0% found this document useful (0 votes)
94 views9 pages

MiCOM C264 REU Board Installation Guide

The document provides installation instructions for the MiCOM C264, detailing how to format flash memory, launch a Telnet session, and configure the REU board using the CAT tool. It includes steps for firmware upgrades and first configurations using the wflash_nios2 tool, as well as security management tasks for user accounts. Editable and read-only REU parameters are also listed, along with their descriptions and settings.

Uploaded by

lukinhass22
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views9 pages

MiCOM C264 REU Board Installation Guide

The document provides installation instructions for the MiCOM C264, detailing how to format flash memory, launch a Telnet session, and configure the REU board using the CAT tool. It includes steps for firmware upgrades and first configurations using the wflash_nios2 tool, as well as security management tasks for user accounts. Editable and read-only REU parameters are also listed, along with their descriptions and settings.

Uploaded by

lukinhass22
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Installation C264/EN IN/E20

MiCOM C264 Page 65/78

Click the Format flash memory button and wait till the end.
NOTE: The passwords and logoff time-outs are spared by this operation.
[Link] Launch a telnet session
To perform tasks that CAT cannot handle, launch the default Windows Telnet client on the
operator PC and wait for the login request:

The "logout" command or the windows close can be used to terminate the session.
As Telnet is launched independently of CAT, multi sessions on two or more computers are
possible.
As Telnet used TCP/IP stack, the computer has to be accessible from the PC in this mode.
7.5.10 REU board CAT configuration
The Configuration tool CAT allows to monitor and update the firmware of the REU Boards.

NOTE: Use CAT version A3.15 or later.

From CAT main panel, select Manage boot and network parameters view
On the panel, click on REU Switch parameters button

FIGURE 4: ACCESS REU SETTINGS


C264/EN IN/E20 Installation

Page 66/78 MiCOM C264

The window REU settings is displayed as below (use the vertical scrollbar to access all
settings).

FIGURE 5: WINDOW REU SETTINGS

Refresh: reload parameter from the board.

Apply: apply parameters set to the board.

Factory Mode: set the setting to default value

The setting table below describes the Editable REU Parameters:

Label Description Field


Name Name of Certificate mandatory
Description Description of certificate
FLASH Status of flashing IDLE
process. ERROR
Status can be set only OK
when state is not BUSY
BUSY. This is used to
reset status before new
update

ETH_MAC_S Source MAC address xx-xx-xx-xx-xx-


used to send xx
supervision frame in
HSR or PRP mode.
ETH_MAC_I Source MAC address xx-xx-xx-xx-xx-
used by HSR/PRP xx
module to answer to
HOST_CPU on interlink
port only.
MODE Allows to set mode of HUB
HSR/PRP module SWITCH
HSR
PRP
RSTP
PORT_A
PORT_B
OFF
Installation C264/EN IN/E20

MiCOM C264 Page 67/78

PTP Enable/disable PTP ON


IEEE1588 protocol. OFF
PTP_PRIMARY_DOMAIN Define the primary 0..255
domain use to
syntonizer internal
hsr/prp ptp clock.
PTP_ANNOUNCE_RECEIPT_TIMEOUT Timeout period of 2..10
announce message.
PTP_LOG_MIN_PDELAY_REQ_INTERVAL Period of Pdelay_Req n = 0..5
message sent to
compute link delay.
Value is 2^n seconds.
HSR_PRP_LIFE_CHECK_INTERVAL Period of hsr/prp 100..5000
supervision frame
sending.
HSR_PRP_ENTRY_FORGET_TIME Period of clearing the 10..1340
duplicate table.
HSR_PRP_SUPERVISION_FRAME Enable or disable of ON
hsr/prp supervision OFF
frame.
PRP_TRANSPARENT_RECEPTION Enable or disable ON
removing of RCT PRP OFF
frame in PRP mode.
AUTO_INTERLINK Enable to automatically ON
switch the interlink port. OFF
FLOW_CONTROL_INTERLINK Enable interlink to ON
sends PAUSE frame OFF
according to 802.3
when there is overflow
in HSR mode.
LLDP_AB Enable lldp on LanA ON
and LanB. OFF
LLDP_I Enable lldp on Interlink ON
port. OFF
LLDP_A_REMOTE The LLDP remote state NONE
LLDP_B_REMOTE of port. ChassisID
LLDP_I_REMOTE PortID
TTL
MAC_SRC
IP
IP_ADDR IP address used by [Link]
internal CPU of
HSR/PRP board for
LLDP protocol.
RSTP_BRIDGE_PRIORITY Value prepended to 0..61440
Ethernet mac address
to form the Bridge
Identifier.
RSTP_PORT_A_PRIORITY Value prepended to port 0..240
RSTP_PORT_B_PRIORITY number from the Port step of 16
Identifier.
RSTP_PORT_A_PATH_COST Value added to current 1..200000000
RSTP_PORT_B_PATH_COST path cost on root port.
RSTP_FORCE_PROTOCOL_VERSION Parameter to force use RSTP
version of RSTP STP.
protocol backward to
STP or to RSTP(v2).
RSTP is also STP
compatible
RSTP_BRIDGE_MAX_AGE Determine the 6..40
maximum distance
between any bridge and
the current root bridge.
C264/EN IN/E20 Installation

Page 68/78 MiCOM C264

RSTP_BRIDGE_ FORWARD_DELAY Delay used for 4..30


compatibility with older
STP standard.
RSTP_BRIDGE_HELLO_TIME Period of BPDU frame. 1..2
UNICAST_FORWARD_ALL Enable the forward to A ON
or B port of unicast OFF
frame targeted to
interlink port.
ACCEPT_ALL Define the sent to ON
Interlink port. OFF
MULTICAST_ALL All multicast frames ON
from port A & B are sent OFF
to Interlink port.
MULTICAST_yy Multicast address xx-xx-xx-xx-xx-
accepted toward xx
Interlink.
Installation C264/EN IN/E20

MiCOM C264 Page 69/78

For information, the setting table below describes the Read Only REU Parameters:

Label Description Field


VERSION Version of running software x.y
x = Major revision
y = Minor revision
FPGA Version of setting FACTORY
USER
EEPROM Status of internal EEPROM OK
KO
EXT_PWR Status of external power supply ON
OFF
PSU_USE Current power supply source EXT_POWER
IED_PWR
TRA/TRB Status of optical transceiver A/B NOT_FITTED
RX_OFF
TX_OFF
OK
RSTP_BRIDGE_ROOT MAC address of the RSTP root xx-xx-xx-xx-xx-xx
bridge.
RSTP_BRIDGE_PORT_A Current state of port State:Role
RSTP_BRIDGE_PORT_B State:
- FORWARDING
- DISCARDING
- DISABLED
Role:
- ROOT
- DESIGNATED
- ALTERNATE
- BACKUP
- DISABLED
C264/EN IN/E20 Installation

Page 70/78 MiCOM C264

[Link] REU firmware upgrade with CAT

To upgrade a firmware of REU2 board, do following:


From Configuration tool CAT main panel, select Browse files view
On Local PC Side tree, select the firmware file to send to board
Click on Send button to send the firmware file forward REU board

The C264 automatically detects the reception of firmware file and upgrade it to REU board;
After upgrade, the REU board restarts with the new firmware.
Installation C264/EN IN/E20

MiCOM C264 Page 71/78

[Link] REU first configuration with wflash_nios2


At first use, or in case of anomaly, the REU is configurable with wflash_nios2 tool.
Wflash_nios2 is software allowing to set the parameter of REU board. The PC which run wflash_nios
is connected directly to the interlink port of REU board.

To read parameters of REU board with wflash_nios2


status
Click on Read button to get the current parameters of REU board
C264/EN IN/E20 Installation

Page 72/78 MiCOM C264

To set parameters of REU board with wflash_nios2


set
Click on Write button to set the new parameters of REU board

The parameters are set as following format:

MODE:HSR:
PTP:OFF:
PTP_PRIMARY_DOMAIN:0:
PTP_ANNOUNCE_RECEIPT_TIMEOUT:3:
PTP_LOG_MIN_PDELAY_REQ_INTERVAL:0:
HSR_PRP_LIFE_CHECK_INTERVAL:2000:
HSR_PRP_ENTRY_FORGET_TIM[Link]
HSR_PRP_SUPERVISION_FRAME:ON:
PRP_TRANSPARENT_RECEPTION:ON:
AUTO_INTERLINK:OFF:ok, safe state.
FLOW_CONTROL_INTERLINK:ON:
LLDP_AB:OFF:
LLDP_I:OFF:
LLDP_A_REMOTE:NONE:
LLDP_B_REMOTE:NONE:
LLDP_I_REMOTE:NONE:
IP_ADDR:[Link]:
RSTP_BRIDGE_PRIORITY:32768:
RSTP_PORT_A_PRIORITY:128:
RSTP_PORT_B_PRIORITY:128:
RSTP_PORT_A_PATH_COST:200000:
RSTP_PORT_B_PATH_COST:200000:
RSTP_FORCE_PROTOCOL_VERSION:RSTP:
RSTP_BRIDGE_MAX_AG[Link]
RSTP_BRIDGE_FORWARD_DELAY:15:
RSTP_BRIDGE_HELLO_TIM[Link]
RSTP_PORT_A:DISABLED:
RSTP_PORT_B:DISABLED:
UNICAST_FORWARD_ALL:OFF:
ACCEPT_ALL:ON:
MULTICAST_ALL:ON:
MULTICAST_00:00-00-00-00-00-00:
MULTICAST_01:00-00-00-00-00-00:
MULTICAST_02:00-00-00-00-00-00:
MULTICAST_03:00-00-00-00-00-00:
MULTICAST_04:00-00-00-00-00-00:
MULTICAST_05:00-00-00-00-00-00:
MULTICAST_06:00-00-00-00-00-00:
MULTICAST_07:00-00-00-00-00-00:
Installation C264/EN IN/E20

MiCOM C264 Page 73/78

To upgrade firmware of REU board with wflash_nios2


Click on check box Update Firmware and select the firmware file to install on REU board.
Click on Write button to send new firmware file to REU board.
After upgrade, the REU board restarts with the new firmware.

7.5.11 Security administrator functions


At installation, no account might be locked and no password is in force (keep the field blank).
The security tasks include:

Management: all the parameters are profile-specific, but valid for all of the three clients
(LHMI, CAT, MiCOM S1): a strong password is desirable (refer to PACiS/EN CS
chapter), 8 characters are indispensable
To unlock an account (observer/system engineer/ system administrator):

Select the user account in the drop-down list (second section)

Click the button Unlock Account.