Expansion Tank Calculations
Expansion Tank Calculations
HORIZONTAL PIPING QTY TERRACE 6F 5F 4F 3F 2F 1F UGF LGF PLANT ROOM TRENCH AHU CONNECTIONS SHAFT 1 SHAFT 2 GRAD.TOTAL PIPING AS PER BOQ CHANGE wrt. BOQ CHW PIPE INSU. WITH 20% FOS CHW VOLUME WITH 20% FOS TOT. CHW. VOLUME TOTAL WITH 20% FOS NOTES: (RMT) (RMT) (RMT) (RMT) (RMT) (Cu.M) (Cu.M) (Cu.M) (Cu.M) 972 972 800 172 972 1166 0 1 126 8 212 100 112 212 254 0 0 200 200 100 100 200 240 0 0 110 12 160 100 60 160 192 0 0 10 19 32 50 -18 32 38 0 0 VERTICAL PIPING QTY 27 4 31 450 -419 31 37 0 0 23 26 27 51 77 150 -73 77 93 1 1 27 19 46 260 -214 46 55 1 1 PIPE LENGTH (RMT) 0 0 0 0 0 0 0 0 0 0 0 0 79 0 0 0 0 0 0 0 0 0 0 0 0 0 0 38 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 30 38 200 38 31 336 250 86 336 404 6 7 0 57 0 39 96 60 36 96 115 3 4 0.00 0 0 200 -200 27 64 71 162 0 162 162 194 11 13
1OF5
7/18/2012
1. LENTH DOESNOT INCLUDE ELBOWS 2. MARKED IN COLOR IS CONDENCER WATER PIPE QUANTITY 3. 40 MM, 50 MM & 65 MM CONNECTIONS ARE CONSIDERED 10 M FOR EACH AHU 4. 25 MM & 32 MM CONNECTIONS ARE CONSIDERED 6 M PER CONNECTION
2OF5
CLOSED EXPANSION TANK CAPACITY CALCULATIONS (PLANT ROOM)- VOLUME OF WATER CALCUALTIONS
PROJECT CLIENT ARCHITECH CONSULTANT HVAC CONTRACTOR :M/s.R. N. COOPER HOSPITAL,VILE PARLE :M/s UNITY PROJECTS LTD. :M/s.G.D SAMBHARE & CO. :M/s.GUPTA CONSULTANT & ASSOCIATES. :M/s VOLTAS LIMITED, MUMBAI Date:-08.08.2011 FLOOR AREA CATERED PIPE DIAMETER 25 mm 0 0 0 0 PIPE LENGTH (RMT) 0 0 972 (RMT) (Cu.M) (Cu.M) (Cu.M) 972 0 32 mm 0 0 0 0 0 0 79 126 8 212 0 40 mm 0 0 0 0 0 0 200 200 0 50 mm 0 0 0 0 0 0 0 38 110 12 160 0 65 mm 0 0 0 0 0 0 3 10 19 32 0 80 mm 0 0 0 0 0 0 27 4 31 0 23 26 100 mm 0 0 0 27 51 77 1 125 mm 0 0 27 19 46 1 150 mm 0 0 30 38 200 38 31 336 6 VERTICAL PIPING QTY SHAFT 1 SHAFT 2 CHW PIPE QTY CHW VOLUME TOT. CHW. VOLUME TOTAL WITH 20% FOS 39 96 3 162 11 200 mm 57
-
250 mm -
300 mm 27 64 71 -
NOTES: 1. LENTH DOESNOT INCLUDE ELBOWS 3. 40 MM, 50 MM & 65 MM CONNECTIONS ARE CONSIDERED 10 M FOR EACH AHU 4. 25 MM & 32 MM CONNECTIONS ARE CONSIDERED 6 M PER CONNECTION
3of7
A B C D E F G H I J K L M N
Total Volume as per Volume of WATER Calculations Total System Volume Static Head on Expansion Tank i.e. Level of Chilled Water Piping above Tank Coefficient of expansion @ 40C Expansion in System Volume Min. +ve pressure at pump Suction Total Min. +ve pressure at Pump Suction in meters Total Min. +ve pressure at Pump Suction in kg / cm Total Min. pressure at Pump Suction in kg / cm ( Absolute ) Allow 1 kg / cm increase due to expansion Maximum pressure at pump suction Pressure Ratio Calculated Tank Size Calculated Tank Size with 15% FOS Selected Capacity
A x 1000
4of7
size 200 300 200 300 300 300 150 150 150 150 200 300 300 200 200 300 300 200 200 200 200 200 150
FF 0.02 0.009 0.02 0.02 0.009 0.009 0.007 0.007 0.007 0.007 0.02 0.009 0.009 0.009 0.02 0.009 0.009 0.009 0.009 0.009 0.009 0.02 0.007
loss in ft 0.39 0.93 0.26 1.79 0.28 2.95 0.14 0.17 0.05 0.48 0.12 30.00 0.39 0.81 0.12 0.39 0.14 0.81 0.12 0.08 0.08 1.83 0.12 0.04 42.50 51.00 15.55
end chiller to end sec. pump 1 elbow 3 tee 2 elbows 11 tee header to pump 1 elbow 1 BFV 1 Y ST. 1 RUBBER BELLOW chiller chiller to p.pump 3 tee 1 elbow 1 elbows 3 tee 1 elbow 1 BFV 1 MBFV 1 BLV 1 RUBBER BELLOW 1 RUBBER BELLOW total 20% FOS primarry pump head (m)
285