0% found this document useful (0 votes)
107 views268 pages

X2View en

The X2View User Manual provides comprehensive instructions for using the X2View software developed by Shanghai Sunfull Automation Co., LTD, including installation, operation, and configuration of various features. It covers topics such as project creation, device management, alarm settings, and web server functionalities. The manual is designed to assist users in effectively utilizing the software for mobile terminal configuration and monitoring.

Uploaded by

Tony Enghog
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views268 pages

X2View en

The X2View User Manual provides comprehensive instructions for using the X2View software developed by Shanghai Sunfull Automation Co., LTD, including installation, operation, and configuration of various features. It covers topics such as project creation, device management, alarm settings, and web server functionalities. The manual is designed to assist users in effectively utilizing the software for mobile terminal configuration and monitoring.

Uploaded by

Tony Enghog
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

X2View User Manual

Shanghai Sunfull Automation Co., LTD


Singapore Milesgo IIoT Pte Ltd
X2View User Manual

Content

1 Preface ........................................................................................................9

1.1 Statement .............................................................................................................. 9

1.2 Technical support .................................................................................................. 9

1.3 Extra tip ..................................................................................................................9

1.4 Term .................................................................................................................... 10

2 Summary ................................................................................................... 11

2.1 Function description ............................................................................................ 11

2.2 Runtime environment .......................................................................................... 12

3 For the first time to use ..............................................................................12

3.1 Start-up guide ......................................................................................................12

3.2 Download X2View software ................................................................................ 12

3.3 X2View install/uninstall ........................................................................................12

3.3.1 Install ........................................................................................................... 13

3.3.2 Uninstall ...................................................................................................... 13

3.4 Run/Exit X2View ..................................................................................................13

3.4.1Run X2View ................................................................................................. 13

3.4.2Exit X2View .................................................................................................. 15

3.5 Use content ......................................................................................................... 16

3.6 Update version .................................................................................................... 16

4 Operation instructions ............................................................................... 16

4.1 New project ..........................................................................................................16

4.2 New driver ............................................................................................................19

4.3 New channel ........................................................................................................22

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.4 Add a device ........................................................................................................24

4.5 Add tags .............................................................................................................. 27

4.5.1 Register type of collection terminal..............................................................29

4.5.2 Register type and number of transfer terminal............................................ 31

4.6 Transfer terminal setting ..................................................................................... 34

4.6.1 BACnet server .............................................................................................34

4.6.2 Modbus server ............................................................................................ 39

4.6.3 Forwarding side .......................................................................................... 43

4.6.4 IEC61850 Server ........................................................................................ 44

4.6.5 Remote databases ......................................................................................45

4.7 Alarm ................................................................................................................... 56

4.7.1 GPRS .......................................................................................................... 56

4.7.2 Phone .......................................................................................................... 57

4.7.3 SMS platform .............................................................................................. 58

4.7.4 WeChat server ............................................................................................ 60

4.7.5 Ding Talk ..................................................................................................... 63

4.7.6 Mail ..............................................................................................................66

4.7.7 Alarm List .................................................................................................... 69

4.7.8 Telegram ..................................................................................................... 70

4.7.9 WeCom ....................................................................................................... 75

4.7.10 Viber .......................................................................................................... 80

4.7.11 WhatsApp ..................................................................................................82

4.7.12 Byte Feishu ............................................................................................... 87

4.8 IOT .......................................................................................................................91

4.8.1 MQTT server ............................................................................................... 91

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.8.2 Energy Conservation Office Energy Consumption Platform ..................... 96

4.8.3 POP3 receiving mailbox ............................................................................. 99

4.8.4 Upload projects remotely ..........................................................................101

4.8.5 Intranet penetration ...................................................................................103

4.8.6 Remote monitoring ................................................................................... 110

4.9 Page configuration ............................................................................................ 112

4.9.1 Page configuration ....................................................................................112

4.9.2 Two options of primitive properties ............................................................121

4.9.3 The use of wildcards .................................................................................123

4.10 Selection of monitoring mode ......................................................................... 126

4.11 Running X2ViewRuntime ................................................................................ 127

4.12 Upload project to gateway .............................................................................. 129

4.13 Download the project ...................................................................................... 130

4.14 Gateway/HMI setting .......................................................................................131

4.15 Start monitor ....................................................................................................135

4.15.1 Offline monitor .........................................................................................135

4.15.2 Online monitor .........................................................................................136

4.16 Timer ............................................................................................................... 138

4.16.1 Timer group .............................................................................................138

4.16.2 Timer ....................................................................................................... 141

4.17 Sequence list/command List ...........................................................................143

4.17.1 Sequence list .......................................................................................... 143

4.17.2 Command list .......................................................................................... 145

4.18 Internal tag ...................................................................................................... 147

4.19 Trigger ............................................................................................................. 148

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.20 Database ......................................................................................................... 149

4.20.1 Alarm text setting .................................................................................... 150

4.20.2 Historical Tags ........................................................................................ 152

4.21 User Manager ..................................................................................................154

4.21.1 User list ................................................................................................... 154

4.21.2 User group .............................................................................................. 156

4.22 Provide a development interface .................................................................... 157

4.23 Provide handset installation package ............................................................. 158

5 Web server .............................................................................................. 158

5.1 Local WEB server ............................................................................................. 158

5.2 Hardware WEB Server ......................................................................................159

5.2.1 Web login .................................................................................................. 160

5.2.2 Download file ............................................................................................ 161

5.2.3 Touch panel options/HMI options .............................................................161

5.2.4 Upload the file ........................................................................................... 162

5.2.5 User management .................................................................................... 162

5.2.6 Network interface setting .......................................................................... 164

5.2.7 Route settings ........................................................................................... 165

5.2.8 Firmware information ................................................................................ 165

5.2.9 System information ................................................................................... 166

5.2.10 Communication statues .......................................................................... 167

5.2.11 Pass-Through by IOT ............................................................................. 167

5.2.12 Forwarding side ...................................................................................... 167

5.2.13 Alarm settings ......................................................................................... 168

5.2.14 Alarm information ....................................................................................169

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5.2.15 Alarm record ........................................................................................... 169

5.2.16 History query ...........................................................................................171

5.2.17 Timer ....................................................................................................... 173

5.2.18 Internal variables .................................................................................... 174

5.2.19 Real-time data .........................................................................................175

5. 2.20 Configuration screen ............................................................................. 176

6 Application case ...................................................................................... 177

6.1 New project ....................................................................................................... 177

6.2 Add new driver .................................................................................................. 180

6.3 Add channel ...................................................................................................... 181

6.4 Add equipment .................................................................................................. 182

6.5 Add tags ............................................................................................................ 183

6.6 The configuration page ..................................................................................... 186

6.7 Create animated links ....................................................................................... 193

6.8 Configuration screen batch associated variables ............................................ 197

7 Replace logo ........................................................................................... 202

7.1 replace logo file ................................................................................................. 202

7.2 Upload logo ....................................................................................................... 203

8 Photoshop usage and Chrome browser configuration ............................ 204

8.1 Photoshop creates gif images .......................................................................... 204

8.2 Configuring Chrome browser ............................................................................208

8.2.1 Automatic start .......................................................................................... 209

8.2.2 Run full screen with parameters ...............................................................210

9 Customized configuration software gallery ..............................................210

9.1 View the system default gallery ........................................................................ 210

9.2 Delete gallery .................................................................................................... 213

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

9.3 Add a gallery ..................................................................................................... 215

10 Programmable .......................................................................................216

10.1 Graphic Programming .....................................................................................216

10.2 Java Script Editor ............................................................................................ 217

10.3 PLC Editor ....................................................................................................... 218

11 Common question description ...............................................................219

11.1 Prompt to call the web server method failed .................................................. 219

11.2 Note the difference between upload and download projects .........................219

11.3 Problems to pay attention to when software .................................................. 219

11.4 Running [Link] to report an error cannot be opened. .......................... 219

11.4.1 The parallel configuration is incorrect. ................................................... 219

11.4.2 Computer deficiency [Link] .......................... 220

12 Appendix ............................................................................................... 221

12.1 Operation steps of GPRS modem .................................................................. 221

12.1.1 Create a user .......................................................................................... 221

12.1.2 Creating user groups .............................................................................. 223

12.1.3 GPRS Modem configuration ...................................................................225

12.1.4 Enable SMS alarm ..................................................................................229

12.2 SMS alarm operation ...................................................................................... 230

12.2.1 Creating user group ................................................................................ 230

12.2.2 Configure alarm information. .................................................................. 232

12.2.3 Turn on WeChat alarm ........................................................................... 238

12.3 Telephones alarm operation procedure ......................................................... 241

12.3.1 Create user ............................................................................................. 241

12.3.2 Creating user groups .............................................................................. 243

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

12.3.3 Configure alarm information ................................................................... 245

12.3.4 Turn on the phones alarm ...................................................................... 249

12.4 DingTalk alarm operation step ........................................................................251

12.4.1 Configure alarm information ................................................................... 251

12.4.2 Open DingTalk alarm ..............................................................................255

12.5 Operation steps of mail alarm .........................................................................257

12.5.1 Create a user .......................................................................................... 257

12.5.2 Creating user groups .............................................................................. 259

12.5.3 Configure alarm information ................................................................... 261

12.5.4 Open mail alarm ..................................................................................... 265

Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

1 Preface

1.1 Statement

X2View is a green software developed by the company for mobile


terminal configuration editors.

This manual belongs to Shanghai Sunfull Automation Technology Co.


Ltd. and authorized license the copyright, all rights reserved, without the
written permission of Sunfull, any companies and persons will be allowed to
extract and copy all or part of this manual‘s contents. The content of this
manual may be changed because of product version upgrades or other
reasons. This handbook is used in conjunction with the fast Rao hardware
gateway and the touch screen, and we do our best to provide accurate
information in this manual.

1.2 Technical support

 Technical support Email: support@[Link]

 Technical support Tel: +86 021-20252795

 Sunfull: [Link] or [Link]

1.3 Extra tip

 Suggest using Google Chrome browser in PC

 Suggest using UC browsers or safari of iOS in mobile phones

 The configuration file must be named by digital or English

 Customizable logo

9 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

1.4 Term

Terms in this meaning


manual

The configuration software for the web configuration


gateway series of Sunfull:
X2View
web configuration software

web configuration gateway product mode:WEB


configuration gateway series, MBus to MQTT gateway
Gateway
series, MQTT gateway series, IOT edge gateway (with
4G module) series

Touch web Configuration Touch Panel product model(with


Panel forwarding function): WEB Configure Touch Panel(86 box
series),WEB Configure Touch Panel(I series)

1.5 Update Notes

Updated Updated content

2023-02-13 Modify DingTalk alarm and add Telegram Zheng


alarm

2023-02-17 WeChat QR code length 64 Zheng

10 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

2023-06-06 Remove the alarm delay time, add WeCom, Zheng


add Modbus routing configuration, etc., update
all configuration dialogs of the software to the
latest, and update the latest functions

2023-06-16 Added description of the intranet penetration Zheng


function

2023-08-28 Add alarm delay time, update all configuration Zheng


dialogs of the software to the latest, update the
latest features

2024-01-24 Add WhatsAPP and other alarms, OPCUA Zheng


account and password, Influxdb database

2 Summary

2.1 Function description


The location information collected by gateway / touch panel is compiled
into configuration in X2View through "Driver Configuration" and "Page
Configuration". Then the configuration is posted on the web page, and finally
it can be accessed by computer or mobile client to realize monitoring
function.

 Software advantages:

1. Green and free installation, support both Chinese and English.

2. Support JS script to achieve logical control.

3. Support multi-Chinese language switching, which is convenient


for users to operate.

4. In "Local PC" monitoring mode, the software X2View is


configured for PC simulation.

5. The gateway has a built-in web server, which enables users to


view real-time change data and communication status through the browser

11 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

and facilitate on-site debugging. In addition, you can download the


configuration software X2View and project files.

6. The collection side supports various protocols.

7. The simulation of the gateway supports linear transformation,


support for the location function, and high and low byte exchange function.

8. Provides a SOAP interface for easy development.

2.2 Runtime environment


OS: Win 7/Win8/Win10/ Win11/WinServer 2008 etc.

Browser: Chrome, IE9(and above), Safari, Firefox, Opera etc.

3 For the first time to use

3.1 Start-up guide

X2View Using the following diagram:

Download X2View Run X2View Driver Configuration:


New Tag
Gateway if the project is modified
Page Configuration: New page
monitoring

Start monitor and Debug the Upload Page Configuration:


project Until no problem. Project Setting the connection (tie point)

3.2 Download X2View software

X2ViewThe software can be downloaded for free at the website


[Link]

Service and Support -> Downloads ->web configuration software.

3.3 X2View install/uninstall


12 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

3.3.1 Install

 X2View is a free installation software, download after clicking the


exe file can be run directly.

 Do not do anything with the registry

 no registry for any operation, no system sensitive area, generally


including the system starting area root directory, the installation
directory (Windows directory), Program directory (Program Files),
account dedicated directory.

 to non-self directory for any write operations.

 programs run wrong itself, in addition to any other file directory


have any effect.

 Feel free to copy and duplicate folders to use

 when running X2View try not to run it on the desktop(or disk C),
and run it as administrator.

 if the upload is not successful, you can run [Link], and if


that still doesn’t work, you can right-click “[Link]”, make
sure that your privilege level is set as an administrator to run this
program.

3.3.2 Uninstall

As long as the program directory and the corresponding shortcut have


been deleted (if you set up a shortcut on the desktop or some other location),
this program should be completely removed from your computer, with no
litter left behind.

3.4 Run/Exit X2View

3.4.1Run X2View

Since multiple project engineering files have been released in the


X2View configuration software, all the first X2View software will also be

13 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

prompted to select the project, or directly select the new project. as shown in
figure 3-4-1.

figure 3-4-1 select project

The driver configuration window is modified with the configuration page


window, the switch between the window automatically saves the current
changes.
Go to the driver configuration page, as shown in Figure 3-4-2

14 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 3-4-3 Driver configuration

Menu Bar: Displays the menu options that can be edited by the current
X2View software.

Shortcut bar: You can switch shortcuts to some tools or enter the
shortcut function block configuration interface.

Driver configuration bar: You can configure third-party devices or


interface protocols, and the steps are generally to configure drivers,
channels, devices, and groups.

Point configuration bar: Establish a corresponding relationship for each


point or information data to be collected.

Message Log Bar: Prints real-time messages on the current


communication status and real-time communication packets.

Status bar: displays information such as the current monitoring mode,


the total number of tags added, and the number of support points.

3.4.2Exit X2View

 click the upper right corner of the close button to close.

 click the upper left corner X2View icon, and select close from the
drop-down menu.

 click on the file menu, select close from the drop-down menu.

15 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

3.5 Use content


Users can get help documents in two ways when using the X2View
configuration software.

 press [F1] key on the keyboard.

 through software "help" menu.

3.6 Update version


The X2View configuration software will be released regularly on the
website of the X2View, and the latest version of X2View can be downloaded
and the old version can be opened.

When the version is updated, be careful to save your own Project file
and copy it to the project folder of the new version X2View configuration
software.(this feature is being optimized)

4 Operation instructions
X2View is a configuration software that runs on a PC, which is used to
configure the project, and then the project is uploaded to the gateway and
the touch screen for monitoring.

4.1 New project

First, open the main program [Link], in the "project management"


dialog box, click "new project". In the "new project" dialog box, enter the
project name and project description, choose "save path", then click “OK”,
go back to "project management" dialog, and finally click "Finish"(note: the
configuration software X2View and upload engineering can be downloaded
from inside the gateway, operation steps, please see the first section XXX),
operation steps as shown in graphic 4-1-1.

16 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

17 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-1-1 New Project

After the project is completed, the corresponding new project files can be
seen in the "management window", as shown in figure 4-1-2.

18 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-1-2 finish new project

Select the new project "test" at the management window and click "Finish" to
enter the main control interface, as shown in figure 4-1-3.

figure 4-1-3 Master control interface

4.2 New driver

As a multitudinous protocol covered by the collection end, we choose


the “ModbusRTUClient” protocol as an example. If you need to know the
configuration of other protocols, click on the "Communication Manual" under
the help menu and open “[Link]”. On the main
control interface, double-click the drive configuration, click the edit menu,
select the new driver, or click the toolbar icon directly, as shown in figure 4-
2-1.

19 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-2-1 select new driver

Select the “ModbusRTUClient” driver in the popped property box, as


shown in figure 4-2-2.

figure 4-2-2 select driver

20 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Edit the selected driven attributes:

Name: you can fill in the driver name, and it can also be named
according to the actual project requirements.

Polling time: determine the frequency of access to all devices, default


100 milliseconds. If the polling time visiting all the equipment needed is
greater than the set time, this setting is not valid. otherwise, if the polling
time visiting all the equipment required time is less than the set, you need to
wait for the time to reach the polling time will be set after the next visit. The
user can change the polling time according to the actual situation. As shown
in figure4-2-3.

figure 4-2-3 set driver properties

Click "OK" to drive the add completion, as shown in figure 4-2-4.

21 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-2-4 finish new driver

4.3 New channel


Select the current driver, right click to select the "new channel" or click the toolbar

icon , as shown in figure 4-3-1.

figure 4-3-1 select new channel


22 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

At the pop-up window, the corresponding communication parameters


are set up according to the driver communication protocol. Because we
choose the “ModbusRTUClient” driver, so the pop-up window is "Serial Port
Communication Configuration", where the name of the channel can be
named according to the actual project requirements, the range of the serial
port is COM1~COM4, the baud rate is 9600 by default, and the data bit is 8
bits by default.

Network timeout time: the gateway waits for the longest response of the
device. When communication is normal, setting up longer does not affect
communication speed. if the response speed of the device is slower, in order
to avoid communication failure, it is recommended to set up a longer one,
with a default of 1000 milliseconds. The specific settings are shown in figure
4-3-2.

figure 4-3-2 Serial Port Communication Configuration

Since this acquisition end uses analog data from the Modbus Slave, the
serial communication parameters should be consistent with the settings in
the “Modbus Slave”, “Response Timeout” default 1500ms, if the device
response speed is slow, in order to avoid communication failure, it is
recommended to set a longer, such as the following figure 4-3-3.

23 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-3-3 Communication parameter comparison

After the channel is added, as shown in figure 4-3-4.

Figure 4-3-4 Adding a channel is complete

4.4 Add a device

Select the current channel, right click select new device or click the
toolbar

, as shown in figure 4-4-1.


24 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-4-1 select new device

After the channel is added, as shown in figure 4-3-4:

Name: the name of the equipment can be filled in, and it can be
named according to the actual project requirements.

Device ID: ID(address) of the collected equipment.

Delay Between Polls: the time interval issued from the current
request frame to the next request frame, with a default of 50 milliseconds.
When the response of the device is slow, this value can be increased.

Bulk Transfer: in the support of group packet communication protocol,


in order to increase transmission speed, the same register type can realize
group packet communication under continuous register address. If the
packet communication is not supported, the parameters under "Bulk
Transfer" should be set to 0. In addition, when the response time of the
device is slow, the time interval between the data frame and the frame can
be set. The 2 and 4 byte floating-point number and order adjustment
function is used in data transmission equipment, such as electric meter in
data transmission will adjust the high and low order, this time will be using
this function, generally use the default parameters, as shown in figure 4-4-2.

25 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-4-2 device properties

Click "OK" and the device is added, as shown in figure 4-4-3.

figure 4-4-3 finish new device

26 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.5 Add tags


Under the device, you can create new tags directly, or you can set up a
group first, then create tags in the group. Right-click the device, select “New
Group“or click the toolbar icon , as shown in figure 4-5-1.

figure 4-5-1 new group

New groups are added to complete, as shown in figure 4-5-2.

27 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-5-2 new group complete

If you don't need to build a group, you can create new labels directly
under the device. Right-click the device, select “new label“ or click the
toolbar icon , as shown in figure 4-5-3.

figure 4-5-3 new tag

After the configuration is complete, as shown in Figure 4-5-4 below

28 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-5-4 Label Addition Complete

Right-click to cut, copy, paste, delete, and also choose to copy the roll
call to facilitate the binding of points on the configuration screen.

You can also select multiple tags to make bulk modifications.

Figure 4-5-5 Right-click on the label

Note:

1. Improve the efficiency of configuring points, which can be imported and


exported to Excel through batch modification.

2. It is recommended that the collector end be allocated in order under the


same register type, and try not to leave free addresses, so as to facilitate
the packaging and improve efficiency.

3. If you don't need to configure the screen, you can directly upload it to the
gateway monitoring when the gateway is used.

4.5.1 Register type of collection terminal

Set the parameters of the collection end in the pop-up "Tag Properties"
dialog box, which:
29 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

(1) Name: It can be named according to the requirements of the


actual project.

(2) Data Type: The datatype of Boolean, Word, Short, DWord, Long,

Float, Double, String can be selected.

(3) Register Type: 1) 0X(Coil Status) —— corresponding BO

2) 1X(Input Status) —— corresponding BI

3) 3X(Input Register) —— corresponding AI

4) 4X(Holding Register) —— corresponding AO

(4) Register Address: notice that the initial address of the Modbus
server's memory address begins at 1.

Linear conversion: linear amplification of the original data or reduction


of the engineering data required to be displayed in the configuration picture.

Tag properties interface is shown in figure 4-5-4.

30 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-5-4 tag setting

4.5.2 Register type and number of transfer terminal

1. support the BACnet IP/MSTP server, which is supported by the


register type and the number of the following tables.

Note: The register number of the gateway is dynamically supported,


and each register can build up to 2048 points at most, and the total number
of registers is not more than 2048(containing virtual points).

31 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

BACnet Register Type BACnet Register Numbers

AI (Reading Only, No Writing) 2048(0~2047)

AO (Reading & Writing) 2048(0~2047)

AV (Reading & Writing) 2048(0~2047)

BI (Reading Only, No Writing) 2048(0~2047)

BO (Reading & Writing) 2048(0~2047)

BV (Reading & Writing) 2048(0~2047)

MSI (Reading Only, No Writing) 2048(0~2047)

MSO (Reading & Writing) 2048(0~2047)

MSV (Reading & Writing) 2048(0~2047)

2. Support the Modbus RTU/TCP server, which is supported by the


register type and the number of the following tables.

Note: The register number of the gateway is dynamically supported,


and each register can build up to 2048 points at a maximum and the total
number of registers is not more than 2048.

4X and 3X register address = BACnet Instance Number*2+1

0X and 1X register address = BACnet Instance Number+1 In transfer


register type is 4X and 3X, only Float type.

Modbus Register Type ModbusRegister


Number

32 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

0X(Coil Status)(Reading & Writing) 2048(1~2049)

1X(Input Status)(Reading Only, No Writing) 2048(1~2049)

4X(Holding Register)(Reading & Writing) 2048(1~1024)

3X(Input Register)(Reading Only, No Writing) 2048(1~1024)

Click "OK" to complete the add tag, as shown in figure 4-5-5.

figure 4-5-5 finish adding tags

Note:

1. we can import and export Excel and batch modification to improve


the efficiency of the configuration point.

2. It is suggested that the collection end is allocated in sequence under


the same register type, and try not to leave free address as much as
possible, so as to facilitate the package and improve the efficiency.

3. if the configuration screen is not needed, when the gateway is used,


it can be uploaded directly to the gateway monitoring, as detailed in
4.9.

33 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.6 Transfer terminal setting

X2View can be converted into some of the following standard protocol


types, and users can choose to select according to their needs. The
parameters of each set interface suggest that the default parameters are
illustrated and modified when necessary.

Note: the following forwarding server can be selected, that is to say at


the same time can be converted into Modbus and BACnet.

4.6.1 BACnet server

[Link] BACnetIP

Click on the "Interface" of the menu bar, select "BACnet Server", and
select "BACnet IP Settings" to open the “BACnetIP Server Setting” settings
screen.

34 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-1 Select BACnet IP Settings in the menu bar

figure 4-6-2 BACnetIP Server Setting

Gateway Name: You can modify the name of the current gateway.

35 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Communication Parameters:

Port: Port 47808 is used by default for BACnet IP communication, and is


generally not modified.

Device ID: the device address (instance number) of the BACnet IP


communication.

COV change accuracy: If the COV mode is enabled in the device


properties during communication, you can modify the COV data change
accuracy.

TrendLog storage interval: You can set the storage period of TrendLog.

List of Alarm Receivers : Add the IP address and port number of the host
computer or BACnet client.

BBMD:If BBMD is set to BACnet cross-network segment, fill in the BBMD


by checking Register as an external device, and then fill in the IP address
of the corresponding host computer in the following IP address, and set the
IP address of the corresponding BBMD device to the IP address of the
current BBMD gateway in the corresponding host computer.

When converting to BACnet protocol, pay attention to the BACnet


character encoding selection, the default is UTF-8. If the host computer
needs Chinese display, such as Johnson Metasys system, it needs to be
selected as Unicode.

Before uploading the project, the automatic arrangement of register


addresses will be clicked, and the system will be sorted automatically
according to the type of register to prevent repetition.

[Link] BACnetMSTP

Click on the "Interface" of the menu bar, select "BACnet Server", and
select "BACnet MSTP Settings" to open the “BACnet MSTP Server Setting”
settings screen. Figure 4-6-3 below shows it

36 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-3 Select BACnet MSTP Settings in the menu bar

Go to the BACnet MSTP settings screen. This option is set to enable it,
as shown in Figure 4-6-4.

figure 4-6-4 BACnet MSTP Server Setting

Gateway Name: You can modify the name of the current gateway.

37 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Communication Parameters:

Device ID: the device address (soft address) of the BACnet MSTP hardware;

Mac address: the Mac address of the BACnet MSTP hardware (hardware
address);

Serial port: which serial port of the hardware gateway is used to transfer out
the BACnet MSTP protocol;

Baud rate, data bits, stop bits, check bits: set the serial port parameters
of the BACnet MSTP bus;

Timeout Period: The timeout period allowed for BACnet MSTP device
communication is generally 50ms by default.

[Link] Arrange address/character encoding

Click "Forwarding End" in the menu bar, select "BACnet Server", and
select "Auto Arrange Register Addresses" or "BACnet Character Encoding"
to automatically arrange the register addresses of the forwarding end and
modify the character encoding format of the BACnet service, as shown in
Figure4-6-5 below.

Figure 4-6-5 Arrange address/character encodings

38 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Before uploading the project, it is recommended to click on the


automatic arrangement of register addresses, and the system will
automatically sort them according to the register type to prevent duplication.

When converting to BACnet protocol, pay attention to BACnet character


encoding selection, the default is UTF-8, if the host computer needs to
display in Chinese, (such as EBI system) needs to be checked as UCS-2.

MBCS: Insight、Delta 、etc.

UCS-2:EBI、etc

UTF-8:Metasys、Niagara 、WEBControl、etc.

4.6.2 Modbus server

[Link] ModbuTCP

Click on the "Interface" of the menu bar, select "Modbus TCP Server",
and select "Modbus TCP Settings" to open the “Modbus TCP Server Setting”
settings screen , as show in Figure 4-6-6 below.

Figure 4-6-6 Select Modbus TCP Settings in the menu bar

39 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-6-7 ModbusTCP Server Setting

If the protocol of the WEB configuration product is Modbus TCP, the Modbus
addresses and data types corresponding to all data points shall follow the
following rules:

(1) When the outgoing register type is 3X and 4X register type, the
corresponding Modbus register address = BACnet register address * 2 + 1;

(2) When the outgoing register type is 0X and 1X register type, the
corresponding Modbus register address = BACnet register address + 1;

(3) The forwarded data type follows the data type of the collection end,
if the linear conversion function is enabled at the point, the forwarded data
type is Float.

[Link] ModbusRTU

Click on the "Interface" of the menu bar, select "Modbus RTU server",
and select "Modbus RTU settings" to open the “Modbus RTU Server
Setting” settings screen, as show in Figure 4-6-8 below.

40 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-8 Select Modbus RTU settings in the menu bar

The top-window is as following figure 4-6-9. The communication


parameters are configured according to the actual situation.

figure 4-6-9 ModbusRTU Server Setting

Communication Parameters:

Station number: Modbus RTU bus address (device address);

Serial port: which serial port of the hardware gateway is used to transfer out
the Modbus RTU protocol;

Baud rate, data bits, stop bits, check bits: set the serial port parameters
of the Modbus RTU bus;

If the protocol of the WEB configuration product is Modbus TCP, the Modbus
addresses and data types corresponding to all data points shall follow the
following rules:

(1) When the outgoing register type is 3X and 4X register type, the
corresponding Modbus register address = BACnet register address * 2 + 1;

(2) When the outgoing register type is 0X and 1X register type, the
corresponding Modbus register address = BACnet register address + 1;

41 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

(3) The forwarded data type follows the data type of the collection end, if the
linear conversion function is enabled at the point, the forwarded data type is
Float.

[Link] Arrange address/character encoding

Click "Forwarding End" in the menu bar, select "Modbus Server", and
select "Auto Arrange Register Addresses" or "Byte Format" to automatically
arrange the register addresses of the forwarding end and modify the byte
format of data transmission, as shown in Figure 4-6-10 below.

Figure 4-6-10 Arrange address/byte format

Before uploading the project, it is recommended to click on the


automatic arrangement of register addresses, and the system will
automatically sort them according to the register type to prevent duplication.

When converting to Modbus protocol, pay attention to the Modbus byte


format selection, the default is big-endian (standard), if the host computer is
WinCC, configuration king, etc., you need to select "little-endian" mode to
change the byte order.

If you select Float to Long, the data type of the Float on the collecting
side will be converted in the form of Long on the Modbus forwarding side,
and the decimal places of the Float type will be discarded, leaving only the
integer part to be sent.

42 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.6.3 Forwarding side

[Link] OPC XML-DA

Click on the "OPC XML-DA WebService " of the menu bar, settings
screen.

The server is opened default, the top-window is as following figure 4-6-


11.

Figure 4-6-11 Select OPC XML-DA Server in the menu bar

Go to the OPC XML-DA Server Setup page. By default, all Xunrao


hardware products enable the OPC XML-DA server, as shown in Figure 4-6-
12 below.

figure 4-6-12OPC XML-DA Service

Note:

(1) The default OPC XML-DA server is enabled

(2) The port of the OPC XML-DA server can be modified by modifying the
port number parameter

(3) The URL format of the OPC XML-DA server is [Link]


43 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

[Link] OPC UA Server

Click on the "OPC UA Server " of the menu bar, settings screen the top-
window is as following figure 4-6-13.

Figure 4-6-13 Select OPC UA Server in the menu bar

Go to the OPC UA settings page. This option allows you to enable the
OPC UA server, and you can change the port number parameter to set the
port number for OPC UA communication. There is no need to configure
DCOM to use OPC UA client access. User authentication and server
certificates can be configured.

figure 4-6-14 OPC UA Server

4.6.4 IEC61850 Server

Click on the "IEC61850 Server " of the menu bar, settings screen. the
top-window is as following figure 4-6-15.

44 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-15 Menu Bar Select IEC61850 Server

Enter the IEC61850 settings interface, you can set the port number and
IED name of the IEC61850;

figure 4-6-16 IEC61850 Server

4.6.5 Remote databases

Click Forward in the menu bar, select Remote Database, or click the

shortcut icon“ ” to enter the external database settings page, as shown


in Figure 4-6-16below.

45 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-16-16 Select External Database in the Menu Bar

Enter the external database setting interface, you can set the database
type (MySQL or Microsoft SQL Server); Storage mode of real-time data: (1)
change storage mode; (2) Customize the cycle storage mode. It is also
possible to store alarm records set in the gateway. Analog data supports
cycle storage mode and change storage mode, and switching points only
support change storage mode.

You can customize parameters such as the gateway name, database


address, database port number, user name, password, database name, and
table name, as shown in Figure 4-6-17. Select to turn it on.

46 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-6-17 Remote SQL Database

Illustrate:

Gateway Name: Specify the name of the current gateway.

Database type: You can set the database type to MySQL or Microsoft SQL
Server.

IP address: the IP address of the external database server, which can be


the IP address of the LAN database server or the IP address of a cloud
data server.

Port Number: The port number of the external database.

Username: Enter the username for database access.

Password: Enter the password for database access.

Database Name: Set the name of the database.

Test: This parameter is used to test whether the currently configured


parameters can be connected to the database.

47 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Real-time Data Table Name: Set the name of the real-time data table. The
fields of the table are XGateway, XTagName, XValue, XQuality,
XTimeStamp, and XDescription (gateway name, point name, value, quality
stamp, time, and description). "Note, the new version has an additional
XDescription field"

XQuality: Good returns 192, Bad returns 0, and Uncertain is 64, indicating
that the value has not been assigned and has not been updated.

Alarm Record Table Name: Set the name of the alarm record table. The
fields in the table are XGateway, XTimeStamp, and XMessage (gateway
name, time, and alarm content).

Create a table: Create a database table with the corresponding name in


the corresponding database.

Note:

The external database function is to store the real-time data read by our
gateway into the MySQL/SQL Server database of the specified LAN or
cloud server at a custom period. Before using the external database
function, you need to enable the historical storage function of tag points in
the tag properties, as shown in Figure 4-6-18

48 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-18 Enabling tags in the external database

[Link] MySQL external database

To enable remote access to MySQL databases, run the following


commands: (1) use MySQL; ② grant all privileges on *.* to root@"%"
identified by 'admin123456' with grant option; ③flush privileges。

Establish the database name and real-time data table set by the
configuration software X2View in the database, and then establish the field
structure shown in Figure 4-6-19 according to the corresponding fields.

49 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-19 Real-time data table fields

After reading the data, the gateway stores the data in the specified
database according to the configured storage mode (change storage or
periodic storage), as shown in Figure 4-6-20.

Figure 4-6-20 Real-time data recording table

50 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Establish the alarm record table name set in the configuration software
X2View in the database, and then establish the field structure as shown in
Figure 4-6-21 according to the corresponding fields.

Figure 4-6-21 Fields in the alarm record table

After reading the data, the gateway stores the data in the specified
database according to the configured storage mode (variable storage or
periodic storage), as shown in Figure 4-6-22.

Figure 4-6-22 Alarm log table

51 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

[Link] SQL Server external database

Establish the database name and real-time data table set by the
configuration software X2View in the SQL Server client tool, and then
establish the field structure as shown in Figure 5-7-23 according to the
corresponding fields. "Note, the new version has an additional XDescription
field"

Figure 4-6-23 Real-time data table fields

After reading the data, the gateway stores the data in the specified
database according to the configured storage mode (change storage or
periodic storage), as shown in Figure 4-6-24.

52 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-24 Real-time data recording table

Establish the alarm record table name set in the configuration software
X2View in the database, and then establish the field structure as shown in
Figure 4-6-25 according to the corresponding fields.

Figure 4-6-25 Fields in the alarm record table

After reading the data, the gateway stores the data in the specified
database according to the configured storage mode (change storage or
periodic storage), as shown in Figure 4-6-26.

53 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-6-26 Alarm log table

[Link] Influx DB external database

If you select InfluxDB as the data type, enter the connection parameters
corresponding to the database, and manually create a database with the
following name in the InfluxDB database, for example: aa, you do not need
to manually create a table name, and the table name will be automatically
generated when storing data normally, for example, data. Note: InfluxDB 2.0
or earlier databases, for example, 1.8 can be supported, but 2.0 and above
are not.

Figure 4-6-27 Real-time data table fields

In the database then based on the corresponding fields and query


results;

54 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

55 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.7 Alarm

4.7.1 GPRS

Click "Alarm" in the menu bar and select "GPRS modem..." or the

shortcut key icon“ ” to enter the SMS alarm setting interface, as shown in
Figure 4-7-1 below.

Figure4-7-1 Select GPRS modem in the menu bar

Enter the 4G GPRS modem interface, check Turn on SMS alarm, and
enable the SMS alarm function; The remote test indicates that an SMS
alarm message is sent through the gateway test.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a

56 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

Figure 4-7-2 4G SMS modem configuration interface

Note:

For more information about how to implement the SMS alarm function at a
data communication point, see the Appendix SMS Alarm Operation Steps.

4.7.2 Phone

Click "Alarm" in the menu bar and select "Phone...", you can enter the
phone alarm setting interface, as shown in Figure 4-7-3below.

Figure 4-7-3 Select Phone in the menu bar

57 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Enter the telephone alarm setting interface, check Turn on telephone alarm,
and you can turn on the telephone alarm function of the 4G gateway;
Remote test means that the alarm is dialed through the gateway test.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a
lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

Figure 4-7-4 Telephone alarm setting screen

Note:For details on how to implement the telephone alarm function at the


data communication point, see the Appendix Telephone Alarm Operation
Steps.

4.7.3 SMS platform

Click "Alarm" in the menu bar and select "SMS Platform...", you can
enter the alarm setting interface of the SMS platform, as shown in Figure 4-
7-5 below.

58 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-5 Select SMS Platform in the menu bar

Go to the SMS platform settings page, as shown in Figure4-7-6 below.


Select the operator to enable the corresponding SMS platform alarm, and
disabling it means that this function is not enabled.

Figure 4-7-6 Alarm setting screen of SMS platform

Illustrate:

Carriers: You can choose the currently supported carrier platforms;

Gateway Name: Enter the name of the gateway.


59 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Enterprise number: the enterprise number filled in when applying for an


account on the platform;

Username: the username filled in when applying for an account on the


platform;

Password: the password filled in when applying for an account on the


platform;

4.7.4 WeChat server

[Link] Gateway configuration

Click on the menu bar "Alarm", select "WeChat", you can open the
WeChat alarm screen, as shown in the following figure 4-7-7.

Figure 4-7-7 Select WeChat in the menu bar


Select to “Enable WeChat alarm” and set WeChat server parameter, as
shown in the following figure 4-7-8.

60 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-7-8 WeChat Alarm

IP address: fill in the IP address of the cloud server. A gateway, a touch


screen, or a computer with a WeChat alarm function, all need to be able to
access the Internet. Note: the cloud server needs to be deployed, detailed
inquiry technical support.

【 Note 】 : If you need to deploy a private cloud, use the customer's own

WeChat public platform to push alarm information, and the customer's


cloud server needs to be deployed.

Company ID: customer's company ID.

Device Name: it will be displayed in the received WeChat alarm content to


distinguish the alarm sent from different devices.

Unique ID: the unique ID of the WeChat alarm gateway (the project file of
the gateway), and the replacement device needs to be clicked
automatically.

Group Name: that is, select the user group that needs to send the alarm
information. Selecting a user group will generate a two-dimensional code.

61 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Users need to scan the two-dimensional code and pay attention to this user
group, and then scan it again to receive the alarm information of the device.
If the user pays attention to another device or another user group, you need
to scan the two-dimensional code again. Without a user group, a user
group can be added to the user group managed by the user in the menu
bar.

Note: you need to apply for a WeChat public number on your own.

When the settings are completed, click monitoring, and the outside limit
will be sent to all users of the user group according to the set alarm content
of WeChat. The received WeChat alarm information is as follows:

figure 4-7-9received WeChat Alarm Information

Note:

For the specific operation steps of how to implement the WeChat alarm
function of the data communication point, please refer to the appendix
WeChat alarm operation steps.

[Link] Test locally


62 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Test local WeChat alarm:

(1) Fill in the WeChat server parameters, including IP address, company ID,
gateway name, gateway ID and group name;

(2) Under the premise that the current computer can access the Internet,
click the test to push WeChat messages to the designated WeChat group.

4.7.5 Ding Talk

[Link] Gateway configuration

Click "Alarm" in the menu bar and select "Ding Talk...", you can enter
the DingTalk alarm setting interface, as shown in Figure 5-6-10 below

Figure 4-7-10 Select Ding Talk in the menu bar

Enter the Ding Talk alarm setting page, as shown in Figure 4-7-11
below. Select Enable Ding Talk Alarm to set it.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
63 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a
lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

Figure 4-7-11 Ding Talk alarm setting screen

Company Name: The company's letterhead that alerts the alarm.

Access Token: Enter the access token of the webhook address generated
by the custom Ding Talk bot in the Ding Talk group chat, as shown in Figure
4-7-12 and Figure 4-7-13.

Figure 4-7-12 Setting up a Ding Talk bot for group chats

64 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-13 Generating a webhook

Note:

(1) The webhook address in Ding Talk needs to be viewed in the robot
management on the PC side, and the webhook address in Ding Talk cannot
be viewed on the mobile phone.

(2) You need to customize the keyword, here we use the header "device
alarm reminder" of our DingTalk alarm. Corresponds to the X2View company
name field described above.

(3) For the specific operation steps of how to realize the DingTalk alarm
function of the data communication point, you can refer to the appendix
DingTalk alarm operation steps.

[Link] Local Testing

Test local Ding Talk alarm:

(1) Fill in the access token of the webhook in Ding Talk Alert;

65 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

(2) Under the premise that the current computer can access the Internet,
click Test to push Ding Talk messages to the designated Ding Talk group
chat.

4.7.6 Mail

[Link] Gateway Configuration

Click "Alarm" in the menu bar and select "Email...", you can enter the
email alarm setting interface, as shown in Figure 4-7-14 below.

Figure 4-7-14 Menu Bar Selecting Messages

Go to the email alert settings page, as shown in Figure 4-7-15 below.


Select Enable email alerts to set the settings.

66 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-15 E-mail alarm setting screen

Illustrate:

Outgoing Mail Server (SMTP): The SMTP server used to fill in the outbox;

Port number: Select the port number used by the SMTP service, and it is
recommended to select port number 465 or 587 for overseas use.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a
lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

E-mail address: Enter the email address of the outbox;

Client Authorization Password: Enter the client authorization code when


the client SMTP service is enabled in the Outbox.

67 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

If you are building a private mail server and enable passwordless mode in
the Outbox, you can leave the client authorization code blank and use the
client authorization code in the Outbox.

Mail servers provided by Shanghai Sunfull

Address: [Link]

Email: alarm@[Link]

Password: admin

Figure 4-7-16 The SMTP service is enabled for the QQ mailbox

Figure 4-7-17 SMTP service is enabled for mailbox 163

Figure 4-7-18 Mailbox 163 obtains the client authorization password

Note:

68 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

For more information about the operation steps of the email alert function,
see Appendix Email Alert Operation Steps.

[Link] Local Testing

Test the email alert service settings:

(1) Fill in the email address of the inbox;

(2) Fill in the prompt message text of the alarm for the alarm content;

(3) Under the premise that the current computer can access the Internet,
click Send to test the email alarm locally.

4.7.7 Alarm List

Click "Alarm" in the menu bar and select "Alarm Point Table" to enter
the alarm point table interface, as shown in Figure 4-7-19 below

69 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-19 Collection of alarm points

Enter the alarm point table page to view all alarm points configured in
the current project, and you can also modify and turn the alarm on and off.
As shown in Figure 4-7-20:

Figure 4-7-20 Alarm points are displayed

4.7.8 Telegram
70 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Click "Alarm" in the menu bar and select "Telegram...", you can enter
the Telegram alarm setting interface, as shown in Figure 4-7-21 below.

Figure 4-7-21 Select Telegram in the menu bar

Go to the Telegram alarm settings page, as shown in Figure 4-7-22


below. Check Turn on Telegram alerts and set them.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program
runs normally, the alarm service is started, not how many seconds the alarm
is delayed. In the debugging stage, you don't want to use it when you upload
a lot of alarms when you upload the project, or when you don't need to send
a lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

71 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-22 Telegram alarm setting screen

Follow the steps below to obtain the token and chat_id of the custom
bot:

1. Search for @BotFather to create a bot

72 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

2. Enter the /newbot command to start creating your bot

3. Enter the name of the bot, ending with bot, not case-sensitive, just send it
directly, if the name is the same, it will prompt you to re-enter

73 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4. Enter @userinfobot get the chatID

5. Open a conversation with the bot

74 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Above we created the "sunfull_test_alarm" bot, and to talk back to it,


send a "@sunfull_test_alarm" in any chat window and click on the message
to open a chat with the sunfull_test_alarm.

If you need the bot to send a message to a group, you'll also need to
pull the bot into the group.

Special note: You need to create a conversation with the bot before the
bot can send a message, otherwise the bot can't send a message actively!

4.7.9 WeCom

Click "Alarm" in the menu bar and select "WeCom...", you can enter the
WeCom alarm setting interface, as shown in Figure 4-7-23 below.

75 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-23 Select WeCom in the menu bar

Enter the WeCom alarm setting interface, as shown in Figure 4-7-24


below. Select Enable Enterprise Alert and set the settings.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally).

Startup delay alarm (seconds): When the program runs normally, the
alarm service is started, which does not refer to the number of seconds the
alarm is delayed. In the debugging stage, you don't want to use it when you
upload a lot of alarms when you upload the project, or when you don't need
to send a lot of invalid alarms when you don't need to send a lot of invalid
alarms when you upload the project.

76 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-24 Enterprise alarm setting screen

Follow the following methods to obtain and configure WeCom alarms.

1. In the enterprise group, click in the upper right corner to add a group bot

2. Click Add bot

77 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

78 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

3. Create a new bot

4. Give the swarm bots a group nickname

79 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5. Obtain the webhook address, and the value of the key field of this address
is to be configured into the X2View software

6. Obtain a token

[Link]
4ca9-a917-45391da16836

4.7.10 Viber

Click "Alarm" in the menu bar and select "Viber...", you can enter the
Viber alarm setting interface, as shown in Figure 4-7-25 below.

80 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-25: Select Telegram in the menu bar

Enter the Viber alarm settings page, as shown in Figure 4-7-26 below.
Select Enable Viber Alarm and set it.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a
lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

81 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-26 Viber alarm setting screen

4.7.11 WhatsApp

Click "Alarm" in the menu bar, select "WhatsApp", and tick it, as shown
in Figure 4-7-27 below.

Figure 4-7-27 Select WhatsApp in the menu bar

82 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Note: This feature requires a customized version of WhatsApp's


firmware information to be supported.

Configure WhatsApp alarm message recipients

Open the http:// gateway IP address: 8080 in a browser to enter the


configuration page, as shown in the following figure, the IP address of the
current demo gateway is [Link], and the default gateway IP address
is [Link]

After entering the configuration page, click the + button in the upper
right corner to add a person who receives WhatsApp alarm, the name is
customized, and you can not repeat it

After adding a user, the user needs to wait for the QR code
authorization and click Authorize to log in

83 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Open WhatsApp Software Scan Authorization

84 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

85 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

After the authorization is successful, the user name and user ID are
displayed, and the user configuration is successful, and the multi-user
configuration is the same as above

86 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

After authorization, you can click Send Test Message to see if the
message can be received, or trigger the gateway point alarm

4.7.12 Byte Feishu

Click "Alarm" in the menu bar and select "Byte Feishu...", you can enter
the alarm setting interface, as shown in Figure 4-7-28 below.

87 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-7-28 Select Feishu in the menu bar

Enter the alarm setting page, as shown in Figure 4-7-29 below. Select
Enable Byte Feishu Alarm and set it.

Set the initial start time of the SMS alarm (how many seconds after the
program runs normally)

Start delay alarm (seconds): How many seconds after the program runs
normally, the alarm service is started, not how many seconds the alarm is
delayed. In the debugging stage, you don't want to use it when you upload a
lot of alarms when you upload the project, or when you don't need to send a
lot of invalid alarms for the first time when you don't need to send a lot of
invalid alarms when you upload the project.

Figure 4-7-29 Alarm setting screen

Add a custom bot to the group

Procedure

Invite a custom bot to the group.

Go to the target group, click the More button in the top right corner of the
group, and tap Settings.

88 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

On the right Settings interface, click Swarm Robots.

On the Swarm Robot interface, click Add Robot.

In the Add Bot dialog box, find Custom Bot, and Add.

89 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Set the name and description of the custom bot and click Add.

Get the webhook address of your custom bot and click Done.

After the bot is successfully added, view the webhook address


corresponding to the bot. The address format is as follows:

Please keep the webhook address and copy it for a record

90 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.8 IOT

4.8.1 MQTT server

The MQTT server is mainly used for Sunfull WEB configuration


products to collect real-time data on site, and upload the data to the cloud
platform MQTT server, with Sunfull configuration gateway, configuration
touch screen and other on-site configuration screens, through the cloud
platform to realize remote mobile phones, iPad, computers to monitor the
on-site configuration screen, and solve the problem of remote monitoring of
on-site pictures by customers.

If you want to convert field data to MQTT IoT protocol, you need to
subscribe to the MQTT server that comes with the configuration gateway
and touch screen. To learn more about the topic format of the message
reported by the gateway and the topic format of the control command
received by the gateway, you can consult Sunfull technical support.

91 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

[Link] MQTT Server Settings

Click IoT in the menu bar and select MQTT Server to enter the MQTT
server settings page, as shown in Figure 4-8-1 below.

Figure 4-8-1 Select MQTT Server in the menu bar

Go to the MQTT server settings page, as shown in Figure 4-8-2 below.


Select Enable MQTT client to set the settings.

92 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-8-2 MQTT Server setting

IOT Platform: different platform means different message format for


MQTT.

IP Address: The IP address of the cloud server which is uploaded by


MQTT.

Note: the client cloud server needs to be deployed. For details, please
refer to Sunfull technical support.

Port: 1883, 2883, 3883(Optional), Multi-channel can play a shunt, reduce


network congestion.

Topic: <Required> custom can only use letters or Numbers.

Gateway Name: [Link] uploading to the cloud, the theme,


gateway name and gateway ID will be checked to see if they are duplicated.

Gateway ID: One gateway corresponds to one topic, and different gateway
suggested topics and gateway id are unique. You can click "Generate" to
get a unique ID.

93 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Keep alive:: in order to maintain the reliability of the long connection and for
both parties to confirm whether or not each other is online, you need to
specify the time to stay online, and the default is recommended 60ms.

QoS: Transport message level, default is 1.

Level 0: at most one transmission. That is to send out the fire off, there is
no later things.(fast speed)

Level 1: at least one transmission. You must wait for an ACK after it is sent.
If there is no ACK, you must find a time to send it again.

Level 2: only one transmission. The message ID will have a simple


lifecycle.(high reliability)

Upload Cycle: in addition to change reporting, this period can also be set
to active reporting, default 60s.

Data change Upload Data: After checking, data precision can be selected.
0.1, 0.01, 0.001, 0.0001, 0.00001, 0.000001(optional)

Disable Control from MQTT: uncheck by default. After checking, the


cloud access configuration page can only be viewed, not controlled.

[Link] Cloud configuration monitoring

First, log in to the ECS as the company administrator (for example, the
address of the Sunfull ECS is [Link]), open configuration
management, and upload the configuration.

For detailed cloud operation instructions, please refer to [Sunfull Cloud


Platform Monitoring Software Operation Instructions (Company
Administrator).doc].

94 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-8-3 Configuration upload

Configuration Name: Enter a name for the configuration project

Configure Home Page File Name: Enter a file name for the initial page

Upload configuration: Select the zip of the configuration project package


to be uploaded

Select Upload, the configuration project file will be uploaded to the cloud
server, refresh the current web page, and the configuration screen you just
uploaded will also be displayed under the configuration management, as
shown in the following figure.

95 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-8-4 Cloud configuration screen display

That is, as long as there is a network, users can use mobile phones,
computers, and iPad to remotely monitor terminal devices through
browsers.

4.8.2 Energy Conservation Office Energy Consumption Platform

[Link] Introduction to the platform services of the Energy


Conservation Office

The function of the energy-saving office energy consumption platform is


mainly used for Sunfull's gateway to collect real-time data on the site, and
upload the data to the corresponding energy-saving office energy
consumption platform in a specific format to solve the data upload problem
of the customer's energy-saving office energy consumption platform.

There are different formats for specific gateways to be reported to


specific energy-saving offices, and specific docking details can be consulted
with Sunfull technical support.

Click "IOT" in the menu bar and select "Energy Saving Office", as
shown in Figure 4-8-5.

Figure 4-8-5 IOT/Energy Conservation Platform

96 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Enter the energy consumption platform setting interface of the Energy


Conservation Office, as shown in Figure 4-8-6 below. Select Enable Energy
Consumption Data Upload to set the settings.

Figure 4-8-6 Energy consumption platform

Enable energy consumption data upload: Select this option to enable


scheduled upload of energy consumption data.

Gateway Code: Custom; The gateway acts as the ID of the collection


device.

Energy Consumption Platform: Select the energy consumption


management platform to be uploaded (different platforms have different
upload formats for gateways).

IP address: the IP address of the interconnected city platform.

Port Number: The port number of the interconnected city platform.

Building Code: Generally provided by the local Energy Conservation


Office.

97 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Gateway Key and MD5 Code: Set the protocol key of the interconnecting
city.

Proactive Reporting Cycle: Set this period for proactive reporting, which
is 120 seconds by default.

Change accuracy: You can set the upload change precision, and the
precision of 1 to 6 decimal places is optional.

Computed: Select whether the data is processed accordingly.

Note: The building code is provided by the Energy Conservation Office and
is generally generated during the declaration process; Whether the
reporting period and value have been calculated or not, the user can select
according to the actual situation.

[Link] Set the data collection point identification

In the device attributes, the device name is used to represent the


current collection point, as shown in Figure 4-8-7, 330106H007 indicates
No. 7 of other buildings in ZZ District, YY City, XX Province; 01 indicates
the code of the current gateway; 0001 indicates the first table that is
currently collected. The type of equipment can be selected according to the
energy consumption classification.

98 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

[Link] Set the data point name and itemized information

In the point attributes, the description of the point indicates the partial
code of the current data, as shown in Figure 4-8-8. The description
represents the itemized information of the current data point, for example,
01B00 indicates the electricity consumption of the air conditioner; The value
type corresponds to the energy consumption data type, for example, the
total positive active energy corresponds to the uploaded code of 1090.

Figure 4-8-8 Setting point attributes

4.8.3 POP3 receiving mailbox

Click "IOT" in the menu bar and select "POP3 Receiving Mailbox" to
open the POP3 receiving email settings page, as shown in Figure 4-8-9
below.

99 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-8-9 POP3 receives mailbox

On the configuration page, you can select POP3 to enable receiving


emails, as shown in Figure 4-8-10 below.

Figure 4-8-10 Enable POP3 to receive emails

Illustrate:

POP3 mail server: The mail server used to receive mailboxes, the POP3
mail server of the commonly used 163 mailbox is [Link], and the
POP3 mail server of qq mailbox is [Link].

E-mail address: Specify the e-mail address to receive the e-mail.

100 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Client authorization password: Enter the client authorization code when the
client POP service is enabled in the outbox, please refer to the 4.7.5 Email
Alarm Description section for details.

Note:

The receiving mailbox used by POP3 will automatically empty the inbox after
receiving the receiving email, so it is recommended to use a newly created
mailbox or an infrequently used mailbox as the receiving mailbox for POP3.

4.8.4 Upload projects remotely

Click IoT in the menu bar and select Remote Upload Project to open the
remote upload project configuration page, as shown in Figure 4-8-11 below.

Figure 4-8-11 Remotely uploading a project

Go to the Remote Update MQTT Server Settings page, select Enable


Remote Upload Project to Gateway, and enter the corresponding IP address
or domain name of the MQTT server and its corresponding port number.

101 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-8-12 Remotely updating MQTT server settings

102 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Note:

The premise for enabling the remote upload function is that: (1) the gateway
needs to be able to connect to the Internet; (2) This function has been
enabled when uploading the project in LAN mode; (3) The computer where
X2View is located is connected to the Internet.

If you enable remote upload, you need to note that the gateway for
remote upload is distinguished based on the gateway name, subject, and
gateway ID set in the MQTT service. If you have multiple gateways, be sure
to distinguish between these three parameters.

4.8.5 Intranet penetration

Click IoT in the menu bar and select Intranet Penetration to open the
remote upload project configuration page, which supports three modes: FRP,
port mapping, and cloud penetration, as shown in Figure 4-8-13 below.

Figure 4-8-13 Intranet penetration

[Link] FRP

Log in to the cloud account and password, and use the gateway to
transparently map port 80 of LAN [Link] to port 10248 of the cloud.

103 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The following message indicates success.

In this case, you can use the cloud IP address [Link] plus port
10248 to access port 80 of the on-site network [Link].

104 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

[Link] Port Mapping

Map port 102 of the local computer to port 10248 of the cloud. When
used together with the FRP function, the Smart200PLC can be uploaded
and downloaded.

Step 1: Create a mapping.

Step 2: View the mapping table.

Step 3: You can cancel the mapping.

[Link] Cloud Transparent Transmission

Step 1: Configure the relevant transparent transmission parameters.

Server name: 上海迅饶透传云平台

IP address: [Link]

Port number: 8001

Note: The following accounts are for testing purposes only

Username: admin3

Master Account Password: ******

PLC/DDC

Sub-account username: sunfull3


105 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Sub-account password: ******

Users can purchase a master account to create sub-accounts (the


company charges an annual fee based on the number of accounts).

Each sub-account corresponds to an on-site gateway.

As long as the sub-accounts are not used at the same time, they can be
used for different projects.

You can also enable and disable the cloud transparent transmission
function through the gateway web page

106 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The following is an example of a Siemens S7 200 Smart PLC.

Step 2,

After the account is filled, you need to upload the project to the LAN for the
first time and bind the gateway account.

107 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Step 3,

Then, configure the gateway and PLC, connect the gateway to the Internet,
and set the IP address of the network port connected between the gateway
and the PLC to the same network segment as the PLC, in this example, the
gateway IP address is set to [Link]. The IP address of the PLC is
[Link].

After the parameters are filled, start the remote download program.

If you see the following prompt, it means that the login is successful and you
can operate the PLC remotely.

Generate a virtual NIC

108 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Step 4,

Open the Step7 software, click Download the program, and add the IP
address of the computer on which the VPN transparent transfer program is
running. Enter the actual PLC IP address [Link] here

Step 5: Complete the downloading procedure.

109 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The sixth step is to monitor the PLC

4.8.6 Remote monitoring

Open “IOT/Remote Upload”, setting it as the blow figure 4-8-14

110 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

IOT Platform: IIOTSaas.

IP Address: The IP address of the cloud server which is uploaded by


MQTT, default [Link].
Port: 1883, 2883, 3883(Optional), Multi-channel can play a shunt, reduce
network congestion.
Topic: <Required> custom can only use letters or Numbers.
Gateway Name: [Link] uploading to the cloud, the theme,
gateway name and gateway ID will be checked to see if they are duplicated.
Gateway ID: One gateway corresponds to one topic, and different gateway
suggested topics and gateway id are unique. You can click "Generate" to
get a unique ID.
We can change to “IOT” Mode upload project and monitor it remotely.

111 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.9 Page configuration

4.9.1 Page configuration

Click “HMI Editor”, as shown in figure 4-9-1.

figure 4-9-1 select configuration

In the pop-up window, first select the bitmap in the gallery window, then
select the corresponding map in the bitmap, take the 3D button as an
example, select the target button, press the left mouse button to drag the
button to the edit area, as shown in figure 4-9-2.

figure 4-9-2 new button

After the button is added, as shown in figure 4-9-3.

112 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-3 finish adding button

If you want to set page attributes, choose the page name to be set in
the configuration page window, right-click the page property, and the
operation interface as shown by figure 4-9-4.

figure 4-9-4 select Page Properties

In the pop-up page attribute dialog box, you can set page width, page
height, set the initial interface (main interface), describe and set background.
Before setting up, it is necessary to confirm the resolution of the final display,
and set it in accordance with the resolution.

113 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

It is suggested that when the new page is built, set the background to
ensure that the content can be displayed on the web page completely, and
the page attribute setting interface is shown in figure 4-9-5.

figure 4-9-5 Page Properties

After the page attribute set is successful (Note: the content outside the
background is not fully displayed on the web page), as shown in figure 4-8-6.

114 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-6 finish Page Properties

Double click the button and select the "Bitmap" in the "Primitive
Properties " dialog box that pops up, such as figure 4-9-7.

figure 4-9-7 select Bitmap

In the pop-up "Bitmap > Discrete" dialog box, click the "External Tag". in
the pop-up "Select External Tag" dialog box, press the figure 4-9-8 step.

115 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-8 select external tag

After clicking "OK", go back to the bitmap > discrete dialog box, click
“add rows”, select the number of rows to increase in the pop-up dialog box,
and the specific operation steps are shown in figure 4-9-9

116 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-9 add rows

Click "OK", go back to the "Bitmap --> Discrete" dialog box, add the line
success, as shown in figure 4-9-10.

figure 4-9-10 finish adding row

Back to the dialog box “Bitmap --> Discrete”, set the value of variables,
associate different values with different values, select bitmap with value 0,
and operate according to figure 4-9-11.

117 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-11 select the bitmap with value=0

In the same way, a bitmap with a value of 1 is added, as shown in figure


4-9-12.

figure 4-9-12 select the bitmap with value=1

Click "OK" to complete multiple rows of addition, as shown in figure 4-9-


13.

118 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-13 click “OK”

Then click "OK" to complete the multi rows add, and return to the
primitive Properties dialog box, select the first "Operation", then select
"control", in the play "Boolean" dialog box, click the name of the variable you
want to choose the association of variables, the corresponding option to
select the type of control "(if the value is written as 0, choose "0". if the write
value is 1, choose "1", if the implementation is reset function, we choose the
"reset" button. if to achieve the reverse function, we choose the "Invert"), as
shown in figure 4-9-14 (this step is to realize the configuration screen in the
button press or bounce "write value" command).

figure 4-9-14 add control

Return to dialog box “Primitive Properties”, such as figure 4-9-15, click


“OK” to complete the animation connection of the button picture.

119 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-15 finish Operation

When the "Primitive Properties" setting is completed, the configuration


page is built, as shown in figure 4-9-16.

figure 4-9-16 page configuration

120 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.9.2 Two options of primitive properties

(1)Animation

9 Tab of the options is mainly aimed at the "display" attributes, such as


numerical display(pressure, temperature and humidity etc.) (water tank,
filling percentage display oil quantity), and "operation connection tab"
control "class attribute distinction. The following are the scope of application
of the 9 tags and the functions that can be realized:

1) Line Color: In Shortcut bar, there are 7 buttons that have line
color.
“ Line”“ Rectangle”“ Circle”“ Ellipse”“ Polyline”“ Polygon”“ Pat
h” The lines of the graphics are displayed in different colors when the tied
tag value is changed.

2) Fill Color: In Shortcut bar, there are 3 buttons that have fill color.

“ Rectangle”“ Circle”“ Ellipse”“ Polygon”, when the tied tag value is


changed, the enclosed figure shows a different filling color, It Can be used
with "Line color".

3) Text Color: In Shortcut bar, there are 2 buttons that have text
color. “ Text“ TextV”, when the tied tag value is changed, the text object
shows a different filling color.

4) Size: In Shortcut bar, there are 7 buttons that have size.

Line”“ Rectangle”“ Circle”“ Ellipse”“ Polyline”“ Polygon”“ P


ath” when the tied tag value is changed, the size of the graph is displayed
in different sizes(the width and height can be set separately).

5) Position: In Shortcut bar, there are 9 buttons that have position.

“ Line”“ Rectangle”“ Circle”“ Ellipse”“ Polyline”“


Polygon”“ Path”“ Text”“ TextV”, when the tied tag value is changed,
the position of the graph or text(horizontal and vertical movement can be
set separately).

121 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

6) Fill Percentage: In Shortcut bar, there are 4 buttons that have fill

percentage. “ Rectangle”“ Circle”“ Ellipse”“ Polyline”, when the


tied tag value is changed, the closed graph shows different percentage of
filling(vertical filling: from top to bottom or from bottom to top. left and right
fill: from left to right or right to left).

7) Bitmap: For the Image object , when the tied tag value is
changed, display different images. (Note: More used to indicate the
ON/OFF state, etc.)

8) Value Display: In Shortcut bar, there are 2 buttons that have this

function. “ Text”“ TextV”, It displays tied tag value.

Note: only the analog amount can be set up for the break bounds
display.
The value of the following figure 4-9-17 shows the analog amount.

figure 4-9-17 Value-->Analog

122 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

9) Special: The visibility for all objects, when the tie tag value
change makes the object visible or not (value= 0, not visible. value=1, the
flash visible): for all objects, when the tie tag value change makes the
object with specific attributes or flashing. the rotation: for all objects, when
the tie tag value change makes the object specific rotation angle at rest,
until the numerical change objects will rotate again.

(2) Operation Option

The 2 tab of the options is mainly aimed at the "control" attributes, such as
picture, jump button operation (opening and closing switch, etc.), analog
value (temperature and humidity pressure), and the "Animation" tab
"display" to distinguish it from the class attribute. The following are the
scope of application of the 2 tags and the functions that can be realized.

1) open / close: for all objects, open the bound picture or close the
bound picture when the left key clicks on the object.

2) user input: for all objects, when left click objects, set 0, set 1, take
the inverse (set 0 to set 1, place 0 sets 1 cycles), or pop up the input dialog
box, allowing users to enter numeric value.

4.9.3 The use of wildcards

[user scenario] there are many devices, such as 20, but each device
can use wildcard function when its location information is same (as shown in
figure 4-9-3-1). The configuration page is configured with only one page,
which specifies which device to open on the main page.

123 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-3-1 driver configuration

The specific operation is to configure 20 buttons on the main page,


open the page property window of the button, and specify the device ID
number in the device bar of the wildcard. As shown in figure 4-8-3-2. In this
way, click device 1 displays the monitoring status of device 1, and click
device 2 will display the monitoring status of device 2, and so on.

figure 4-9-3-2 Page Configuration

The configuration of the common page, like the following picture, will be
used as a driver for wildcards. The channel numbers and device numbers

124 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

are displayed on the screen so that it will not confuse the equipment
currently open.

figure 4-9-3-3 set common page

Open the text’s Primitive Properties that need to display device number,
and select “Value-->String”. In the Pop-up window, you can click “Internal
Tag…” to open Internal Tag window. The wildcard device can be selected
directly from the internal variable name as the variable name. Specific
settings, As shown in figure 4-9-3-4.

125 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-9-3-4 set device No.’s of Common Page

4.10 Selection of monitoring mode

There are two monitoring modes to switch: the local mode and the
gateway mode.

Local: it refers to running a pure software program on the PC to


realize PC local simulation of the configuration page.

Gateway/HMI: it refers to the configuration project uploaded to the


hardware gateway/Touch Panel on the PC, the configuration is published
through the gateway, and the configuration is monitored by the PC end and
the mobile terminal.

IOT: this mode can monitor data from cloud remotely.

Open the "X2View" main window, double-click the "Drive


Configuration", enter the "Drive Configuration" window, clicking “tools” and
selecting the “Monitor Mode”, you can switch between the two modes of
"local" and "gateway", as shown in figure 4-7-1.

On the "X2View" main window, "Drive Configuration", “Page


Configuration”, can switch the monitoring mode.

126 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-10-1 select a monitor mode

4.11 Running X2ViewRuntime


After the project configuration is completed, click the menu bar "Tools" to
select "start monitor" or click on the toolbar icon . It will start the
X2ViewRunTime runtime program as shown in figure 4-11-1.

figure 4-11-1select monitor

In different monitoring modes, the monitoring operation is aimed at


different objects, and the gateway/touch screen monitoring mode is to
monitor the real-time changing data on the gateway or touch screen; In the
127 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

local monitoring mode, the real-time change data during the local software
simulation is monitored. In the cloud platform monitoring mode, the real-time
data of the gateway or touch screen is monitored through the cloud platform.
When starting monitoring in local monitoring mode, the X2ViewRunTime
runtime program will be started, and only the program needs to be started in
the background to realize the gateway conversion function on the PC, as
shown in Figure 4-11-2.

figure 4-11-2 RunTime log

Back to the “Driver Configuration”, you can see some real-time data on
the device are consistent with the data on the X2View, as shown in figure 4-
11-3.

figure 4-11-3 collect data successful

128 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.12 Upload project to gateway

After configuring the project, the project can be uploaded to the


hardware gateway. In gateway mode, click the menu bar "gateway" to select

"upload project" or click on the toolbar , As shown in figure 4-12-1.

Note: 1, if you want to change Logo, you need to check the login icon.
2, If you edit the JS, you need to check the Java script.

figure 4-12-1 Upload project to gateway

Enter the gateway IP address in the pop-up dialog box, and click
"Upload", as shown in figure 4-12-2.

figure 4-12-2 upload project to gateway

129 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Backup Project: save the current configuration project to the gateway


/ touch panel, without backup will not be saved.

Recover Project: the project restored to the last backup to the


gateway / touch panel.

Delete Project: Delete the project of the gateway / touch panel.

Reboot: restart gateway / touch screen

Upload: upload the current project to the gateway / touch panel, and
can’t be used as a restore configuration. If more pictures are used in the
configuration, it will affect the speed of uploading. Please wait patiently.

Login icon: Check the login icon, and the web end login icon will be
changed.

Video: To select video, the video files that are linked by the
configuration page can be uploaded together to ensure the normal play.

Java Script: Select the Java script, then the JS folder will also be
uploaded. Be sure to check if you pay attention to the revision.

After uploading, the pop-up dialog box prompts the upload


successfully. (Note: the IP address of the gateway must be correct. The
gateway's default IP address is [Link], the IP address on PC is set
to the same network segment, and Ping can be uploaded later).

If the upload fails , check the network , and ping IP.

4.13 Download the project

The monitoring engineering files within the gateway can be


downloaded to the local.

In order to prevent the project from being downloaded, you should


enter the username “admin” and the password “admin123456” before
downloading. Before you download the project, you must click on the
backup configuration first. So even if someone later uploads a project, it
can be restored with a restore configuration project.

130 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-13-1 download Project

4.14 Gateway/HMI setting

In the gateway monitoring mode, click on the menu bar "gateway / touch
screen" and select "parameter settings", such as figure 4-14-1.

figure 4-14-1select Gateway/HMI Setting

Network port settings: you can change the IP address of the


hardware gateway / touchscreen. The default IP address of gateway is
[Link], and the subnet mask is [Link] by default. The default
gateway [Link] is set up, and click “OK”. The "Ping" function tests
whether the current IP address is successful in Ping. The "login page
131 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

function" can be logged on to the web server where the gateway is located,
as shown in figure 4-14-2.

Note: Gateway default IP address is [Link]. If users change IP


address for the first time, users need only one wire (cross or direct
connection) to connect with gateway. We need to set PC first and gateway to
the same network segment, then enter the gateway's current IP address
[Link] in the current IP address text box, then click on the application,
so that the gateway parameter setting operation corresponds to the current
IP address gateway, and then set the new IP address.

figure 4-14-2 Ethernet Setting

Option: as show figure 4-14-3.

Setting the compression package password for the download


engineering file, touch screen related opening buzzer, and brightness setting.

132 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-14-3 Option

Time: Hardware gateway can read the current system time, and if time
does not match the normal time, you can click "Read" refresh function
hardware gateway system, automatic update cycle refers to the time of the
system hardware gateway update interval of terminal equipment on the
bottom layer, as shown in figure 4-13-4.

figure 4-14-4 Time

133 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Firmware information: you can find the name of the hardware


gateway / touch panel and the machine code when click “Refresh”, as shown
in figure 4-14-5.

figure 4-14-5 firmware

System: the system can see the current usage of the hardware
gateway memory, and the gateway can be restarted remotely. Delete
configuration is generally used in engineering when updating gateway, users
typically use less, just click on the restore configuration is not recommended,
you can restore the deleted user project gateway in the project, as shown in
figure 4-14-6.

134 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-14-6 System

The above functions can also be accessed through the web server and
set up on the web page.

4.15 Start monitor

4.15.1 Offline monitor

We can simulator data on “Offline Monitor” mode, gateway don’t need


collect real device or collect real data, it just for simulator.

135 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-15-1 Offline Monitor

4.15.2 Online monitor

Gateway must collect real device and collect real data.

136 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-15-2 Online Monitor

After configuring the above steps, open the “Modbus Slave”` software,
select "Connection" under the "Connection" menu, select TCP/IP in the pop-
up "Connection" dialog box, and click "OK", as shown in figure 4-15-3.

figure 4-15-3 select TCP/IP

In the "Setup" menu, select "Slave Definition", in the pop-up dialog box,
select "Function" option and we drive configuration in the same function
code. the "Address" option under the initial input address. the "Length"
option under the input address length, as long as the input address contains
the same type we drive address configuration register.

figure 4-15-4 slave definition

After configuring Modbus Slave, in X2View, click "Online Monitor", will


login the interface, username: admin Password: admin123456, after login,
you can see the configuration, as shown in figure 4-15-5.

137 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-15-5 visit by browser

4.16 Timer

Web configuration gateway supports timers and timing list functions.


Users can automatically start and stop devices and set values at any time by
setting up timing lists and timers.

4.16.1 Timer group

The function of timing group list is to facilitate users to manage points in


the same time period, and to place timed points at the same time point in a
group, which is convenient for users to view and manage. The timing group
list refers to the internal clock of the gateway, so before using the timer
function, please calibrate the time of the gateway first. The following steps
are as follows: click on the "Monitor Object" in the menu bar and select the
"Timed Group", as shown in figure 4-16-1.

138 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-16-1 select timer list

In the "Timer Group List" dialog box that is popped out, click right to
select the new timing group, as shown in figure 4-16-2.

figure 4-16-2 New Timer Group

In the pop-up "Timer Group" dialog box, set the corresponding


properties, double click the tag to complete the add. Note that the selected
point must be controlled.

139 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-16-3 finish to new timer group

After clicking "OK", back to the timer group list dialog box, you can see
the just set timer group, as shown in figure 4-16-4.

figure 4-16-4 finish to set timer group

Repeating the above steps, users can add multiple timed group lists
according to actual requirements. Right - click can be edited or deleted on
the timing group.

140 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.16.2 Timer

The timer function is to edit the timer and manage the timer when the
timer is grouped. The operation steps are as follows:

Click the monitor object menu, and select the "Timer" in the pop-up
dialog, as shown in figure 4-16-5.

figure 4-16-5 select timer

After selecting the timer in the monitor object, the "Timer" dialog box is
popped out, with its properties as shown in figure 4-16-6.

figure 4-16-6 Timer

141 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Right click the blank, select "New Timer" in the pop-up list, open the
timer edit window, and its related properties are:

1) Timer Group: select the timer group.

2) Monday to Sunday: can be single or multiple selections, tick, tick


timer is only carried out in time.

figure 4-16-7 Timer Group Edit

3) time: range 00: 00: 00-23: 59: 59.

4) value: at the time, the value will set to 1.

142 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.17 Sequence list/command List

Web configuration gateway supports sequence list and command group


function. Users can set up sequence list and command group to set up
startup delay time and stop delay time settings for external variables.

4.17.1 Sequence list

The function of time sequence list is to facilitate users to set up delay


time for individual external variables and stop the delay time setting. It is
recommended to calibrate the gateway time before use. The following steps
are as follows: click on the "Monitor Object" in the menu bar and select the
"Sequence List", as shown in figure 4-17-1.

figure 4-17-1 Sequence List

In the "Sequence List" dialog box that is popped out, click the right
button to select "New Tag…", as shown in figure 4-17-2.

143 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-17-2 New Sequence List

In the pop-up "Timing Settings" dialog box, set the corresponding time,
select the external variable, double click the tag to complete the choice. Note
that the selected point must be controlled.

figure 4-17-3 add external tag

After clicking "OK", back to the time sequence list dialog box, you can
see the just set timing group, as shown in figure 4-17-4.

144 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-17-4 complete settings

Repeating the above steps, users can add multiple sequence lists
according to actual requirements. Right - click can be edited or deleted on
the sequence list.

4.17.2 Command list

The command group function is a new good time sequence for group
management. The specific operation steps are as follows:

Click the monitor object menu, and select the "Command List" in the
pop-up dialog, as shown in figure 4-17-5.

145 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-17-5 select command list

After selecting the "Command Group List" in the "Monitor Object", the
"Command Group List" dialog box is popped out, as shown in figure 4-17-6.

figure 4-17-6 New Command List

The command group function is a new good time sequence for group
management. The specific operation steps are as follows:

Click the monitor object menu, and select the "New Command Group" in
the pop-up dialog, as shown in figure 4-17-6.

146 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The new command group can be querying within the internal variables,
and can also modify its properties to facilitate the application.

figure 4-17-7 Command Group List

4.18 Internal tag

The system has the following internal variables by default, and the user
can’t modify the name of the internal variable, which is convenient for the
user to call on the configuration page. As shown in figure 4-18-1.

 Date, time, week, IP

 The communication state of the built equipment

 Name wildcards for drivers, channels, devices, and group names

 alarm signal, TF card status

 Definition of the command group list

In addition, users can add custom internal variables according to their


needs, import Excel and import Excel to modify internal variables in batch.
Custom can modify the name.

147 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-18-1 Internal Tag List

Right click to new, edit, copy, paste, cut, delete and edit internal tags,
select new open internal tags in the properties window. It can be filled in for
its description, data type, BACnet register type, BACnet register address,
unit, alarm content, historical storage. As shown in figure 4-18-2.

Among them, the alarm content setting reference 4.7.

figure 4-18-2 Internal Tag Properties

The defined internal variables can be used in conjunction with the configuration
picture, and can be monitored in real time on the configuration picture.

4.19 Trigger

148 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The command group function is a new good time sequence for group
management. The specific operation steps are as follows:

Click the monitor object menu, and select the "Trigger" in the pop-up
dialog, as shown in figure 4-19-1.

figure 4-19-1 select trigger

After selecting the "Trigger" in the "Monitor Object", the "Trigger" dialog
box is popped out, as shown in figure 4-19-2.

Note: It will set “Source” tag value to “Target” tag value when “Source”
value changed.

figure 4-19-2 New Trigger

4.20 Database

149 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

When the data reaches the upper and lower limit of the set alarm, the
gateway will record the alarm content. Users can view the current alarm
information through X2View configuration software or web page, or check
the historical alarm record in X2View configuration software or web page.

4.20.1 Alarm text setting

When the tag is added, you can click open the alarm text to set it. To
add and change the alarm content, right-click the current label selection
attribute or double click the label. As shown in figure 4-20-1.

figure 4-20-1 Alarm Text

Click “Alarm Text”, you can set the alarm contend and lower limit. There
are four alarm States opened here.

If a general alarm is used, only the two columns of the middle ID (low
alarm) and 3(high alarm) are required to be filled, and the user group [2, 3]:
select the corresponding user group.

If the alarm is serious, ID can be set to 1 (ultra-low alarm) and 4 (ultra-


high alarm) up and down limit, user group [1, 4]: select the corresponding
user group.
150 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The following diagram, beyond the 2, 3 range, is sent to all members of


the user group [general user]. Out of the 1, 4 range is sent to all members of
the user group [administrator].

Note: the normal state alarm content indicates the alarm information
under the non-alarm condition. If the requirement is required, it can be set up.

figure 4-20-2 edit Alarm Text

After the configuration is completed, the uploading project is launched.

X2View configuration software can also query the history of alarm data.
If you want to realize the alarm record and query function, we must meet the
following two points:

1. Enable Local SQL.

2. Save Cycle.

3. Max Records.

The database maximum record setting steps are as follows:

Click the database settings under the database menu. As shown in


figure 4-20-3 below.

151 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-20-3 Database Setting

Set as shown in figure 4-20-4.

figure 4-20-4 Set Max Recorders

4.20.2 Historical Tags

Select the "Historical Tags", as shown in figure 4-20-5.

152 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-20-5 Historical Tags

We can modify or batch modify “Enable/Disable” historical tags..

figure 4-20-6modify Historical Tags

Finish modify historical tags is shown in figure 4-20-7.

153 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 4-20-7 finish modify historical tags

4.21 User Manager

The web configuration gateway supports user and user group functions

and manages the users' rights. In the configuration page, different


operations can be set for different users.

4.21.1 User list

The menu bar clicks on the user management, selects the user, and
opens the user list window. Right click can be added to the user and
password, by exporting to CSV, and importing to CSV to modify users in
batch.
154 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-21-1 User List

Click “New User”, “Modify User”, open the user window, and modify the
Username, Password, Limitation, Phone, E-Mail.

Note: Limitation “Operator” can set data value, “General” can’t set data
value.

155 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 4-21-2 User Window

4.21.2 User group

The user group function is a new good user for group management. The
specific operation steps are as follows:

Click the user management menu and select the "User Group" in the
pop-up dialog, as shown in figure 4-21-3.

figure 4-21-3 User Group

After selecting the user group in user management, the "user group"
dialog box is popped out, as shown in figure 4-21-4.

figure 4-21-4 User Group


156 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

The user group function is a new good user for group management.
Right click and choose “New User Group” and pop up the user group edit
window. Select the user to join the user group, as shown in figure 4-20-5.

When the determination is completed, it will be displayed in the user


group list. Right click can also be added and modified to the user group list.

In addition, with the WeChat alarm, you can directly build a new user
group and do not need new users. The user is added by scanning the two-
dimensional code.

figure 4-21-5 user group edit window

4.22 Provide a development interface


The gateway / touch panel opens the following interface and gives
examples that users can increase the flexibility of configuration software
based on their own development.

 C#
 HTML+JS

 Java

 Python
157 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

4.23 Provide handset installation package


The mobile installation package includes the Android version and the
iOS version. Android can get installation package [Link] in X2View
configuration software, and Apple users can search EZView for free
download in the app Store. After the user installs it on the phones, it can
access the monitored configuration page through the app.

5 Web server
All hardware products of Shanghai Sunfull have the
corresponding configuration software, the PC version of the
software WEB server called during local simulation, and the
hardware WEB server. The PC web server during software
simulation is mainly used to call the service port on the computer
when configuring the local simulation of the software. The WEB
server on the hardware is mainly used for browser access, and
then the parameters of the hardware are modified.

5.1 Local WEB server

Click on the menu bar "IOT", select "Local WEB Server..." or


click on the shortcut icon "" to enter the local WEB server settings
interface, as shown in Figure 5-1-1.

158 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Figure 5-1-1 Menu Bar Selection of Local WEB Server

Enter the local web server settings interface, as shown in


Figure 5-1-2.

Figure 5-1-2 Local WEB Server Setting Interface

Explanation:

The port set on the WEB server here is mainly used to configure
the software to switch the service port on the computer when in
local mode, to avoid occupying the same service port as other
software or programs, which may cause the configuration
software to be unable to simulate locally.

5.2 Hardware WEB Server


Gateway comes with its own web server, and the default port is fixed at
80. Users can log in to the web server through the browser and modify the
IP address of the hardware gateway in the web page, view real-time data,
history storage, real-time alarm, download X2View configuration software
and engineering files, etc.

Note: The default IP address of gateway 2 is [Link]. If the IP


address needs to be modified, please connect PC and gateway directly with
a network cable(cross or direct connection), then set PC and gateway as the
same network segment, enter [Link] login gateway(user name:
admin, password: admin123456) in the browser, and then modify the
gateway IP address in “Network Port Settings”.
159 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5.2.1 Web login

Enter the ID address of the gateway in the browser, as shown in figure


5-2-1

figure 5-2-1 Enter the gateway IP address

Enter the login interface and enter the user name and password(note:
the factory default user name is “admin” and the password is “admin123456“,
Users can add a personal account in user management after successful
login), as shown in figure 5-2-2.

Tip: After login, please select English from the language options.

figure 5-2-2 Users login

160 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5.2.2 Download file

The upper computer configuration software, current project file and


commonly used debugging software can be downloaded and used with the
gateway as shown in figure 5-2-3.

figure 5-2-3 Download the file

5.2.3 Touch panel options/HMI options

Include touch calibration, WeChat alarm testing, upload engineering to


Cloud and gateway/touch panel ping functions, as figure 5-2-4.

The configuration gateway displays HMI options without touch


calibration.

161 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-4 Touch screen options

Click “touch” to calibrate, and then click on the touch panel to calibrate
the touch position.

Click WeChat alarm test, you can send test alarm message to the user’s
mobile phones to test whether the WeChat alarm setting is normal on
the touch panel.

Ping: Gateway “ping” function.

Upload project to the cloud: directly link to the cloud platform and
upload the project.

5.2.4 Upload the file

This is shown in the figure below

Figure 5-2-5 Uploading the project

Like cloud upload, you need to package the project file into a .zip
compressed package and upload it

5.2.5 User management

The user can manage the gateway and login account by adding,
modifying, deleting, etc. As shown in figure 5-2-6.

162 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-6 user management

Note: In the X2View configuration gateway, if ordinary users are added


and logged into the configuration gateway with ordinary user permissions, it
can jump directly to the initial window set in the configuration software, so
that users can directly view the edited configuration panel. X2View
configuration gateway factory default user name: guest, password: 123456
for normal user.

figures 5-2-7 normal user login

After clicking the login button, you can directly enter the initial window of
the edited configuration. See figures 5-2-8 below.

163 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-8 log directly into the initial window

5.2.6 Network interface setting

HMI2004-A9 support double network ports:

Network 1 default address: [Link](normally not as


communication).

Network 2 default address: [Link](as network communication


port).

Touch panel supports single port:

Network default address: [Link](as a network communication


port).

164 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-9 Network setting

5.2.7 Route settings

You can configure a Modbus route to transparently transmit


ModbusTCP from ModbusRTU, as shown in Figure 5-2-10.

Figure 5-2-10 Route information

5.2.8 Firmware information

165 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Firmware Information: you can check the current gateway’s firmware


version information, machine code and serial number, as shown in figure 5-
2-11.

figure 5-2-11 The firmware information

5.2.9 System information

You can check share of memory, available memory, and used memory
of gateway, and remotely restart the gateway, delete the configuration
project, and restore the configuration project, as shown in figure 5-2-12.

figure 5-2-12 view system information

166 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5.2.10 Communication statues

Real-time communication data frames can be checked as to facilitate

troubleshooting by users, as shown in figure 5-2-13.

figures 5-2-13 check communication status

5.2.11 Pass-Through by IOT

Figure 5-2-14 Pass-Through by IOT

5.2.12 Forwarding side


167 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Forwarding can be managed for Modbus, BACnet, OPCUA, etc. Figure


5-2-15 shows the figure.

Figure 5-2-15 Forwarder

5.2.13 Alarm settings

You can manage text messages, phone calls, emails, etc. Figure 5-2-16
shows the show.

Figure 5-2-16 Alarm settings


168 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5.2.14 Alarm information

If ”Alarm Text” is set in the label attribute, when the value of the label
reaches the alarm condition, the specific alarm content can be printed on the
alarm information interface for the convenience of users analysis. If “Alarm
Text” is not set, the function is turned off as shown in figure 5-2-17.

figure 5-2-17 check alarm information

5.2.15 Alarm record

You can query the historical alarm information

It is divided into five sections: query, alarm, operate, reset and download.

Button 1: “Query”. Enter the time period to be inquired and click all the
buttons to find the alarm information and operation information of the points
within that time.

Button 2: “Alarm”. Enter the time period to be inquired and click the alarm
button to find the alarm information of the points within that time.

Button 3: “Operation”. Enter the time period to be inquired and click the
operation button to find the operation information of the points with that time.

Button 4: “Reset”. Reset time is empty, you can re-select the time period to
be queried.

169 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Button 5: “Download”. Then alarm information during this period can


downloaded and saved as CSV file.

figure 5-2-18 alarm record

Query the alarm record, as shown in figure 5-2-19 below.

figure 5-2-19 alarm record query result

Query operation records, as shown in figure 5-2-20

170 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-20 alarm record query result

5.2.16 History query

Historical query is designed to make it easy for users to query historical


information. When the user opens the history storage of the label in the
configuration software. The historical information can be inquired in this
interface.
It is divided into four sections: “Query”, “Alarm”, “Reset”, “Download”,
and “Return”. The user first selects the storage point to query (multiple
choices are available), the maximum number of points can be customized by
the user on the touch screen, and then user sets the time range of the query
to start the query.
Button 1: “Query”. Enter the time period of historical information that
needs to be inquired Click the query button to find the historical information
of points within that time period .
Button 2: “Reset”. Reset time is empty, you can re-sect the time period
to be queried.
Button 3: “Download”. You can download and save the storage point
information during this period as a CSV file or PNG image.

171 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-21 History query

Query the storage point as shown in figure 5-2-22 below. If you mouse
over the graph, you can see the specific values.

figure 5-2-22 Bar graph

Shortcut toolbar: It can be used to switch the bar graph to “Data View”,
display as “Line Chart”, and also “Restore to Bar Graph”, and “Download
Pictures”.

Data view:

172 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-23 data view

Line chart

figure 5-2-24 line chart

5.2.17 Timer

In the timer interface, you can query the points that have set the timer
information, and you can see the timing grouping, the timing effective value,
the timing start time, the timing end time, the description, and the timing
effective time (the value is 1 bit valid, 0 invalid) as shown in figure 5-2-25

173 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-25 timer

You can also edit the timing information on this interface by clicking the
label you want to modify. If the lights are turned on Saturday and Sunday,
they are effectively removed. Click “OK” after editing, and The modification
will be successful, as shown in figure 5-2-26
below.

figure 5-2-26 the timing information was modified successfully

5.2.18 Internal variables

174 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

You can query the device’s off-line status, newly created internal
variables, and the system date and time that comes with the system, as
shown in figure 5-2-27 below.

figure 5-2-27 check the real-time data

5.2.19 Real-time data

You can check the real-time data collected by the gateway on the
webpage, as shown in figure 5-2-28 below.

figure 5-2-28 check real-data


175 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-29 write value operation

5. 2.20 Configuration screen

The gateway configuration screen can be checked on the web page. As


shown in 5-2-30.

figure 5-2-30 check real-time data

Controls are also available in the configuration screen for operation, as


shown in figure 5-2-31

176 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 5-2-31 write value operation

6 Application case
The following is an example of “X2View_Demo” to illustrate the
operation process of establishing configuration of X2View from scratch.

6.1 New project


Open the X2View configuration software, display “Project Manage”
dialog box, and click the “New” button, as shown in figure 6-1-1

177 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-1-1 Click “New Project”

In the “New” dialog box that pops up, fill in the project name, project

Description and save path in sequence. After confirmation, click “OK”


button, as shown in figure 6-1-2.

figure 6-1-2 New project parameters

At this point, we can see that "X2View_Demo" in the "Project


Management" dialog box is in the selected state, as shown in figure 6-1-3.

178 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-1-3 Finish

Click the “Finish” button to enter the main control interface of X2View,
as shown in figure 6-1-4.

figure 6-1-4 select drive configuration

179 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

6.2 Add new driver


In the main control interface of X2View, click the menu of “Edit ”, select
“New Driver” or directly click the toolbar icon , as shown in figure 6-2-1.

figure 6-2-1 Drive configuration edit interface

Click “New Driver” and select the type of driver on the acquisition side.
For this project, we select “ModbusRTUClient”, click “Edit “on the menu bar,
select “New Driver” or directly click the toolbar icon, as shown in figure 6-2-2.

180 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure6-2-2 new driver

6.3 Add channel

After the driver is added successfully, click “New Channel” and the ”Set
Serial Communication Parameters” dialog box pops up. The related
properties are as follows:

1)Channel Name: Fill in the channel name.


2)Communication parameters:
(1) Serial port: The serial port number for gateway devices to
communicate with other devices.
(2) Baud rate: the communication baud rate of devices connected to
the gateway.300-115200 BPS support.
(3) Data bit: 8 by default
(4) Stop bit: default is 1.
(5) Check bit: default is none.
(6) Flow control: Default is none.

181 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

3)Response Timeout: The time that the request frame waits for the
response frame, beyond which the “Quality” label value is “Bad”, the default
is 1500ms.
The configuration of specific parameters is shown in figure 6-3-1

figure 6-3-1. Create a new channel

6.4 Add equipment


After adding the channel, select the current channel, right-click and click

and select “New Device” or click the toolbar , and the “Device Properties”
dialog box pops up. The properties are as follows.

1) Name: Enter the device name.

2) Device ID: The address of the device connected to the gateway.

3) Delay Between Polls: The time interval from the current request
frame to the next request frame is 50ms by default.

4) Bulk Transfer: Group packed sending is supported, If the device


does not support group packet, all four group packet parameters can be
set to 0

Configuration of specific parameters is shown in figure 6-4-1.

182 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-4-1 New device

6.5 Add tags

Under the device, you can directly create a new label, or you can first
create a group, and then create a new label in the group. In this project, a
label is built in a group, so select the device, right-click and select “New
Group” or click the toolbar icon, and the “Group Properties” dialog box pops
up, as shown in figure 6-5-1.

183 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-5-1 new group

Once you’re done, select the group, right-click on it and select “New
Tag” or directly click the toolbar icon. The associated properties:

1)Roll call: Enter the name of the point for easy reading. In this case,
we input “air supply temperature” to represent the air supply temperature of
the air conditioner.

2)Description: additional information for roll call, option.

3)Data type: The data type to be collected can usually be inquired in


the instruction manual provided by the equipment manufacturer.

4)Register type: The type of register to be collected, usually in the


instruction manual provided by the equipment manufacturer.

5)Register address: The register address of the collection point can


usually be found in the instruction manual provided by the equipment
manufacture.

(1) Hexadecimal representation is supported, such as address1 BH,


this can be expressed as 0x1B or 28 (offset 1).

(2) If you want to read the data in BCD code form, you can add the
suffix BCD after the register Address, namely “[Link]”(A stands for
Modbus register Address).

6)Linear transformation: To establish a linear scaling relationship


between “Raw Data” and “Engineering Data”, the specific configuration
parameters are shown in figure 6-5-2

184 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-5-2. Create a new label

Similarly, we will create “Supply_air_HUM”, “Return_Air_TEMP”,


“CO2_Concentration” and other labels successively, and the completed
project is shown in figure 6-5-3

185 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-5-3 Completion of project

6.6 The configuration page


Click the window menu, select “Page Configuration”, or directly click the
icon in the upper right corner to return to the main control screen and select
configuration page, as shown in figure 6-6-1.

186 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-1. Select "Page Configuration"

Switch to “Page Configuration”, and see that there is a default page,


“Page0”, with an icon to the left of its name , as shown in figure 6-6-2.

figure 6-6-2 Configuration screen edit window

Home Page:

When there is more than one configuration page, if you want to change
the home page, you can right-click “Page Properties” on the page to be set
and tick “Home Page”. The home page is set successfully, as shown in
figure 6-6-3.

187 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-3 sets up the main page

Background Setting: Once checked, you can change the background


color and transparency of the current page, as shown in figure 6-6-4.

Page Width, Page Height: Change this option to achieve a full -screen

display, as shown in figure 6-6-4, depending on the resolution of the display


device(cell phones, monitor).

Previous Page, Next Page: Jump to previous and next page.

188 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-4 page sizes and background Settings

Prepare a base image. It is suggested that the base image file.

File be named in English. It can be JPG, BMP, JPEG, PNG, GIF format,
as shown in figure 6-6-5.

figure 6-6-5, Base image file


189 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

In the configuration screen edit window, click the drawing menu, click
the picture, and the mouse will turn into a cross. When the configuration is
complete, adjust the base to the appropriate size, as shown in figure 6-6-6.

figure 6-6-6 Selects the "Image" option

Click "Picture" and the mouse will turn into a cross shape. Click where
you want to insert the picture file, and a dialog box will pop up asking you to
open the folder where the picture is located, as shown in figure 5-6-7.

190 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-7 selects the image

Open the folder in which the image resides and click “Open”, as shown
in figure 6-6-8.

figure 6-6-8 selects the base image

After opening the base, to resize the base, use the menu bar

tool , as shown in figure 6-6-9.

191 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-9. Adjust base size

Click the drawing menu, select “Text(Landscape)”, and the mouse


becomes a cross shape. Click where the text needs to be inserted, and the
“Text Properties” dialog box pops up, as shown in figure 6-6-10.

figure 6-6-10 selects the "Text" option

Enter text in the text properties box that pops up and click “OK”, as
shown in figure 6-6-11.

192 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-6-11 Adds text

6.7 Create animated links

Click , to make the object selected, then directly double-click the


object or right-click on it and select animate connections. The meta
properties dialog box pops up, as shown in figure 6-7-1.

193 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-7-1 creates an animated connection

In the “Primitive Attribute” dialog box that pops up, we click the
“Discrete” button under “Bitmap”. The “Discrete Bitmap” dialog box pops up,
as shown in figure 6-7-2.

figure 6-7-2 Select "Discrete"

In the “Bitmap  Discretization” dialog box, click the variable name


button to bring up the select “External Variable” window, as shown in figure
6-7-3.

194 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-7-3 creates the animation link

When the configuration is complete, make sure that both driver


configuration and configuration screen have been saved. In the driver
configuration window, click “tools” menu, select “Monitor Mode”->
“Gateway/HMI”, upload the project to the gateway, and then click “Online
Monitor” in the toolbar, as shown in figure 6-7-4.

195 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-7-4 Upload project

After starting monitoring, a web page will pop up to log in, default
username: admin, password: admin123456, and click “Login”. Enter the
web configuration interface to view “Network”, “Communication Traffic”,
“Timer”, and other information, as shown in figure 6-7-5.

figure 6-7-5 Login screen

The web real-time configuration screen is shown in figure 6-7-6.

196 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-7-6 Configuration screen

6.8 Configuration screen batch associated variables

The function of batch correlation variable of configuration screen is to


make it easier and faster for customers to correlate points of the same
screen when editing the configuration screen. Next, we need to copy the
already made image of “Page0” to the newly created image “Page1”, and
correlate all the points of Device 2 to the new image “Page1”. In the driver
configuration interface, Device1 and Device2 devices with the same reading
point location are established under Modbus RTU, channel 1, and Device 1
point location information has been associated to “Page0” screen.

When the point position is associated, only the call information in page 0
is needed.

ModbusTCP.Channel_1.Device_1.[Link] start- stop forward to

ModbusTCP.Channel_1.Device_2.[Link] the system start and


stops.

Replace device 1 in the roll call with device 2.

197 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-8-1 The driver is configured with two devices

Specific operations are as follows:

In the configuration screen, copy the paste the first page of “Page0” into
the second page of “Page1”, as shown in figure 6-8-2 below.

figure 6-8-2 Page1 has been copied


198 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

On the page 1 screen after copying, the user can select multiple or all
components for batch modification. Select all the components here, and
right-click one of them to select “Modify variables”, as shown in figure 6-8-3
below.

figure 6-8-3 Batch modify variables

Click “Open” to see the list of selected variables. Partial variable name
modification is supported here, or right click on the title bar of “variable
name” to make all modifications.

1, Partial modification. See figure 6-8-4 below.

199 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-8-4 is modified in part

2, All changes. Figure 6-8-5 below.

figure 6-8-5 has all been modified

Select all modification here, and replace Device 1 with Device 2 to


complete the batch associated point position operation of “Page1”. see
figure 6-8-6.

200 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-8-6 Batch replacement

When the replacement is complete, see figure6-8-7 below.

figure 6-8-7 Completes the batch modification

After closing the variable list window, you can view “Page1” screen to
see that name has been successfully associated, as shown in figure 6-8-8
below.

201 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 6-8-8. Batch link of points is successful

7 Replace logo

7.1 replace logo file


Method 1: For users who need to change the logo, they can replace
the logo, the can replace the logo, JPG file with the logo file they need in the
“X2View/www/public” folder. The name must be “[Link]”.

202 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 7-1-1 Logo replacement

Method 2: Quick view logo, users can in the configuration screen


open “View/Open Logo File” method can quickly view the Logo file and
replace it with user’s own logo.

figure 7-1-2 quickly view the Logo file

7.2 Upload logo

203 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

After the replacement, check the “Start Logo“ in the “Upload Project”
interface and click “Upload”.

figure 7-2-1 Upload login icon

8 Photoshop usage and Chrome browser


configuration

8.1 Photoshop creates gif images


In the case of Photoshop CS5(similar to other versions), create a single
GIF from multiple JPG or PNG images. Before creating, please first view
“X2View > MapStorage> GIF” folder in advance to create the GIF image. If
you do not need an image from the folder, then create it by yourself.
1. Open Photoshop CS5

204 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 8-1-1 opens the software

2. Click the “File” menu, and select “Open”, in the pop-up dialog box,
select the material to make a GIF.

figure 8-1-2 Import the material

[Link] in all the graphs you need separately.

205 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 8-1-3 Drag the material into the layer.

[Link] the “Window” menu and select “Animation” to open the


“Timeline” panel. Hide “Layers 1” and “Layer 2” in the first frame and set the
time to complete the first frame animation.

figure 8-1-4 Sets the time

206 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

5. As shown in figure 8-1-5, click the button at 1, select “New Frame”


from the pop-up menu, create the second frame animation, select the
second frame, set the delay time, and hide “Layer 0” and “Layer 2”, Similarly,
create a third frame animation, set the delay time, and hide “Layer 0” and
“Layer 1”.

figure 8-1-5 Create a new frame

After setting up, click the “File” menu and select store in “Format(D)
stored for Web and Devices”.

figure 8-1-6 Select the storage mode


207 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Click preview in the “Format(D) stored for Web and Devices” dialog box
to see if the GIF file meets the requirements, not satisfied, then modify,
preview again, until satisfied.

figure 8-1-7 Preview the GIF animation

After the preview, go back to the “Store in Format(D) for Web and
Devices” window, click “Store”, select the storage location, and save the
finished GIF graphics to your computer.
Note: use to this method to create GIF graphics, you need to prepare
more than two materials in advance, if the animation is rotated around a
center, make sure that the center of all images coincides with a point (use a
reference line for accurate positioning).

8.2 Configuring Chrome browser


Take Google Chrome browser as an example.
①Automatic start
②Operation with parameters
③Run in full screen mode

208 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

④Close all tabs on exit. These


Four parameters are independent of each other, and you can set some
Or all of them as needed. First, create a new chrome shortcut to the Desktop
and rename it “project A”.
8.2.1 Automatic start

The shortcut Windows + R opens the run window, type shell: startup,
and click “OK”, as shown in figure 8-2-1.

figure 8-2-1 Open the "Run" window

Drag the shortcut “project A” to the open “startup” folder, as shown in


figure 8-2-2, so that it will start automatically when you reboot.

figure 8-2-2. Drag the shortcut to the Startup folder

209 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

8.2.2 Run full screen with parameters

Right-click the shortcut “project A”, select “properties”, add the URL of
the launch page after the original text in the “Target(T)” box, and click ”OK”
after the addition.
Before Change: "C: \Program Files\Internet Explorer\[Link]"
After Change: "C: \Program Files\Internet Explorer\[Link]" --
kiosk [Link]

figure 8-2-3 sets the shortcut properties

This way, when you launch the browser from this shortcut, the default is
to launch Google Chrome in full screen and open the [Link] login
page.
Note: In full-screen mode, pressing F11 will not quit the full-screen, and
mouse moving to the top of the screen will not prompt you to quit the full-
screen, there’s no “Close” button. Use the “Ctrl+W” key combination to exit
Google Chrome.

9 Customized configuration software gallery

9.1 View the system default gallery

210 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Sunfull configuration software gallery can also be customized, according


to the specific needs of specific needs of users. They can also delete
unnecessary galleries, or join commonly used galleries.
The X2View software comes with a default gallery. Users can view in
the software “www/svgeditor/icons” folder in place, vector and GIF image
library.

figure 9-1-1 gallery

To view a picture, you can also right click the picture in the X2View
configuration software to view the file, as shown in figure 9-1-2 below.

211 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 9-1-2 looks at the file

Click to open the bitmap, you can see a lot of gallery folder, which
contains a variety of commonly used graphics. Such as buttons, sensors,
measuring ruler and so on. If the user does not need the bitmaps, the can
delete them themselves, so that the X2View configuration software does not
load the deleted library. If you want to add to the gallery, you can also add to
the gallery. See figure 9-1-3 below.

212 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 9-1-3 bitmap folder figure.

Open the software to see the X2View configuration software default


gallery, as shown in figure 9-1-4 below.

figure 9-1-4 X2View Default gallery

9.2 Delete gallery

If we delete the “3D Button” folder directly, the “3D Button” gallery will
not appear in the X2View configuration software, as shown in figure 9-2-
1 below.

213 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 9-2-1 Delete the "3D button" folder

Re-open the X2View configuration software, you can see that there is
no ”3D button” gallery, as shown in figure 9-2-2 below.

figure 9-2-2 X2View Delete the "3D Button" gallery

214 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

9.3 Add a gallery


Similarly, if users need to add their own gallery, they can add it under
the corresponding file, such as adding”3D_Button_Add” folder, as shown in
figure 9-3-1.

figure 9-3-1. Add a new "3D_Button_Add" gallery folder

Reopen the X2View configuration software and see that X2View has
loaded our new gallery, as shown in figure 9-3-2 below.

figure 9-3-2 Add "3D button - Add" gallery

215 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Notes:
1, the method of deleting and adding vector diagrams is the same as

the above bitmap operation.

2, the sequence of image library loading is based on the sequence of


folders.

10 Programmable
Here provide three tools for program, “Graphic Programming”, “Java
Script Editor”, “PLC Editor”.

10.1 Graphic Programming

Click “Programmable/Graphic Programming” in the menu bar, as shown


in figure 10-1-1 below.

216 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 10-1-1 Graphic Programming

10.2 Java Script Editor


Click “Programmable/Java Script Editor” in the menu bar, as figure 10-
1-2 below.

217 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 10-1-2 Java Script Editor

10.3 PLC Editor

Click “Programmable/PLC Editor” in the menu bar, as shown in figure


10-1-3 below.

figure 10-1-3 PLC Editor

218 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

11 Common question description

11.1 Prompt to call the web server method failed


For the use of gateways on PCS, when monitoring is started, the print
message continues with an error message “Failed to call the
“[Link] web service method failed”, there are three main
reasons for this situation.

The first possibility is that the current monitoring mode is “Gateway


Mode” and needs to be adjusted to “Local Mode”.

The second possibility is that the port number of the current web server
is occupied by other applications on the machine.

The third is that the X2ViewRuntime program is shut down and you just
have to restart monitoring.

11.2 Note the difference between upload and


download projects
Special note: after the project configuration is completed on the PC,
upload the project to the gateway through the “Upload Project” function.
When you need to view the projects in the gateway. Download the projects
in the gateway to the configuration software through the download projects
function.

11.3 Problems to pay attention to when software


Try not to put the X2View configuration software on the C drive or
Desktop, but on other drives.

11.4 Running [Link] to report an error cannot


be opened.

11.4.1 The parallel configuration is incorrect.

219 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

After running the program, you are prompted “The application cannot
start because the parallel configuration of the application is incorrect. For
more information. Refer to the application event log, or use the command
line “[Link]” as shown in figure 11-4-1 below:

figure 11-4-1 shows an incorrect parallel configuration

Open the X2View folder and run the two system compatible programs

vc2005_redist.[Link] and vc2008_redist.[Link], as figure11-4-2:

figure 11-4-2 Compatibility program

11.4.2 Computer deficiency [Link]

If you are unable to start this program, and because there is a missing
API-Ms-win-CRt-Runtime-L1-1-0 DLL in your computer, you can try
reinstalling the program to resolve this problem, as shown in figure 11-4-3
below:

220 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 11-4-3 Missing file

Method 1:Run the two system compatible programs


vc2005_redist.[Link] and vc2008_redist.[Link], as shown in figure 11-4-
4 below:

figure 11-4-4 Compatibility program

Method 2: Via link https: //[Link]/zh-


CN/download/[Link]?id=48145

Download missing files from your computer, open the path to the
download file and double-click the “Run Program” to install the missing file.

12 Appendix

12.1 Operation steps of GPRS modem

12.1.1 Create a user

The menu bar under “User Management” selects the “User” to enter the
user list interface, as shown in figure 12-1-1:
221 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-1 User

Right-click in the margins of the user list and select “New User” to enter
the user properties screen, as shown in figure 12-1-2.

figure 12-1-2 A new user

Enter the username, password, and corresponding cell phones number


in the user properties field, as shown in figure 12-1-3:

222 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-3 Add user information

Note: After completing the user and the corresponding mobile phones
number, click “OK” and close the user list.

12.1.2 Creating user groups

Select “User Group” under “User Management” in the menu bar to enter
the user group list interface, as shown in figure 12-1-4:

figure 12-1-4 User group


223 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Right-click in the margins of the user group list and select “New User
Group” to enter the user group properties screen, as shown in figure 12-1-5.

figure 12-1-5 New user group

Fill in the name of the user group to be created, and double-click the
user to add it to the current user group member bar on the right:

figure 12-1-6 Add user group information

224 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Description: User group creation completed, click “OK” and close the
user group list.

12.1.3 GPRS Modem configuration

Right-click the label location to enter the label properties configuration

as shown in figure 12-1-7 below.

figure 12-1-7 Go into the tag properties

Click the alarm text to enter the alarm property settings, as shown in

figure 12-1-8 below:

225 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-8 Label property Settings

[Link] Edit the alarm content of the switch volume

226 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-9 Switch volume alarm setting

Description: 1. User Group [1] The bound user group corresponds to an

alarm with ID 1(the current value is 0)

2. User Group [2] The bound user group corresponds to an alarm with

ID 2(the current value is 1)

Note: If you do not need an alarm with the current value of 0/1, you can

leave the alarm text of the corresponding ID column ID column empty, as


Shown below: 12-1-10

figure 12-1-10 Switch volume alarm setting

[Link] Edit the alarm content of the analog quantity

227 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-11 The analog quantity alarm setting

Description: 1. User Group[2, 3]The bound user group “L_Alarm”

corresponds to an alarm with IDS 2 and 3(higher than 20 and lower than 40,
higher than 60 and lower than 80)

2. User Group [1, 4]The bound user group “H_Alarm” corresponds


to an alarm with IDS 1 and 4(an alarm below 20 and an alarm above
80)

Note: If you do not need an alarm at a certain level, leave the alarm
text blank in the corresponding ID column, as shown in figure 12-1-12 below:

228 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-1-12 Analog quantity alarm setting

12.1.4 Enable SMS alarm

The menu bar “Alarm” select “GPRS Modem”, as shown in figure 12-1-
13

figure 12-1-13 Menu bar SMS Settings

229 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Check "Enable SMS Alarm" on the GPRS SMS Cat configuration


interface ("Disable 4G dial-up” Internet access if you do not need to use a
4G card), as shown in figure 12-1-14 below:

figure 12-1-14 Turn on SMS alarm

The SMS alert message receives the image shown in figure 12-1-15.

figure 12-1-15 SMS alarm message

12.2 SMS alarm operation

12.2.1 Creating user group

Select user group under user management in the menu bar to enter the
user group list interface, as shown in figure 12-2-1:
230 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure12-2-1 user group

Right-click in the margins of the user group list and select “New User
Group” to enter the user group properties screen, as shown in figure 12-2-2.

figure 12-2-2 New user group

231 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Fill in the user group name you want to create, as shown in figure 12-2-
3:

figure 12-2-3 User group Settings

Description: User group creation completed, click “OK`” and close the
user group list.

12.2.2 Configure alarm information.

Right-click the label point to enter the label property configuration

232 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-4 Go into the tag properties

Click the alarm text to enter the alarm property settings, as shown in

figure 12-2-5.

233 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-5 Label property Settings

[Link] Edit the alarm content of the switch volume

234 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-6 Switch volume alarm content setting

Description: ① The “User Group [1]” bound to the user group

corresponds to an alarm with ID 1(the current value is 0)

② The “User Group [2]” bound to the user group corresponds to an

alarm with ID 2(the current value is 1)

Note: If you don’t need an alarm with the current value of 0/1, you Can
leave the alarm text in the corresponding ID column empty, as shown in
figure 12-2-7.

235 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-7 switch volume alarm content setting

[Link] Edit the alarm content of the analog quantity

236 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-10 The analog quantity alarm content setting

Description: 1. User Group[2, 3]The bound user group “L_Alarm”

corresponds to an alarm with IDS 2 and 3(higher than 20 and lower


than 40, higher than 60 and lower than 80)

2. User Group [1, 4]The bound user group “H_Alarm” corresponds


to an alarm with IDS 1 and 4(an alarm below 20 and an alarm above
80)

Note: If some level of alarm is not required, the alarm text in the
corresponding ID column can be set blank, as shown below

figure 12-2-11 shows:

237 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-11 The analog quantity alarm content setting

12.2.3 Turn on WeChat alarm

Select “WeChat” from the menu bar to enter the WeChat function
enabled interface, as shown in figure 12-2-12:

figure 12-2-12 Menu bar WeChat Settings

238 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Check the "Enable WeChat Alarm" button on the WeChat alarm


interface, as shown in figure 12-2-13

figure 12-2-13 Turn on WeChat alarm

IP address: fill in the IP address of the cloud server (in the figure, the
IP address of Sunfull WeChat alarm cloud). Gateway with WeChat alarm
function, touch screen, or computer, all need to be able to surf the internet.

Note: If the private cloud needs to be deployed, use the customer's


own WeChat public platform to push the alarm information, and the client
cloud server needs to carry out relevant deployment, and consult Sunfull
technical support for details.

Company ID: Keep the same company ID when applying for the
company administrator account. English characters is of not more than 12
characters.

Device Name: In the received WeChat alarm content will be displayed,


to distinguish between different devices issued by the alarm.

239 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Unique ID: Refers to the unique ID of the WeChat alarm gateway (the
project file of the gateway), which needs to be automatically generated by
clicking to change the device.

Group Name: That is select the user group that needs to send alarm
information.

Code: Obtain the WeChat alarm QR code of the corresponding user


group.

Note:

①Selecting a user group will generate QR code, which the user need
to scan.

②Add attention to enter the user group, scan again to receive the alarm
information of the device. If the user pays attention to another device or
another user group, it needs to be scanned again QR code. If there is no
user group, it can be in the user managed user group on the menu bar, add
user groups.

③ The generation of WeChat alarm QR code requires the current


computer to be able to surf the Internet.

The WeChat alarm message receives the image, as shown in figure 12-
2-14

240 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-2-14 The analog quantity alarm content setting

12.3 Telephones alarm operation procedure

12.3.1 Create user

Under the menu bar user management, select the user to enter the user
list interface:

241 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-1 User management Settings

Right-click in the blank of the user list and select “New user” to enter the
user properties interface, as shown in Figure 13-3-12 below.

figure 12-3-12 New user Settings

Enter the username, password and the corresponding mobile phones


number in the user property field:

242 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-3 Add the user and cell phones number

Note: After completing the user and the corresponding mobile phones
number, click “OK” and close the user list.

12.3.2 Creating user groups

Under user management in the menu bar, select user groups to enter
the user group list interface:

figure 13-3-4 User group Settings


243 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Right-click in the blank of the user group list and select New user group

to enter the user group properties interface:

figure 12-3-5 New user group

Fill in the name of the user group to be created, and double-click the
user to add it to the current user group member bar on the right

figure 12-3-6 Users are added to user groups


244 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Description: User group creation completed, click “OK” and close the
user group list.

12.3.3 Configure alarm information

Right-click the label point to enter the label property configuration:

figure 12-3-7 Alarm information setting

Click the alarm text to enter the alarm property settings:

245 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-8 Alarm text

[Link] Edit the alarm content of the switch volume

246 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-9 Switch point alarm text

Description: ①The User Group [1] is bound to an alarm with ID 1(the

current Value is 0)

②User Group [2] Bound user group corresponds to an alarm with ID


2(the current value is 1 alarm)

Note: If the alarm with the current value of 0/1 is not needed, the alarm
text in the corresponding ID column can be set blank, as shown in the figure
below:

247 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-10 The switch point cancels the alarm setting

[Link] Edit the alarm content of the analog quantity

figure 12-3-11 Analog quantity alarm content

248 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

Description: ① The User Group [2, 3] binding user group “L_Alarm”

corresponds to an alarm with IDS 2 and 3(higher than 20 and lower


than 40, higher than 60 and lower than 80)

②User Group [1, 4] Bind user group “H_Alarm” to alarm with IDS 1

and 4(alarm below 20, alarm above 80)

Note: If an alarm of some level is not required, the alarm text in the
corresponding ID column can be set blank, as shown in the figure below.

figure 12-3-12 Analog quantity cancel alarm

12.3.4 Turn on the phones alarm

Menu bar alarm and select the phones to enter the enabled interface of
4G SMS cat function:

249 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-3-13 Telephones alarm setting

Check "Enable Telephone Alarm" on the setting interface of 4G SMS


cat (check "Disable 4G dial-up” internet access if you do not need to use 4G
card for Internet access):

figure 12-3-14 Turn on the phones alarm


250 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

12.4 DingTalk alarm operation step

12.4.1 Configure alarm information

Right-click the label point to enter the label property configuration:

figure 12-4-1 DingTalk alarm configuration

Click the alarm text to enter the alarm property settings:

251 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-2 Alarm text configuration

[Link] Edit the alarm content of the switch volume

252 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-3 Switch point alarm setting

Description: ① When the current value is 0, the alarm with ID 1 will be

triggered (the current value is 0 alarm).

② When the current value is 1, an alarm with ID 2 will be triggered

(the current value is 1 alarm).

Note: If the alarm with the current value of 0/1 is not needed, the alarm text
in the corresponding ID column can be set blank, as shown in the figure
below:

figure 12-4-4 The switch point cancels the alarm setting

[Link] Edit the alarm content of the analog quantity

253 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-5 Analog quantity alarm setting

Description: ①ID1 corresponds to an alarm below 20 (an alarm below 20).

② ID2 corresponds to an alarm below 40 and above 20 (an alarm

below 40 and above 20).

③ID3 corresponds to alarm above 40 and below 60 (alarm above 40

and below 60).

③ID4 corresponds to alarm higher than 80 (alarm higher than 80).

⑤The specific alarm threshold value is set by custom.

Note: If an alarm of some level is not required, the alarm text in the
corresponding ID column can be set blank, as shown in the figure below:

254 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-6 The analog quantity alarm is cancelled

12.4.2 Open DingTalk alarm

Menu bar alarm select phones to enter the enabled interface of


DingTalk setting:

255 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-7 DingTalk alarm setting

Check the box of "Enalbe DingTalk Alarm" on the interface of stitching


setting.

figure 12-4-8 Open the nail alarm

Fill in the webhook address generated by the customized DingTalk


robot in the DingTalk group chat, and the specific location is shown in the
figure

256 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-4-9 Acquire the nailing robot webhook

Note: The webhook address in the DingTalk needs to be checked in the robot
management on the PC side, while the mobile side cannot check the webhook address
in the nail.

12.5 Operation steps of mail alarm

12.5.1 Create a user

Under the menu bar user management, select the user to enter the user
list interface:

257 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-1 User management configuration

Right-click in the blank of the user list and select “New User” to enter
the user properties interface:

figure 12-5-2 A new user

Enter the username, password and the corresponding E-mail address in


the user property field:

258 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-3 User mail Settings

Description: Click “OK” to close the user list after completing the user and
the corresponding mailbox.

12.5.2 Creating user groups

Under user management in the menu bar, select user groups to enter
the user group list interface:

figure 12-5-3 User group Settings

Under “User Management” in the menu bar, select “User Group” to


enter the user group list interface:

259 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-4 New user group

Fill in the name of the user group to be created, and double-click the
user to add it to the current user group member bar on the right:

figure 12-5-5 Users are assigned to user groups

Description: When the user group creation is complete, click “OK” and
close the user group list.

260 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

12.5.3 Configure alarm information

Right-click the label point to enter the label property configuration:

figure 12-5-6 Configure alarm

Click the alarm text to enter the alarm property settings:

261 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-7 Alarm text setting

[Link] Edit the alarm content of the switch volume

262 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-8 Switch point alarm content

Description: ① The User Group [1] is bound to an alarm with ID 1(the

current value is 0).

②User Group [2] binding user group corresponds to an alarm with ID

2(the current value is 1 alarm)

Note: If the alarm with the current value of 0/1 is not needed, the alarm text
in the corresponding ID column can be set blank, as shown in the figure
below:

figure 12-5-9 Cancel switch point alarm

[Link] Edit the alarm content of the analog quantity

263 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-10 The analog quantity alarm setting

Description: ① User Group [2, 3] binds user group “L_Alarm” which

corresponds to an alarm with IDS 2 and 3(above 20, below 40, above
60, below 80)

②The User Group [1, 4] bound user group “H_Alarm” corresponds to

an alarm with IDS 1 and 4(an alarm below 20 and an alarm above 80)

Note: If an alarm of some level is not required, the alarm text in the
corresponding ID column can be set blank, as shown in the figure below:

264 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-11 The analog quantity alarm is cancelled

12.5.4 Open mail alarm

Select Mail from the menu bar for alarm and enter the enabling interface
of E-mail alarm:

figure 12-5-12 Email alarm Settings

Check "Enable Mail Alarm" in the E-mail alarm interface:


265 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-13 Turn on the mail alert service

Description:

Sending Mail server(SMTP): fill in the SMTP server used by the sending box.

Port number: select the port number used by SMTP service. 465 or 587 port number is
recommended for foreign use.

Email address: Fill in the email address of the outbox.

Client authorization password: fill in the client authorization code when the outbox
opens client SMTP service.

figure 12-5-14 QQ Email take on POP3 /SMTP service

266 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure12-5-14 163 开启 POP3/SMTP 服务

figure12-5-15 163 Mailbox gets client authorization code

Note: ① If email alarm is enabled, it is recommended not to use Chinese

name calling and Chinese alarm contents.

②If you can't receive mail through QQ mailbox, you need to add the

current gateway mailbox to the white list in the incoming query, as shown in
the figure below

267 / 268
Add: 28 Senang Crescent,#05-11,Bizhub 28,Singapore 416601 Tel: +65 80385403 URL: [Link]
milesgoiiot@[Link] / sales@[Link]
X2View User Manual

figure 12-5-16 QQ email self-service