0% found this document useful (0 votes)
82 views1 page

Appendix Table 4b

The document outlines allowances for electrical diversity in various premises, detailing the percentage of total current demand applicable for lighting, heating, cooking, and other appliances. It specifies different calculations for individual households, small shops, and small hotels, emphasizing the importance of adequate distribution board ratings. Additionally, it notes that certain installations, like thermostatically controlled water heaters and thermal storage heating, do not allow for diversity.

Uploaded by

jungwoocomel14
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views1 page

Appendix Table 4b

The document outlines allowances for electrical diversity in various premises, detailing the percentage of total current demand applicable for lighting, heating, cooking, and other appliances. It specifies different calculations for individual households, small shops, and small hotels, emphasizing the importance of adequate distribution board ratings. Additionally, it notes that certain installations, like thermostatically controlled water heaters and thermal storage heating, do not allow for diversity.

Uploaded by

jungwoocomel14
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

CONFIDENTIAL EC/OCT 2014/ECM216

TABLE 4B
Allowances for diversity

Purpose of final circuit fed Types of premises


from conductors or switch Individual household Small shops, stores, offices Small hotels, boarding
gear to which diversity installations, including and business premises houses, guest houses etc.
applies individual dwellings of a
block
1. Lighting 66% of total current 90% of total current 75% of total current
demand demand demand
2. Heating and power 100% of total current 100% f.l. of largest 100% f.l. of largest
(but see 3 to 8 demand up to 10A + 50% of appliances + 75% f.l. of appliances + 80% f.l. of
below) any current demand in remaining appliances 2ndnlargest appliance + 60%
excess of 10A f.l. of remaining appliances
3. Cooking appliances 10A + 30% f.l. of connected 100% f.l. of largest 100% f.l. of largest
cooking appliances in excess appliance + 80% f.l. of 2nd appliance + 80% f.l. of 2nd
of 10A + 5A if socket outlet largest appliance + 60% f.l. largest appliance + 60% f.l.
incorporated in unit of remaining appliances of remaining appliances
4. Motors (other than 100% f.l. of largest 100% f.l. of largest motor +
lift motors which appliance + 80% f.l. of 2nd 50% f.l. of remaining motors
are subject to largest appliance + 60% f.l.
special of remaining appliances
consideration)
5. Water-heaters 100% f.l. of largest 100% f.l. of largest 100% f.l. of largest
(intantaneous appliance + 100% f.l. of 2nd appliance + 100% f.l. of 2nd appliance + 100% f.l. of 2nd
type) largest appliance + 25% f.l. largest appliance + 25% f.l. largest appliance + 25% f.l.
of remaining appliances of remaining appliances of remaining appliances
6. Water-heaters No diversity allowable
(thermostatically
controlled)
7. Floor warming No diversity allowable
installations
8. Thermal storage No diversity allowable
space heating
installations
9. Standard 100% of current demand of 100% of current demand of largest circuit + 50% of current
arrangements of largest circuit + 40% of demand of every other circuit
final ciruits in current demand of every
accordance with other circuit
Appendix 5
10. Socket oulets 100% of current demand of 100% of current demand of 100% of current demand of
other than those largest point of utilisation + largest point of utilisation + largest point of utilisation +
included in 9 40% of current demand of 70% of current demand of 40% of current demand of
above and every other point of every other point of every point in main rooms
stationary utilisation utilisation (dining rooms, etc.) + 40%
equipment other of current demand of every
than those listed other point of utilisation
above

 For the purpose of this Table as instantaneous water-heater is deemed to be water-heater of any loading which
heats water only while the tap is turned on and therefore uses electricity intermittently.
 It is important to ensure that the distribution boards are of sufficient rating to take the total load connected to
them without the application of any diversity.

© Hak Cipta Universiti Teknologi MARA


CONFIDENTIAL

You might also like