - r
2
EXPERIMENT NO.9
CALIBRATION OF LPF WATTMETER BY PHANTOM LOADING
AIM : Testing and Calibration of the given LPF wattmeter by using a sub-standard Wattmeter by phantom
loading method.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1 Wattmeter(Testing or standard) Dynamometer type, LPF 10A, 300V 1 no
2. Wattmeter(Sub-standard or calibrated) Dynamometer type, UPF 10A, 300V 1 no.
3. Voltmeter MI 300 V 1 no.
4. Ammeter MI 10A 1 no.
5. Rheostat 350, 1.2A 1no.
6 Single Phase Variac 0-270V, 10A 1 no
7 Connecting wires 1 set
CIRCUIT DIAGRAM:
THEORY :
Electrodynamometer type wattmeter has two coils connected in different circuits for measurement
of power. The fixed coils or field coils are connected in series with the load and so carry the current in
the circuit. The fixed coils, therefore, form the current coil or simply C.C of the wattmeter. The
moving coil is connected across the voltage and, therefore, carries a current proportional to the voltage. A
high non-inductive resistance is connected in series with the moving coil to limit the current to a small
value. Since the moving coil carries a current proportional to the voltage, it is called the pressure coil or
voltage coil or simply called P.C. of the wattmeter.
Both fixed and moving coils are air cored. The voltage rating of the wattmeter is limited to about 600 V by
the power requirements of the voltage circuit since most of the power is absorbed by the resistance in series
with the moving coil and considerable heat is generated. For higher voltages, the pressure coil circuit is
designed for 110V, and a potential transformer is used to step down the voltage.
If V= Voltage across the pressure coil,
I = Current through the current coil and
= Angle between V& I, then
P = Power being measured = VI cos
The deflection is directly proportional to the power being measured and the scale is essentially uniform
over the range in which (dM/d ) is constant. By suitable design, the mutual inductance between fixed
and moving coil and be made to vary linearly with angle over a range of 40
o
to 50
o
on either side of zero
mutual inductance position.
On lagging loads the wattmeter will read high, as the effect of the inductance of the pressure coil circuit is
to bring the pressure coil current more nearly into phase with the load current than would be the case if this
inductance were zero. Very serious errors may be introduced by pressure coil inductance at low power
factors unless special precautions are taken.
Many wattmeters are compensated for errors caused by inductance of pressure coil by means of a capacitor
connected in parallel with a portion of multiplier (series resistance).
Measurement of power in circuits having low power factor by ordinary electrodynamometer wattmeter is
difficult and inaccurate because:
i) The deflecting torque on the moving system is small (owing to low power factor) even when
the current and pressure coils are flly excited;
ii) Errors introduced because of inductance of pressure coil tend to be large at low power factors.
Special features are incorporated in an electrodynamometer wattmeter to make it a low power factor type of
wattmeter. These features are discussed in details below:
1. Pressure Coil Current. The pressure coil circuit is designed to have a low value of resistance,
so that the current, flowing through it, is increased to give an increased operating torque. The pressure coil
current in a low power factor wattmeter may be as much as 10 times the value employed for high power
factor wattmeter.
2. Compensation for Pressure coil Current. The power being measured in a low power factor
circuit is small and current is high on account of low power factor. It is absolutely necessary to compensate
for the pressure coil current in low power factor wattmeter.
When the current rating of meter under test is high a test with actual loading arrangements would involve a
considerable waste of power. In order to avoid this Phantom loading as Fictitious loading is done. Phantom
loading consists of supplying the pressure coil from a circuit of required normal voltage and the current coil
from a separate low voltage supply. It is possible to circulate the rated current through the current coil with
a low voltage supply as the impedance of this circuit is very low, with this arrangement. The total power
supplied for the test is that due to the small pressure coil current at normal voltage, plus that due to the
current circuit current applied at low voltage. The total power therefore, required for testing the meter with
phantom loading is comparatively small.
PROCEDURE :
1. Connections are made as per the circuit diagram.
2. With variac I and II in minimum position and the rheostat in minimum position, close the
DPST-I switch to connect the supply-I.
3. Vary the variac-I gradually to apply the rated voltage (230V). to pressure coils of both p.f meter
and wattmeter
4 Close the DPST-II switch and vary the variac-II to adjust a suitable current of (1A or 2A) in the
current coils of LPF wattmeter and p.f meter. as indicated by ammeter. Note down the readings
of all the instruments
5 Now vary the current (upto 4A) in current coils of both wattmeter and p.f meter in steps using
single phase variac & rheostat and note down readings for each step. Tabulate the readings.
6 Bring the rheostat to minimum position, vary the variac-II and variac-I to minimum position and
open the DPST switches.
7. Evaluate True power (S1) , Actual power (S2) , %error, %correction.
8. Draw the graph between Load current (vs) % Error.
TABULAR FORM:
S.No Voltmeter
Reading
V (volts)
Ammeter
Reading,
I (Amps)
P.F
meter
reading
Wattmeter
Reading(S2)
(Watts)
True power (S1)
VIcos(Watts)
% error
(S1-S2)/S1
%Correction
(S2-S1)/S1
MODEL CALCULATIONS:
True power (S1) = V * I *cos
Actual power (S2) = Wattmeter reading.lpf
% error = [(S1- S2) / S1] * 100
%correction = [(S2 S1) /S1] * 100
MODEL GRAPH :
%error
Load current
PRECAUTIONS:
1. Avoid lose connections.
2. Take readings without parllox error.
3 Keep variac at their minimum position initially
4 Vary the variac such that the current and voltage are within the rated value
5 Meter readings should not exceed their ratings.
6 Live terminals should not be touched.
7 If any wattmeter reads, reading, change either current coil or pressure coil connections.
9 Load current should not exceed rated current value.
10 Load should be varied very smoothly.
11 Keep rheostat at its minimum resistance position initially.
12 Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
RESULT: The LPF wattmeter is calibrated using phantom loading and calibration curve is plotted
for the given wattmeter
QUESTIONS:
1. What is meant by correction factor ?
2. The load current in LPF wattmeter is high / low ?
3. Why are the LPF wattmeter designed to have a smaller controlling torque ?
4. What is the need of introducing compensating coil?
5. State a few errors in dynamometer wattmeter?
6. Applications of LPF wattmeter?
7. Why more operating torque is produced in LPF wattmeter?
8. Why the controlling torque in an LPF wattmeter is less?
9. What are the different methods used for measurement for 3-phase power?
10. Explain the working principle of induction wattmeter?
.
Calibration Of Lpf Wattmeter By Phantom Loading
Calculations:
True power S1 = VICos
Actual power S2 = wattmeter reading LPF
% error = ((S1-S2)/S1)*100
%correction = ((S2-S1)/S1)*100
By taking values
V = 230 v
I = 1 amp
S1 = 230 * 1* 0.95 =218.5 watts
S2 = 90 watts
% error = ((S1-S2)/S1)*100 = 58.81%
%correction = ((S2-S1)/S1)*100 = -58.81%
EXPERIMENT NO.10
MEASUREMENT OF 3-PHASE ACTIVE POWER BY USING 2 CTS AND SINGLE WATTMETER
METHOD
AIM : To measure the 3-phase active power by using a single wattmeter and 2 CTs.
APPARATUS :
Sl. NO. NAME TYPE RANGE QTY.
1 Wattmeter Dynamometer type, LPF 10A, 300V 1 no
2. CTs 1:1, 5/5A 2 no.
3. Voltmeter MI 300 V 1 no.
4. Ammeter MI 10A 2 no.
5. 3-phase variable inductive load Balanced star 350, 1.2A 1no.
6 Three Phase Variac 0-270V, 10A 1 no
7 Connecting wires 1 set
CIRCUIT DIAGRAM
THEORY :
To measure 3- phase power using two CTs. Power can be measured in many ways, for an balanced load,
only one wattmeter is enough to measure the 3- phase power, and for an unbalanced load, two wattmeter
method is used to measure the 3- phase power. The primary windings of CTs are connected in series with
two phases. The secondary of both the CTs are connected as shown in figure the current coil of wattmeter
connected across both secondaries of CTs. The pressure coil is connected between the two phases.
PROCEDURE :
1. Make the connections as per the circuit diagram.
2. Keep the 3 phase variac in minimum position and close the TPST switch.
3. Vary the 3- phase variac gradually and apply the rated voltage (415V).
4. Note down all the meter readings and tabulate them.
5. Vary the inductive load in steps upto the rated current and tabulate the meter readings in each step.
6. Reduce the voltage to zero gradually by varying the 3 variac and open the TPST switch.
TABULATION:
S.NO V W Ict1 Ict2 load
PRECAUTIONS :
1. Avoid loose connections.
2. The secondary of CT should not be kept open.
3. Take readings without error.
4. Keep variac at their minimum position initially
5. Vary the variac such that the current and voltage are within the rated value
6. Meter readings should not exceed their ratings.
7. Live terminals should not be touched.
8 If any wattmeter reads zero or negative reading, change either current coil or pressure coil
connections.
9. Load current should not exceed rated current value.
10. Load should be varied very smoothly.
13. Take proper care, such that the ammeter reading, should not exceed the current rating of LPF
wattmeter.
RESULT :
The 3- active power of the inductive load is calculated using single phase wattmeter and two CTs
method. at balanced load condition.
QUESTIONS:
1. What is Burden of transformer?
2. Define (C.T&P.T) A. Transformation ratio
B. Turns ratio
C .Nominal ratio
D .RCF
3 Why C.T secondary should not be opened?
4 Comparison between C.T & P.T
EXPERIMENT NO.11
LVDT AND CAPACITANCE PICKUP-CHARACTERISTICS AND CALIBRATION
AIM:
To measure the displacement using linear variable differential transformer.
APPARATUS:.
CIRCUIT DIAGRAM:
THEORY:
Linear variable differential transformer LVDT is a transducer. Basically it is passive inductive transformer
similar to a potential transformer.
LVDT consists of three windings, one primary and two secondaries of equal turns. Primary is wound
centrally between two secondaries. All three windings are wound on a hollow tubular former through
which magnetic core slides.
Core affects magnetic coupling between primary and the secondaries while primary is connected to an AC
signal.
Normal / null position of core causes equal induced voltage in both the secondaries. Hence the total
difference voltage of both the secondaries becomes zero. Any deviation in core position from its null
position induces unequal voltage from both secondaries and hence the difference signal of it is a non zero
quantity, this non zero quantity varies with core position. Ideally displacement versus change in difference
signal should be linear.
When ES1=ES2 (core at null position or central position)
Ediff=0
When core is moved left
ES1>ES2 &
Ediff (ES1-ES2) is in phase with ES1
When core is moved right ES1<ES2
Ediff (ES1-ES2) is in phase with ES2.
Amount of Ediff. is proportional to the displacement of core. Phase angle of the output voltage decides the
direction of core from its normal null position.
Electronic circuit can be used to recover appreciable difference signal from LVDT. LVDT offers linearity
in the output for certain Range of displacement. Change in its output voltage is stepless and resolution
depends on test equipment. Higher magnitude output is possible. LVDT can tolerate high degree of
vibration and shorts and hence more rugged. Repeat accuracy is better due to low hysteresis.
Disadvantages of LVDT are its sensitivity towards stray magnetic field (magnetic shielding is possible),
large displacement is required for appreciable differential output.
PROCEDURE:
1. Connections are made as per the circuit diagram.
2. Switch on the supply keep the instrument in ON position for 10 minutes for initial warm up.
3. Rotate the micrometer core till it reads 20.0 mm and adjust the CAL potentiometer to display 10.0
mm on the LVDT trainer kit.
4. Rotate the micrometer core till it reads 10.0 mm and adjust the zero potentiometer to display 20.0
mm on the LVDT trainer kit.
5. Rotate back the micrometer core to read 20.0 mm and adjust once again the CAL potentiometer
till the LVDT trainer kit display reads 10.0 mm. Now the instrument is calibrated for 10mm
range.
6. Rotate the core of micrometer in steps of 2 mm and tabulate the readings of micrometer, LVDT
trainer kit display and multimeter reading.
Observations:
GRAPH:
PRECAUTIONS:
1. Allow the instrument in ON position for 10 min. for initial warm up.
2. While calibrating vary the cal/span pot slowly and smoothly.
RESULT:
Displacement is measured using linear variable differential transformer and graphs of indicated
displacement Vs actual displacement, %Error Vs actual displacement and output voltage Vs actual
displacement.
QUESTIONS:
1. What is LVDT?
2. What is transducer?
3. How many transducers are there?
4. How many windings the transformer in LVDT have in its construction?
5. How the secondaries are connected in the transformer of LVDT?
EXPERIMENT NO.12
MEASUREMENT OF IRON LOSS IN A BAR SPECIMEN USING A CRO AND USING A
WATTMETER
AIM:
To measure the iron losses in strip (sheet) material using Lloyd - Fisher Square.
APPARATUS:
CIRCUIT DIAGRAM
THEORY:
The voltage across the secondary i.e. voltmeter reading given the rms value of the induced voltage.
E = 4 k
fm
f N
2
N
2
= No. of turn of the secondary winding.
Bm
1
=
2 f
AsfN AK
E
(apparent value)
As = area of specimen; m
2
Bm = Bm
1
0
H
m
,
_
1
As
Ac
A
c
= Cross sectional area of coil; m
2
H
m
= Magnetizing force corresponding to maximum flux density; A/m. (obtained from B.H. curve of
specimen)
Wattmeter reading = iron loss in the specimen + Copper loss in the secondary
Cu loss =
rc rp
E
2
+
Where rp = resistance of pressure coil
Rc = resistance of coil S
1
.
Total iron loss = P
i
=
rc rp
E
V
PE
2
+
watt
Pi = eddy current loss + hysterias loss
Eddy current loss = Volume x
3P
t2Kf Bm 4f
2 2 2
PRECAUTIONS:
1. Connect the circuit, without any loose connection.
2. V
1
& V
2
voltmeter used in the secondary should be either electro static on electro dynamometer
type.
3. Take the meter readings without parallel error.
RESULT:
Iron loss are calculated in a bar specimen by using Lloyed fisher square method, by conducting the
experiment.
QUESTIONS:
1. What are the methods of measuring iron losses?
2. What are the two types of squares used to measure iron losses?
3. Which square is preferred to measure iron losses?
4. How the strips are located in Epstein square and Lloyd-Fisher square?
5. What are iron losses?
6. What are the types of iron losses?
7. How the hysteresis loss is minimized?
8. How the eddy current loss is minimized?
9. Define form factor?