Structure Set

The document outlines the design plans for a residential building, including column, roof beam, and slab plans. It specifies soil bearing capacity, required steel reinforcement grades, and concrete mix ratios for various structural elements. Additionally, it includes clear cover requirements for reinforcement and emphasizes adherence to provided dimensions and architectural details.

Uploaded by

akash.ipr.psa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views10 pages

Structure Set

The document outlines the design plans for a residential building, including column, roof beam, and slab plans. It specifies soil bearing capacity, required steel reinforcement grades, and concrete mix ratios for various structural elements. Additionally, it includes clear cover requirements for reinforcement and emphasizes adherence to provided dimensions and architectural details.

Uploaded by

akash.ipr.psa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

DESIGN: COLUMN PLAN

NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500/550 grade should be used.

C.B. C.B. M7.5 = [Link] ( USED AS P.C.C. )


DRESS
6'-6" X 4'-10" BEDROOM
DRESS
6'-11" X 4'-10"
DRESS
6'-6" X 4'-11"
DRESS
6'-11" X 4'-11"
M10= [Link]
14'-6" X 11'-7"
M15= [Link]
TOILET BEDROOM BEDROOM BEDROOM
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
TOILET TOILET TOILET 18'-0" X 11'-8"
6'-6" X 6'-5"
6'-11" X 6'-5" 20'-0" X 11'-7"
6'-5" X 6'-5"
14'-6" X 11'-8"
6'-11" X 6'-5" M25= [Link]
CLEAR COVER TO MAIN
TERRACE
TERRACE
25'-3" X 23'-7" REINFORCEMENT:
OPEN OPEN OPEN
[Link] : 50 mm
LIVING ROOM [Link] [Link] : 50 mm
21'-4" X 11'-7" LIVING ROOM KITCHEN TOILET KITCHEN + DINING
18'-0" X 11'-7" 14'-0" X 11'-7" 8'-0" X 11'-7" 18'-0" X 11'-7" [Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
3'-9" X 48'-9"
BALCONY

PLY PARTITION
[Link] SLAB : 20 mm
[Link] : 40 mm
1"
[Link] WALL : 25 mm
HALL 12'-112
18'-4" X 17'-11" [Link] : 25 mm
[Link] : 15 mm
17'-9"

HALL HALL
[Link]

[Link]

[Link]

[Link]

[Link]

[Link]
DRAWING ROOM DRAWING ROOM LOBBY DRAWING ROOM LOBBY
13'-0" X 17'-7" 13'-0" X 17'-11" 6'-0" X 17'-11"
12'-0" X 17'-11"
13'-0" X 17'-11" 6'-0" X 17'-11"
12'-0" X 17'-11"
[Link] : 15 mm
[Link] RETAINING
STRUCTURES : 20/30 mm

UP UP UP UP UP UP

Project Type: Residential


LVL 1'-6" LVL 1'-6"
BALCONY
21'-8" X 6'-7"
BALCONY
25'-5" X 6'-7"
BALCONY
25'-4" X 6'-7"
BALCONY
25'-5" X 6'-7"
Date: 23-07-2024
MAIN GATE
Sheet No.: S-01
MAIN GATE
SHEET NO. : S-01A
GF COLUMN PLAN FF COLUMN PLAN SF COLUMN PLAN

This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
CB1 RB1 RB1
4' 1" 1" C.B. DESIGN: ROOF BEAM
6'-02 14'-12 AND SLAB PLAN
DRESS DRESS
6'-6" X 4'-10" BEDROOM
6'-11" X 4'-10"
14'-6" X 11'-7"
RB4 RB4 RB4 S2
RB4 S2 RB4
S2 S2
S1

TOILET BEDROOM
TOILET 6'-11" X 6'-5" 20'-0" X 11'-7"
6'-6" X 6'-5" NOTE:
SOIL BEARING CAPACITY
CB1 RB1 RB1 Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
4' 1" FE - 500/550 grade should be used.
13'-62
M7.5 = [Link] ( USED AS P.C.C. )
OPEN M10= [Link]
LIVING ROOM
RB4 M15= [Link]
21'-4" X 11'-7" M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
RB4 RB4 RB4 LIVING ROOM
RB4 M25= [Link]
S1

18'-0" X 11'-7"
S2 S2 CLEAR COVER TO MAIN
S2 REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
[Link] FOUNDATION.
CB3 RB3 RB3 RB4 RB2 BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
4' 1" [Link] SLAB : 20 mm
5'-3" 11'-72 [Link] : 40 mm
[Link] WALL : 25 mm
[Link] : 25 mm
[Link] : 15 mm
S2 [Link] : 15 mm
S1

[Link] RETAINING
HB HALL
STRUCTURES : 20/30 mm
DRAWING ROOM 18'-4" X 17'-11"
RB3 13'-0" X 17'-7" RB3 RB3 RB3 RB3 Project Type: Residential
S2
Date: 23-07-2024
Sheet No.: S-01
SHEET NO. : S-01B

CB3 RB3 UP UP RB2


4' RB4 RB4
S1
S1
RB5 RB5 S2 RB5 S2 RB5 RB5
S1

LVL 1'-6"

MAIN GATE MAIN GATE

RB3 RB3 RB2

GF ROOF BEAM &SLAB PLAN


This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
CB1 RB1 RB1
4' 1" 1" C.B. DESIGN: ROOF BEAM
6'-02 14'-12 AND SLAB PLAN
DRESS DRESS
6'-6" X 4'-11" 6'-11" X 4'-11"

RB4 RB4 RB4 S2


RB4 S2 RB4
S2 S2
S1

BEDROOM BEDROOM
TOILET TOILET 18'-0" X 11'-8"
14'-6" X 11'-8" NOTE:
6'-5" X 6'-5" 6'-11" X 6'-5"
SOIL BEARING CAPACITY
CB1 RB1 RB1 Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
4' 1" 6'-7" FE - 500/550 grade should be used.
13'-62
M7.5 = [Link] ( USED AS P.C.C. )
OPEN M10= [Link]
M15= [Link]
3'-9" X 48'-9"
BALCONY

M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )


RB4 KITCHEN RB4 TOILET
RB4 RB4 KITCHEN + DINING
RB4
S1

14'-0" X 11'-7" 8'-0" X 11'-7" 18'-0" X 11'-7" M25= [Link]


S2 S2 CLEAR COVER TO MAIN
S2 REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
[Link] FOUNDATION.
CB3 RB3 RB3 RB4 RB2 BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
4' 1" [Link] SLAB : 20 mm
5'-3" 11'-72 [Link] : 40 mm
[Link] WALL : 25 mm
[Link] : 25 mm
S2 [Link] : 15 mm
[Link] : 15 mm
S1

LOBBY [Link] RETAINING


6'-0" X 17'-11" STRUCTURES : 20/30 mm
HALL
DRAWING ROOM
12'-0" X 17'-11"
RB3 13'-0" X 17'-11" RB3 RB3 RB3 RB3 RB3
S2 Project Type: Residential
Date: 23-07-2024
Sheet No.: S-01

S1
SHEET NO. : S-01C

CB3 RB3 UP UP RB2


4' RB4 RB4
S1 S1
RB5 21'-8"
BALCONY RB5 S2 RB5 S2 RB5 BALCONY RB5
S1

X 6'-7" 25'-5" X 6'-7"

RB3 RB3 RB2

FF ROOF BEAM &SLAB PLAN


This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
DESIGN: ROOF BEAM
AND SLAB PLAN

NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
TERRACE
TERRACE According to given site soil condition.
25'-3" X 23'-7" STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500/550 grade should be used.

OPEN M7.5 = [Link] ( USED AS P.C.C. )


M10= [Link]
M15= [Link]
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= [Link]
CLEAR COVER TO MAIN
REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
CB3 RB3 RB3 RB4 RB2 [Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
4' [Link] BEAM : 50 mm
[Link] SLAB : 20 mm
[Link] : 40 mm
[Link] WALL : 25 mm
[Link] : 25 mm
S2 LOBBY [Link] : 15 mm
S1

6'-0" X 17'-11" [Link] : 15 mm


S2 [Link] RETAINING
S2 RB3 HALL STRUCTURES : 20/30 mm
DRAWING ROOM
12'-0" X 17'-11"
RB3 13'-0" X 17'-11" RB3 RB3 RB3 RB3
S2 Project Type: Residential
Date: 23-07-2024

S1
Sheet No.: S-01
SHEET NO. : S-01D

CB3 RB3 UP UP RB2


4' RB4 RB4
S1 S1
RB5 BALCONY RB5 S2 RB5 S2 RB5 BALCONY RB5
S1

25'-4" X 6'-7" 25'-5" X 6'-7"

RB3 RB3 RB2

TF ROOF BEAM &SLAB PLAN


This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
DESIGN: SCHEDULE OF BEAM
AND SLAB

SCHEDULE OF ROOF BEAM NOTE:


SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.

REIN. AT REIN. AT EXTRA AT EXTRA AT RINGS STEEL REINFORCEMENT


SIZE (IN) Steel Reinforcement confirming to IS 1786-1985 code,
NAME FE - 500/550 grade should be used.

THICKNESSXDEPTH TOP BOTTOM BOTTOM TOP UP TO L/3 AFTER L/3 M7.5 = [Link] ( USED AS P.C.C. )
M10= [Link]
M15= [Link]
RB1 12" x 18" 3-16 TMT 3-20 TMT 2-16 TMT 2-16 TMT 8 # @ 5" C/C 8 # @ 6" C/C M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= [Link]
CLEAR COVER TO MAIN
RB2 9" x 18" 3-16 TMT 3-16 TMT 2-12 TMT 2-12 TMT 8 # @ 5" C/C 8 # @ 6" C/C REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
RB3 9" x 16" 2-16 TMT 2-16 TMT 2-12 TMT 2-12 TMT 8 # @ 5" C/C 8 # @ 6" C/C [Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
RB4 9" x 12" 2-12 TMT 2-12 TMT 8 # @ 5" C/C 8 # @ 6" C/C [Link] SLAB : 20 mm
2-12 TMT 2-12 TMT [Link] : 40 mm
[Link] WALL : 25 mm
[Link] : 25 mm
RB5 9" x 12" 2-12 TMT 2-12 TMT 2-10 TMT 2-10 TMT 8 # @ 5" C/C 8 # @ 6" C/C [Link] : 15 mm
[Link] : 15 mm
[Link] RETAINING
CB1 12" x 18" 3-16 TMT 3-20 TMT - 2-16 TMT 8 # @ 4" C/C 8 # @ 5" C/C STRUCTURES : 20/30 mm

CB3 9" x 16" 2-16 TMT 2-16 TMT - 2-10 TMT 8 # @ 4" C/C 8 # @ 5" C/C Project Type: Residential
Date: 23-07-2024
Sheet No.: S-01
HB 9" x 5" 2-12 TMT 2-12 TMT - - 8 # @ 5" C/C 8 # @ 6" C/C SHEET NO. : S-02

SLAB DETAILS

Slab No. THK. (IN) SHORT SPAN LONG SPAN REMARK

S1 5" 10 Ø @ 6" C/C 8 Ø @ 7" C/C One Way


S2 5" 10 Ø @ 6" C/C 10 Ø @ 6" C/C Two Way

This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
DESIGN: TYPICAL PLAN AND SECTION
OF BEAM

NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500/550 grade should be used.

M7.5 = [Link] ( USED AS P.C.C. )


M10= [Link]
M15= [Link]
A1 A2 M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= [Link]
L/3 CLEAR COVER TO MAIN
L/3 L/3
2-12mmØ BOTTOM 2-12mmØ BOTTOM REINFORCEMENT:
2-12mmØ TOP 2-12mmØ TOP
2-12mmØ EX. TOP B1 2-12mmØ EX. TOP B2 [Link] : 50 mm
8mmØ @ 5"c/c STIRRUPS 8mmØ @ 5"c/c STIRRUPS L/3 [Link] [Link] : 50 mm
[Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
[Link] SLAB : 20 mm
2-12mmØ BOTTOM 2-12mmØ BOTTOM [Link] : 40 mm
L/4 2-12mmØ EX. BOTTOM L/4 L/4 2-12mmØ EX. BOTTOM L/4 [Link] WALL : 25 mm
A1 2-12mmØ TOP
8mmØ @ 150mm c/c STIRRUPS
A2 2-12mmØ TOP
8mmØ @ 150mmc/c STIRRUPS
[Link] : 25 mm
[Link] : 15 mm
B1 B2 [Link] : 15 mm
[Link] RETAINING
5" slab

5" slab

5" slab

5" slab
2-12mmØ TOP 2-12mmØ TOP 2-12mmØ TOP 2-12mmØ TOP
2-12mmØ EX. TOP 2-12mmØ EX. TOP STRUCTURES : 20/30 mm
8 mmØ @ 5"c/c STIRRUPS 8 mmØ @ 150mm c/c STIRRUPS 8 mmØ @ 5"c/c STIRRUPS 8 mmØ @ 150mm c/c STIRRUPS
7"

7"

7"

7"
2-12mmØ BOTTOM 2-12mmØ EX. BOTTOM 2-12mmØ BOTTOM 2-12mmØ EX. BOTTOM
2-12mmØ BOTTOM 2-12mmØ BOTTOM
Project Type: Residential
SECTION A1-A1 SECTION B1-B1 SECTION A2-A2 SECTION B2-B2 Date: 23-07-2024
Sheet No.: S-01
SHEET NO. : S-03
TYPICAL PLAN AND SECTION VIEW OF BEAM PANEL

This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
DESIGN: TYPICAL SECTION OF SLAB
10mm@6"c/c 8mm@7"c/c

Ly/4
AREA STATEMENT:
Plot Area :
Ground Floor Area :
First Floor Area :
10mm@6"c/c
NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
A A' STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
Lx/4
FE - 500/550 grade should be used.
10mm@6"c/c
M7.5 = [Link] ( USED AS P.C.C. )
Ly

M10= [Link]
10mm@6"c/c M15= [Link]
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
10mm@6"c/c M25= [Link]
CLEAR COVER TO MAIN
S2 S2 B S1 B'
REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
[Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
[Link] SLAB : 20 mm
[Link] : 40 mm
[Link] WALL : 25 mm
Lx
[Link] : 25 mm
[Link] : 15 mm
[Link] : 15 mm

TYPICAL PLAN VIEW OF SLAB PANEL [Link] RETAINING


STRUCTURES : 20/30 mm

Project Type: Residential


Date: 23-07-2024
TOP DISTRIBUTION MAIN BAR CRANK BAR Sheet No.: S-01
SHEET NO. : S-04

Lx/4 Lx/4
5"

DISTRIBUTION BAR

TYPICAL SECTION VIEW OF SLAB PANEL


This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
TREAD = 12"
RISER = 5.96"=151.38MM DESIGN: GF STAIRCASE DETAILS

AREA STATEMENT:
Plot Area :
Ground Floor Area :
13 First Floor Area :

4'
NOTE:
SOIL BEARING CAPACITY

6'-6" Foundations have been designed


According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500/550 grade should be used.

TREAD = 12" M7.5 = [Link] ( USED AS P.C.C. )


14 RISER = 5.96"=151.38MM M10= [Link]
M15= [Link]
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= [Link]
CLEAR COVER TO MAIN
10 8mm @150mm c/c
REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
10mm @150mm c/c [Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
8mm @150mm c/c [Link] BEAM : 50 mm
REFRENCE POINT
[Link] SLAB : 20 mm
[Link] : 40 mm
[Link] WALL : 25 mm
As/Slab R/F [Link] : 25 mm
[Link] : 15 mm
[Link] : 15 mm
20
STAIRCASE RCC DETAILS TYPICAL [Link] RETAINING
STRUCTURES : 20/30 mm
05 Clear Height 12' Project Type: Residential
Date: 23-07-2024
Sheet No.: S-01
SHEET NO. : S-05A

24
01

UP

TYPICAL STAIRCASE SECTION


This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
LINTEL DETAILS DESIGN: LINTEL DETAIL
B
AREA STATEMENT:
Top Reinft Plot Area :
Ground Floor Area :
First Floor Area :
Stirrups NOTE:

D
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
Bottom Reinft FE - 500/550 grade should be used.

Clear Span (L) M7.5 = [Link] ( USED AS P.C.C. )


M10= [Link]
M15= [Link]
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= [Link]
CLEAR COVER TO MAIN
REINFORCEMENT:
[Link] : 50 mm
[Link] [Link] : 50 mm
[Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
[Link] BEAM : 50 mm
[Link] SLAB : 20 mm
[Link] : 40 mm
Clear Span (L) Breadth(B) Depth(D) Top Bottom Links/ [Link] WALL : 25 mm
(in) (in) (in) Reinft Reinft Stirrups [Link] : 25 mm
[Link] : 15 mm
[Link] : 15 mm
[Link] RETAINING
3' 9"/5" 4"-5" 2 NOS 10 TMT 2 NOS 10 TMT 8MM RINGS @ 200MM c/c STRUCTURES : 20/30 mm

Project Type: Residential


Date: 23-07-2024
3' - 6' 9"/5" 5" 2 NOS 10 TMT 2 NOS 10 TMT 8MM RINGS @ 200MM c/c Sheet No.: S-01
SHEET NO. : S-06

6' - 12' 9"/5" 6" 2 NOS 12 TMT 2 NOS 12 TMT 8MM RINGS @ 200MM c/c

12' - 14' 9"/5" 7" 2 NOS 12 TMT 2 NOS 12 TMT 8MM RINGS @ 200MM c/c

NOTE: LINTEL WILL BE AT 7' TO 8' HEIGHT ON ALL THE WALLS AS PER NEED
NOTE: IF WALL BREADTH IS 9" THAN 9" WILL BE THE BREADTH OF LINTEL BEAM AND
IF WALL BREADTH IS 5" THAN BREADTH OF LINTEL BEAM WILL BE 5".

This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
#. CONCRETE.
AS PER IS 456 : 2000
IS 456-2000 CODE FOR PCC AND RCC . DESIGN: RCC NOTE
THE MAXI. SIZES OF AGGREGATE USED IN RCC IS LIMITED TO 20 MM
HOWEVER 10 mm ,15 mm are also used, in some expectations 25 mm is also used . AREA STATEMENT:
Plot Area :
Ground Floor Area :
#. REINFORCING STEEL First Floor Area :
1. AS PER IS 800-2007 NOTE:
SOIL BEARING CAPACITY
2. REINFORCEMENT SHALL BE USED TMT BARS . Foundations have been designed

3. TMT Bars - Thermo-Mechanical Treated Bars STEEL According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
[Link] BAR GRADE Fe-500, Fe-550D OR HIGHER GRADE STEEL. FE - 500/550 grade should be used.

[Link] steel bars from different brands like TATA, Jindal, JSW and more M7.5 = [Link] ( USED AS P.C.C. )
M10= [Link]
M15= [Link]
#. TWO LAYERS OF BITUMENOUS PAPER TO BE PROVIDED ON M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
SUPPORTS UNDER SLABS, BEAMS AND LINTELS. M25= [Link]
CLEAR COVER TO MAIN
REINFORCEMENT:
#. STRUCTURE DRAWINGS ARE DESIGN ACCORDING TO IS CODE . [Link] : 50 mm
[Link] [Link] : 50 mm
# .LAPPING LENGTH SHOULD BE PROVIDED 48D -50D ( D-DIA OF BAR ) , [Link] FOUNDATION.
BOTTOM/SIDES : 75 mm
#. MINIMUM SPACING BETWEEN LONGITUDINAL BARS SHOULD BE 2 INCHES OR 50 MM . [Link] BEAM : 50 mm
[Link] SLAB : 20 mm
[Link] : 40 mm
NOTE-Types of Formwork ( Formwork removal time after casting of Concrete ) [Link] WALL : 25 mm
1. Vertical Formwork of Column, beam, and wall - 16 Hours to 24 hours [Link] : 25 mm
[Link] : 15 mm
[Link] removal for beams and arches [Link] : 15 mm
#.Span length up to 6m -14 Days [Link] RETAINING
#.Span length beyond 6m -21 Days STRUCTURES : 20/30 mm
[Link] removal for slab
#.Span length up to 4.5m -7 days Project Type: Residential
#.Span length beyond 4.5m -14 days Date: 23-07-2024
NOTE-Curing Time For : Sheet No.: S-01
SHEET NO. : S-07
1. PCC ( Plain Cement Concrete ) - 14 days
[Link] ( Reinforced Cement Concrete ) :- 10 days
[Link] :- 10 days
4. Plastering & Pointing : - 7 days
5. Brick & Stone Work :- 7 days
NOTE-Cement Sand Ratio For Plaster
Cement : Sand = 1:5 for the first coat of plaster with 12 mm thickness.
Cement : Sand = 1:3 for the second coat of plaster with 8 mm thickness.
NOTE-Mortar Mix Ratio
The ratio of cement to sand in brick
masonary are generally used 1:3 to 1:6

This drawing is the property of [Link] It may not be used for any purpose other than the owner.
[Link] does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect