ISOPRO-LP420-8 PRECISION ISOLATING INTERFACE
RAIL MOUNTING 8 CHANNEL ISOLATION MODULE FOR 2/4 WIRE 0/4-20mA INPUTS
SDIPL/8CHRTD / REV 4 / 08-2016
MODULE DEPTH 90 MM
MODULE WIDTH 183 MM
HEIGHT ABOVE RAIL 55 MM.
INPUT RANGE IS 0/4-20mA
OUTPUT RANGE IS 0/4-20mA
CORRESPONDING TO INPUT.
DESCRIPTION: TECHNICAL DATA:
The LPRTD-8 is a rail-mounted isolator which accepts eight 0 OR 4-20
mA field inputs, and provides 8 corresponding 0/4-20 mA outputs, BOARD TYPE:8 channel linear 0/4-20mA current loop
to interface to DCS, PLC etc inputs. interface board with input to output and input to input
isolation.
The unit is powered by the panel 24V supply. Field inputs are isolated
from their outputs and from each other to 2 [Link] current outputs SUPPLY FOR 2-WIRE TRANSMITTER INPUT:18V
are referred to the 24V supply common. @20mA for any channel. [Link]-CIRCUIT
PROOF.
A 2-wire transmitter is connected to field terminals A and B,and the
output of a 3 or 4 wire transmitter is received between terminals B and
INPUT LOOP DROP FOR 3 /4 WIRE INPUT:3V
[Link] link or jumper setting is involved to select type of input. MAX. FOR ANY CHANNEL. ISOLATED.
ISOLATION:2.0 KV AC RMS isolation between Input
The unit allows low-error transfer of signals across unequal plant
ground systems,eliminates multiple grounding issues, prevents
and Output AND between field inputs.
transfer of hazardous or interfering voltage & currents into sensitive OUTPUT DRIVE: 0 or 4-20mA current output to
and costly i/o circuitry & provides a safe and accurate way to transfer
inputs referred to supply common. Max. input load 110
signals to and from your system.
[Link] limit 35mA.
Module dimensions are a compact 183 mm wide by 90 mm deep. SUPPLY:24VDC +/- 2%,200mA ,with LED indication
UNIQUE FEATURES INCLUDE: and reverse polarity protection.
ACCURACY:+/- 0.1% of span, including linearty error.
COMPACT MODULE WITH 2kV GALVANIC ISOLATION, Temp. Coeff. Of output < 0.003% per deg. C.
WITH 8 CHANNELS CONVENIENTLY IN ONE PACKAGE.
REPEATIBILITY:better than 0.02% of span.
INPUT TO OUTPUT COUPLING:GALVANIC,
ISOLATION ACCURACY (0.1%).TEMP. COEFF. ONLY 0.003%
capacitance of 15pF and leakage resistance>200Mohm.
PER DEGREE CELSIUS.
INPUT RANGE :0-30mA.
LOW COUPLING CAPACITANCE OF15pF. RESPONSE TIME:better than 50msec at full load.
INPUT AND OUTPUT CONNECTIONS: Screw type
CONVENIENT INPUT TYPE SELECTION BY SIMPLE TERMINAL PCB Terminal Block, PHOENIX MECANO MKDS.
CONNECTION CHANGE.
MOUNTING: DIN Rail (35 mm width).
VERY LOW SELF-GENERATED SWITCHING NOISE.
DIMENSIONS:180 mm width along dinrail,90 mm
S
[Link] above rail 55 mm max.
HIGH ACCURACY OVER LOAD, TEMPERATURE VARIATIONS. 39,Ashoknagar Rangehill Road
Due to constant improvements,specifications subject to change without notice Pune 411007,India
Tel 9766594354
Sapre Designs & Instruments Pvt. Ltd. [Link]
e-mail:ashusapre@[Link]
COMMITTED TO CUSTOMER - DRIVEN INNOVATION contact:Ashutosh Sapre
90mm
+ +24V
24V SYSTEM
d.c SUPPLY
- 0V
+ A
TO 2-WIRE
TRANSMITTER B
4-20mA -
CH.1 CH.1
0/4-20mA
CH.2 OUTPUT,TO PLC,
INSTRUMENT,DCS
B + ETC.
FROM 3/4-WIRE
TRANSMITTER C
0/4-20mA -
CH.2
NOTE THAT FOR OUTPUTS,
THE 0V OF THE 24V SUPPLY
IS THE LOW END REFERENCE.
THE 0V OF SUPPLY IS
INTERNALLY CONNECTED
TO MINUS OUTPUTS OF ALL
CHANNELS.
183mm
FIELD SIDE CIRCUITS ARE
ISOLATED FROM THE 24V
SIDE AND FROM EACH OTHER.
ISOLATION MODULE
CH.8
CH.8
NOTES:
1)INPUT OF ANY CHANNEL IS ISOLATED FROM ITS OUTPUT. ALL INPUTS ARE IN TURN ISOLATED (FULLY FLOATING) FROM EACH
OTHER, SO USER CAN CONNECT VARIOUS INPUTS HAVING DIFFERING A.C GROUND REFERENCES, WITHOUT FEAR OF
GROUND-LOOP CURRENTS OR SPURIOUS SIGNAL INJECTION
2)ALL CHANNEL OUTPUTS SHARE A COMMON LOW REFERENCE, THIS BEING THE 0V OF THE 24V SUPPLY.
3)WIDTH AND DEPTH ON DIN-RAIL ARE SHOWN IN mm.(TOP VIEW).THE HEIGHT OF MODULE IS 55 [Link] IS UNIVERSAL DIN-RAIL.
S
DATE:10/8/2016 SCALE: 1:1 DRAWN: APPVD:
ISOPRO-LP420-8
Sapre Designs dimensions and connection
& Instruments details
Pvt. Ltd. DRAWING NO: