0% found this document useful (0 votes)
22 views9 pages

49 Wireless

n

Uploaded by

AZIZ UR RAHMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views9 pages

49 Wireless

n

Uploaded by

AZIZ UR RAHMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

See discussions, stats, and author profiles for this publication at: [Link]

net/publication/345482397

Wireless Controlling of Electrical Lighting Systems through Digital Signal to


Reduce the Complexity in the Electrical Network

Article in International Journal of Advanced Research in Electrical Electronics and Instrumentation Engineering · September 2015
DOI: 10.15662/IJAREEIE.2015.0409049

CITATIONS READS

0 559

3 authors, including:

C Mahesh Edirisinghe Y.H.N. Dilhani


University of Colombo University of Colombo
73 PUBLICATIONS 278 CITATIONS 3 PUBLICATIONS 2 CITATIONS

SEE PROFILE SEE PROFILE

All content following this page was uploaded by C Mahesh Edirisinghe on 08 November 2020.

The user has requested enhancement of the downloaded file.


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015

Wireless Controlling of Electrical Lighting


Systems through Digital Signal to Reduce the
Complexity in the Electrical Network
MT Thahir1, Mahesh Edirisinghe2, YHN Dilhani3
PG Student, Faculty of Science, University of Colombo, Colombo 03, Sri Lanka1
Senior Lecturer, Faculty of Science, University of Colombo, Colombo 03, Sri Lanka2
UG Student, Faculty of Science, University of Colombo, Colombo 03, Sri Lanka3

ABSTRACT: The innovative approach of wireless controlling in electrical lighting systems through electrical digital
signal is presented in this study, which can be used to replace the wired wall switches in order to reduce the complexity
in the electrical network while enhancing the operational safety. Importantly, the system would facilitate to
communicate very effectively without any interference between devices, when more wireless control devices used in
large electrical systems in industries and it introduces two way communication for status indication. The developed
system consist of a PIC18F452 Microcontroller Unit, a RF Module, a Switch Unit, a Relay Unit, an AC Current
Sensing Circuit, a Voltage Regulator and a Power Supply Unit. The central process of constructing the system was
designing and implementing the Switch Unit and the Relay Unit to control the electrical load connected to the Relay
Unit. The developed system operates on XBee networking protocol IEEE 802.15.4 and functions within the ISM 2.4
GHz frequency band and are pin-for-pin compatible with each other whereas the effective outdoor distance range is
radially outward of 70 m. Moreover, specific advantages and conveniency of using the developed system over
conventional wired network is also been discussed.

KEYWORDS: Wireless electrical network, Wiring complexity, RF network, ISM band network.

[Link]
Nowadays most of technological and industrial sectors are focused on introducing low cost, minimal power consuming
and long lasting data communication systems to deploy in modern industries and often endeavour to find solutions for
difficulties and failures which may arouse in traditional wire connecting systems and perhaps even with existing large
scale wireless systems [1]. Gradually, wireless technology has been risen swiftly for monitoring and controlling of
various processes in industrial and other applications with vast potential of advance in technology. Therefore, currently,
this technology governs a wide role with the intention of diminishing the drawbacks of existing complicated wired
systems which has been used for monitoring and controlling of processes over decades.

As a common fact, in industrial and commercial lighting systems have very complicated cable laying and the wire
connections throughout the premises cost huge amount of money, time and effort. In contrasting that, using the RF
wireless modules to communicate between devices in premises, no complex wire connections are [Link] far, many
researches have been conducted and some novel researches are undergoing in order to improve and enhance the
feasibility of wireless systems in numerous areas [2]. Typically, it has been investigated to be used in industrial
environment to automate and to diminish the man power while making the process more rapid and more productive [2-
4]. Nevertheless as mentioned and discussed in [5], there is a consequence that the wireless systems are operated by
storage batteries which require longer lifetimes and the consequences of expanding this technology on various
industries are investigating on many research areas.

Meantime as mentioned in [6], there had been designed laboratory set up on wireless controlling using four IR lamps
with corresponding sensors, and if there is some malfunction at one end, there is no way to predict the function on the

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7648


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015


other side and it could be crucial when remote controlling. Moreover, in most of wireless controlling, they seems only
being focused on one way communication which is similar situation as reported in [6] and henceforth there are only
limited number of researches have been conducted up to now. As an elucidation, one of the main objective of this study
is to introduce two way communication system to operate distant circuit while avoiding existing drawbacks and
presenting innovative model to enhance the effectiveness.

Moreover, using radio frequency (RF), it enables to control distance objects using a variety of radio signals transmitted
by a corresponding remote control device. Furthermore, using RF control system, it can control a variety of mechanical
or electronic devices to complete various switching operations. As a complementary method to IR remote control type,
the RF remote control is widely used in operative functions at home garages, electric gates, automatic barriers,
industrial applications, wireless burglar alarm systems and etc.

Typically, electrical lighting systems in industrial, residential, commercial places and street lamps are monitored and
controlled by conventional wired system, which may not efficient in terms of cost and maintenance. In contrasting, in
wireless technology introduces a more sophisticated, economical and reliable wireless switching systems with risk
preventive actions for the benefits of consumers. The proposed Wireless Controlling of Electrical Lighting System
through digital signal (WiCELS) would adopt to overcome this issues. Even though wireless technology has many
advantages over conventional systems, WiCELS is not widely available for controlling electrical industrial and
commercial lighting systems in Sri Lankan context at the present.

In this study it was expected to improve currently existing wireless control system to indicate the status on the
receiving end, enabling for more precise and fault free functioning. Moreover, it is expected to introduce two way
communication system using RF controlling to designate the status of the receiving end while diminishing the
malfunctions which may occur due to less awareness of the condition at the other end, which may lead to monitor and
control the processes more accurately and precisely without any interference between devices. The WiCELS module
introduced in this study, is expected to introduce an unique feature to indicate the real status of the RX via LED
indicator in the TX unit to display whether the lamp is really lit up or not for visually make sure even from some
distance. With the purpose of that, an innovative prototype model has been designed and its importance has been
discussed in this paper by illustrating the above mentioned process. While improving unique advantages of existing
devices, some further drawbacks from other related products have been eliminated through WiCELS technology.
Moreover, this module also would facilitate to communicate very effectively without any interference between devices
when more wireless control devices used in a large electrical system in industries.

A single lamp Relay Unit and its corresponding Switch Unit is illustrated in Fig 1 which provides an overview of the
proposed WiCELS module. As can be seen there, a four byte length code is used as a device identification with one byte
length code for Relay Unit identification which will make secure controlling and prevent interference whereas status
display LEDs indicate the lamp status whether it is really in operation or not.

Fig. 1: Overview of the proposed WiCELS module for single lamp control.

[Link] METHODOLOGY
In order to contrast the main objective of the research, it was determined to design a prototype model which is
operating by means of wireless control technology. The WiCELS module utilized in this prototype model is consisting
of a PIC18F452 Microcontroller Unit, RF Module, an Switch Unit, a Relay Unit, an AC Current Sensing Circuit, a
Voltage regulator and a Power Supply Unit. The central process of constructing the prototype was designing and
implementing the Switch Unit and the Relay Unit.

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7649


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015

With the intention of communicating between the Switch Unit and the Relay Unit, XBee protocol has been equipped. It
is essential to interact between these two units by means of RF Module as an essential requirement of the proposed
system. As stated in [7], the XBee RF Module was engineered to meet IEEE 802.15.4 standards and support the unique
needs of low-cost, low-power wireless sensor networks and provide reliable delivery of data between devices. The
modules operate within the ISM 2.4 GHz frequency band and are pin-for-pin compatible with each other.

Despite the fact that in a single XBee unit, there could be implemented up to 8 switches and 8 LEDs in order to indicate
the prominence of the bulbs, only 4 switches and 4 LEDs are comprised in the prototype by the means of convenience,
though it could be extend to any extent as required when it comes to the real world application. The Switch Unit
comprises of PIC18F452 CMOS FLASH based 8-bit microcontroller, six operating switches, four LEDs, and a RF
Module transceiver whereas the Relay Unitalso contains a PIC18F452, four lamps as the load and a RF Module
Transceiver. All connections of the wireless control of lighting systems have been made according to the functional
block diagram as shown in Fig 2 whereas Fig 2(a) and Fig 2(b) show the Switch Unitand Relay Unit respectively.

Fig. 2: Functional block diagram of the WiCELS Module (a) Switch Unit; (b) Relay Unit.

It is important to have an overlook of the operation procedure of the WiCELS which has been used in this study. For the
purpose of controlling the lamps, in the Switch Unit there has been used four switches to ON/OFF individually and
additional two switches to ON/OFF all lamps at the same time as indicated in Fig 2(a). The schematic diagram of the
Switch Unit is shown in Fig 3. If one of the six switches is pressed, the particular pin which is connected to the switch
of the PIC microcontroller gets logic 1, then it loads corresponding four byte Device ID and one byte Relay ID serially
and send it as an encoded signal from TX pin of microcontroller to the RF Module in the Switch Unit.

Fig. 3: Schematic diagram of the Switch Unit.

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7650


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015


As soon as a push button (SW1-SW6) in the Switch Unit is pressed, the PIC will send a unique encoded code according
to its input (as per the relevant switch pressed) to the receiver of the Relay Unitthrough the transmitter of the Switch
Unit. The signal from the Switch Unit will be transmitted in the form of RF to the Relay Unit. The receiver of the Relay
Unitwill accept the signal and match the signal with the DeviceID, it is ok then match the Lamp ID and send it to the
corresponding transistor and to the relevant LED which would indicate that which relay is in operate. When the Relay
Unit receives the signal, it will be processed at the PIC microcontroller. The Relay Unit will be received the voltage
signal corresponding to the signal which is being processed by the microcontroller and transmitted from the Switch
Unit via RF Module. The schematic diagram of the Relay Unitis shown in Fig 4. At the processing, initially
corresponding four byte Device ID signal will be compared with its programmed Device ID serially and if it is
acceptable then the received one byte Relay ID signal will be compared. Thus the particular Relay Switch will be
energized according to the signal processed. The AC Current Sensing Circuit indicated in Fig 5 which is coupled to the
Relay Unit detects the current through the particular lamp. As shown in Fig 5, there is an AC Current Sensing Unit for
each lamp in order to identify the particular lamp to be lit ON or OFF when current is flowing through it by using
optocouplers.

Fig. 4: Schematic diagram of the Relay Unit.

Fig. 5: Schematic diagram of the AC Current Sensing Circuit.

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7651


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015


Once the feedback to the microcontroller and the signal of the detection will be transmitted to the Switch Unit, it
enables to energize the particular LED as a status display of the lamp hence, status of the lamps can be identified. The
microcontroller in WiCELS is PIC18F452 which is programmed by using C language with MikroC PRO 2010 compiler
and the software development process for the Switch Unit and the Relay Unit can be summarized using a flow chart as
shown in Fig 6.

Fig. 6: Flow chart of the software development (a) Switch Unit; (b) Relay Unit.

III. IMPLEMENTATION AND VALIDATION


With the completion of programming process and hardware construction, the prototype module had to undergo testing
stage in order to ensure that the overall system is well functions throughout the overall process. Initially, test was
carried out to make sure that the critical voltages supply by the Power Supply Unit are satisfactory to operate PICs, RF
Modules and other electrical components. Hence, the Power Supply Unit was tested and a voltage of 12 V was
obtained. Subsequently, the regulator which was used in both Switch Unit and Relay Unit was subjected to test. In this
case a DC voltage of 3.3 V was read ensuring that the microcontroller and the RF Module were received enough power
for its operation. A photograph taken during the testing of the power supply unit is shown in Fig 7(a) whereas Fig 7(b)
shows a photograph taken during the testing of the regulator circuit which shows 3.178 V after fully loaded.

Fig. 7: Photograph taken during the testing of (a) Power Supply Unit; (b) Regulator Circuit.

Successively, the functionality of the circuit of the Relay Unit was tested and the success was gauged based on LED
illuminations. Next, the functionality of the Switch Unit was tested with the aid of LED illumination results. A
photograph taken during the testing of the Relay Unit circuit is shown in Fig 8(a) whilst Fig 8(b) shows a photograph
taken during the testing of Switch Unit circuit. The overall testing was based on the dual functionality of the Switch
Unit and the Relay Unit. When the Regulated Power Supply is connected to the Relay Unit, it will be indicated by
illuminating the red colour LED whereas illumination of green colour LEDs will indicate that the particular relay is
ready for its operation as specified by the PIC in the Relay Unit as indicated in Fig 8(a). The RF Module in the Relay
Unit will receive signal from Switch Unit indicating particular LED glowing for particular relay function and
illuminating specific lamp for it. As a result of that, feedback signal from the Relay Unit will be sent to the Switch

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7652


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015


Unitin order to indicate the status of lamp by glowing its particular LED. Once this circuit is connected to the power
supply, the red and green LEDs will lit ON for a few second designating that the circuit has a supply and has no
malfunction in terms of connectivity and the microcontroller is ready for its operation.

Fig. 8: Photograph taken during the testing (a) Relay Unit circuit; (b) Switch Unit circuit.

Furthermore, the output signal of the Switch Unit is tested at its USART terminal and for the Relay Unit it was tested at
its RF module by keeping the distance of one meter away from the Switch Unit. Captured waveforms of five byte signal
generated (4 byte Device ID signal + 1 byte Relay ID signal) for the Switch Unit and the Relay Unit are pictured in Fig
9(a) and Fig 9(b) respectively.

Fig. 9: Recorded output signal (a) Switch Unit: USART pin; (b) Relay Unit: RF Module.

After the completion of the construction of the proposed system, a series of test procedures was essential to carry out in
order to assure that the developed system is functioning fault free without interfering and accurately, whereas Fig 10
shows the pictorial overview of the prototype constructed consist of a Microcontroller Unit, a RF Module, an Switch
Unit, a Relay Unit, an AC Current Sensing Circuit, a Voltage Regulator, and a Power Supply Unit.

Fig. 10: Photograph of the overall system.

In order to verify the effectiveness of the directive angle, as well as the distance between the Switch Unit and the Relay
Unit will affect the RF signal of the TX and RX, an experiment had been conducted by varying the distance between
two units in different levels of height on a sunny weather condition. For that, distance between the two units was
initially kept at one meter apart and subsequently altered from 10 m to 100 m in 10 m increments whilst the angle
between them varied in increments of 45° from 0° to 315° to test the radially outward response and the proper
functionality of the RX signal was observed with the help of foresaid LEDs in the Switch Unit.

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7653


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015

Meanwhile, another test was carried out in order to find the effect of line-of-sight. For that, the Switch Unit height was
changed from the ground level up to 3 m and for every variation of 0.5 m height, the Relay Unit height was kept at
ground level and its response was observed by changing the separation distance up to 100 m by following the same
increment distance as mentioned above. The line-of-sight testing procedure was further extended by changing the Relay
Unitheight from ground level up to 3 m with a variation of 0.5 m height with respect to ground. According to the results
obtained, it is apparent that the overall results for all the angles measured remain unaltered regardless of the position of
the two units up to 90 m which is the specified range for RF Unit by the manufacturer [7]. Furthermore, in order to find
the response under rainy weather condition, foresaid experiment was repeated by creating artificial water spray channel
and the effective response distance was found to be maximum of 70 m. However, by recalling the manufactures
specifications as mentioned in [7], the effective operation distance may reduce down to 30 m if the developed WiCELS
unit is used in an indoor or an urban environment. Therefore, in here it works as omi-directional transceiver system and
it can be concluded that the line-of-sight alignment is not required which can be considered as an added advantage.
IV. DISCUSSION
The aim of this project is to develop a wireless control of electrical lighting systems through electrical digital signal
(WiCELS) that enables to control electrical lamps/power outlets without return wires. Further, it mainly focused on
practical purposes which may useful for even household electrical systems something that can be related on a daily
basis whereas the developed system does not required a physical interface between the RF Module used and the
microcontroller. In here, the system hardware has been successfully built with the expected functionality and it was
thoroughly tested and now is ready for commercialization. The innovative approach of WiCELS is to reduce the
complexity in the electrical network which is the expected outcome of this project which will replace the conventional
wired wall switches.

When it comes to practical applications, it is highly recommend to use developed WiCELS in electrical lighting
systems, so that it will facilitate to reduce the complexity of the wired network while enhancing the operational safety
where the system will be isolated from live wiring. Furthermore, it requires less installation time with a convenient
installation process, undeniably less maintenance once implemented together with having an advantage of status
indicators. Hence there is no requirement of routine physical checking which would reduce the labour cost as well. It is
important to mention that no line-of-sight alignment is necessarily required for the functionality of the system and four
byte Device ID and one byte Relay ID provide to have a secure communications with no interferences possible even
within different WiCELS units.

Furthermore, it is important to mention here that using the developed system, it would enable to reach out for certain
areas remotely which would be more hazardous or considerably difficult to reach out by a human being without causing
any damages. Moreover, effects due to the transients generated by lightning induced voltages could be minimized by
the developed system as it consist of least length of wires compared to conventional wired network.

The block diagram of an implemented application of a typical street light wiring using WiCELSis shown in Fig 11(a),
which clearly illustrates the simplicity of the wiring network and hence bunch of return wires and conduits to the
Switch Unit is reduced by the WiCELS. The foresaid street light wiring system consist of 5 Single Lamp Relay Units
(SLRU) with separate one byte Relay IDs and a 5 Gang Switch Unit with a four byte Device ID as a WiCELS, as
illustrated in the Fig 11(a). Also, considering another application in typical residential wiring, a WiCELS being
constructed and programmed for a four Gang Switch Unit and a four lamps Relay Unit with a four byte Device ID and
four respective one byte Relay IDs as illustrated in Fig 11(b).

It is important to mention that the power consumption of the Relay Unit is 195 mA at 12 V DC when all switches in
operation. However, it can be further reduced by introducing electronic solid state switches in place of relay switches
and by introducing sleep mode of the RF module under stand-by-mode. Additionally, a rechargeable 3 V battery bank
can be fixed in the Relay Unit so that the operation data of the microcontroller will not lose.

As described before, the distance of the RF module has a radially outward limit of 90 m as the transceiver covering
range at outdoor in a sunny day and will dropdown to 70 m in a rainy day. Therefore, strictly speaking, outdoor range

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7654


ISSN (Print) : 2320 – 3765
ISSN (Online) : 2278 – 8875

International Journal of Advanced Research in Electrical,


Electronics and Instrumentation Engineering
(An ISO 3297: 2007 Certified Organization)

Vol. 4, Issue 9, September 2015


of the WiCELS should be considered as 70 m. However, if it is required a higher covering range, the wireless RF
Module should be replaced by the devices such as XBee PRO 802.15.4 or ZigBee 802.15.4 that can exceed the range
up to 1.6 km. Consequently, required power consumption of that system will be increased by more than 10 times the
required power of the developed system. Therefore, it is recommended to carry out proper system requirement analysis
before the designing stage, so that the Relay Unit, the Switch Unit and a proper RF module can be effectively
implemented.

Fig. 11: Block diagram of a typical applicationusing WiCELS (a) street light wiring; (b) residential wiring.

V. CONCLUSION
The foremost achievement obtained of this experimental study, can be concluded as an effective and innovative
approach of overcoming the shortcomings in existing conventional wiring networks such as complexity, cost of
installation and maintenance, time consumption and also as an appropriate modification of avoiding possible
interferences which may occur in modern wireless systems by introducing RF technology together with two way
communication between two units for switching operation with status indication and more secure [Link]
innovative approach of wireless controlling of electrical lighting systems through electrical digital signal (WiCELS) is
the outcome of this project which will replace the wired wall switches. For this system, a RF Module, operates on XBee
networking protocol which was engineered to meet IEEE 802.15.4 has been equipped and it functions within the ISM
2.4 GHz frequency band and are pin-for-pin compatible with each other. As a result of final testing, the effective
outdoor distance range of the developed system is with approximately radially outward limit of 70 m. It is highly
recommend to use developed WiCELS in electrical lighting systems, so that it will facilitate to reduce the complexity of
the wired network.

REFERENCES
[1] Hanssmann, M., Rhee, S., and Liu, S. (2009). No wiring constraints. Industry Applications Magazine, IEEE, 15(4), 60-65.
[2] Song, J., Mok, A. K., Chen, D., and Nixon, M. (2006, August). Using real-time logic synthesis tool to achieve process control over wireless
sensor networks. In Embedded and Real-Time Computing Systems and Applications, 2006. Proceedings. 12th IEEE International Conference
on (pp. 420-426).
[3] Gungor, V. C., and Hancke, G. P. (2009). Industrial wireless sensor networks: Challenges, design principles, and technical
approaches. Industrial Electronics, IEEE Transactions on, 56(10), 4258-4265.
[4] Antoniou, M., Boon, M. C., Green, P. N., Green, P. R., and York, T. A. (2009, February). Wireless sensor networks for industrial processes.
In Sensors Applications Symposium, 2009. SAS 2009 IEEE (pp. 13-18).
[5] Raghunathan, V., Ganeriwal, S., and Srivastava, M. (2006). Emerging techniques for long lived wireless sensor networks. Communications
Magazine, IEEE, 44(4), 108-114.
[6] Bemporad, A., Di Cairano, S., Henriksson, E., and Johansson, K. H. (2010). Hybrid model predictive control based on wireless sensor
feedback: An experimental study. International Journal of Robust and Nonlinear Control, 20(2), 209-225.
[7] Manual, P. (2009). [Link]-802.15.4 Protocol. Digi International Inc., Minnetonka, MN, 55343.

Copyright to IJAREEIE DOI: 10.15662/IJAREEIE.2015.0409049 7655

View publication stats