Table of Contents
18
DeviceBus for Honeywell Smart Distributed System 18.25
DeviceBus for Square D/Seriplex ® 18.26
DeviceBus for Phoenix Contact InterBus®-S 18.27
EIA Industrial RS-485 PLTC/CM 18.28
Interconnect 18.29
VFD (Variable Frequency Drive) Cable 18.30
Belden Infinity® Flexible Automation Cable 18.31–18.40
Introduction: Overview & Application Guide 18.31
C-TC+ Control Cables: 600V Multi-conductor 18.32
FCC Control Cables: 600V Multi-conductor 18.34
Flex Data Cables: 300V Twisted Pairs 18.39
Flex Vision Cables: 75 Ohm Coax 18.40
UL Instrumentation Cable 18.41–18.62
300V Power-limited Tray Cables: Overview 18.41
300V PLTC/ITC: Pairs & Triads 18.42
Thermocouple Extension Cable & Wire: Overview 18.53
Thermocouple Extension Cables: Shielded Pairs 18.54
Thermocouple Extension Cables: High-Temperature, Plenum 18.55
Thermocouple Wire: Unshielded 18.55
600V Tray Cables: Overview 18.56
600V Tray Cables: Pairs & Triads 18.57
UL Control Cable 18.63–18.76
600V Type TC Cables: Overview 18.63
600V Type TC Cables: Multi-conductor 18.64
600V Type MC & Teck-Style ® Cables: Overview 18.70
600V Type MC Cables: Multi-conductor 18.71
600V Dual-rated Type MC/Teck 90 Teck-Style Cables 18.74
CSA Instrumentation Cable 18.77–18.83
300V TC/CIC: Pairs & Triads 18.77
300V CIC: Pairs & Triads and Overview 18.78
300V ACIC: Armored Pairs & Triads 18.80
600V CIC: Pairs & Triads 18.82
600V ACIC: Armored Pairs & Triads 18.83
CSA Control Cable 18.84–18.95
600V and 1000V: TC/CIC Multi-conductor 18.84
600V: CIC Multi-conductor 18.85
600V: ACIC & Teck90 18.87
1000V: Teck90 18.92
1000V: VFD Cable 18.95
Technical Information 18.96–18.98
ControlNet is a ControlNet International trademark. • DeviceNet is an Open DeviceNet Vendor Association, Inc. trademark.
Interbus is a Phoenix Contact trademarks. • Seriplex is a Square D/Schneider AEG registered trademark.
Introduction
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.3
PLC/DCS PLC/DCS
System Name Belden Part Number System Name Belden Part Number
Manufacturer Manufacturer
ABB/Bailey FOUNDATION Fieldbus See Protocol listings on page 8.6 GE Fanuc — DeviceNet See Protocol listings on page 8.6
Controls Industrial IT 800 X A 9880 Network Trunk Cable Sensor Device SDS See Protocol listings on page 8.6
Networks
Infinet 9880 Network Trunk Cable
9463 Blue Hose® (Standard) Honeywell Access 4000 System 9248 RG-6 PVC
Masterpiece 200 9880 Network Trunk Cable FOUNDATION Fieldbus See Protocol listings on page 8.6
9907 Thin Network Trunk Cable (Type SP50 ISA/IEC)
MICRO-DCI 3105A 1-Pair, RS-485 IPC 620 System I/O 9271 Twinax, 25 AWG, 124 Ohm
MICROLINK 9860 Twinax, 16 AWG, 124 Ohm IPC 620 System 9729 Up to 4,000 ft.
Modcell 3105A 1-Pair, RS-485 Serial Interface 9182 Up to 10,000 ft.
Profibus DP & PA See Protocol listings on page 8.6 89182 Plenum
Allen-Bradley/ ControlNet™ See Protocol listings on page 8.6 Series C RS-485 Foundation Fieldbus
Rockwell Industrial Ethernet
DeviceNet™ See Protocol listings on page 8.6
Automation 3000 UCN & LCN 3131A RG-6 Quad Shield PVC
DH, DH+, Remote I/O 9463 Blue Hose (Standard)
3094A RG-11 Quad Shield PVC
9463F Flexible Version (9463)
Honeywell Smart Distributed 3086A Mini
129463 Aluminum Armor (9463)
Microswitch System 3087A Micro
139463 Steel Armor (9463) Division
189463 Continuous Armor (9463)
YR28826 Dual Version (9463) Invensys/ FOUNDATION Fieldbus See Protocol listings on page 8.6
Foxboro (Type SP50 ISA/IEC)
YC39151 Dual Armored (9463)
I/A Series Carrier Band 8233 Small Trunk
9463DB Direct Burial (9463)
3095A Plenum
YR29565 Various Color Jackets (9463)
9290 Drop Cable
3072F 600V TC Rated (9463)
I/A Series Fieldbus 9207 Twinax
YR41104 Low Smoke, Halogen Free
89207 200°C, Plenum
YR28764 Super Thick (PLTC)
3073F 600V Tray Cable
89463 FEP 200°C, Plenum
I/A Series Node Bus 9880 Trunk Cable
DH-485 3074F 600V Tray Cable
89880 Plenum Version
3106A 1.5-Pair, RS-485 (PLTC)
Industrial Ethernet See Protocol listings on page 8.6
9842 2-Pair, RS-485
Limitorque DCC100 3105A Actuator Bus Cable, 1-Pair,
YM39500 Flexible Version (3106A) RS-485
Industrial Ethernet See Protocol listings on page 8.6 Matsushita FP Series C-NET 9207 Twinax, 20 AWG, Stranded,
Longline 8723 Interface Cable 100 Ohm
Communications 88723 Plenum Version 9860 Twinax, 16 AWG, Solid,
Cutler-Hammer/ IMPACC System YR29090 Proprietary Trunk Cable 124 Ohm
Westinghouse I/Q System 9463 Blue Hose (Standard) FP Series MEWNET-F 9207 Twinax, 20 AWG, Stranded,
100 Ohm
Emerson DeviceNet See Protocol listings on page 8.6
Process 9860 Twinax, 16 AWG, Solid,
FOUNDATION Fieldbus See Protocol listings on page 8.6
Management (Type SP50 ISA/IEC) 124 Ohm
FP Series MEWNET-H 9248 RG-6, 75 Ohm, 18 AWG
(Fisher/ HART See Protocol listings on page 8.6
Rosemont FP Series MEWNET-TR 9207 Twinax, 20 AWG, Stranded,
Industrial Ethernet See Protocol listings on page 8.6
Systems) — 100 Ohm
Modbus See Protocol listings on page 8.6
9860 Twinax, 16 AWG, Solid,
Delta V Profibus DP See Protocol listings on page 8.6 124 Ohm
Provox Plus 3091A RG-11 Quad Shield PVC FP Series MEWNET-W 9207 Twinax, 20 AWG, Stranded,
3131A RG-6 Quad Shield PVC 100 Ohm
RS-485 See Protocol listings on page 8.6 9806 4-Pair, RS-232, RS-422
GE Fanuc — DeviceNet See Protocol listings on page 8.6 FP Series MEWNET-W2 9207 Twinax, 20 AWG, Stranded,
I/O Bus Genius YR29841 PLTC Version 100 Ohm
9030, 9070 9182 Communications Bus 9860 Twinax, 16 AWG, Solid,
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.4
PLC/DCS PLC/DCS
System Name Belden Part Number System Name Belden Part Number
Manufacturer Manufacturer
Mitsubishi CC-Link See Protocol listings on page 8.6 Omron Controller Link 9207 Twinax
Electric DeviceNet See Protocol listings on page 8.6 (continued) 89207 Twinax, 200°C, Plenum
Automation Melsecnet II 1505A Precision RG-59/U Coax 9815 Twinax, 100 Ohm,
(10/10H) 1505F High-Flex 1505A Direct Burial
1506A Plenum Precision RG-59/U, 3073F 600V Tray Cable, Twinax
Outdoor, Direct Burial SYSBUS-2 3073F 600V Tray Cable, Twinax
8241 Standard RG-59/U Coax SYSMAC BUS 9841 22 AWG, 1-Pair, RS-485
8241F High-Flex 8241F 3105A 22 AWG, 1-Pair, RS-485
Modbus See Protocol listings on page 8.6 SYSMAC LINK 9231 RG-59U Coax
Profibus DP See Protocol listings on page 8.6 Phoenix DeviceNet See Protocol listings on page 8.6
Serial 8777 Control and Instrumentation Contact Industrial Ethernet See Protocol listings on page 8.6
Communications Interconnect Cable
Interbus®-S See Protocol listings on page 8.6
Modicon/ Industrial Ethernet See Protocol listings on page 8.6
Profibus DP FMS & PA See Protocol listings on page 8.6
Schneider AEG Modbus 8777 Modem Drop Cable, Reliance/A-B Auto Max M9B021 2-Fiber Breakout
22 AWG, 3-Pair Distributed Power I100255 2-Fiber Loose Tube PVC
128777 Aluminum Armor (8777)
I100266 2-Fiber Loose Tube CPE
138777 Steel Armor (8777)
R-Net 9259 RG-59 PVC
88777 FEP 200°C, Plenum
89259 RG-59, 200°C, Plenum
Modbus II 3092A RG-6 Quad Shield PVC
Rotork Pakscan II E RS-485 3105A 22 AWG, 1-Pair, RS-485
3132A RG-6 Quad Shield, 150°C,
Plenum Siemens/ FMC (Field Mountable 3105A 1-Pair, RS-485
Moore Controller) 3106A 1.5-Pair, RS-485
3092F RG-6 Quad Shield PVC,
Flexible Version 3107A 2-Pair, RS-485
123092A Aluminum Armor (3092A) 3108A 3-Pair, RS-485
133092A Steel Armor (3092A) 3109A 4-Pair, RS-485
Modbus Plus YM29560 24 AWG, 1-Pair, RS-485 FOUNDATION See Protocol listings on page 8.6
YC39000 Aluminum Armor (YM29560) Fieldbus
(Type SP50 ISA/IEC)
YC39222 Steel Armor (YM29560)
YQ29258 24 AWG, 1-Pair, 150°C, Hiway 9860 Network Trunk Cable
Plenum Industrial Ethernet
See Protocol listings on page 8.6
Remote I/O 3092A RG-6 Quad Shield PVC MODULNET 3094A RG-11 Quad Shield PVC
3092F RG-6 Quad Shield PVC, 3131A RG-6 Quad Shield PVC
Flexible Version Profibus DP & FMS See Protocol listings on page 8.6
123092A Aluminum Armor (3092A) (Purple)
133092A Steel Armor (3092A) Profibus PA (Blue) See Protocol listings on page 8.6
123092F Aluminum Armor, RG-6 SINEC Series H1 9907 Thin Network Trunk Cable
Quad Shield PVC 9880 Network Trunk Cable
3132A RG-6 Quad Shield, 150°C, SINEC Series H2B 3131A RG-6 Quad Shield
Plenum 3094A RG-11 Quad Shield
3094A RG-11 Quad Shield PVC SINEC Series L1 3107A 2-Pair, RS-485
123094A Aluminum Armor (3094A) SINEC Series L2 3079A 300V Twinax
133094A Steel Armor (3094A) Thicknet Ethernet 9880 Network Trunk Cable
3095A RG-11 Quad Shield, 150°C, Trunk
Plenum 129880 Aluminum Interlocked
Omron ComboBus/D See DeviceNet Protocol listings Armor Trunk
(DeviceNet™) on page 8.6 139880 Steel Interlocked Armor
ComboBus/S 9409 18 AWG, 1-Pair, 300V Trunk
PLTC Control Thinnet Ethernet 9907 Thin Network Trunk Cable
9318 18 AWG, 1-Pair, 300V Trunk
PLTC Control, Shielded FEP = Fluorinated Ethylene-propylene
3073 600V Tray Cable, Twinax
89740 18 AWG, 1-Pair, 300V,
Control
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.5
PLC/DCS PLC/DCS
System Name Belden Part Number System Name Belden Part Number
Manufacturer Manufacturer
Smar FOUNDATION Fieldbus See Protocol listings on page 8.6 Yokogawa — DeviceNet™ See Protocol listings on page 8.6
(Type SP50 ISA/IEC) CENTUM FOUNDATION See Protocol listings on page 8.6
Industrial Ethernet See Protocol listings on page 8.6 Fieldbus
Profibus DP FMS & PA See Protocol listings on page 8.6 (Type SP50 ISA/IEC)
RS-485 See Protocol listings on page 8.6 HART See Protocol listings on page 8.6
Square D/ FIP/Fieldbus 3079A 22 AWG, 1-Pair, Shielded Industrial Ethernet See Protocol listings on page 8.6
Schneider AEG 123079A Aluminum Armor (3079A) Profibus See Protocol listings on page 8.6
Industrial Ethernet See Protocol listings on page 8.6 RS-485 See Protocol listings on page 8.6
Model 50, RS-422 8760 18 AWG, 1-Pair, Shielded Yokogawa — DeviceNet See Protocol listings on page 8.6
Cable FA-M3 Industrial Ethernet See Protocol listings on page 8.6
128760 Aluminum Armor (8760)
Passport I/O – I/O Net 3105A 22 AWG, 1-Pair, RS-485 Modbus See Protocol listings on page 8.6
123105A Aluminum Armor (3105A) Profibus See Protocol listings on page 8.6
3106A 22 AWG, 1.5-Pair, RS-485 RS-485 See Protocol listings on page 8.6
123106A Aluminum Armor (3106A) Yokogawa — DeviceNet See Protocol listings on page 8.6
Power Logic 9841 24 AWG, 1-Pair, RS-485 STARDOM FOUNDATION See Protocol listings on page 8.6
9842 24 AWG, 2-Pair, RS-485 Fieldbus
(Type SP50 ISA/IEC)
Square D/ Seriplex® 3124A CBL-1822-P20
HART See Protocol listings on page 8.6
Schneider AEG 3125A CBL-1622-P16
Industrial Ethernet See Protocol listings on page 8.6
3126A CBL-162212-P16
Profibus See Protocol listings on page 8.6
123124A Aluminum Armor (3124A)
RS-485 See Protocol listings on page 8.6
123125A Aluminum Armor (3125A)
Westinghouse WDPF 9292 RG-11 PVC
123126A Aluminum Armor (3126A)
FEP = Fluorinated Ethylene-propylene
9463 Blue Hose® (Standard)
9463F Flexible Version (9463) ControlNet is a ControlNet International, Ltd. trademark.
129463 Aluminum Armor (9463) DeviceNet is an Open DeviceNet Vendor Association, Inc. trademark.
139463 Steel Armor (9463) EtherNet/IP is a ControlNet International, Ltd. trademark,
under license by Open DeviceNet Vendor Association, Inc.
189463 Continuous Armor (9463)
HART is a HART Communication Foundation trademark.
YR28826 Dual Version (9463)
InterBus is a Phoenix Contact trademark.
9463DB Direct Burial (9463) Modbus is a Modicon, Inc. trademark.
YR29565 Various Color Jackets 9463) PROFIBUS is a PROFIBUS International trademark.
SY/Net Network 3072F 600V TC Rated (9463) PROFINET is a PROFIBUS International trademark.
Trunk Cable YR41194 Low-Smoke, Halogen-Free SDS is a Honeywell International, Inc. trademark.
YR28764 Super Thick (PLTC) Seriplex is a Square D/Schneider AEG trademark.
89463 FEP 200°C, Plenum
SY/Net TNIM Cable 9272 20 AWG, 1-Pair, Shielded
89272 FEP 200°C, Plenum
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.6
System Name Belden Part Number System Name Belden Part Number
Can Open/HART/ 3105A 1-Pair, RS-485 (PLTC) Industrial Ethernet 11700A Cat 5e, 4-Pair, Bonded, Upjacketed
RS-485 (continued)
3106A 1.5-Pair, RS-485 (PLTC) 11700A2 Cat 5e, 4-Pair, Bonded, Upjacketed,
3107A 2-Pair, RS-485 (PLTC) Oil Res II
CC-Link YR47198 20 AWG/3c, Foil + Braid Shield 121700A Cat 5e, 4-Pair, Bonded, Armored
YR47205 20 AWG/3c Shielded + 18 AWG/2c Power 7919A Cat 5e, 4-Pair, Shielded
ControlNet™ 3092A RG-6 PVC Quad Shield 7921A Cat 5e, 4-Pair, Bonded, Shielded
(Foil + Braid)
3092F RG-6 PVC Quad Shield, Flex Version,
Aluminum Braid 7927A Cat 6, 4-Pair, Bonded
YR28890 RG-6 PVC Quad Shield, Flex Version, 7931A Cat 6, 4-Pair, Bonded, Gas Res,
Copper Braid High + Low Temperature
3093A RG-6 FEP Quad Shield, Plenum 11872A Cat 6, 4-Pair, Bonded, Upjacketed
123092A Aluminum Armor (3092A) 121872A Cat 6, 4-Pair, Bonded, Armored
133092A Steel Armor (3092A) Interbus®-S 3119A 18 AWG/3c, 24 AWG/3-Pair, Composite
183092A Continuous Armor (3092A) 3120A 24 AWG/3-Pair
DataHighway (DH) 9463 20 AWG Twinax, Blue Hose IronWorks® 8471 16 AWG, 1-Pair, UL AWM 2598
& DataHighway Plus 3072F 600V, TC Blue Hose 8917 16 AWG, 1-Cond, UL AWM 1015
(DH+) Remote I/O 9463DB Direct Burial Blue Hose 85102 16 AWG, 2-Cond, VW1, Plenum
9463F High-Flex, Blue Hose Modbus 8777 22 AWG, 3-Pair, Modem Drop Cable
89463 High-Temp, Plenum Blue Hose 128777 Aluminum Armor (8777)
129463 Aluminum Armor (9463) 138777 Steel Armor (8777)
139463 Steel Armor (9463) 88777 FEP 200°C, Plenum (8777)
189463 Continuous Armor (9463) Profibus DP 3079A 22 AWG 300V Twinax
YR28826 Dual Blue Hose & FMS (Purple) 3079E 22 AWG 300V Twinax, Flex Version
YC39151 Dual Armored Blue Hose Profibus PA (Blue) 3076F 18 AWG, 2-Conductors, Type A
YR28764 Thick Wall PLTC Blue Hose RS-485/HART/ 9841 1-Pair
YR29565 Colored Blue Hose Can Open 82841 1-Pair, Plenum
YR41104 Low-Smoke, Zero-Halogen Blue Hose 89841 1-Pair, Plenum, High-Temperature
DeviceNet™ 3082A PVC (Thick) 9842 2-Pair
3082F High-Flex (Thick) 82842 2-Pair, Plenum
3082K CL2 (Flat) 9843 3-Pair
3082KP Auxiliary Power (Flat) 9844 4-Pair
3083A CPE (Thick) 7200A 1-Pair, RS-485, Hi-Flex
3084A PVC (Thin) 7201A 2-Pair, RS-485, Hi-Flex
3084F High-Flex (Thin) 7202A 3-Pair, RS-485, Hi-Flex
3085A CPE (Thin)
7203A 4-Pair, RS-485, Hi-Flex
7895A CL2 PVC (Cable III Mid)
7206A 1-Pair, RS-485, Hi-Flex
7896A CL1 PVC (Type V Trunk Cable)
3105A 1-Pair, RS-485 (PLTC)
7897A CL1 PVC (Thick)
3106A 1.5-Pair, RS-485 (PLTC)
7900A CL1 Unshielded (Drop Cable IV)
3107A 2-Pair, RS-485 (PLTC)
FOUNDATION Fieldbus 3076F Type A, H1 1900m (31.25K)
3108A 3 Pair, RS-485 (PLTC)
(Type SP50 ISA/IEC) 3077F Type B, H1 1200m (31.25K)
3109A 4 Pair, RS-485 (PLTC)
HSE Copper & Fiber
(see Cables for Industrial Ethernet, pg. 18.6) Seriplex® 3124A 1-Pair 18 AWG, 1-Pair 22 AWG
Hart/RS-485/ 3105A 1-Pair, RS-485 (PLTC) 3125A 1-Pair 16 AWG, 1-Pair 22 AWG
Can Open 3106A 1.5-Pair, RS-485 (PLTC) 3126A 1-Pair 16 AWG, 1-Pair 22 AWG,
1-Pair 12 AWG
3107A 2-Pair, RS-485 (PLTC)
123124A Aluminum Armor (3124A)
Industrial Ethernet 7932A Cat 5e, 2-Pair, Bonded
123125A Aluminum Armor (3125A)
7933A Cat 5e, 2-Pair, Bonded, Shielded
123126A Aluminum Armor (3126A)
7918A Cat 5e, 4-Pair
7924A Cat 5e, 4-Pair, Bonded, Flexible Smart Distributed 3086A 1-Pair 16 AWG, 1-Pair 20 AWG
System (SDS) 3087A 2-Pairs 22 AWG
7930A Cat 5e, 4-Pair, Flexible
FEP = Fluorinated Ethylene-propylene
7922A Cat 5e, 4-Pair, Bonded, PLTC
7934A Cat 5e, 4-Pair, Bonded, Burial
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.7
®
DataTuff Twisted Pair and TrayOptic® Fiber Optic Cables
Overview
The reliability of your industrial Ethernet quality and reliability into each cable This performance advantage is achieved by
network depends on the cable infrastructure. it manufactures. Decades of leadership bonding the individual insulated conductors
Data transmission errors can lead to and experience in supplying reliable along their longitudinal axes, resulting in
interruptions in critical control functions high-end cable solutions, such as uniform conductor-to-conductor spacing and
resulting in lost production time and even Blue Hose®, to industrial networks and the elimination of gaps between conductors
safety issues. Belden’s family of industrial control systems are combined to give that can occur during installation. This is
Ethernet cables is designed to withstand the you industrial Ethernet cables that a critical construction feature because
rigors of industrial environments. Whether perform to maximum network capability. non-uniform conductor spacing and gaps
it’s exposure to oil and sunlight, temperature change the physical characteristics of the
Our dedication to quality manufacturing
variation, abrasion and crushing, or the cable such that the electrical performance of
practices and processes assures consistent
presence of electromagnetic interference the cable suffers. Only Bonded-Pair cables
products of uncompromising quality.
(EMI) or radio frequency interference (RFI), deliver the electrical integrity you demand.
turn to Belden for the solution.
Belden offers an extensive line of high Installable Performance®
TrayOptic Cables
performance cables in both copper with Patented Bonded-Pair
constructions with DataTuff cables as well Technology Belden® TrayOptic cables are a line of
as fiber optic designs with TrayOptic cables. indoor/outdoor fiber optic cables designed
Belden’s Bonded-Pair versions of DataTuff
to meet the demanding requirements
cables are unique in the industry to give
of industrial applications. When the
Performance Assurance from you an Installable Performance advantage.
installation demands the combination of
Blue Hose® to Industrial Ethernet This patented design yields superior
sophisticated fiber optic technology and
electrical performance even after the
rugged durability, turn to Belden.
To assist you in achieving optimum effects and stresses of pulling, twisting
network performance, Belden has built and bending during typical installations.
Category 5e Cable
u 7932A 2 ● ● ● 20 ● ● ●
u 7933A 2 ● ● ● 20 ● ● ●
7923A 4 ● ● ● 40 ● ● ● ●
7918A 4 ● ● 35 ● ● ● ●
7924A 4 ● ● ● 40 ● ● ● ●
u 7930A 4 ● ● 25 ● ● ● ●
u 7922A 4 ● ● ● 40 ● ● ● ●
PLTC
u 7934A 4 ● ● ● 40 ● ● ●
7928A 4 ● ● ● 40 ● ● ● ● ●
11700A 4 ● ● ● 40 ● ● ● ●
u 11700A2 4 ● ● ● 40 ● ● ●
Oil Res I&II
121700A 4 ● ● ● 40 ● ● ●
u 121700R 4 ● ● ● 40 ● ● ●
7929A 4 ● ● ● 35 ● ● ● ●
7919A 4 ● ● 25 ● ● ● ●
7921A 4 ● ● ● 75 ● ● ● ●
18 • Industrial Cables
Category 6 Cable
7927A 4 ● ● ● 45 ● ● ●
7931A 4 ● ● ● 40 ● ● ● ● ●
11872A 4 ● ● ● 45 ●
121872A 4 ● ● ● 45 ● ● ●
*Shielded products are recommended for high-noise environments. **Stranded products are recommended where more flexibility is needed.
†
Products with Bonded-Pair technology provide Installable Performance® advantages — refer to Belden’s Bonded-Pair Cable Bulletin #BP02
EtherNet/IP is a trademark of ControlNet International, Ltd. under license by Open DeviceNet Vendor Association, Inc.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.8
®
Category 5e DataTuff Twisted Pair Cables, 2-Pair and 4-Pair
Heavy-Duty Sunlight and Oil-Resistant Jackets
Enhanced Cat 5e • 24 AWG Bonded-Pairs Solid BC Conductors • Rip Cord • See Color Codes below
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black, Red or Teal)
7932A NEC: 2 1000 304.8 19.0 8.61 .207 5.26 1 2.0 65.3 63.3 60.8 100±12 20.0
Compliant u CMR 2000 ▲ 609.6 38.0 17.24 4
8
4.0
5.7
56.3
51.8
52.3
46.1
48.7
42.7
100±12
100±12
23.6
25.4
CEC: 10 6.4 50.3 43.9 40.8 100±12 26.0
CMR FT4 16 8.1 47.3 39.1 36.7 100±12 26.0
25 10.3 44.3 34.1 32.8 100±15 25.5
31.25 11.6 42.9 31.3 30.9 100±15 25.0
Rip Cord 62.5 16.8 38.4 21.6 24.8 100±15 23.5
100 21.7 35.3 17.1 20.8 100±15 22.5
▲ 155 27.7 32.5 4.7 16.9 100±18 19.0
2000 ft. put-up available in Black only. • M-12 or RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals 200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 250 36.4 29.3 — 12.8 100±20 18.0
Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 350 44.3 27.2 — 9.9 100±22 17.0
7923A NEC: 4 1000 304.8 28.0 12.7 .230 5.84 1 2.0 65.3 63.3 60.8 100±12 20.0
Compliant CMR, 2000 ▲ 609.6 54.0 24.5 4 4.0 56.3 52.3 48.7 100±12 23.6
8 5.7 51.8 46.1 42.7 100±12 25.4
CMX- 10 6.4 50.3 43.9 40.8 100±12 26.0
Outdoor 16 8.1 47.3 39.1 36.7 100±12 26.0
CEC: 25 10.3 44.3 34.1 32.8 100±15 25.5
31.25 11.6 42.9 31.3 30.9 100±15 25.0
CMR FT4 62.5 16.8 38.4 21.6 24.8 100±15 23.5
Rip Cord 100 21.7 35.3 17.1 20.8 100±15 22.5
▲ 155 27.7 32.5 4.7 16.9 100±18 19.0
2000 ft. put-up available in Black only. • RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals 200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 250 36.4 29.3 — 12.8 100±20 18.0
Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 • P-07-KA060003-MSHA* 350 44.3 27.2 — 9.9 100±22 17.0
Polyolefin Insulation • Waterblocked Sunlight- and Oil-resistant Black Polyethylene Jacket
7934A — 4 1000 304.8 25.0 11.34 .230 5.84 1 2.0 62.3 60.0 60.8 100±15 20.0
Compliant u 4
8
4.1
5.8
53.3
48.8
49.0
43.0
48.7
42.7
100±15
100±15
23.6
25.4
Halogen-Free 10 6.5 47.3 41.0 40.8 100±15 26.0
Burial 16 8.2 44.3 36.0 36.7 100±15 26.0
20 9.3 42.8 33.5 34.7 100±15 26.0
25 10.4 41.3 30.9 32.8 100±15 25.5
31.25 11.7 39.9 28.0 30.9 100±15 25.0
62.5 17.0 35.4 19.0 24.8 100±15 23.5
100 22.0 32.3 11.0 20.8 100±15 22.5
RJ-45 Compatible • Jacket sequentially marked at 3 ft. intervals 155 28.1 29.5 1.4 16.9 100±25 15.8
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 200 32.0 27.8 1.0 14.7 100±25 15.0
Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 • Waterblocked per Telcordia, IEC and ICEA
Plenum • FEP Insulation • Sunlight-, Oil- and Gas-resistant Black FEP Jacket
Compliant 7928A NEC: 4 1000 304.8 24.0 10.9 .187 4.75 1 2.0 65.3 63.3 60.8 100±12 20.0
High & Low Temp Limited 4 4.0 56.3 52.3 48.7 100±12 23.6
8 5.7 51.8 46.1 42.7 100±12 25.4
Oil Res I & II Combustible 10 6.4 50.3 43.9 40.8 100±12 26.0
Gas Res FHC 25/50 16 8.1 47.3 39.1 36.7 100±12 26.0
CMP 25 10.3 44.3 34.1 32.8 100±15 25.5
31.25 11.6 42.9 31.3 30.9 100±15 25.0
CEC: 62.5 16.8 38.4 21.6 24.8 100±15 23.5
CMP FT6 100 21.7 35.3 17.1 20.8 100±15 22.5
155 27.7 32.5 4.7 16.9 100±18 19.0
RJ-45 Compatible 200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -70°C Cold Bend per UL1581 • Installation Temperature: -55°C to +150°C • Operating Temperature: -70°C to +150°C** 250 36.4 29.3 — 12.8 100±20 18.0
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 350 44.3 27.2 — 9.9 100±22 17.0
Polyolefin Insulation • PVC Inner Jacket • .035″ Industrial Grade PVC Outer Jacket (Black, Gray, Red, Teal or Blue)
11700A NEC: 4 1000 304.8 39.0 17.7 .285 7.24 1 2.0 65.3 63.3 60.8 100±12 20.0
Compliant CMR, 3000 † 914.4 117.0 53.2 4 4.0 56.3 52.3 48.7 100±12 23.6
8 5.7 51.8 46.1 42.7 100±12 25.4
Upjacketed CMX- Nominal 10 6.4 50.3 43.9 40.8 100±12 26.0
Outdoor Core OD: 16 8.1 47.3 39.1 36.7 100±12 26.0
CEC: .200 5.08 25 10.3 44.3 34.1 32.8 100±15 25.5
31.25 11.6 42.9 31.3 30.9 100±15 25.0
CMR FT4 62.5 16.8 38.4 21.6 24.8 100±15 23.5
100 21.7 35.3 17.1 20.8 100±15 22.5
Rip Cords 155 27.7 32.5 4.7 16.9 100±18 19.0
200 32.0 30.8 3.0 14.7 100±20 19.0
†3000 ft. put-up available in Black only. • Outer jacket is sunlight- and oil-resistant. • Jacket sequentially marked at 2 ft. intervals
250 36.4 29.3 — 12.8 100±20 18.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 350 44.3 27.2 — 9.9 100±22 17.0
RJ-45 Compatible • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 • P-07-KA060005-MSHA*
Oil Res I & II 11700A2 NEC: 4 1000 †† 304.8 42.0 19.1 .285 7.24 1 2.0 65.3 63.3 60.8 100±12 20.0
Upjacketed u CMR 2000 †† 609.6 86.0 39.1 4
8
4.0
5.7
56.3
51.8
52.3
46.1
48.7
42.7
100±12
100±12
23.0
24.5
CEC: Nominal 10 6.4 50.3 43.9 40.8 100±12 25.0
CMR FT4 Core OD: 16 8.1 47.3 39.1 36.7 100±12 25.0
.200 5.08 25 10.3 44.3 34.1 32.8 100±15 24.3
31.25 11.6 42.9 31.3 30.9 100±15 23.6
62.5 16.8 38.4 21.6 24.8 100±15 21.5
Rip Cord 100 21.7 35.3 17.1 20.8 100±15 20.1
††1000 ft. put-up available in Black or Blue only, 2000 ft. put-up in Black only. • RJ-45 Compatible • Outer jacket is sunlight resistant. 155 27.7 32.5 4.7 16.9 100±18 19.0
200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -10°C Cold Bend per UL1581 • Installation Temperature: +5°C to +75°C • Operating Temperature: -10°C to +75°C** 250 36.4 29.3 — 12.8 100±20 18.0
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 350 44.3 27.2 — 9.9 100±22 17.0
ACR = Attenuation Crosstalk Ratio • BC = Bare Copper • ELFEXT = Equal Level Far-end Crosstalk • NEXT = Near-end Crosstalk • PSUM = Power Sum • RL = Return Loss • TC = Tinned Copper
*Pennsylvania Department of Environmental Resources and United States Mine Safety and Health Administration Certification. EtherNet/IP is a trademark of ControlNet International, Ltd.
**Subject to length de-rating. under license by Open DeviceNet Vendor Association, Inc.
DataTuff Color Codes: Pair 1 = White/Blue Stripe & Blue, Pair 2 = White/Orange Stripe & Orange, Pair 3 = White/Green Stripe & Green, Pair 4 = White/Brown Stripe & Brown
For two pair products: use color codes for Pairs 2 & 3
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.9
®
Category 5e DataTuff Twisted Pair Cables, 2-Pair and 4-Pair
Heavy-Duty Sunlight and Oil-Resistant Jackets
Enhanced Cat 5e • 22 AWG Bonded-Pairs Solid Bare Copper Conductors • Rip Cord • See Color Code Chart (below)
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant Black PVC Jacket
PLTC 7922A NEC: 4 1000 304.8 46.3 21.0 .301 7.65 1 2.0 65.3 63.3 60.8 100±12 20.0
u PLTC, 2000 609.6 92.5 42.0 4
8
4.0
5.7
56.3
51.8
52.3
46.1
48.7
42.7
100±12
100±12
23.0
24.5
CMR, 10 6.4 50.3 43.9 40.8 100±12 25.0
CMX- 16 8.1 47.3 39.1 36.7 100±12 25.0
Outdoor 25 10.3 44.3 34.1 32.8 100±15 24.3
31.25 11.6 42.9 31.3 30.9 100±15 23.6
CEC: 62.5 16.8 38.4 21.6 24.8 100±15 21.5
CMR FT4 100 21.7 35.3 17.1 20.8 100±15 20.1
Rip Cord 155 27.7 32.5 4.7 16.9 100±18 19.0
200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -25°C Cold Bend per UL1581 • Installation Temperature: -10°C to +75°C • Operating Temperature: -25°C to +75°C** 250 36.4 29.3 — 12.8 100±20 18.0
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 350 44.3 27.2 — 9.9 100±22 17.0
Enhanced Cat 5e • 24 AWG Bonded-Pairs Stranded (7x32) TC Conductors • See Color Code Chart (below)
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black, Red or Teal)
Stranded 7924A NEC: 4 1000 304.8 30.0 13.6 .242 6.15 1 2.4 65.3 62.9 60.8 100±12 20.0
4 4.8 56.3 51.5 48.7 100±12 23.6
Flexible CMR, 2000 † 609.6 58.0 26.3 8 6.8 51.8 45.0 42.7 100±12 25.4
CMX- 10 7.7 50.3 42.6 40.8 100±12 26.0
Outdoor 16 9.7 47.3 37.5 36.7 100±12 26.0
25 12.4 44.3 31.9 32.8 100±15 25.5
CEC: 31.25 13.9 42.9 29.0 30.9 100±15 25.0
CMR FT4 62.5 20.2 38.4 18.3 24.8 100±15 23.5
100 26.0 35.3 9.2 20.8 100±18 22.5
155 33.2 32.5 — 16.9 100±18 19.0
†2000 ft. put-up available in Black only. • RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals
200 38.4 30.8 — 14.7 100±20 19.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 250 43.7 29.3 — 12.8 100±20 18.0
Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151; 5,734,126 and 5,763,823 350 53.2 27.2 — 9.9 100±22 17.0
Enhanced Cat 5e • 24 AWG Bonded-Pairs Solid BC Conductors • Overall Beldfoil® Shield (100%) • Drain Wire • See Color Codes (below)
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black, Red or Teal)
7933A NEC: 2 1000 304.8 32.0 14.5 .227 5.77 1 2.0 62.3 60.3 60.8 100±15 20.0
Compliant u CMR 2000 ▲ 609.6 64.8 29.4 4
10
4.1
6.5
53.3
47.3
49.2
40.8
48.7
40.8
100±15
100±15
23.6
26.0
Shielded CEC: 16 8.2 44.3 36.1 36.7 100±15 26.0
CMR FT4 31.25 11.7 39.9 28.2 30.9 100±15 25.0
62.5 17.0 35.4 18.4 24.8 100±15 23.5
100 22.0 32.3 10.3 20.8 100±15 22.5
Drain Wire 200 32.4 27.8 1.0 14.7 100±25 15.0
▲
2000 ft. put-up available in Black only. • M-12 or RJ-45 Compatible • Shield is bonded to jacket inner wall for electrical stability.
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C**
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black or Blue)
Shielded 7929A NEC: 4 1000 304.8 37.0 16.8 .265 6.73 1 2.0 62.3 60.3 60.8 100±15 20.0
CMR, 2000 ▲ 609.6 72.0 32.7 4 4.1 53.3 49.2 48.7 100±15 23.0
10 6.5 47.3 40.8 40.8 100±15 25.0
CMX- 16 8.2 44.3 36.1 36.7 100±15 25.0
Outdoor 31.25 11.7 39.9 28.2 30.9 100±15 23.6
CEC: 62.5 17.0 35.4 18.4 24.8 100±15 21.5
Drain Wire 100 22.0 32.3 10.3 20.8 100±15 20.1
CMR FT4 200 32.4 27.8 1.0 14.7 100±25 15.0
▲
2000 ft. put-up available in Black only. • RJ-45 Compatible • Shield is bonded to jacket inner wall for electrical stability.
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C**
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 • P-07-KA060003-MSHA*
Enhanced Cat 5e • 24 AWG Bonded-Pairs Solid BC Conductors • Overall Beldfoil (100%) + TC Braid Shield (70% Coverage) • Drain Wire◆
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black, Red, Blue or Teal)
7921A NEC: 4 1000 304.8 55.0 24.9 .330 8.38 1 2.0 62.3 60.3 60.8 100±15 20.0
Compliant CMR, 2000 ▲ 609.6 106.0 48.1 4 4.1 53.3 49.2 48.7 100±15 23.6
Heavy-shielded CMX- 10 6.5 47.3 40.8 40.8 100±15 26.0
16 8.2 44.3 36.1 36.7 100±15 26.0
Outdoor 31.25 11.7 39.9 28.2 30.9 100±15 25.0
CEC: 62.5 17.0 35.4 18.4 24.8 100±15 23.5
CMR FT4 100 22.0 32.3 10.3 20.8 100±15 22.5
Drain Wire
18 • Industrial Cables
▲
2000 ft. put-up available in Black only. ◆24 AWG solid spiral drain wire.
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C**
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • NEMA WC-63.1 Category 5e • U.S. Patents 5,606,151 and 5,734,126
ACR = Attenuation Crosstalk Ratio • AL = Aluminum • BC = Bare Copper • ELFEXT = Equal Level Far-end Crosstalk • NEXT = Near-end Crosstalk • PSUM = Power Sum • RL = Return Loss • TC = Tinned Copper
EtherNet/IP is a trademark of ControlNet International, Ltd. under license by Open DeviceNet Vendor Association, Inc.
*Pennsylvania Department of Environmental Resources and United States Mine Safety and Health Administration Certification.
**Subject to length de-rating.
DataTuff Color Codes: Pair 1 = White/Blue Stripe & Blue, Pair 2 = White/Orange Stripe & Orange, Pair 3 = White/Green Stripe & Green, Pair 4 = White/Brown Stripe & Brown
For two pair products: use color codes for Pairs 2 & 3
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.10
®
Category 5e DataTuff Twisted Pair Cables, 4-Pair
Heavy-Duty Sunlight and Oil-Resistant Jackets
Enhanced Cat 5e • 24 AWG Bonded-Pairs Solid BC Conductors • Polyester Wrap • Rip Cord • See Color Code Chart (below)
AL Interlocked Armor • Polyolefin Insulation • PVC Inner Jacket • .045″ Industrial Grade PVC Outer Jacket (Black or Gray)
Interlocked AL Armor 121700A NEC: 4 1000 304.8 159.0 72.0 .530 13.46 1 2.0 65.3 63.3 60.8 100±12 20.0
CM 3000 † 914.4 459.0 210.6 4 4.0 56.3 52.3 48.7 100±12 23.0
8 5.7 51.8 46.1 42.7 100±12 24.5
CEC: Nominal 10 6.4 50.3 43.9 40.8 100±12 25.0
HL Core OD: 16 8.1 47.3 39.1 36.7 100±12 25.0
CMG FT4 .200 5.08 25 10.3 44.3 34.1 32.8 100±15 24.3
31.25 11.6 42.9 31.3 30.9 100±15 23.6
Rip Cord 62.5 16.8 38.4 21.6 24.8 100±15 21.5
100 21.7 35.3 17.1 20.8 100±15 20.1
†3000 ft. put-up available in Black only. • RJ-45 Compatible • Outer jacket is sunlight- and oil-resistant. 155 27.7 32.5 4.7 16.9 100±18 19.0
200 32.0 30.8 3.0 14.7 100±20 19.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 250 36.4 29.3 — 12.8 100±20 18.0
Jacket sequentially marked at 1 meter intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126 350 44.3 27.2 — 9.9 100±22 17.0
AL Interlocked Armor • Polyolefin Insulation • PVC Inner Jacket • .045″ Industrial Grade PVC Outer Jacket (Black or Blue)
Interlocked AL Armor 121700R NEC: 4 1000 304.8 159.0 72.0 .530 13.46 (Same as above)
-40°C Cold Impact u CM 3000 914.4 459.0 210.6
CEC: 5000 † 1524.0 690.0 313.0 Nominal
HL Core OD:
CMG FT4 .200 5.08
Rip Cord
†5000 ft. put-up available in Blue only. • RJ-45 Compatible • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C**
Outer jacket is sunlight- and oil-resistant. • Jacket sequentially marked at 1 meter intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • U.S. Patents 5,606,151 and 5,734,126
Cat 5e • 24 AWG Solid Bare Copper Conductors • Twisted Pairs • Rip Cord • See Color Code Chart (below)
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black or Blue)
7918A NEC: 4 1000 304.8 28.0 12.7 1
.230 2.0
5.84 62.3 60.3 60.8 100±15 20.0
4 4.1 53.3 49.2 48.7 100±15 23.0
CMR, 2000 †† 609.6 52.0 23.6 10 6.5 47.3 40.8 40.8 100±15 25.0
CMX-Outdoor 16 8.2 44.3 36.1 36.7 100±15 25.0
CEC: 31.25 11.7 39.9 28.2 30.9 100±15 23.6
Rip Cord 62.5 17.0 35.4 18.4 24.8 100±15 21.5
CMR FT4 100 22.0 32.3 10.3 20.8 100±15 20.1
††2000 ft. put-up available in Black only. • RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals 200 32.4 27.8 1.0 14.7 100±25 15.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** • Third party verified to TIA/EIA-568-B.2, Category 5e
Cat 5e • 24 AWG Solid BC • Twisted Pairs • Overall Beldfoil® Shield (100% Coverage) • 24 AWG Stranded TC Drain Wire • See Color Code Chart
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant PVC Jacket (Black or Blue)
Shielded 7919A NEC: 4 1000 304.8 35.0 15.9 .265 6.73 1 2.0 62.3 60.3 60.8 100±15 20.0
4 4.1 53.3 49.2 48.7 100±15 23.0
CMR, 2000 † 609.6 68.0 30.9 10 6.5 47.3 40.8 40.8 100±15 25.0
CMX-Outdoor 16 8.2 44.3 36.1 36.7 100±15 25.0
CEC: 31.25 11.7 39.9 28.2 30.9 100±15 23.6
62.5 17.0 35.4 18.4 24.8 100±15 21.5
Drain Wire CMR FT4 100 22.0 32.3 10.3 20.8 100±15 20.1
†2000 ft. put-up available in Black only. • RJ-45 Compatible • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** • Cable passes -40°C Cold Bend per UL1581
Shield is bonded to jacket inner wall for electrical stability. • Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • P-07-KA060004-MSHA*
Cat 5e • 24 AWG Stranded (7x32) Bare Copper Conductors • Twisted Pairs • See Color Code Chart (below)
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant Black PVC Jacket
Stranded/Flexible 7930A NEC: 4 1000 304.8 29.0 13.2 .240 6.09 1 2.5 62.3 59.8 60.8 100±15 20.0
u CMR, 2000 609.6 56.0 25.4 4
10
4.9
7.8
53.3
47.3
48.4
39.5
48.7
40.8
100±15
100±15
23.0
25.0
CMX-Outdoor 16 9.9 44.3 34.4 36.7 100±15 25.0
CEC: 31.25 14.1 39.9 25.8 30.9 100±15 23.6
62.5 20.4 35.4 15.0 24.8 100±15 21.5
CMR FT4 100 26.4 32.3 5.9 20.8 100±15 20.1
200 38.9 27.8 — 14.7 100±25 15.0
Installation Temperature: 0°C to +75°C • Operating Temperature: -25°C to +75°C** • Cable passes -25°C Cold Bend per UL1581
RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2, Category 5e • P-07-KA060003-MSHA*
ACR = Attenuation Crosstalk Ratio • BC = Bare Copper • ELFEXT = Equal Level Far-end Crosstalk • FEP = Fluorinated Ethylene-propylene •
NEXT = Near-end Crosstalk • PSUM = Power Sum • RL = Return Loss • TC = Tinned Copper
EtherNet/IP is a trademark of ControlNet International, Ltd. under license by Open DeviceNet Vendor Association, Inc.
*Pennsylvania Department of Environmental Resources and United States Mine Safety and Health Administration Certification.
**Subject to length de-rating.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.11
®
Category 6 DataTuff Twisted Pair Cables, 4-Pair
Heavy-Duty Jackets
Enhanced Cat 6 • 23 AWG Bonded-Pairs Solid BC Conductors • Patented E-Spline Center Member • Rip Cord • See Color Code Chart
Polyolefin Insulation • .030″ Industrial Grade Sunlight- and Oil-resistant Black PVC Jacket
7927A NEC: 4 1000 304.8 44.0 20.0 .251 6.38 1 1.9 80.3 78.5 70.8 100±12 20.0
CMR 2000 609.6 88.0 39.9 x x 10 5.7 65.3 59.6 50.8 100±12 25.0
31.25 10.2 57.9 47.7 40.9 100±15 25.0
CEC: .339 8.61 62.5 14.7 53.4 38.7 34.9 100±15 25.0
CMR FT4 100 18.9 50.3 31.4 30.8 100±15 25.0
155 23.9 47.5 23.5 27.0 100±15 22.8
200 27.5 45.8 18.3 24.8 100±15 21.7
Rip Cord 250 31.2 44.3 13.2 22.8 100±20 20.5
350 37.7 40.2 4.5 19.9 100±22 19.8
400 40.6 39.3 0.6 18.8 100±22 19.5
RJ-45 Compatible • Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2-1, Category 6 500 46.2 37.8 >0.0 ◆ 16.8 100±22 18.4
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 550 48.8 37.2 — 16.0 100±22 18.0
◆PSUM ACR >0 is guaranteed to 460 MHz. • U.S. Patents 5,606,151; 5,734,126; 5,789,711 and 6,297,454-B1 600 51.4 36.6 — 15.2 100±22 17.6
Cat 6 • 23 AWG Bonded-Pairs Solid BC Conductors • See Color Code Chart (below)
Plenum • FEP Insulation • Sunlight-, Oil- and Gas-resistant Black FEP Jacket
High & Low Temp 7931A NEC: 4 1000 304.8 35.0 15.9 .214 5.44 1 2.0 72.3 70.3 64.8 100±15 20.0
Oil Res I & II Limited 10 6.0 57.3 51.3 44.8 100±15 25.0
20 8.5 52.8 44.3 38.7 100±15 25.0
Gas Res Combustible 31.25 10.7 49.9 39.2 34.9 100±15 23.6
FHC 25/50 62.5 15.4 45.4 30.0 28.8 100±15 21.5
CMP 100 19.8 42.3 22.5 24.8 100±15 20.1
200 29.0 37.8 8.8 18.7 100±22 18.0
CEC: 250 32.8 36.3 3.5 16.8 100±32 17.3
CMP FT6
RJ-45 Compatible
Cable passes -70°C Cold Bend per UL1581 • Installation Temperature: -55°C to +150°C • Operating Temperature: -70°C to +150°C**
Jacket sequentially marked at 2 ft. intervals • Third party verified to TIA/EIA-568-B.2-1, Category 6 • U.S. Patents 5,606,151 and 5,734,126
Enhanced Cat 6 • 23 AWG Bonded-Pairs Solid BC Conductors • Rip Cord • See Color Code Chart (below)
Polyolefin Insulation • PVC Inner Jacket • .035″ Industrial Grade PVC Outer Jacket (Black or Gray)
Upjacketed 11872A NEC: 4 1000 304.8 66.0 30.0 .475 12.07 1 1.9 72.3 70 64.8 100±12 20.0
CM x x 4 3.7 63.3 59 52.7 100±12 23.0
10 5.9 57.3 51 44.8 100±12 25.0
CEC: .265 6.73 16 7.5 54.3 46 40.7 100±12 25.0
CM 31.25 10.6 49.9 39 34.9 100±15 23.6
FT1 Nominal 62.5 15.4 45.4 30 28.8 100±15 21.5
100 19.8 42.3 25 24.8 100±15 21.0
Core OD: 155 25.1 39.5 14 20.9 100±15 21.0
Rip Cords .365 9.27 200 29.0 37.9 10 18.7 100±15 21.0
x x 310 37.1 34.9 — 14.9 100±20 18.0
350 39.8 34.2 — 13.9 100±22 17.0
†Value provided for information only. • RJ-45 Compatible • Cable passes -25°C Cold Bend per UL1581 .165 4.19 400 † 43.0 33.3 — 12.7 100±32 14.0
Installation Temperature: -10°C to +75°C • Operating Temperature: -25°C to +75°C** 500 † 49.0 31.8 — 10.8 100±32 14.0
Jacket sequentially marked at 2 ft. intervals • Verified to TIA/EIA-568-B.2-1, Category 6 • U.S. Patents 5,606,151, 5,734,126 and 5,821,467
Enhanced Cat 6 • 23 AWG Bonded-Pairs Solid BC Conductors • Polyester Wrap • Rip Cord • See Color Code Chart (below)
AL Interlocked Armor • Polyolefin Insulation • PVC Inner Jacket • .055″ Industrial Grade PVC Outer Jacket (Black or Gray)
Interlocked AL Armor 121872A NEC: 4 1000 304.8 222.0 100.6 .684 17.37 1 1.9 72.3 70 64.8 100±12 20.0
CM 4 3.7 63.3 59 52.7 100±12 23.0
10 5.9 57.3 51 44.8 100±12 25.0
CEC: Nominal 16 7.5 54.3 46 40.7 100±12 25.0
HL Core OD: 31.25 10.6 49.9 39 34.9 100±15 23.6
CMG FT4 .365 9.27 62.5 15.4 45.4 30 28.8 100±15 21.5
100 19.8 42.3 25 24.8 100±15 21.0
x x 155 25.1 39.5 14 20.9 100±15 21.0
Rip Cord .165 4.19 200 29.0 37.9 10 18.7 100±15 21.0
310 37.1 34.9 — 14.9 100±20 18.0
350 39.8 34.2 — 13.9 100±22 17.0
†Value provided for information only. • RJ-45 Compatible • Jacket sequentially marked at 1 meter intervals 400 † 43.0 33.3 — 12.7 100±32 14.0
Cable passes -40°C Cold Bend per UL1581 • Installation Temperature: -25°C to +75°C • Operating Temperature: -40°C to +75°C** 500 † 49.0 31.8 — 10.8 100±32 14.0
Verified to TIA/EIA-568-B.2-1, Category 6 • U.S. Patents 5,606,151, 5,734,126 and 5,821,467
ACR = Attenuation Crosstalk Ratio • AL = Aluminum • BC = Bare Copper • ELFEXT = Equal Level Far-end Crosstalk • NEXT = Near-end Crosstalk • PSUM = Power Sum • RL = Return Loss • TC = Tinned Copper
**Subject to length de-rating.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.12
Applications Specifications
Gel-filled
Buffer Tube
Dielectric Central
Strength Member
TrayOptic Series
Riser (NEC/CEC OFNR/OFN FT4)
2 2 0.440 11.18 I100255 88 131 I100266 83 124
4 4 0.440 11.18 I100455 88 131 I100466 83 124
6 6 0.440 11.18 I100655 88 131 I100666 83 124
8 4 0.440 11.18 I400855 88 131 I400866 83 124
12 6 0.440 11.18 I601255 88 131 I601266 83 124
18 6 0.440 11.18 I601855 88 131 I601866 83 124
24 6 0.440 11.18 I602455 88 131 I602466 83 124
36 6 0.440 11.18 I603655 88 131 I603666 83 124
48 12 0.540 13.72 I604855 136 202 I604866 129 192
60 12 0.540 13.72 I606055 136 202 I606066 129 192
72 12 0.540 13.72 I607255 136 202 I607266 129 192
All optical fiber products can be supplied in compliance with RoHS regulations. Please contact Customer Service for more details.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.13
Coaxial Cables
Thinnet 10Base2 Ethernet • 20 AWG Stranded (19x32) .037″ TC Conductor • Duobond® II (100% Coverage) + TC Braid (93% Coverage)
Foam Polyethylene Insulation • Gray PVC Jacket
UL AWM 9907 NEC: 500 152.4 12.5 5.7 20 AWG .102 2.59 Duobond II .185 4.70 50 80% 25.4 83.3 1 .43 1.4
Style 1354 CL2 U-1000 U-304.8 25.0 11.4 (19x32) + 93% 10 1.30 4.3
(30V 60°C) CM 1000 304.8 25.0 11.4 .037″ TC Braid 50 2.90 9.5
CEC: 1640 500.0 41.0 18.6 TC 5.8Ω/M′ 100 4.20 13.8
For Plenum versions of 9907, 200 6.10 20.0
CM U-2500 U-762.0 60.0 27.3 8.8Ω/M′ 19.0Ω/km see 89907 or 82907. 400 8.90 29.2
2500 762.0 62.5 28.4 28.9Ω/km 700 12.10 39.7
3280 1000.0 82.0 37.3 900 13.90 45.6
DEC Part No. 17-01248-00 1000 14.80 48.6
Plenum • Foam FEP Insulation • Gray Fluorocopolymer Jacket
150°C 89907 NEC: 500 152.4 13.0 5.7 20 AWG .095 2.41 Duobond II .160 4.06 50 80% 25.4 83.3 1 .43 1.4
CL2P 1000 304.8 24.0 10.9 (19x32) + 93% 10 1.30 4.3
CMP 2500 † 762.0 60.0 27.3 .037″ TC Braid 50 2.90 9.5
CEC: TC 5.8Ω/M′ 100 4.18 13.8
200 6.10 20.0
CMP FT6 8.8Ω/M′ 19.0Ω/km 400 9.20 30.2
RG-58/U Type 28.9Ω/km 700 12.90 42.3
DEC Part No. 17-01246-00 900 15.00 49.2
Suitable for Outdoor and Direct Burial applications. 1000 16.00 52.5
Thicknet 10Base5 Ethernet • 12 AWG Solid .086″ Bare Copper Conductor • Duobond IV* Quad Shield (100% Coverage)
Foam Polyethylene Insulation • Yellow PVC Jacket
UL AWM 9880 NEC: 500 152.4 66.0 30.0 12 AWG .243 6.17 Duobond IV .405 10.29 50 78% 26.0 85.0 1 .19 .62
Style 1478 CL2 1000 304.8 131.0 59.5 (solid) (Duobond II 5 .37 1.21
(30V 60°C) CM 1640 500.0 219.0 99.9 .086″ + 94% TC Braid 10 .52 1.71
CEC: BC + Duofoil ® 50 1.20 3.94
For Plenum version of 9880, 100 1.70 5.58
CM 1.4Ω/M′ + 90% TC 200 2.55 8.37
4.7Ω/km Braid) see 89880. 400 3.90 12.80
1.5Ω/M′ 700 5.50 18.10
DEC Part No. 17-00451-00 5.0Ω/km 900 6.50 21.30
Ring-band stripes marked every 2.5 meters to aid users in tap placement. 1000 6.90 22.60
Plenum • Foam FEP Insulation • Orange Fluorocopolymer Jacket
150°C 89880 NEC: 1000 304.8 134.0 60.9 12 AWG .245 6.22 Duobond IV .375 9.53 50 78% 26.0 85.0 1 .18 .59
CL2P 1640 † 500.0 224.7 102.1 (solid) (Duobond II 5 .37 max. 1.21
CMP .086″ + 90% TC Braid 10 .52 max. 1.71
CEC: BC + Duofoil 50 1.15 3.77
100 1.65 5.41
CMP FT6 1.4Ω/M′ + 90% TC 200 2.45 8.04
4.7Ω/km Braid) 400 3.80 12.50
DEC Part No. 17-00324-00 1.5Ω/M′ 700 5.60 18.40
Ring-band stripes marked every 2.5 meters to aid users in tap placement. 5.0Ω/km 900 6.80 22.30
Suitable for Outdoor and Direct Burial applications. 1000 7.20 23.60
BC = Bare Copper • DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • TC = Tinned Copper
Contact the Belden Customer Service Department for a Comprehensive Connector Cross Reference. 1-800-BELDEN-1.
*Duobond IV = Duobond II + 94% tinned copper braid + Duofoil ® + 90% tinned copper braid.
(Plenum version is Duobond II + 90% tinned copper braid + Duofoil + 90% tinned copper braid.)
† Spools and/or UnReel® cartons are one piece, but length may vary ±10% from length shown.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.14
Belden® Blue Hose® Selection Guide for PLC and DCS Applications
9463 Blue Hose Standard Data Highway Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
A Standard Data Highway Cable that is sometimes referred to as Blue (color coded Blue, Clear), Beldfoil® + 55% tinned copper braid and drain
Hose. Designed to be used in light industrial environments. Available wire, Blue sunlight-resistant PVC jacket. Nominal diameter: .238″.
in Blue, Brown or Orange up to 10,000 ft. special lengths.
3072F 600V Data Highway Cable — UL Type TC 1-pair, 18 AWG stranded (7x26) tinned copper, flame-retardant
A DataTray® cable designed for cable tray use in industrial applications. polyolefin insulation (color coded Blue, White), Beldfoil + 55% tinned
Cable can occupy same tray or conduit as 600V power cables. copper braid and drain wire, Blue sunlight-resistant PVC jacket.
Nominal diameter: .324″. UL-1277 600V TC/PLTC/ITC/CMG.
9463F High-Flex Cable 1-pair, 20 AWG stranded (42x36) tinned copper, polyethylene insulation
A highly flexible version of the standard Blue Hose cable. The cable (color coded Blue, Clear), Beldfoil + 85% tinned copper braid,
also has heavier braid coverage for better noise immunity. Blue sunlight-resistant PVC jacket. Nominal diameter: .243″.
YR28826* Dual Blue Hose Cable 2-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
Dual Data Highway/Remote I/O cable has two Twinax pairs individually (color coded Blue, Clear), each pair Beldfoil shielded (1 pair Blue tape
shielded with an overall braid. Designed for use in daisy chain and 1 pair Green tape), 85% tinned copper braid and drain wire,
applications or applications requiring two Blue Hose cables. Blue PVC jacket. Nominal diameter: .382″.
YC39151* Dual Armored Data Highway Cable 2-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
Features two twinax pairs individually shielded with an overall braid, an (color coded Blue, Clear), each pair Beldfoil shielded, 55% tinned copper
inner PVC jacket, aluminum interlocked armor, with an outer PVC jacket. braid and drain wire, Blue PVC inner jacket, aluminum interlocked armor,
Designed for use in daisy chain applications or applications requiring Blue sunlight-resistant PVC outer jacket. Nominal diameter: .820″.
two Blue Hose cables, with the extra mechanical protection and
electrical shielding provided by the armor.
9463DB Gel-Filled Direct Burial Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
A gel-filled Blue Hose cable featuring a low-density polyethylene (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and drain
(LDPE) jacket. Especially suited for high-moisture environments and wire, CoreGuard® flooding compound, Blue sunlight-resistant low density
burial applications. polyethylene jacket. Nominal diameter: .240″.
89463 Plenum Cable 1-pair, 20 AWG stranded (7x28) tinned copper, FEP insulation (color
A plenum, 200°C grade cable that is suitable for installations where coded Blue, Clear), Beldfoil + 76% tinned copper braid and drain wire,
high and low temperatures, as well as corrosive environments, Blue FEP jacket. Nominal diameter: .203″.
are encountered.
YR28764* Thick-Wall, Heavy-Duty Cable — UL Type PLTC 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
A rugged, heavy-duty cable specially designed for abusive environments. (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and
A .069″ thick jacket provides extra protection against cuts and abrasion. drain wire, Blue sunlight-resistant PVC jacket. Nominal diameter: .380″.
YR41104* Low Smoke, Zero Halogen Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
For applications concerned with smoke emissions, toxicity and (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and
electronic component corrosion. drain wire, Blue Haloarrest® jacket. Nominal diameter: .256″.
129463 Aluminum Interlocked Armor Blue Hose Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
Features interlocked aluminum armor combined with a PVC jacket and (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and drain
is an ideal alternative to conduit installation. Provides both mechanical wire, Blue PVC inner jacket, aluminum interlocked armor, Blue PVC sun-
protection and electrical shielding. Up to 25 Data Highway cables can light-resistant outer jacket. Nominal overall diameter: .563″.
be bundled under one sheath.
139463 Steel Interlocked Armor Blue Hose Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
Features interlocked galvanized steel armor combined with a PVC jacket. (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and drain
Provides mechanical protection and electrical shielding, as well as wire, Blue PVC inner jacket, steel interlocked armor, Blue sunlight-
prevention against the low-frequency 60 Hz magnetic noise from power resistant outer PVC jacket. Nominal overall diameter: .563″.
lines. Up to 25 cables can be bundled under one sheath.
189463 Continuously Corrugated Aluminum Armor Blue Hose Cable 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
Features continuously corrugated aluminum armor combined with (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and drain
a PVC jacket. Provides mechanical protection, electrical shielding wire, Blue PVC inner jacket, continuously corrugated aluminum armor,
and is impervious to moisture. Blue sunlight-resistant PVC outer jacket. Nominal overall diameter: .500″.
YR29565* Colored Blue Hose 1-pair, 20 AWG stranded (7x28) tinned copper, polyethylene insulation
When your application calls for multiple Blue Hose cables you can (color coded Blue, Clear), Beldfoil + 55% tinned copper braid and
rest assured that Belden has the solution. This special construction drain wire, sunlight-resistant PVC jacket. Nominal diameter: .238″.
is available in Red, Yellow, Green, White or Pink.
*Custom made product. Minimum order quantity may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.15
78 Ohm • 20 AWG Stranded (7x28) .038″ TC Conductors • Beldfoil® (100% Coverage) + TC Braid Shield (55% Coverage) • TC Drain Wire
Polyethylene Insulation • Blue Sunlight-resistant PVC Jacket (Color Code: Clear, Blue)
Blue Hose 9463 NEC: 100 30.5 4.2 1.9 20 AWG .154 3.91 Beldfoil .238 6.05 78 66% 19.7 64.6 1 .6 2.0
UL AWM CM CL2 U-500 U-152.4 18.5 8.4 (7x28) +55% 10 2.1 6.9
Style 2464 CEC: 500 152.4 18.5 8.4 .038″ TC Braid 50 5.0 16.4
(300V 80°C) CM U-1000 U-304.8 37.0 16.8 Tinned 4.1Ω/M′ 100 7.5 24.6
▲ 200 11.0 36.1
1000 304.8 37.0 16.8 Copper 13.4Ω/km 400 16.0 52.5
Z- Fold® 6000 ▲ † 1828.8 222.0 100.9 9.5Ω/M′
◆†
10000 3048.0 370.0 168.0 31.0Ω/km
CPE jacket optional.
Drain Wire
Polyethylene Insulation • Blue Sunlight-resistant LDPE Jacket (Color Code: Clear, Blue)
Flooded 9463DB — 1000 304.8 33.0 15.0 20 AWG .154 3.91 Beldfoil .240 6.10 78 66% 19.7 64.6 1 .6 2.0
Direct Burial 5000 1524.0 155.0 70.4 (7x28) +55% 10 2.1 6.9
Blue Hose .038″ TC Braid 50 5.0 16.4
300V 80°C Tinned 4.1Ω/M′ 100 7.5 24.6
200 11.0 36.1
Z- Fold® Copper 13.4Ω/km 400 16.0 52.5
9.5Ω/M′
31.0Ω/km
Drain Wire
Allen-Bradley P/N 1770-CD
78 Ohm • 20 AWG Stranded (42x36) .038″ TC Conductors • Overall Beldfoil (100% Coverage) + TC Braid Shield (85% Coverage)
Polyethylene Insulation • Blue Sunlight-resistant PVC Jacket (Color Code: Clear, Blue)
High-Flex 9463F NEC: 1000 304.8 42.0 19.1 20 AWG .154 3.91 Beldfoil .243 6.17 78 66% 19.7 64.6 1 .6 2.0
Blue Hose CM CL2 5000 1524.0 205.0 93.1 (42x36) +85% 10 2.1 6.9
UL AWM CEC: .038″ TC Braid 50 5.0 16.4
Style 2464 CM Tinned 5.0Ω/M′ 100 7.5 24.6
200 11.0 36.1
(300V 60°C) Copper 6.4Ω/km 400 16.0 52.5
9.5Ω/M′
31.0Ω/km
78 Ohm • 20 AWG Stranded (7x28) .038″ TC Conductors • Overall Beldfoil (100% Coverage) + TC Braid Shield (76% Coverage) • Drain Wire
Plenum • FEP Insulation • Blue FEP Jacket (Color Code: Clear, Blue)
High 89463 NEC: 1000 304.8 34.0 15.4 20 AWG .151 3.83 Beldfoil .203 5.16 78 69% 19.7 64.6 1 .6 2.0
Temperature CMP CL2P 2500 762.0 90.0 40.9 (7x28) +76% 10 2.1 6.9
Blue Hose CEC: .038″ TC Braid 50 5.0 16.4
300V 200°C CMP FT6 Tinned 4.1Ω/M′ 100 7.5 24.6
200 11.0 36.1
Z- Fold® Copper 13.4Ω/km 400 16.0 52.5
9.5Ω/M′
31.0Ω/km
Drain Wire
Allen-Bradley P/N 1770-CD
18 • Industrial Cables
DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • LDPE = Low-density Polyethylene • TC = Tinned Copper
*Pennsylvania Department of Environmental Resources and United States Mine Safety and Health Administration Certification.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.16
78 Ohm • 20 AWG Stranded (7x28) TC Conductors • Overall Beldfoil® (100% Coverage) + TC Braid Shield (55% Coverage) • TC Drain Wire
Aluminum Interlocked Armor • PE Insulation • Blue Sunlight-resistant PVC Outer Jacket* (Color Code: Clear, Blue)
Aluminum 129463 NEC: 1000 † 304.8 122.0 55.5 20 AWG .154 3.91 Beldfoil Inner Jacket: 78 66% 19.7 64.6 1 .6 2.0
Armored CM CL2 6000 † 1828.8 924.0 420.0 (7x28) +55% .238 6.05 10 2.1 6.9
Blue Hose CEC: .038″ TC Braid 50 5.0 16.4
300V 60°C CM, Tinned 4.1Ω/M′ Overall:
100 7.5 24.6
200 11.0 36.1
CMG FT4, Copper 13.4Ω/km .563 14.30 400 16.0 52.5
HLBCD 9.5Ω/M′
(Haz Loc) 31.0Ω/km
Drain Wire
Steel Interlocked Armor • PE Insulation • Blue Sunlight-resistant PVC Outer Jacket* (Color Code: Clear, Blue)
Steel 139463 NEC: 1000 † 304.8 220.0 100.0 20 AWG .154 3.91 Beldfoil Inner Jacket: 78 66% 19.7 64.6 1 .6 2.0
Armored CM CL2 6000 † 1828.8 1488.0 676.4 (7x28) +55% .238 6.05 10 2.1 6.9
Blue Hose CEC: .038″ TC Braid 50 5.0 16.4
300V 60°C CM, Tinned 4.1Ω/M′ Overall:
100 7.5 24.6
200 11.0 36.1
CMG FT4, Copper 13.4Ω/km .563 14.30 400 16.0 52.5
HLBCD 9.5Ω/M′
(haz loc) 31.0Ω/km
Drain Wire
*Blue PVC inner jacket.
Allen-Bradley P/N 1770-CD
Continuously Corrugated AL Armor • PE Insulation • Blue Sunlight-resistant PVC Outer Jacket* (Color Code: Clear, Blue)
Continuously 189463 NEC: 2000 † 609.6 258.0 117.1 20 AWG .154 3.91 Beldfoil Inner Jacket: 78 66% 19.7 64.6 1 .6 2.0
Armored PLTC (7x28) +55% .238 6.05 10 2.1 6.9
Blue Hose .038″ TC Braid 50 5.0 16.4
300V 60°C Tinned 4.1Ω/M′ Overall:
100 7.5 24.6
200 11.0 36.1
Copper 13.4Ω/km .500 12.70 400 16.0 52.5
9.5Ω/M′
31.0Ω/km
Drain Wire
78 Ohm • 20 AWG Stranded (7x28) .038″ Tinned Copper Conductors • Tinned Copper Braid Shield (93% Coverage)
Polyethylene Insulation • Blue PVC Jacket (Color Code: Clear, Blue)
UL AWM 9272 NEC: 100 30.5 4.5 2.0 20 AWG .156 3.96 93% .244 6.20 78 66% 19.7 64.6 1 .6 2.0
Style 2092 CM U-500 U-152.4 20.5 9.3 (7x28) TC Braid 10 2.1 6.9
(300V 60°C) CEC: 500 152.4 20.0 9.1 .038″ Shield 50 5.0 16.4
CM U-1000 U-304.8 41.0 18.6 Tinned 3.4Ω/M′ For Plenum version of 9272, 100 7.5 24.6
see 89272. 200 11.0 36.1
1000 304.8 40.0 18.2 Copper 11.2Ω/km 400 16.0 52.5
9.5Ω/M′ CPE jacket optional.
31.0Ω/km
95 Ohm • RG-22B/U Type • 18 AWG Stranded (7x26) Bare Copper Conductors†† • TC Double Braid Shield (95% Coverage)
Polyethylene Insulation • PE Inner Jacket • Black Non-contaminating PVC Outer Jacket
80°C 9250 — 500 152.4 61.5 27.9 18 AWG .285 7.24 2 .416 10.57 95 66% 16.0 52.5 1 .3 1.0
VW-1 1000 304.8 121.0 54.9 (7x26) TC Braid 10 .9 3.0
.046″ 95% 20 1.3 4.3
BC Shield 50 2.1 6.9
CPE jacket optional. 100 3.0 9.8
6.6Ω/M′ .9Ω/M′ 400 6.3 20.7
21.5Ω/km 3.0Ω/km
††One conductor has tinned center strand.
AL = Aluminum • BC = Bare Copper • DCR = DC Resistance • PE = Polyethylene • TC = Tinned Copper
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.17
100 Ohm • 20 AWG Stranded (7x28) .037″ One TC, One BC Conductor • Duofoil® (100% Coverage) + TC Braid Shield (86% Coverage)
Polyethylene Insulation • Polyethylene Inner Jacket • Black PVC Outer Jacket
75°C 9207 NEC: 100 30.5 7.1 3.2 20 AWG .236 5.99 Duofoil .330 8.38 100 66% 14.5 47.6 1 .3 1.0
CMG CL2 U-500 U-152.4 34.0 15.5 (7x28) + 86% 10 1.2 3.9
CEC: 500 152.4 34.5 15.7 .037″ TC Braid 50 2.8 9.2
CMG FT4 1000 304.8 68.0 30.9 1 TC 2.5Ω/M′ For Plenum version of 9207, 100 4.1 13.5
see 89207. 200 6.4 21.0
1640 500.0 111.5 50.7 1 BC 8.2Ω/km 400 10.2 33.5
2000 609.6 136.0 61.8 9.5Ω/M′ CPE jacket optional.
3280 1000.0 219.8 99.9 31.0Ω/km
IBM P/N 7362211 5000 1524.0 350.0 159.1
124 Ohm • 25 AWG Stranded (7x33) .021″ Tinned Copper Conductors • Beldfoil® (100% Coverage) • Stranded Tinned Copper Drain Wire
Polyethylene Insulation • Blue PVC Jacket (Color Code: Clear, Blue)
UL AWM 9271 NEC: 100 30.5 3.2 1.5 25 AWG .170 4.32 100% .240 6.10 124 66% 12.2 40.0 1 .6 2.0
Style 2092 CM 500 152.4 14.0 6.4 (7x33) Beldfoil 10 1.7 5.6
(300V 60°C) CEC: U-1000 U-304.8 27.0 12.3 .021″ Shield 50 3.6 11.8
CM 1000 304.8 28.0 12.7 Tinned 12.0Ω/M′ 100 5.0 16.4
200 6.9 22.6
Copper 39.4Ω/km CPE jacket optional. 400 9.6 31.5
31.8Ω/M′
104.3Ω/km
Shorting Fold
124 Ohm • 16 AWG Solid .051″ Bare Copper Conductors • Duofoil (100% Coverage) + Tinned Copper Braid Shield (90% Coverage)
Foam Polyethylene Insulation • Black PVC Jacket (Color Code: Clear, Blue)
UL AWM 9860 NEC: 500 152.4 52.0 23.6 16 AWG .322 8.18 Duofoil .440 11.18 124 78% 10.9 35.8 1 .2 .6
Style 2448 CMX 1000 304.8 103.0 46.8 (solid) +90% 10 .7 2.3
(30V 60°C) CEC: 2000 609.6 202.0 91.8 .051″ TC Braid 50 1.8 5.9
CMX Bare 1.3Ω/M′ 100 2.9 9.5
CPE jacket optional. 200 4.1 13.5
Copper 4.3Ω/km 400 6.2 20.3
4.2Ω/M′
13.8Ω/km
150 Ohm • 22 AWG Stranded (19x34) .031″ Tinned Copper Conductors • Duofoil (100% Coverage) • Stranded Tinned Copper Drain Wire
Datalene® Insulation • Black PVC Jacket (Color Code: Black, Yellow)
UL AWM 9182 NEC: U-500 U-152.4 22.5 10.2 22 AWG .275 6.98 100% .345 8.76 150 78% 8.8 28.9 1 .4 1.3
Style 2668 CL2X CMX 500 152.4 23.0 10.4 (19x34) Duofoil 10 1.2 3.9
(30V 60°C) CEC: 1000 304.8 44.0 20.0 .031″ Shield For Plenum version of 9182, 50 2.7 8.9
VW-1 CMX Tinned 6.3Ω/M′ see 89182. 100 4.3 14.1
200 6.2 20.3
Copper 20.7Ω/km Dual version: YR41609 400 8.8 28.9
14.0Ω/M′
45.9Ω/km CPE jacket optional.
Plenum • Foam FEP Teflon® Insulation • Black FEP Teflon Jacket (Color Code: Black, Yellow)
89182 NEC: 100 30.5 6.4 2.9 22 AWG .278 7.06 100% .307 7.80 150 78% 8.8 28.9 1 .4 1.3
CMP 500 † 152.4 28.0 12.7 (19x34) Duofoil 10 1.2 3.9
CL2P 1000 † 304.8 53.0 24.1 .031″ Shield 50 2.7 8.9
CEC: Tinned 6.3Ω/M′ 100 4.3 14.1
200 6.2 20.3
CMP FT6 Copper 20.7Ω/km 400 8.8 28.9
14.0Ω/M′
45.9Ω/km
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.18
18 AWG Stranded (7x26) Tinned Copper Conductors • Overall Beldfoil® (100% Coverage) + TC Braid Shield (55% Coverage) • TC Drain Wire
Flame-retardant Polyolefin Insulation • Blue Sunlight-resistant PVC Jacket (Color Code: Natural, Blue)
UL Type TC 3072F NEC: 250 76.2 17.5 8.0 18 AWG .192 4.88 Beldfoil .324 8.23 78 65% 19.5 64 1 .5 1.7
600V 75°C CMG, ITC 500 152.4 35.0 15.9 (7x26) +55% 10 2.0 6.5
TC, PLTC 1000 304.8 69.0 31.3 .046″ TC Braid 50 3.8 12.4
Z- Fold® CEC: 2500 762.0 170.0 77.2 Tinned (100% 100 5.4 17.6
† 200 7.6 24.8
CMG FT4 5000 1524.0 345.0 156.6 Copper Shield) For CPE jacketed version 400 10.7 35.1
10000 † 3048.0 710.0 322.3 6.9Ω/M′ 3.2Ω/M′ order Part No. YM45044.
22.7Ω/km 10.4Ω/km
Drain Wire
P-MSHA-C-7K-1827*
UL Type TC 3073F NEC: 250 76.2 21.0 9.5 18 AWG .246 6.25 Beldfoil .388 9.86 100 65% 15.3 50.2 1 .4 1.3
600V 75°C CMG, ITC 1000 304.8 85.0 38.6 (7x26) +55% 10 1.3 4.4
TC, PLTC 5000 † 1524.0 420.0 190.7 .046″ TC Braid 50 3.0 9.7
Z- Fold® CEC: Tinned (100% 100 4.2 13.8
200 6.0 19.5
CMG FT4 Copper Shield) 400 7.5 24.7
6.9Ω/M′ 2.9Ω/M′ CPE jacket optional.
22.7Ω/km 9.6Ω/km
Drain Wire
UL Type TC 3074F NEC: 500 152.4 62.5 28.4 18 AWG .328 8.33 Beldfoil .460 11.68 124 65% 12.3 40.3 1 .3 1.1
600V 75°C CMG, ITC 1000 304.8 121.0 54.9 (7x26) +55% 10 1.1 3.5
TC, PLTC 2500 762.0 300.0 136.2 .046″ TC Braid 50 2.4 7.8
CEC: Tinned (100% 100 3.4 11.1
Z- Fold® 200 4.8 15.7
CMG FT4 Copper Shield) 400 6.8 22.2
6.9Ω/M′ 2.8Ω/M′ CPE jacket optional.
22.7Ω/km 9.1Ω/km
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.19
RG-6/U Type • 18 AWG Solid Bare Copper-covered Steel Conductor • Duobond® IV* Quad Shield (100% Coverage)
Foam Polyethylene Insulation • PVC Jacket (Black or Intrinsically Safe Blue)
3092A NEC: 500 152.4 20.0 9.1 18 AWG .180 4.57 Duobond IV .298 7.57 75 82% 16.2 53.1 1 .35 1.1
CL2R CMR 1000 304.8 39.0 17.7 (solid) Quad 2 .38 1.2
CEC: 2000 609.6 78.0 35.4 .040″ Shield 5 .45 1.5
CMG FT4 2500 762.2 92.5 42.0 BCCS 3.6Ω/M′ 10 .59 1.9
Sweep tested 5 MHz to 50 MHz. 20 .86 2.8
28.0Ω/M′ 11.8Ω/km 50 1.37 4.5
91.8Ω/km CPE jacket optional. 100 1.97 6.5
200 2.82 9.3
300 3.48 11.4
Allen-Bradley P/N 1786 400 4.04 13.3
Plenum • Foam FEP Insulation • Fluorocopolymer Jacket (Black or Intrinsically Safe Blue◆)
150°C 3093A NEC: 1000 ◆ 304.8 40.0 18.2 18 AWG .170 4.32 Duobond IV .274 6.96 75 82% 16.3 53.5 1 .36 1.2
CMP 2000 † 609.6 80.0 36.3 (solid) Quad 2 .38 1.2
CEC: 2500 † 762.0 95.0 43.1 .040″ Shield 5 .50 1.6
CMP FT6 BCCS 3.6Ω/M′ 10 .65 2.1
20 .95 3.1
28.0Ω/M′ 11.8Ω/km Sweep tested 5 MHz to 50 MHz. 50 1.50 4.9
91.8Ω/km 100 2.12 7.0
200 2.99 9.8
◆
Blue available as standard in 1000 ft. only. 300 3.66 12.0
Suitable for Outdoor and Direct Burial applications. • Allen-Bradley P/N 1786 400 4.23 13.9
RG-6/U Type • 20 AWG Stranded (105x40) Bare Copper Conductor • Duobond IV* Quad Shield (100% Coverage)
Foam Polyethylene Insulation • Black PVC Jacket
High-Flex 3092F NEC: 1000 304.8 44.0 20.0 20 AWG .183 4.65 Duobond IV .303 7.70 75 79% 17.0 55.8 1 .36 1.2
CL2R CMR 5000 1524.0 220.0 99.8 (105x40) Quad 2 .47 1.5
CEC: .040″ Shield 5 .80 2.6
Sweep tested 5 MHz to 400 MHz. 10 1.20 3.9
CMG Bare 3.6Ω/M′
CPE jacket optional. 20 2.00 6.6
FT4 Copper 11.8Ω/km 50 3.20 10.5
10.5Ω/M′ 123092F — Aluminum Armor 100 4.60 15.1
34.4Ω/km 133092F — Steel Armor 200 6.50 21.3
IEEE 802.4 MAP/IEEE 802.7 Mini-MAP. • Allen-Bradley P/N 1786 300 8.00 26.2
For Rockwell authorized Flexible ControlNet order YR28890 (Tinned Copper Braid version). 400 9.30 30.5
RG-6/U Type • 18 AWG Solid Bare Copper-Covered Steel Conductor • Duobond IV* Quad Shield (100% Coverage)
Aluminum Interlocked Armor • Foam Polyethylene Insulation • PVC Inner Jacket • Black PVC Sunlight Resistant Outer Jacket
75°C 123092A NEC: 1000 †† 304.8 180.0 81.7 18 AWG .180 4.57 Duobond IV Inner Jacket 75 82% 16.2 53.2 1 .35 1.2
u CM (solid) Quad .298 7.57 2 .38 1.3
CEC: .040″ Shield Overall: 5 .45 1.5
CMG, BCCS 3.6Ω/M′ .620 15.75 10 .59 1.9
20 .86 2.8
FT4, HL 28.0Ω/M′ 11.8Ω/km 50 1.37 4.5
91.9Ω/km 100 1.97 6.5
Sweep tested 5 MHz to 50 MHz.
200 2.82 9.3
CPE jacket optional. 300 3.48 11.4
133092A — Steel Armor 400 4.04 13.3
Allen-Bradley P/N 1786
Jacket sequentially marked at 1 meter intervals.
Continuously Corrugated Aluminum Armor • Foam Polyethylene Insulation • PVC Inner Jacket • Black PVC Outer Jacket
75°C 183092A NEC: 2000 ▲ 609.6 350.0 158.9 18 AWG .180 4.57 Duobond IV Inner Jacket 75 82% 16.2 53.2 1 .35 1.2
u CL2, CM (solid) Quad .298 7.57 2 .38 1.3
.040″ Shield Overall: 5 .45 1.5
BCCS 3.6Ω/M′ .570 14.48 10 .59 1.9
20 .86 2.8
28.0Ω/M′ 11.8Ω/km 50 1.37 4.5
91.9Ω/km 100 1.97 6.5
Sweep tested 5 MHz to 50 MHz. 200 2.82 9.3
Allen-Bradley P/N 1786 300 3.48 11.4
Jacket sequentially marked at 2 ft. intervals. 400 4.04 13.3
BCCS = Bare Copper-covered Steel • DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene
18 • Industrial Cables
*Duobond IV Quad Shield = Duobond II Foil + 60% aluminum braid + Duofoil + 40% aluminum braid.
†
Final put-up length may vary 0 to +10% from length shown.
††
Final put-up length may vary ±5% from length shown.
▲
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.20
RG-6/U Type • 20 AWG Stranded (105x40) Bare Copper Conductor • Duobond® IV* Quad Shield (100% Coverage)
Foam Polyethylene Insulation • Black PVC Jacket
High-Flex 3092F NEC: 1000 304.8 44.0 20.0 20 AWG .183 4.65 Duobond IV .303 7.70 75 79% 17.0 55.8 1 .36 1.2
CL2R CMR 5000 1524.0 225.0 102.2 (105x40) Quad 2 .47 1.5
CEC: .040″ Shield 5 .80 2.6
CMG Bare 3.6Ω/M′ 10 1.20 3.9
Sweep tested 5 MHz to 400 MHz. 20 2.00 6.6
FT4 Copper 11.8Ω/km 50 3.20 10.5
10.5Ω/M′ CPE jacket optional. 100 4.60 15.1
34.4Ω/km 200 6.50 21.3
300 8.00 26.2
IEEE 802.4 MAP/IEEE 802.7 Mini-MAP. 400 9.30 30.5
RG-6/U Type • 18 AWG Solid Bare Copper-covered Steel Conductor • Duobond IV* Quad Shield (100% Coverage)
Gas-Injected Foam Polyethylene Insulation • Gray PVC Jacket
3131A NEC: 1000 304.8 41.0 18.6 18 AWG .180 4.57 Duobond IV .300 7.62 75 82% 16.2 53.1 1 .35 1.1
CL2R CMR 2500 762.0 100.0 45.4 (solid) Quad 2 .38 1.2
CEC: .040″ Shield 5 .45 1.5
CMR FT4 BCCS 3.6Ω/M′ 10 .59 1.9
Sweep tested 5 MHz to 400 MHz. 20 .86 2.8
28.0Ω/M′ 11.8Ω/km 50 1.37 4.5
91.8Ω/km CPE jacket optional. 100 1.97 6.5
200 2.82 9.3
IEEE 802.4 MAP/IEEE 802.7 Mini-MAP. 300 3.48 11.4
Tap marks every 2.6 meters to aid users in installation. 400 4.04 13.3
Plenum • Foam FEP Insulation • Gray Fluorocopolymer Jacket
150°C 3132A NEC: 1000 304.8 36.0 16.3 18 AWG .170 4.32 Duobond IV .274 6.96 75 82% 16.3 53.5 1 .36 1.2
CMP (solid) Quad 2 .38 1.2
CEC: .040″ Shield 5 .50 1.6
CMP FT6 BCCS 3.6Ω/M′ 10 .65 2.1
20 .95 3.1
28.0Ω/M′ 11.8Ω/km Sweep tested 5 MHz to 400 MHz. 50 1.50 4.9
91.8Ω/km 100 2.12 7.0
IEEE 802.4 MAP/IEEE 802.7 Mini-MAP. 200 2.99 9.8
Tap marks every 2.6 meters to aid users in installation. 300 3.66 12.0
Suitable for Outdoor and Direct Burial applications. 400 4.23 13.9
RG-11/U Type • 14 AWG Solid Bare Copper-covered Steel Conductor • Duobond IV* Quad Shield (100% Coverage)
Gas-Injected Foam Polyethylene Insulation • Gray PVC Jacket
3094A NEC: 500 152.4 35.5 16.1 14 AWG .280 7.11 Duobond IV .407 10.34 75 82% 16.2 53.1 1 .16 .5
CL2R CMR 1000 304.8 62.0 28.1 (solid) Quad 2 .18 .6
CEC: 2000 609.6 140.0 63.6 .064″ Shield 5 .26 .9
CMG FT4 BCCS 1.5Ω/M′ 10 38 1.2
Sweep tested 5 MHz to 400 MHz. 20 .55 1.8
11.0Ω/M′ 4.9Ω/km 50 .83 2.7
36.1Ω/km CPE jacket optional. 100 1.17 3.8
200 1.60 5.3
IEEE 802.4 MAP 300 1.99 6.5
Tap marks every 2.6 meters to aid users in installation. 400 2.30 7.5
Plenum • Foam FEP Insulation • Gray Fluorocopolymer Jacket
150°C 3095A NEC: 1000 304.8 76.0 34.5 14 AWG .280 7.11 Duobond IV .387 9.83 75 82% 16.5 54.1 1 .17 .6
CMP (solid) Quad 2 .22 .7
CEC: .064″ Shield 5 .28 .9
CMP FT6 BCCS 3.9Ω/M′ 10 .40 1.3
20 .60 2.0
11.0Ω/M′ 12.8Ω/km 50 1.20 3.9
36.1Ω/km Sweep tested 5 MHz to 400 MHz. 100 1.70 5.6
IEEE 802.4 MAP 200 2.50 8.2
Tap marks every 2.6 meters to aid users in installation. 300 3.04 10.0
Suitable for Outdoor and Direct Burial applications. 400 3.50 11.5
BCCS = Bare Copper-covered Steel • DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene
*Duobond IV Quad Shield = Duobond II Foil + 60% aluminum braid + Duofoil® + 40% aluminum braid.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.21
FOUNDATION Fieldbus/PROFIBUS PA • 18 AWG Stranded (7x26) TC Conductors • Beldfoil® Shield (100% Coverage) • TC Drain Wire
Polyolefin Insulation • Orange or Blue PVC Jacket (Color Code: Blue, Orange)
Type A 3076F NEC: 250 76.2 10.5 4.8 (2) 18 AWG .088 2.24 100% .253 6.43 100 @ 66% 24.0 78.7 .039 .08 .26
300V 105°C PLTC CM 500 152.4 18.5 8.4 (7x26) Beldfoil 31.25 KHz
(31.25 KBits/sec) ITC 1000 304.8 37.0 16.8 .048″ Shield
CEC: 2500 762.0 85.0 38.6 Tinned 7.5Ω/M′ 123076F — Version with Aluminum Interlocked Armor
CM 5000† 1524.0 170.0 77.2 Copper 24.6Ω/km 133076F — Version with Steel Interlocked Armor
7.5Ω/M′ YM47023 — CPE jacketed version
24.6Ω/km YM46698 — Black & White color-coded pairs
Shorting Fold YM47090 — Various colored jackets
YM41725 — LSZH (FRNC) jacketed version
Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Blue available as standard in 1000 ft. put-up only.
FOUNDATION Fieldbus • 22 AWG Stranded (7x30) TC Conductors • Beldfoil Shield (100% Coverage) • Tinned Copper Drain Wire
Polyolefin Insulation • Orange PVC Jacket (Color Code: Blue, Orange)
Type B 3077F NEC: 500† 152.4 11.0 5.0 (2) 22 AWG .059 1.50 100% .196 4.97 100 @ 66% 23.5 77.1 .039 .14 .45
300V 105°C PLTC CM 1000† 304.8 23.0 10.4 (7x30) Beldfoil 31.25 KHz
(31.25 KBits/sec) ITC .030″ Shield
CEC: Tinned 11.4Ω/M′
CM Copper 37.4Ω/km 123077F — Version with Aluminum Interlocked Armor
17.1Ω/M′ 133077F — Version with Steel Interlocked Armor
56.0Ω/km CPE and LSZH jacketed versions also available.
Shorting Fold
PROFIBUS DP • 22 AWG Solid Bare Copper Conductors • Beldfoil (100% Coverage) + Tinned Copper Braid Shield (65% Coverage)
FHDPE Insulation • Chrome or Purple PVC Jacket (Color Code: Red, Green)
300V 75°C 3079A NEC: 1000 304.8 56.0 25.4 (2) 22 AWG .099 2.52 Beldfoil .315 8.00 150 78% 8.5 27.9 .2 .27 .9
PLTC CMG 2000 609.6 112.0 50.8 (solid) + 65% 4.0 .67 2.2
CEC: 3600 1097.6 201.6 91.4 .026″ TC Braid 16.0 1.37 4.5
CMG FT4 Bare Shield 123079A — Aluminum Interlocked Armor 100.0 3.75 12.3
133079A — Steel Interlocked Armor 300.0 6.52 21.4
Copper (100%
16.0Ω/M′ Coverage) YR45047 — CPE jacketed version
52.5Ω/km 3.9Ω/M′ YR44731 — LSZH (FRNC) jacketed version
UL AWM 20201 (600V) 12.8Ω/km
Siemens Sinec L2 cable.
PROFIBUS DP • 22 AWG Stranded (7x30) Bare Copper Conductors • Beldfoil (100% Coverage) + TC Braid Shield (65% Coverage)
FR-FPE Insulation • Purple PVC Jacket (Color Code: Red, Green)
300V 75°C 3079E NEC: 1000 304.8 44.0 20.0 (2) 22 AWG .099 2.52 Beldfoil .315 8.00 150 78% 8.5 27.9 .2 .34 1.1
PLTC CMG 1640 500.0 73.8 33.5 Stranded + 65% 4.0 .81 2.7
CEC: 3280 1000.0 144.3 65.5 (7x30) TC Braid 16.0 1.64 5.4
CMG FT4 Bare Shield
Copper (100%
16.0Ω/M′ Coverage)
52.5Ω/km 3.9Ω/M′
12.8Ω/km
18 • Industrial Cables
DCR = DC Resistance • FHDPE = Foamed High-Density Polyethylene • FR-FPE = Flame-Retardant Polyethylene • FRNC = Flame-Retardant Non-Corrosive • LSZH = Low-Smoke Zero-Halogen • TC = Tinned Copper
†
Final put-up length may vary -0 to +10% from length shown.
▲
For HSE, see Industrial Ethernet Section for copper and fiber cables.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.22
600V Class 1 Thick • 15 and 18 AWG Stranded TC Conductors • Individually Foil Shielded (100% Coverage) + Overall TC Braid (65% Coverage)
PVC/Nylon Insulation (Power) • FEP Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
High Velocity 7897A NEC: 500 152.4 69.5 31.6 (2)15 AWG TC 100% Power Pair: .460 11.7 — — — — — — —
Thick TC-ER 1000 304.8 135.0 61.3 (19x28) Individual Red&Black
600V 75°C 2000 609.6 274.0 124.4 3.6Ω/M′ Foil
11.8Ω/km + Overall
(2)18 AWG TC 65% Data Pair:
(19x30) TC Braid Blue&White 120 75% 12.0 39.4 .125 .13 .43
6.9Ω/M′ 1.8Ω/M′ .500 .25 .82
22.6Ω/km 5.9Ω/km 1.000 .40 1.31
18 AWG stranded (19x30) tinned copper drain wire.
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
600V Class 1 ODVA Cable V • 16 and 18 AWG Stranded TC Cond. • Individ. Foil Shielded (100% Coverage) + Overall TC Braid (65% Coverage)
PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
600V 75°C 7896A NEC: 500 152.4 89.0 40.4 (2)16 AWG TC 100% Power Pair: .525 13.34 — — — — — — —
TC-ER 1000 304.8 168.0 76.2 (19x29) Individual Red&Black
2000 609.6 340.0 154.2 4.9Ω/M′ Foil
16.1Ω/km + Overall
(2)18 AWG TC 65% Data Pair:
(19x30) TC Braid Blue&White 120 64% 14.7 48.2 .125 .13 .43
6.9Ω/M′ 1.8Ω/M′ .500 .25 .82
C(UL) AWM I/II A/B
22.6Ω/km 5.9Ω/km 1.000 .40 1.31
16 AWG stranded (19x29) tinned copper drain wire.
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
600V Class 1 ODVA Cable IV • 16 and 18 AWG Stranded Tinned Copper Conductors • Unshielded
PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
Drop 7900A NEC: 500 152.4 51.0 23.1 (2)16 AWG TC Unshielded Power Pair: .430 10.92 — — — — — — —
600V 75°C TC-ER 1000 304.8 105.0 47.6 (19x29) Red&Black
CEC: 4.9Ω/M′
FT1 16.1Ω/km
(2)18 AWG TC Data Pair:
(19x30) Blue&White 120 64% 14.7 48.2 .125 .13 .43
6.9Ω/M′ .500 .25 .82
C(UL) AWM I/II A/B 22.6Ω/km 1.000 .40 1.31
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-C
DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • F -R = Flame-retardant • TC = Tinned Copper • TC-ER = Tray Cable Exposed Run per 2005 NEC Article 336
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.23
300V Class 2 Thick • 15 and 18 AWG Stranded TC Cond. • Individually Foil Shielded (100% Coverage) + Overall TC Braid (65% Coverage)
PVC Insulation (Power) • FPE Insulation (Data) • Sunlight- and Oil-resistant PVC Jacket (Available in Gray or Red)
Thick 3082A NEC: 500 † 152.4 71.0 32.2 (2)15 AWG TC 100% Power Pair: .480 12.19 — — — — — — —
75°C CMG, 1000 304.8 138.0 62.6 (19x28) Individual Red&Black
PLTC-ER 2000 † 609.6 280.0 127.0 3.6Ω/M′ Foil
CEC: 11.8Ω/km + Overall
CMG FT4 (2)18 AWG TC 65% Data Pair:
(19x30) TC Braid Blue&White 120 75% 12.0 39.4 .125 .13 .43
6.9Ω/M′ 1.8Ω/M′ .500 .25 .82
† 22.6Ω/km 5.9Ω/km 1.000 .36 1.18
500 ft. and 2000 ft. put-ups not available in Red.
UL AWM 20201 (600V) • C(UL) AWM I/II A
18 AWG stranded (19x30) tinned copper drain wire.
Meter marks on jacket to aid users in installation. • Allen-Bradley P/N 1485 CPI-A
High-Flex 3082F NEC: 500 † 152.4 72.5 32.9 (2)15 AWG TC 100% Power Pair: .480 12.19 — — — — — — —
Thick CMG, 1000 304.8 140.0 63.5 (65x33) Individual Red&Black
75°C PLTC-ER 2000 † 609.6 284.0 128.8 3.6Ω/M′ Foil
CEC: 11.8Ω/km + Overall
CMG FT4 (2)18 AWG TC 65% Data Pair:
(65x36) TC Braid Blue&White 120 75% 12.0 39.4 .125 .13 .43
6.9Ω/M′ 1.8Ω/M′ .500 .25 .82
† 22.6Ω/km 5.9Ω/km 1.000 .36 1.18
500 ft. and 2000 ft. put-ups not available in Red.
UL AWM 20201 (600V) • C(UL) AWM I/II A
18 AWG stranded (65x36) tinned copper drain wire.
Meter marks on jacket to aid users in installation. • Allen-Bradley P/N 1485 CPI-A
300V Class 2 Thin • 22 and 24 AWG Stranded TC Conductors • Individ. Foil Shielded (100% Coverage) + Overall TC Braid (65% Coverage)
PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight- and Oil-resistant PVC Jacket
Thin 3084A NEC: 500 152.4 22.0 10.0 (2)22 AWG TC 100% Power Pair: .280 7.11 — — — — — — —
75°C CL2 CMG 1000 † 304.8 47.0 21.3 (19x34) Individual Red&Black
CEC: 2000 609.6 96.0 43.6 17.5Ω/M′ Foil
CMG FT4 57.4Ω/km + Overall
(2)24 AWG TC 65% Data Pair:
(19x36) TC Braid Blue&White 120 75% 12.0 39.4 .125* .29* .95*
†
1000 ft. put-up also available in Red. 28.0Ω/M′ 3.2Ω/M′ .500* .50* 1.64*
22 AWG stranded (19x34) tinned copper drain wire. • C(UL) AWM I/II A 91.9Ω/km 10.5Ω/km 1.000* .70* 2.30*
Meter marks on jacket to aid users in installation. • Allen-Bradley P/N 1485 CPI-C
High-Flex 3084F NEC: 500 152.4 22.0 10.0 (2)22 AWG TC 100% Power Pair: .275 6.99 — — — — — — —
Thin CL2 CMG 1000 304.8 47.0 21.3 (154x44) Individual Red&Black
75°C CEC: 2000 609.6 96.0 43.6 17.5Ω/M′ Foil
CMG FT4 57.4Ω/km + Overall
(2)24 AWG TC 65% Data Pair:
(105x44) TC Braid Blue&White 120 75% 12.0 39.4 .125* .29* .95*
C(UL) AWM I/II A 28.0Ω/M′ 3.2Ω/M′ .500* .50* 1.64*
22 AWG stranded (26x36) tinned copper drain wire. 91.9Ω/km 10.5Ω/km 1.000* .70* 2.30*
Meter marks on jacket to aid users in installation. • Allen-Bradley P/N 1485 CPI-C
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.24
300V Class 2 ODVA Cable III • 20 and 18 AWG Stranded TC Cond. • Indiv. Foil Shielded (100% Coverage) + Overall TC Braid (65% Coverage)
PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
Mid 7895A NEC: 500 152.4 41.0 18.6 (2)18 AWG TC 100% Power Pair: .378 9.60 — — — — — — —
75°C CMG PLTC 1000 304.8 84.0 38.1 (19x30) Individual Red&Black
CEC: 6.9Ω/M′ Foil
CMG FT4 22.6Ω/km + Overall
(2)20 AWG TC 65% Data Pair:
(19x32) TC Braid Blue&White 120 75% 12.0 39.4 .125 .29 .95
UL AWM 20201 (600V) 10.9Ω/M′ 3.2Ω/M′ .500 .50 1.64
20 AWG stranded (19x32) tinned copper drain wire. 35.8Ω/km 10.5Ω/km 1.000 .70 2.30
Meter marks on jacket to aid users in installation.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.25
22 AWG Stranded Tinned Copper Conductors • Each Pair Individually Beldfoil® Shielded (100% Coverage) • Drain Wire
PVC Insulation (Power) • FPE Insulation (Data) • Gray PVC Jacket
UL AWM 3087A NEC: 500 152.4 19.0 8.6 (4)22 AWG 100% Power Pair: .290 7.37 — — — — — — —
Style 2464 CL2 1000 304.8 41.0 18.6 (19x34) Beldfoil Blue&Brown
30V 80°C CEC: 2000 609.6 84.0 38.1 .030″ Each Pair
CSA AWM Ι/ΙΙ A FT1 Tinned
Copper Data Pair:
17.5Ω/M′ Black&White 120 76% 12.0 39.4 .125 .23 .76
57.4Ω/km .500 .42 1.38
1.000 .60 1.97
Micro Cable (Drop)
22 AWG stranded (19x34) tinned copper drain wire.
16 and 20 AWG Stranded Tinned Copper Conductors • Each Pair Individually Beldfoil Shielded (100% Coverage) • Drain Wire
PVC Insulation (Power) • FPE Insulation (Data) • Gray PVC Jacket
UL AWM 3086A NEC: 500 152.4 43.5 19.7 (2)16 AWG TC 100% Power Pair: .398 10.11 — — — — — — —
Style 2464 CL2 1000 304.8 88.0 39.9 (19x29) Beldfoil Blue&Brown
30V 80°C CEC: .067″ Each Pair
CSA AWM Ι/ΙΙ A FT1 3.6Ω/M′
11.8Ω/km
(2)20 AWG TC Data Pair:
(19x32) Black&White 120 76% 12.0 39.4 .125 .18 .59
.041″ .500 .35 1.15
10.0Ω/M′ 1.000 .47 1.54
Mini Cable (Trunk) 32.8Ω/km
20 AWG stranded (19x32) tinned copper drain wire.
DCR = DC Resistance • FPE = Foamed Polyethylene • TC = Tinned Copper
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.26
18 and 22 AWG Stranded Tinned Copper Conductors • Overall 100% Beldfoil® Shield (100% Coverage) • 22 AWG (7x30) TC Drain Wire
Foam HDPE Insulation (Power) • Foam HDPE Insulation (Data) • Orange PVC Jacket
UL AWM Style 20201 3124A NEC: 1000 304.8 47.0 21.3 (2)18 AWG 100% Power Cdrs: .308 7.82 — — 20.0 65.6
(600V 75°C) CL2 CM (16x30) Overall Red&Black
CEC: .040″ TC Beldfoil
CM 6.8Ω/M′ Shield
21.3Ω/km 10.7Ω/M′
(2)22 AWG 35.1Ω/km Data Cdrs:
(7x30) White&Green — 78% 16.0 52.5
.030″ TC
18.1Ω/M′
Seriplex CBL 1822-P18 59.4Ω/km
16 and 22 AWG Stranded Tinned Copper Conductors • Overall 100% Beldfoil Shield (100% Coverage) • 22 AWG (7x30) TC Drain Wire
Foam HDPE Insulation (Power) • Foam HDPE Insulation (Data) • Orange PVC Jacket
300V 75°C 3125A NEC: 500 152.4 31.5 14.3 (2)16 AWG 100% Power Cdrs: .368 9.35 — — 28.0 91.9
CL2 CM 1000 304.8 63.0 28.6 (26x30) Overall Red&Black
CEC: .060″ TC Beldfoil
CM 4.5Ω/M′ Shield
14.8Ω/km 10.7Ω/M′
(2)22 AWG 35.1Ω/km Data Cdrs:
(7x30) White&Green — 78% 16.0 52.5
.030″ TC
18.1Ω/M′
Seriplex CBL 1622-P1 59.4Ω/km
16, 22 and 12 AWG Stranded Tinned Copper Conductors • Overall Beldfoil Shield (100% Coverage) • 22 AWG (7x30) TC Drain Wire
Foam HDPE Insulation (Control) • Foam HDPE Insulation (Data) • PVC Insulation (Power) • Orange PVC Jacket
300V 75°C 3126A NEC: 1000 304.8 112.0 50.8 (2)16 AWG 100% Control Cdrs: .486 12.34 — — 28.0 91.9
CL2 CM (26x30) Overall Red&Black x x
CEC: .060″ TC Beldfoil .363 9.22
CM 4.5Ω/M′ Shield
14.7Ω/km 10.7Ω/M′
(2)22 AWG 35.1Ω/km Data Cdrs:
(7x30) White&Green — 78% 16.0 52.5
.030″ TC
18.1Ω/M′
59.4Ω/km
(2)12 AWG Power Cdrs: — — — —
(65x30) Black&White,
.090″ TC Red&White
1.8Ω/M′
Seriplex CBL 162212-P16 5.9Ω/km
DCR = DC Resistance • HDPE = High-density Polyethylene • TC = Tinned Copper
*Capacitance between one conductor and other conductors connected to shield.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.27
18 and 24 AWG Stranded Tinned Copper Conductors • Overall Beldfoil® Shield (100% Coverage) + Tinned Copper Braid (90% Coverage)
PVC Insulation (Power) • PE Insulation (Data) • Green Polyurethane Jacket
UL AWM Style 20233 3119A — 500 152.4 35.5 16.1 (3)18 AWG 100% Power: .333 8.46 — — — —
(300V 80°C) 1000 304.8 71.0 32.2 (7x26) Overall Red, Blue,
.060″ TC Beldfoil Green w/
6.6Ω/M′ + 90% Yellow Stripe
21.7Ω/km TC Braid
(3pr)24 AWG 2.7Ω/M′ Data:
(7x32) 8.9Ω/km Pink&Gray, 100 66% 15.4 50.5
.024″ TC White&Brown,
23.4Ω/M′ Yellow&Green
76.8Ω/km
24 AWG Stranded Tinned Copper Conductors • Overall 100% Beldfoil Shield (100% Coverage) + Tinned Copper Braid (90% Coverage)
Polyethylene Insulation • Green Polyurethane Jacket
UL AWM Style 20233 3120A — 500 152.4 26.0 11.8 (3pr)24 AWG 100% Pink&Gray, .277 7.04 100 66% 15.4 50.5
(300V 80°C) 1000 304.8 49.0 22.2 (7x32) Overall White&Brown,
TC Beldfoil Yellow&Green
26.0Ω/M′ + 90%
85.3Ω/km TC Braid
2.7Ω/M′
8.9Ω/km
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.28
22 AWG Stranded (7x30) TC Conductors • Twisted Pairs • Overall Beldfoil® Shield (100% Coverage) + TC Braid (90% Coverage) • Drain Wire▲
Datalene® Insulation • Black UV Resistant PVC Jacket (CPE jacket optional)
Oil Res II 3105A▼ NEC: 1 See 500 152.4 23.0 10.4 14.7Ω/M′ 2.8Ω/M′ .284 7.21 120 78% 11.0 36.1 20.9 68.6
300V CM PLTC Chart 1000 304.8 50.0 22.7 48.2Ω/km 9.2Ω/km
† For CPE jacketed version
CEC: (below) 5000 1523.9 255.0 115.8
order Part No. YR44345
CM FT1
3106A NEC: 1.5 ◆ White/Orange, 500 152.4 27.0 12.3 14.7Ω/M′ 2.8Ω/M′ .300 7.62 120 78% 11.0 36.1 20.9 68.6
CM PLTC Orange/White, 1000 304.8 51.0 23.2 48.2Ω/km 9.2Ω/km
For CPE jacketed version
CEC: Blue/White 5000 † 1523.9 260.0 118.1
order Part No. YR46721
CM FT1
3107A▼ NEC: 2 See 1000 304.8 69.0 31.3 14.7Ω/M′ 1.8Ω/M′ .356 9.04 120 78% 11.0 36.1 20.9 68.6
CM PLTC Chart 4000 1219.2 300.0 136.2 48.2Ω/km 5.9Ω/km
For CPE jacketed version
CEC: (below) 5000 † 1523.9 385.0 174.8
order Part No. YR46792
CM FT1
3108A NEC: 3 See 1000 304.8 93.0 42.2 14.7Ω/M′ 1.5Ω/M′ .420 10.67 120 78% 11.0 36.1 20.9 68.6
CM PLTC Chart 2000 609.6 184.0 83.5 48.2Ω/km 4.9Ω/km
For CPE jacketed version
CEC: (below)
order Part No. YR45287
CM FT1
3109A NEC: 4 See 1000 304.8 107.0 48.6 14.7Ω/M′ 1.4Ω/M′ .420 10.67 120 78% 11.0 36.1 20.9 68.6
CM PLTC Chart 2000 609.6 218.0 99.0 48.2Ω/km 4.6Ω/km
CEC: (below) For CPE jacketed version
▼
3015A and 3107A are DMX512 Type. CM FT1 order Part No. YR44768
▲
22 AWG stranded tinned copper drain wire.
AL Interlocked Armor • Datalene® Insulation • PVC Inner Jacket • Black UV Resistant PVC Outer Jacket
300V 123107A NEC: 2 See 5000 †† 1523.9 1140.0 514.1 14.7Ω/M′ 1.8Ω/M′ .650 16.51 120 78% 11.0 36.1 20.9 68.6
u CM PLTC Chart 48.2Ω/km 5.9Ω/km
CEC: (below)
CMG FT4
▲
22 AWG stranded tinned copper drain wire.
DCR = DC Resistance • TC = Tinned Copper
* Capacitance between conductors.
**Capacitance between one conductor and other conductors connected to shield.
† Final put-up length may vary -0 to +10% from length shown.
†† Final put-up length may vary ±10% for spools or reels and ±5% for UnReel® cartons from length shown.
◆
All conductors are under the braid shield; one pair is under the Beldfoil shield.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.29
24 AWG Stranded (7x32) TC Conductors • Twisted Pairs • Individually Beldfoil® Shielded (100% Coverage) • 24 AWG Stranded TC Drain Wire
Datalene® Insulation • Chrome PVC Jacket
UL AWM Style 2493 9729 NEC: 2 Red&Black, 100 30.5 4.3 2.0 24.0Ω/M′ 15.0Ω/M′ .266 6.76 100 76% 12.5 41.0 23.2 76.1
(300V 60°C) CM White&Black 500 152.4 20.5 9.3 78.7Ω/km 49.3Ω/km
CEC: 1000 304.8 39.0 17.7
CM 10000 3048.0 390.0 177.1
For Plenum version of 9729,
see 89729 or 82729.
Z-Fold®
24 AWG stranded (7x32) tinned copper drain wire.
22 AWG Stranded (7x30) TC Conductors • Twisted Pairs • Individually Beldfoil Shielded (100% Coverage) • 22 AWG Stranded TC Drain Wire
Polypropylene Insulation • Chrome PVC Jacket
UL AWM Style 2919 8777 NEC: 3 Red&Black, 100 30.5 4.6 2.1 15.0Ω/M′ 10.6Ω/M′ .273 6.93 50 66% 30 98 55 180
(30V 80°C) CM White&Black, 250 76.2 11.0 5.0 49.2Ω/km 34.8Ω/km
CEC: Green&Black U-500 U-152.4 21.0 9.5
CM 500 152.4 21.0 9.5
U-1000 U-304.8 41.0 18.6
1000 304.8 42.0 19.1
For Plenum versions of 8777,
1640 499.9 67.2 30.5
see 88777, 87777 or 82777.
3280 999.7 137.8 62.5
5000 1524.0 210.0 95.3
Z-Fold® 10000 3048.0 450.0 204.3
22 AWG Stranded (7x30) TC Conductors • Twisted Pairs • Individually Beldfoil Shielded (100% Coverage) • 24 AWG Stranded TC Drain Wire
Polypropylene Insulation • Chrome PVC Jacket (Pairs Cabled on Common Axis to Reduce Diameter)
300V RMS 60°C 8723 NEC: 2 Red&Black, 100 30.5 2.3 1.0 16.0Ω/M′ 14.7Ω/M′ .168 4.27 45 66% 35 115 62 203
CM Green&White U-500 U-152.4 10.5 4.8 52.5Ω/km 48.3Ω/km
CEC: 500 152.4 10.0 4.5
CM U-1000 U-304.8 20.0 9.1
1000 304.8 20.0 9.1
Z-Fold® 1640 499.9 32.8 14.9 For Plenum versions of 8723,
U-2000 U-609.6 40.0 18.2 see 88723, 87723 or 82723.
2000 609.6 40.0 18.2
3280 999.7 65.6 29.8
5000 1524.0 95.0 43.1
10000 3048.0 200.0 90.8
24 AWG stranded (7x32) tinned copper drain wire.
Plenum • FEP Insulation • Red FEP Jacket (Pairs Cabled on Common Axis to Reduce Diameter)
300V RMS, Non-conduit 88723 NEC: 2 Red&Black, 100 30.5 3.4 1.5 16.0Ω/M′ 14.7Ω/M′ .148 3.76 40 69% 35 115 67 220
CMP Green&White 500 152.4 11.0 5.0 52.5Ω/km 48.3Ω/km
CEC: 1000 304.8 21.0 9.5
CMP FT6
Z-Fold®
18 AWG Stranded (16x30) TC Conductors • Twisted Pair • Overall Beldfoil Shield (100% Coverage) • 20 AWG Stranded TC Drain Wire
Polyethylene Insulation • Chrome PVC Jacket
UL AWM Style 2092 8760 NEC: 1 Black 250 76.2 6.8 3.1 — — .222 5.64 — — 24 79 44 144
(300V 60°C) CM &Clear U-500 U-152.4 13.0 5.9
CEC: 500 152.4 13.0 5.9
CM U-1000 U-304.8 26.0 11.8
1000 304.8 26.0 11.8 For Plenum versions of 8760,
2000 609.6 50.0 22.7 see 88760, 87760 or 82760.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.30
4-cond. (3) Stranded TC Circuit Conductors + (1) Ground* • Overall Beldfoil® (100% Coverage) + TC Braid Shield (85% Coverage) • TC Drain Wire*
XLPE Insulation (Circuit Condrs) • PVC Insulation (Ground) • Black Sunlight- and Oil-resistant PVC Jacket
1000V UL 29500 16 26x30 250† 76.2 46.2 21.0 .53 13.46 128 568 3.9 99.06
Flexible Motor Supply Cable 500† 152.4 93.0 42.2
600V UL 1277 Type TC-ER All Allen-Bradley Series 1000† 304.8 182.0 82.6
per 2005 NEC Article 336 160 and 1305 drives. 6000† 1828.8 1080.0 490.3
1000V CSA AWM Ι/ΙΙ A/B FT4 29501 14 41x30 250† 76.2 59.7 27.1 .55 13.97 212 942 4.5 114.30
90°C Wet/Dry 500† 152.4 120.0 54.5
Allen-Bradley 1336F(S)-BRF05 1000† 304.8 233.0 105.8
through BRF100 5000† 1524.0 1215.0 551.6
29502 12 65x30 250† 76.2 69.8 31.7 .60 15.24 336 1495 4.9 124.46
500† 152.4 151.5 68.8
1000† 304.8 298.0 135.3
Allen-Bradley 1336F(S)-BRF150, BRF200 5000† 1524.0 1570.0 712.8
29503 10 105x30 250† 76.2 91.3 41.4 .66 16.76 525 2335 5.4 137.16
500† 152.4 194.5 88.3
1000† 304.8 375.0 170.3
Allen-Bradley 1336F(S)-B015 5000† 1524.0 2025.0 919.4
29504 8 7x19x29 250† 76.2 158.5 72.0 .89 22.61 1328 5906 7.3 185.42
500† 152.4 332.0 150.7
1000† 304.8 660.0 299.6
Allen-Bradley 1336F(S)-B020 5000† 1524.0 3135.0 1423.3
29505 6 7x19x27 250† 76.2 221.3 100.5 .99 25.15 2048 9109 8.0 203.20
1000† 304.8 906.0 411.3
Allen-Bradley 1336F(S)-B025, B030 3500† 1066.8 3206.0 1455.5
29506 4 7x19x25 250† 76.2 319.5 145.1 1.15 29.21 3152 14021 9.2 233.68
1000† 304.8 1231.0 558.9
Color Code: ICEA Method 4 Allen-Bradley 1336F(S)-BX040, B040 3000† 914.4 3843.0 1744.7
(Black and Numbered); 29507 2 7x19x23 250† 76.2 437.8 198.7 1.29 32.77 4872 21672 10.5 266.70
Green/Yellow Ground 500† 152.4 875.5 397.5
UL Direct Burial. Allen-Bradley 1336F(S)-B050, 1000† 304.8 1711.0 776.8
XHHW-2, RHW-2 rated circuit conductors. BX060, B060 2000† 609.6 3682.0 1671.6
Three (3) Stranded TC Circuit Conductors + (3) Symmetrical Bare Copper Grounds • (2) Spiral Copper Tape Shields (100% Coverage)
XLPE Insulation (Circuit Condrs) • Black Sunlight- and Oil-resistant PVC Jacket
1000V UL 29528 1 7x19x22 250 †† 76.2 398.8 181.0 1.20 30.48 2650 11788 12.0 304.8
Flexible Motor Supply Cable u 1000 †† 304.8 1642.0 746.0
600V UL 1277 Type TC-ER 3000 † 1524.0 4779.0 2169.7
per 2005 NEC Article 336 29529 1/0 7x19x21 250 †† 76.2 525.8 238.7 1.29 32.77 3537 15733 12.9 327.7
600V CSA AWM Ι/ΙΙ A/B FT4 u 1000 †† 304.8 2050.0 930.7
90°C Wet/Dry 2000 † 609.6 3954.0 1795.1
29530 2/0 7x19x20 250 †† 76.2 602.0 273.3 1.40 35.56 4200 18682 14.0 355.6
u 1000 †† 304.8 2362.0 1072.4
2000 † 609.6 4744.0 2153.8
29531 3/0 7x19x19 250 †† 76.2 699.5 317.6 1.52 38.61 5025 22352 15.2 386.1
u 1000 †† 304.8 2708.0 1229.4
Color Code: ICEA Method 4 3000 † 1524.0 5436.0 2467.9
(Black and Numbered)
29532 4/0 7x19x18 250 †† 76.2 881.0 400.0 1.68 42.67 6670 29670 16.8 426.7
UL Direct Burial. u 500 †† 152.4 1873.0 850.3
XHHW-2 circuit conductors. 1500 † 457.2 5619.0 2551.0
TC = Tinned Copper • TC-ER = Tray Cable - Exposed Run per 2005 NEC Article 336 • XLPE = Cross-linked Polyethylene
*Ground(s) and drain wire(s) are same AWG as circuit conductors. Encoder Cables
†Final put-up length may vary ±10% from length shown. Belden also offers the following standard cables for
††Final put-up length may vary ±5% from length shown.
encoder applications. Encoder cables help feed
information to the microprocessor regarding both
the speed and the position of the rotor.
Part No. Pairs AWG
8790 (Power Supply) 1 18
9729 2 24
9730, 89730 3 24
9728 4 24
9892 4 20
See Index for page numbers.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.31
Belden Infinity is a complete line of control, Belden Infinity Means More Product Series Descriptions
data, video, and power cables specifically Performance And Longer Life
designed to handle the rigorous speeds ● C-TC+ — The C-TC+ series is designed
and near-constant motion encountered in Reduced Cable Memory — Belden for C-track and extreme flex applications
automated equipment such as robots, pick Infinity’s unique design and neutralized up to 9 million flex cycles*. This series
and place machines, automatic handling cabling, results in cables that are relaxed, utilizes super fine stranding and some
systems, multi-axis machine tools, and with almost no memory. of the tightest lay lengths allowed by
conveyor systems. UL, providing outstanding flex life.
Greater Flex Life — Belden Infinity cables
When the application demands highly flexible offer superior flexibility and are able to handle ● FCC — The FCC series is a cost
cables offering exceptional cable life and the vigorous motions and high speeds effective alternative for C-track and
performance, specify Belden Infinity. encountered in automated equipment. moderate flexing applications rated
Greater System Uptime — Belden up to 1 million flex cycles*.
Infinity cables combine specialized ● Flex Data Cables — Belden Infinity
manufacturing techniques with precision Flex Data cables are designed for
copper stranding and rugged insulation industrial applications where precise
and jacketing compounds to maximize data transmission is combined with
flex life and reliability. high-flexing. These cables are ideal
No Talc Problems — Unlike the potentially for effective operation of computer
harmful talc used in other cables, Belden’s controlled equipment or other
non-toxic, non-irritating slipper compound automated production processes,
facilitates flexing and also complies with even in harsh environments.
OSHA regulations. It’s safer for employees ● Flex Vision — Belden Infinity Vision
and operators and is less likely to contami-
cables are continuous flex video
nate solder joints or mechanical compounds.
cables designed for machine vision
CE Conformity — All Belden Infinity applications. They are ideal for motion-
cables are CE marked per the Conformité controlled video and with inspection
Européenne low voltage directive, allowing and measurement equipment.
trade of product in Europe.
Custom Designs — Other designs
available upon request.
Application Guide
Inspection
Multi- Automated Material Pick & Automated Motion- &
C-Track Axis Assembly Handling Place Storage Gantry Machine Controlled Measure
Belden Infinity Series Systems Machining Robotics Systems Systems Systems Retrieval Systems Vision Video Equip. Festooning Servo Power
FCC
Oil & abrasion resistant
600V UL & CSA rated ● ● ● ● ● ● ● ● ● ● ●
Life Expectancy:
Over 1 million flex cycles*
C-TC+
Oil & abrasion resistant
600V UL & CSA rated ★ ★ ● ★ ★ ★ ★ ★ ★ ★ ★ ★
Life Expectancy:
Over 9 million flex cycles*
DATA
Oil & abrasion resistant
300V UL & CSA rated ● ● ● ● ● ● ● ● ● ●
Life Expectancy:
Over 1 million flex cycles*
VISION
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.32
20 AWG Stranded (74x38) Bare Copper Conductors • Unshielded • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • Orange Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7101A 3 250 † 76.2 11.0 5.0 .020 .51 .045 1.14 .275 6.99 45 200
CSA AWM Ι/ΙΙ A/B 500 † 152.4 24.5 11.1
1000 † 304.8 47.0 21.3
7102A 4 250 † 76.2 13.3 6.0 .020 .51 .045 1.14 .295 7.49 59 262
500 † 152.4 27.5 12.5
1000 † 304.8 53.0 24.1
7105A 9 250 † 76.2 29.8 13.5 .020 .51 .055 1.40 .435 11.05 130 578
500 † 152.4 52.0 23.6
1000 † 304.8 104.0 47.2
7106A 12 250 † 76.2 32.3 14.6 .020 .51 .055 1.40 .455 11.56 178 792
500 † 152.4 66.5 30.2
1000 † 304.8 134.0 60.8
7107A 18 250 † 76.2 50.0 22.7 .020 .51 .065 1.65 .545 13.84 260 1156
500 † 152.4 101.0 45.9
Temp Rating: -40° to 90°C 7108A 25 250 † 76.2 71.5 32.5 .020 .51 .080 2.03 .665 16.89 370 1645
(-5° to 90°C flexing) 500 † 152.4 143.5 65.2
20 AWG Stranded (74x38) Bare Copper Conductors • TC Braid Shield (85% Coverage) • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Orange Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7106AS 12 250 † 76.2 57.5 26.1 .020 .51 Inner: .535 13.59 194 863
CSA AWM Ι/ΙΙ A/B 500 † 152.4 116.0 52.7 .025 .64
Outer:
.055 1.40
18 AWG Stranded (114x38) Bare Copper Conductors • Unshielded • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • Orange Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7110A 3 500 † 152.4 26.0 11.8 .020 .51 .035 .89 .300 7.62 69 307
CSA AWM Ι/ΙΙ A/B 1000 † 304.8 50.0 22.7
7113A 7 250 † 76.2 29.0 13.2 .020 .51 .060 1.52 .438 11.13 155 689
500 † 152.4 55.5 25.2
1000 † 304.8 111.0 50.4
7115A 12 250 † 76.2 40.3 18.3 .020 .51 .060 1.52 .513 13.03 270 1201
500 † 152.4 84.5 38.4
7116A 18 250 † 76.2 63.0 28.6 .020 .51 .060 1.52 .598 15.19 400 1779
500 † 152.4 126.0 57.2
Temp Rating: -40° to 90°C 7117A 25 250 † 76.2 89.3 40.5 .020 .51 .083 2.11 .744 18.90 570 2535
(-5° to 90°C flexing) 500 † 152.4 179.0 81.3
18 AWG Stranded (114x38) Bare Copper Conductors • TC Braid Shield (85% Coverage) • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Orange Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7111AS 4 250 † 76.2 4.0 1.8 .020 .51 Inner: .405 10.29 84 373
CSA AWM I/II A/B 500 † 152.4 60.5 27.5 .025 .64
Outer:
.050 1.27
7115AS 12 250 † 76.2 72.8 33.1 .020 .51 Inner: .600 15.24 252 1121
500 † 152.4 144.5 65.6 .025 .64
Outer:
.065 1.65
PVC = Polyvinyl Chloride • TC = Tinned Copper
*Based on proper installation techniques in a C-track cable guide.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.33
16 AWG Stranded (190x38) Bare Copper Conductors • Unshielded • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • Orange Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7122A 3 250 † 76.2 16.3 7.4 .020 .51 .045 1.14 .325 8.26 114 507
CSA AWM Ι/ΙΙ A/B 500 † 152.4 43.5 19.8
1000 † 304.8 84.0 38.1
7125A 7 250 † 76.2 38.5 17.5 .020 .51 .060 1.52 .480 12.19 260 1156
500 † 152.4 73.5 33.4
1000 † 304.8 148.0 67.2
7126A 9 250 † 76.2 49.3 22.4 .020 .51 .060 1.52 .545 13.84 340 1512
1000 † 304.8 195.0 88.5
7127A 12 250 † 76.2 53.3 24.2 .020 .51 .060 1.52 .570 14.48 450 2001
500 † 152.4 122.5 55.6
1000 † 304.8 243.0 110.3
7128A 18 250 † 76.2 85.3 38.7 .020 .51 .060 1.52 .670 17.02 680 3025
500 † 152.4 172.0 78.1
Temp Rating: -40° to 90°C 7129A 25 250 † 76.2 124.5 56.5 .020 .51 .080 2.03 .820 20.83 950 4226
(-5° to 90°C flexing) 500 † 152.4 247.5 112.4
16 AWG Stranded (190x38) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Orange Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7123AS 4 250 † 76.2 40.8 18.5 .020 .51 Inner: .420 10.67 154 685
CSA AWM Ι/ΙΙ A/B 500 † 152.4 78.0 35.4 .025 .64
Outer:
.040 1.02
14 AWG Stranded (266x38) Bare Copper Conductors • Unshielded • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • Orange Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7136A 4 250 † 76.2 39.0 17.7 .025 .64 .050 1.27 .430 10.92 212 943
CSA AWM Ι/ΙΙ A/B 500 † 152.4 74.5 33.8
14 AWG Stranded (266x38) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Orange Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7136AS 4 250 † 76.2 74.0 33.6 .025 .64 Inner: .500 12.70 208 925
CSA AWM Ι/ΙΙ A/B 500 † 152.4 145.0 65.8 .025 .64
Outer:
.045 1.14
12 AWG Stranded (413x38) Bare Copper Conductors • Unshielded • Color Code: Red w/numbers + Green/Yellow ground
PVC Insulation • Orange Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7145A 4 250 † 76.2 72.5 32.9 .030 .76 .075 1.91 .545 13.84 274 1218
CSA AWM Ι/ΙΙ A/B 500 † 152.4 146.0 66.3
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.34
20 AWG Stranded (10x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7400A 2 250 † 76.2 11.0 5.0 .022 .56 .040 1.02 .240 6.10 26 116
CSA AWM Ι/ΙΙ A/B 500 † 152.4 25.0 11.4
1000 † 304.8 44.0 20.0
7401A 3 250 † 76.2 13.0 5.9 .022 .56 .040 1.02 .250 6.35 39 173
500 † 152.4 30.0 13.6
1000 † 304.8 59.0 26.8
7402A 4 250 † 76.2 15.0 6.8 .022 .56 .040 1.02 .275 6.99 52 231
500 † 152.4 33.0 15.0
1000 † 304.8 64.0 29.1
7403A 5 250 † 76.2 17.5 8.0 .022 .56 .040 1.02 .300 7.62 65 289
500 † 152.4 38.0 17.3
1000 † 304.8 72.0 32.7
7404A 7 250 † 76.2 22.0 10.0 .022 .56 .040 1.02 .345 8.76 91 405
500 † 152.4 44.5 20.2
1000 † 304.8 86.0 39.0
7405A 9 250 † 76.2 29.5 13.4 .022 .56 .053 1.35 .410 10.41 117 520
500 † 152.4 71.5 32.5
1000 † 304.8 144.0 65.4
7406A 12 250 † 76.2 30.8 14.0 .022 .56 .053 1.35 .420 10.67 156 693
500 † 152.4 88.5 40.2
1000 † 304.8 177.0 80.4
7407A 18 250 † 76.2 53.5 24.3 .022 .56 .053 1.35 .500 12.70 234 1041
500 † 152.4 104.0 47.2
Temp Rating: -40° to 90°C 7408A 25 250 † 76.2 65.3 29.6 .022 .56 .065 1.65 .615 15.62 325 1445
(-5° to 90°C flexing) 500 † 152.4 130.5 59.3
20 AWG Stranded (10x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7401AS 3 500 † 152.4 54.0 24.5 .022 .56 Inner: .320 8.13 45 200
CSA AWM Ι/ΙΙ A/B .025 .64
Outer:
.035 .89
7402AS 4 250 † 76.2 32.8 14.9 .022 .56 Inner: .330 8.38 52 231
500 † 152.4 64.0 29.1 .025 .64
Outer:
.035 .89
7403AS 5 250 † 76.2 34.8 15.8 .022 .56 Inner: .370 9.40 65 289
500 † 152.4 68.0 30.9 .025 .64
Outer:
.035 .89
7404AS 7 250 † 76.2 37.8 17.1 .022 .56 Inner: .420 10.67 91 405
500 † 152.4 71.5 32.5 .025 .64
Temp Rating: -40° to 90°C Outer:
(-5° to 90°C flexing) .040 1.02
BC = Bare Copper • TC = Tinned Copper
*Based on proper installation techniques in a C-track cable guide.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.35
18 AWG Stranded (16x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7409A 2 250 † 76.2 13.3 6.0 .022 .56 .040 1.02 .264 6.71 50 222
CSA AWM Ι/ΙΙ A/B 500 † 152.4 26.5 12.0
1000 † 304.8 51.0 23.2
7410A 3 250 † 76.2 16.3 7.4 .022 .56 .040 1.02 .280 7.11 74 329
500 † 152.4 25.0 11.4
1000 † 304.8 48.0 21.8
7411A 4 250 † 76.2 18.8 8.5 .022 .56 .040 1.02 .305 7.75 98 436
500 † 152.4 31.0 14.1
1000 † 304.8 58.0 26.3
7412A 5 250 † 76.2 21.8 9.9 .022 .56 .040 1.02 .330 8.38 122 542
500 † 152.4 36.0 16.3
1000 † 304.8 69.0 31.3
7413A 7 250 † 76.2 27.5 12.5 .022 .56 .040 1.02 .385 9.78 171 760
500 † 152.4 46.0 20.9
1000 † 304.8 120.0 54.5
7414A 9 250 † 76.2 36.5 16.6 .022 .56 .050 1.27 .452 11.48 220 978
500 † 152.4 87.0 39.5
1000 † 304.8 174.0 79.0
7415A 12 250 † 76.2 40.0 18.2 .022 .56 .050 1.27 .475 12.07 292 1298
500 † 152.4 75.5 34.3
1000 † 304.8 161.0 73.1
7416A 18 250 † 76.2 55.8 25.3 .022 .56 .050 1.27 .560 14.22 440 1957
500 † 152.4 112.5 51.1
7417A 25 250 † 76.2 74.3 33.7 .022 .56 .072 1.83 .696 17.68 520 2313
500 † 152.4 149.0 67.6
7418A 34 250 † 76.2 111.3 50.5 .022 .56 .072 1.83 .788 20.02 830 3692
500 † 152.4 215.5 97.8
Temp Rating: -40° to 90°C 7419A 41 500 † 152.4 295.0 133.9 .022 .56 .075 1.91 .860 21.84 1001 4453
(-5° to 90°C flexing) 7420A 50 250 † 76.2 186.5 84.7 .022 .56 .083 2.11 .940 23.88 1220 5427
18 AWG Stranded (16x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7411AS 4 250 † 76.2 29.0 13.2 .022 .56 Inner: .365 9.27 83 369
CSA AWM Ι/ΙΙ A/B 500 † 152.4 56.5 25.7 .025 .64
Outer:
.032 .81
7413AS 7 250 † 76.2 37.5 17.0 .022 .56 Inner: .450 11.43 145 645
500 † 152.4 74.0 33.6 .025 .64
Outer:
.035 .89
7415AS 12 250 † 76.2 61.5 27.9 .022 .56 Inner: .550 13.97 230 1023
500 † 152.4 124.0 56.3 .025 .64
Outer:
.045 1.14
7416AS 18 250 † 76.2 83.3 37.8 .022 .56 Inner: .650 16.51 374 1663
500 † 152.4 169.0 76.7 .025 .64
Outer:
.055 1.40
7417AS 25 250 † 76.2 113.8 51.6 .022 .56 Inner: .765 19.43 520 2313
500 † 152.4 228.0 103.5 .025 .64
Temp Rating: -40° to 90°C Outer:
(-5° to 90°C flexing) .060 1.52
BC = Bare Copper • TC = Tinned Copper
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.36
16 AWG Stranded (26x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7421A 2 250 † 76.2 15.0 6.8 .022 .56 .040 1.02 .290 7.37 70 311
CSA AWM Ι/ΙΙ A/B 500 † 152.4 35.0 15.9
1000 † 304.8 68.0 30.9
7422A 3 250 † 76.2 18.8 8.5 .022 .56 .040 1.02 .305 7.75 105 467
500 † 152.4 34.5 15.7
1000 † 304.8 65.0 29.5
7423A 4 250 † 76.2 22.5 10.2 .022 .56 .040 1.02 .330 8.38 140 623
500 † 152.4 41.5 18.8
1000 † 304.8 80.0 36.3
7424A 5 250 † 76.2 27.5 12.5 .022 .56 .040 1.02 .360 9.14 175 778
500 † 152.4 49.5 22.5
1000 † 304.8 96.0 43.6
7425A 7 250 † 76.2 35.0 15.9 .022 .56 .040 1.02 .425 10.80 236 1050
500 † 152.4 64.0 29.1
1000 † 304.8 129.0 58.6
7426A 9 250 † 76.2 50.5 22.9 .022 .56 .060 1.52 .540 13.72 304 1352
500 † 152.4 95.0 43.1
1000 † 304.8 190.0 86.3
7427A 12 250 † 76.2 55.3 25.1 .022 .56 .065 1.65 .565 14.35 405 1801
500 † 152.4 114.0 51.8
1000 † 304.8 220.0 100.0
7428A 18 250 † 76.2 79.0 35.9 .022 .56 .065 1.65 .650 16.51 608 2705
500 † 152.4 158.0 71.7
7429A 25 250 † 76.2 109.0 49.5 .022 .56 .060 1.52 .750 19.05 875 3892
500 † 152.4 218.5 99.2
Temp Rating: -40° to 90°C 7430A 34 250 † 76.2 171.3 77.7 .022 .56 .075 1.91 .878 22.30 1145 5093
(-5° to 90°C flexing)
16 AWG Stranded (26x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7423AS 4 250 † 76.2 36.0 16.3 .022 .56 Inner: .400 10.16 140 623
CSA AWM Ι/ΙΙ A/B 500 † 152.4 68.0 30.9 .025 .64
Outer:
.035 .89
7427AS 12 250 † 76.2 81.8 37.1 .022 .56 Inner: .630 16.00 420 1868
500 † 152.4 164.5 74.7 .025 .64
Outer:
.060 1.52
7428AS 18 250 † 76.2 119.0 54.1 .022 .56 Inner: .740 18.80 630 2802
500 † 152.4 238.5 108.3 .025 .64
Temp Rating: -40° to 90°C Outer:
(-5° to 90°C flexing) .070 1.78
BC = Bare Copper • TC = Tinned Copper
*Based on proper installation techniques in a C-track cable guide.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.37
14 AWG Stranded (41x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7434A 2 250 † 76.2 34.0 15.5 .023 .58 .045 1.14 .335 8.51 201 894
CSA AWM Ι/ΙΙ A/B 500 † 152.4 66.5 30.2
1000 † 304.8 92.0 41.8
7435A 3 250 † 76.2 39.8 18.1 .023 .58 .045 1.14 .350 8.89 201 894
500 † 152.4 78.5 35.6
1000 † 304.8 98.0 44.5
7436A 4 250 † 76.2 49.3 22.4 .023 .58 .050 1.27 .395 10.03 201 894
500 † 152.4 95.0 43.1
1000 † 304.8 131.0 59.5
7438A 7 500 † 152.4 150.5 68.3 .023 .58 .060 1.52 .525 13.33 373 1659
7439A 9 250 † 76.2 110.8 50.3 .023 .58 .070 1.78 .620 15.75 480 2135
500 † 152.4 223.0 101.2
7440A 12 250 † 76.2 142.5 64.7 .023 .58 .075 1.91 .660 16.76 640 2847
500 † 152.4 285.5 129.6
Temp Rating: -40° to 90°C 7442A 25 250 † 76.2 223.8 101.7 .023 .58 .090 2.29 .930 23.62 1337 5947
(-5° to 90°C flexing)
14 AWG Stranded (41x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7436AS 4 250 † 76.2 49.3 22.4 .023 .58 Inner: .482 12.24 212 943
CSA AWM Ι/ΙΙ A/B 500 † 152.4 95.0 43.1 .025 .64
Outer:
.055 1.40
7438AS 7 250 † 76.2 74.8 33.9 .023 .58 Inner: .563 14.30 371 1650
500 † 152.4 150.5 68.3 .025 .64
Temp Rating: -40° to 90°C Outer:
(-5° to 90°C flexing) .060 1.52
12 AWG Stranded (65x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7444A 3 250 † 76.2 53.5 24.3 .028 .71 .060 1.52 .450 11.43 253 1125
CSA AWM Ι/ΙΙ A/B 500 † 152.4 103.5 47.0
7445A 4 250 † 76.2 63.5 28.8 .028 .71 .070 1.78 .505 12.83 338 1503
500 † 152.4 124.0 56.3
12 AWG Stranded (65x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7445AS 4 250 † 76.2 85.8 38.9 .028 .71 Inner: .580 14.73 338 1503
CSA AWM Ι/ΙΙ A/B 500 † 152.4 171.5 77.9 .030 .76
Outer:
.070 1.78
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.38
10 AWG Stranded (105x30) Bare Copper Conductors • Unshielded (Color Code: Black w/numbers + Green/Yellow ground)
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7447A 4 250 † 76.2 70.8 32.1 .030 .76 .070 1.78 .570 14.48 672 2989
CSA AWM Ι/ΙΙ A/B 500 † 152.4 142.5 64.7
10 AWG Stranded (105x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7447AS 4 250 † 76.2 92.8 42.2 .030 .76 Inner: .660 16.76 546 2429
CSA AWM Ι/ΙΙ A/B 500 † 152.4 185.5 84.3 .035 .89
Outer:
.065 1.65
8 AWG Stranded (168x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7450A 4 250 † 76.2 113.8 51.6 .045 1.14 .070 1.78 .715 18.16 920 4092
CSA AWM Ι/ΙΙ A/B 500 † 152.4 228.0 103.5
8 AWG Stranded (168x30) BC Conductors • TC Braid Shield (85% Coverage) • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • PVC Inner Jacket • Gray Oil- and Abrasion-resistant PVC Outer Jacket
UL AWM Style 2587 (600V 90°C) 7450AS 4 250 † 76.2 141.3 64.1 .045 1.14 Inner: .815 20.70 872 3879
CSA AWM Ι/ΙΙ A/B 500 † 152.4 281.0 127.6 .040 1.02
Outer:
.065 1.65
6 AWG Stranded (266x30) Bare Copper Conductors • Unshielded • Color Code: Black w/numbers + Green/Yellow ground
PVC Insulation • Gray Oil- and Abrasion-resistant PVC Jacket
UL AWM Style 2587 (600V 90°C) 7453A 4 250 † 76.2 185.0 84.0 .060 1.52 .085 2.16 .925 23.50 1472 6548
CSA AWM Ι/ΙΙ A/B
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.39
Flex Data • 24 AWG Stranded (41x40) BC Condrs. • Twisted Pairs • Overall Beldfoil® (100% Coverage) + TC Braid Shield (85% Coverage)**
Foam Polyethylene Insulation with Skin • Green Oil-resistant PVC Jacket
300V 60°C 7200A 1 NEC: 232 White, 500 152.4 17.0 7.7 .240 6.10 15.0 49.2 120
CM 485 Blue 1000 304.8 38.0 17.3
CEC:
CM
7201A 2 NEC: 232 See 500 152.4 31.0 14.1 .322 8.18 15.0 49.2 120
CM 485 Color Code 1000 304.8 60.0 27.2
CEC: Chart
CM (below)
7202A 3 NEC: 232 See 500 152.4 33.5 15.2 .347 8.81 15.0 49.2 120
CM 485 Color Code 1000 304.8 68.0 30.9
CEC: Chart
CM (below)
7203A 4 NEC: 232 See 500 152.4 39.0 17.7 .362 9.20 15.0 49.2 120
CM 485 Color Code 1000 304.8 79.0 35.9
CEC: Chart
CM (below)
7205A 1 NEC: 232 White, 500 152.4 17.5 7.9 .232 5.89 14.0 45.9 100
CM 422 Blue 1000 304.8 38.0 17.3
CEC:
CM
7206A 1 NEC: 232 White, 1000 304.8 59.0 26.8 .302 7.67 10.0 32.8 150
CM 485 Blue
Temp Rating: -20° to 60°C CEC:
(-5° to 60°C flexing) CM
BC = Bare Copper • TC = Tinned Copper
*Based on proper installation techniques in a C-track cable guide.
**24 AWG stranded (41x40) tinned copper drain wire.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.40
Sub-Mini Type • 30 AWG Stranded (7x38) Tinned Cadmium Bronze Conductor • Tinned Copper “French Braid” Shield (95% Coverage)
Foam Polyethylene Insulation • Matte Blue Belflex® Jacket
UL AWM 7500A CEC: 250 † 76.2 3.0 1.4 108.0Ω/M′ 13.3Ω/M′ .056 1.42 .110 2.79 75 78% 16.7 54.8 2.2 .9 2.95
Style 1354 FT1 500 † 152.4 5.0 2.3 354.3Ω/km 43.6Ω/km 5 1.4 4.59
30V 80°C 1000 † 304.8 9.0 4.1 10 2.0 6.56
CSA AWM Ι/ΙΙ A/B 30 3.4 11.16
50 4.4 14.44
100 6.4 21.00
Mini Type • 25 AWG Stranded (19x38) Bare Copper Conductor • Tinned Copper “French Braid” Shield (95% Coverage)
Foam Polyethylene Insulation • Matte Blue Belflex Jacket
UL AWM 7501A CEC: 500 † 152.4 7.5 3.4 35.0Ω/M′ 9.1Ω/M′ .090 2.29 .146 3.71 75 77% 17.7 58.1 2.2 .6 1.97
Style 1354 FT1 1000 † 304.8 14.0 6.4 114.8Ω/km 29.9Ω/km 5 .9 2.95
30V 80°C 10 1.3 4.27
CSA AWM Ι/ΙΙ A/B 30 2.2 7.22
50 2.9 9.52
100 4.2 13.78
RG-59 Type • 22 AWG Stranded (19x34) Bare Copper Conductor • Tinned Copper “French Braid” Shield (95% Coverage)
Foam Polyethylene Insulation • Matte Blue Belflex Jacket
UL AWM 7502A CEC: 250 † 76.2 10.5 4.8 13.4Ω/M′ 6.4Ω/M′ .146 3.71 .242 6.15 75 79% 18.0 59.1 2.2 .4 1.31
Style 1354 FT1 500 † 152.4 15.0 6.8 44.0Ω/km 21.0Ω/km 5 .5 1.64
30V 80°C 1000 † 304.8 34.0 15.4 10 .8 2.63
CSA AWM Ι/ΙΙ A/B 30 1.4 4.59
50 1.8 5.91
100 2.7 8.86
RG-6/U Type • 20 AWG Stranded (7x15x40) Bare Copper Conductor • Tinned Copper “French Braid” Shield (95% Coverage)
Foam Polyethylene Insulation • Matte Blue Belflex Jacket
UL AWM 7503A CEC: 250 † 76.2 12.0 5.5 8.1Ω/M′ 11.0Ω/M′ .185 4.70 .275 6.99 75 80% 17.3 56.8 2.2 .3 0.98
Style 1354 FT1 500 † 152.4 18.0 8.2 26.6Ω/km 36.1Ω/km 5 .4 1.31
30V 80°C 1000 † 304.8 40.0 18.2 10 .6 1.97
CSA AWM Ι/ΙΙ A/B 30 1.1 3.61
50 1.5 4.92
100 2.2 7.22
RG-11 Type • 16 AWG Stranded (7x37x40) Bare Copper Conductor • Tinned Copper “French Braid” Shield (95% Coverage)
Foam Polyethylene Insulation • Matte Blue Belflex Jacket
UL AWM 7504A CEC: 1000 † 304.8 84.0 38.1 3.5Ω/M′ 3.6Ω/M′ .285 7.24 .405 10.29 75 81% 17.3 56.8 2.2 .2 0.66
Style 1354 FT1 11.5Ω/km 11.8Ω/km 5 .3 0.98
30V 80°C 10 .4 1.31
CSA AWM Ι/ΙΙ A/B 30 .8 2.63
50 1.0 3.28
100 1.5 4.92
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.41
UL Instrumentation Cable
300V Power-Limited Tray Cables — Overview
Soft annealed bare or tinned copper with Cable jackets are resistant to sunlight, ● UL Subject 13
PVC flame retardant insulation and jacket. moisture and vapor penetration. PVC/PVC
● UL Subject 2250
Other insulation and jacket options are constructions, with 3 conductors or more
available (see table below). Communication and 20 AWG or larger, are suitable for ● NEC Article 725 Class 2 and
wire included on all multi-pair/multi-triad direct burial. Class 3 Circuits
1000 and 3000 series part numbers, 22 AWG ● NEC Type PLTC Listed, which is
(7x30) bare copper, orange PVC insulation. Unshielded
approved for cable tray use in Class 1,
Nylon rip cord included in all PVC/PVC Twisted non-shielded pairs and triads Division 2, hazardous areas and
instrumentation cables. provide a minimal OD allowing greater tray non-hazardous areas, cable trays,
and conduit fill. Non-shielded instrument raceways, conduit and supported
Other Construction Options: pairs may be utilized when recommended by messenger wires.
by the instrument manufacturer and used
● Sunlight-resistant.
UL Listed for PLTC in a metallic conduit.
● Oil-resistant per UL Class 43
Insulation/Jacket Max. Temp Rating Overall Shield
● NEC Type ITC per Article 727.
XLPE/PVC 90°C Recommended for use in instrumentation ITC cables may carry up to 5 amps
XLPE/CPE 90°C applications where signals are transmitted at 150V, which is significantly greater
PVC/PVC 105°C in excess of 100 millivolts except in areas than that allowed for PLTC only cables.
PVC/CPE 105°C
where high voltage and current sources ITC cables may also be installed in
create excessive noise interference. specific applications, per the NEC,
PE/PVC 75°C
The Beldfoil® shield with drain wire in addition to those allowed for PLTC.
FPE/PVC 75°C
provides 100% coverage for maximum
TPE/TPE 105°C ● UL 1685 (UL 1581) Vertical Tray Flame
shield effectiveness.
XLPE/Haloarrest® 90°C Test comparable to IEEE 383-1974
Individually Shielded and (70,000 BTU/hr.) Flame Test.
Overall Shielded ● PVC/PVC constructions are CMG, FT4,
Armoring Capabilities
Individually shielded pairs or triads with IEEE 1202 and IEEE 383-2003 rated,
an overall shield are recommended for and meet ICEA T-29-520 Flame Test.
Belden also has the capability to protect
electronic, instrumentation and control cables use in instrumentation applications where ● Design options — call 1-800-BELDEN-1
with interlocking or continuous armor and optimum noise rejection is required. or 1-800-BELDEN-3.
smooth or corrugated protective metal tapes. Individual pair/triad shields are fully isolated
from each other and contain a separate PLTC-ER
drain wire for grounding, to provide
To Specify Part Number As an option, Belden offers all PVC insulated,
maximum protection from crosstalk and
1 2 3456 common mode interference. Cables with PVC jacketed instrumentation cables, and
Overall Armor Core
an overall shield provide additional several other insulation and jackets, with a
Jacket Type Trade
Type Number
electrostatic noise protection. PLTC-ER (Exposed Run) rating, formerly
referred to as Open Wiring.
Overall Jacket
Per NEC Article 725, a PLTC-ER rated cable
Code Material may be installed in an industrial establish-
1 PVC ment between a cable tray and the utilization
3 CPE equipment or device. A PLTC-ER rated cable
4 TPE must meet the crush and impact require-
5 HDPE ments of UL Type MC cable By eliminating
6 Oil Res II the need for metal conduit and/or armor,
7 Haloarrest® I using a PLTC-ER rated cable results in
Armor
savings in both installation and maintenance.
Code Material
2 Aluminum Interlock
3 Steel Interlock
8 Continuously Corrugated Aluminum
18 • Industrial Cables
Standard lengths may be subject to tolerance. Custom lengths may be available upon
request. Contact the Belden Electronics Division Customer Service Department for
additional information. 1-800-BELDEN-1 or 1-800-BELDEN-3.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.42
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9322 1 E2 U-500 U-152.4 11.0 5.0 .037 .94 .201 5.10 28 124 2.00 50.80
CEC: CMG FT4 U-1000 U-304.8 22.0 10.0
IEEE 1202/383
ICEA T-29-520 9512 2 E2 500 152.4 22.0 10.0 .042 1.07 .310 7.82 46 204 3.00 76.20
1000 304.8 42.0 19.1
Drain Wire 9513 3 E2 500 152.4 26.5 11.6 .042 1.07 .324 8.23 63 280 3.25 82.55
1000 304.8 51.0 23.2
9514 4 E2 500 152.4 33.0 14.8 .042 1.07 .356 9.04 80 355 3.50 88.90
1000 304.8 67.0 30.5
9516 6 E2 500 152.4 45.0 20.4 .053 1.35 .418 10.62 118 524 4.25 107.95
1000 304.8 89.0 40.4
9520 9 E2 500 152.4 64.5 29.3 .053 1.35 .482 12.29 172 765 4.75 120.65
Rip Cord
1000 304.8 121.0 55.0
9521 11 E2 500 152.4 73.0 32.7 .053 1.35 .506 12.85 200 889 5.35 135.89
1000 304.8 147.0 66.4
9524 15 E2 500 152.4 89.5 40.7 .053 1.35 .594 15.09 280 1245 6.00 152.40
1000 304.8 178.0 80.9
9526 19 E2 500 152.4 114.5 52.0 .063 1.60 .644 16.36 350 1557 6.33 160.78
1000 304.8 224.0 101.8
9527 27 E2 500 152.4 156.5 71.1 .063 1.60 .763 19.38 500 2224 7.50 190.50
1000 † 304.8 321.0 145.9
Rip Cord
Communication Wire
†
Final put-up length may vary ±10% from length shown.
††
Bulk = Check length available for specific construction.
E1, E2 = Refer to Industrial Technical Information section for color code.
Alternate color coding available upon request.
Multiple pair or triad cables have each pair/triad numbered for ease of identification.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.43
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9363 1 E1 U-500 U-152.4 13.5 6.1 .037 .94 .208 5.28 29 129 2.00 50.80
CEC: CMG FT4 U-1000 U-304.8 26.0 11.8
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Rip Cord
Communication
Drain Wires Wire
*For tinned copper conductors, order with B suffix. E1, E2 = Refer to Technical Information section for color code. Alternate color coding available upon request.
†
For Exposed Run rated 3000 series cables, order with “E” suffix, e.g. 3001AE. Multiple pair or triad cables have each pair/triad numbered for ease of identification.
††
Bulk = Check length available for specific construction.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.44
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9320 1 E2 U-500 U-152.4 14.5 6.6 .037 .94 .217 5.51 40 178 2.00 50.80
CEC: CMG FT4 U-1000 U-304.8 28.0 12.7
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.45
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9364 1 E1 U-500 U-152.4 17.0 7.7 .037 .94 .228 5.79 46 205 2.25 57.15
CEC: CMG FT4 U-1000 U-304.8 32.0 14.5
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Drain Wire 3024A 24 E1 Bulk †† Bulk — — .074 1.88 1.031 26.19 920 4093 9.25 234.95
Communication Wire
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Black PVC Jacket (Other options below)
NEC: PLTC, ITC, CMG 3018A 2 E1 Bulk †† Bulk — — .055 1.40 .372 9.45 102 454 3.75 95.25
CEC: CMG FT4
IEEE 1202/383 1083A 4 E1 10000 † 3048.0 1410.8 640.9 .053 1.35 .451 11.46 228 1014 4.50 114.30
ICEA T-29-520
1084A 8 E1 7500 † 2286.0 1755.0 796.1 .064 1.63 .575 10.81 432 1922 5.75 146.05
1085A 12 E1 5000 † 1524.0 1735.0 787.0 .064 1.63 .714 18.14 636 2829 7.15 181.61
1092A 16 E1 Bulk †† Bulk — — .064 1.63 .793 20.14 841 3741 7.90 200.66
1086A 24 E1 2500 † 762.0 1602.5 726.9 .074 1.88 .992 25.20 1250 5561 9.90 251.46
Rip Cord
3067A 36 E1 Bulk †† Bulk — — .074 1.88 1.292 32.82 1875 6273 13.00 330.20
Drain Wires
Communication Wire
†
Final put-up length may vary ±10% from length shown.
††
Bulk = Check length available for specific construction.
E1 = Refer to Technical Information section for color code.
Alternate color coding available upon request.
Multiple pair or triad cables have each pair/triad numbered for ease of identification.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.46
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9318 1 E2 U-500 U-152.4 17.5 7.9 .037 .94 .233 5.92 60 267 2.25 57.15
CEC: CMG FT4 U-1000 U-304.8 33.0 15.0
IEEE 1202/383
ICEA T-29-520 9552 2 E2 500 152.4 35.5 16.1 .042 1.07 .368 9.34 65 289 3.70 93.98
1000 304.8 69.0 31.4
Drain Wire
9553 3 E2 500 152.4 49.5 22.0 .053 1.35 .411 10.44 145 645 4.10 104.14
1000 304.8 98.0 49.4
9554 4 E2 500 152.4 57.0 25.8 .053 1.35 .447 11.35 187 832 4.50 114.30
1000 304.8 112.0 50.8
9556 6 E2 500 152.4 78.5 35.7 .053 1.35 .497 12.62 270 1201 5.00 127.00
Rip Cord
1000 304.8 153.0 69.5
9559 9 E2 500 152.4 108.0 49.0 .053 1.35 .579 14.71 395 1757 5.80 147.32
1000 304.8 215.0 97.6
9563 11 E2 500 152.4 133.0 60.4 .063 1.60 .665 16.89 478 2126 6.75 171.45
1000 304.8 270.0 122.5
9565 15 E2 500 152.4 169.0 76.8 .063 1.60 .739 18.77 640 2847 7.50 190.50
1000 304.8 342.0 155.5
Individually Shielded (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9368 2 E2 500 152.4 37.5 17.0 .042 1.07 .378 9.60 125 556 3.75 95.25
CEC: CMG FT4 1000 304.8 73.0 33.2
IEEE 1202/383
ICEA T-29-520 9369 3 E2 500 152.4 55.0 25.0 .053 1.35 .423 10.74 220 979 4.25 107.95
1000 304.8 109.0 49.5
3029A 4 E1 Bulk † Bulk — — .053 1.35 .461 11.71 296 1317 4.50 114.30
9388 4 E2 500 152.4 71.5 32.5 .053 1.35 .461 11.71 296 1317 4.60 116.84
1000 304.8 135.0 61.4
Rip Cord
9389 6 E2 500 152.4 97.0 44.1 .053 1.35 .538 13.67 440 1957 5.25 133.35
Drain Wire 1000 304.8 190.0 86.4
9390 9 E2 500 152.4 137.5 63.0 .064 1.63 .652 16.56 666 2963 6.50 165.10
1000 304.8 270.0 123.6
9391 11 E2 500 152.4 158.5 72.0 .064 1.63 .729 18.52 815 3626 7.25 184.15
1000 304.8 321.0 145.9
9392 15 E2 500 152.4 209.0 95.0 .064 1.63 .808 20.52 1100 4893 8.00 203.20
1000 304.8 428.0 194.5
E1, E2 = Refer to Technical Information section for color code.
Alternate color coding available upon request.
Multiple pair or triad cables have each pair/triad numbered for ease of identification.
†
Bulk = Check length available for specific construction.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.47
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
1480A 24 E1 2500 † 762.0 1712.5 777.5 .074 1.88 1.019 25.88 1443 6419 10.25 260.35
5000 † 1524.0 3390.0 1539.1
Drain Wires
Communication Wire 1481A 36 E1 Bulk †† Bulk — — .074 1.88 1.163 29.54 2148 9556 11.75 298.45
3042A 50 E1 Bulk †† Bulk — — .084 2.13 1.389 35.28 2935 13057 14.00 355.60
E1 = Refer to Technical Information section for color code.
Alternate color coding available upon request.
Multiple pair or triad cables have each pair/triad numbered for ease of identification.
†
Final put-up length may vary ±10% from length shown.
††
Bulk = Check length available for specific construction.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.48
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9365 1 E1 U-500 U-152.4 22.0 10.0 .037 .94 .245 6.22 74 329 2.50 63.50
CEC: CMG FT4 U-1000 U-304.8 43.0 19.5
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Individually Shielded + Overall Beldfoil (100% Coverage) • PVC Insulation • Black PVC Jacket (Other options below)
NEC: PLTC, ITC, CMG 3028A 2 E1 Bulk †† Bulk — — .055 1.40 .450 11.43 175 779 4.50 114.30
CEC: CMG FT4
IEEE 1202/383 3031A 4 E1 Bulk †† Bulk — — .053 1.35 .533 13.50 255 1134 5.25 133.35
ICEA T-29-520
3033A 8 E1 Bulk †† Bulk — — .064 1.63 .654 16.50 560 2491 6.50 165.10
3068A 12 E1 Bulk †† Bulk — — .063 1.60 .840 21.30 800 3559 8.50 215.90
3037A 16 E1 Bulk †† Bulk — — .074 1.88 .974 24.70 1320 5872 10.50 266.70
3039A 24 E1 Bulk †† Bulk — — .074 1.88 1.200 30.50 1620 7207 11.25 285.75
Rip Cord
Drain Wires
Communication Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.49
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9316 1 E2 U-500 U-152.4 21.5 9.8 .037 .94 .256 6.50 90 400 2.50 63.50
CEC: CMG FT4 U-1000 U-304.8 41.0 18.6
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Rip Cord
Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Black PVC Jacket (See chart below for other options)
NEC: PLTC, ITC, CMG 1030A 1 E1 1000 304.8 46.0 20.9 .037 .94 .257 6.53 94 418 2.50 63.50
CEC: CMG FT4 10000 † 3048.0 480.0 217.7
IEEE 1202/383
ICEA T-29-520 3043A 2 E1 Bulk †† Bulk — — .053 1.35 .437 11.10 83 369 4.50 114.30
Drain Wire 1528A 3 E1 7500 † 2286.0 967.5 438.9 .053 1.35 .457 11.61 250 1112 4.75 120.65
1484A 4 E1 7500 † 2286.0 1200.0 544.8 .053 1.35 .495 12.57 330 1468 5.00 127.00
1485A 8 E1 7500 † 2286.0 2010.0 911.7 .053 1.35 .597 15.16 616 2740 6.00 152.40
1486A 12 E1 5000 † 1524.0 1965.0 892.1 .064 1.63 .741 18.80 892 3968 7.50 190.50
3050A 16 E1 Bulk †† Bulk — — .064 1.63 .831 21.10 661 2940 8.50 215.90
Rip Cord 1489A 24 E1 1250 † 381.0 923.8 419.4 .074 1.88 1.032 26.20 1749 7780 10.50 266.70
1490A 36 E1 1250 † 381.0 1313.8 596.4 .074 1.88 1.178 29.80 2606 11592 11.75 298.45
Communication Wire
3056A 50 E1 Bulk †† Bulk — — .088 2.24 1.550 39.37 3615 16082 15.50 393.70
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Black PVC Jacket (Options below)
NEC: PLTC, ITC, CMG 1492A 2 E1 7500 † 2286.0 885.0 401.8 .053 1.35 .450 11.43 232 1032 4.50 114.30
CEC: CMG FT4
IEEE 1202/383 1493A 4 E1 7500 † 2286.0 1387.5 629.4 .055 1.40 .512 13.11 420 1868 5.00 127.00
ICEA T-29-520
1494A 8 E1 5000 † 1524.0 1640.0 743.9 .066 1.68 .687 17.50 795 3537 7.00 177.80
1495A 12 E1 2500 † 762.0 1202.5 545.5 .066 1.68 .822 20.73 1170 5205 8.25 209.55
3051A 16 E1 Bulk †† Bulk — — .074 1.88 .936 23.77 661 2940 10.00 254.00
1498A 24 E1 5000 † 1524.0 4340.0 1968.6 .074 1.88 1.149 29.18 2296 10214 11.50 292.10
Rip Cord
Drain Wires 1499A 36 E1 Bulk †† Bulk — — .084 2.13 1.334 33.88 3167 14088 13.50 342.90
Communication Wire 3057A 50 E1 Bulk †† Bulk — — .088 2.24 1.600 40.64 2066 9190 16.00 406.40
E1, E2 = Refer to Technical Information section for color code.
Alternate color coding available upon request.
18 • Industrial Cables
Multiple pair or triad cables have each pair/triad numbered for ease of identification. Conductor, Insulation and Jacket Options**
†
Final put-up length may vary ±10% from length shown.
††
Bulk = Check length available for specific construction. To Specify: Bare Tinned Insulation/Jacket
1234 A E A B PVC/PVC
Start Add or Add for C D XLPE/PVC
with replace Exposed
Part letter code Run rating K L TPE/TPE
No. for desired if desired
conductor, Q R XLPE/CPE
insulation & jacket
S T XLPE/Haloarrest®
**For 1000 and 3000 Series cables only.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.50
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage)• PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CMG 9366 1 E1 U-500 U-152.4 27.5 12.5 .037 .94 .270 6.86 116 516 2.75 69.85
CEC: CMG FT4 U-1000 U-304.8 54.0 24.5
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Rip Cord
Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Black PVC Jacket (See chart below for other options)
NEC: PLTC, ITC, CMG 1031A 1 E1 1000 304.8 58.0 26.4 .037 .94 .271 6.88 130 578 2.75 69.85
CEC: CMG FT4 10000 † 3048.0 610.0 276.7
IEEE 1202/383
ICEA T-29-520 3044A 2 E1 Bulk †† Bulk — — .053 1.35 .483 12.27 259 1152 4.75 120.65
3046A 4 E1 Bulk †† Bulk — — .053 1.35 .570 14.40 473 2104 5.75 146.05
3048A 8 E1 Bulk †† Bulk — — .063 1.60 .760 19.30 902 4013 7.50 190.50
3052A 16 E1 Bulk †† Bulk — — .074 1.88 1.032 26.21 1758 7821 11.25 285.75
Rip Cord
3054A 24 E1 Bulk †† Bulk — — .074 1.88 1.180 29.90 2615 11633 11.75 298.45
Drain Wire
Communication Wire
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Black PVC Jacket (Options below)
NEC: PLTC, ITC, CMG 3045A 2 E1 Bulk †† Bulk — — .053 1.35 .506 12.80 304 1352 5.00 127.00
CEC: CMG FT4
IEEE 1202/383 3047A 4 E1 Bulk †† Bulk — — .053 1.35 .569 14.45 563 2505 6.00 152.40
ICEA T-29-520
3049A 8 E1 Bulk †† Bulk — — .064 1.63 .764 19.41 1081 4809 8.00 203.20
3069A 12 E1 Bulk †† Bulk — — .074 1.88 .998 25.35 1500 6673 10.00 254.00
3053A 16 E1 Bulk †† Bulk — — .074 1.88 1.150 29.20 2117 9418 11.50 292.10
3055A 24 E1 Bulk †† Bulk — — .084 2.13 1.320 33.53 3153 14026 13.25 336.55
Rip Cord
Drain Wires
Communication Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.51
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CL3R 9314 1 E2 U-500 U-152.4 32.5 14.7 .042 1.07 .324 8.23 140 623 3.25 82.55
CEC: FT4 1000 304.8 66.0 29.9
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Rip Cord
Overall Beldfoil Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CL3R 9367 1 E1 500 152.4 43.5 19.7 .042 1.07 .343 8.71 188 836 3.50 88.90
CEC: FT4 1000 304.8 88.0 40.0
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.52
UL Instrumentation Cable
300V Power-Limited Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • Chrome PVC Jacket
NEC: PLTC, ITC, CL3R 9312 1 E2 500 152.4 49.0 22.3 .042 1.07 .373 9.47 225 1001 4.25 107.95
CEC: FT4 1000 304.8 96.0 43.6
IEEE 1202/383
ICEA T-29-520
Rip Cord
Drain Wire
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.53
UL Instrumentation Cable
Thermocouple Extension Cables and Thermocouple Wire — Overview
*The Temperature Range and Limits of Error are for standard grade thermocouples, Reference ANSI MC96.1-1982 for special grade thermocouples.
The Temperature Ranges for type E, J, K and T thermocouple wires listed above pertain to 20 AWG wire.
Additional constructions available upon request.
Standard lengths may be subject to tolerance. Custom lengths may be available upon
request. Contact the Belden Electronics Division Customer Service Department for
additional information. 1-800-BELDEN-1
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.54
UL Instrumentation Cable
Thermocouple Extension Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
20 AWG Pairs Solid Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Overall Beldfoil® Shield (100% Coverage) • PVC Insulation • PVC Jacket
300V 105°C 3111A JX 1 White, Red Black 5000 † 1524.0 115.0 52.2 .016 .41 .206 5.23
NEC: PLTC, ITC, CMG
CEC: CMG FT4 3112A KX 1 Yellow, Red Yellow 5000 † 1524.0 120.0 54.5 .016 .41 .206 5.23
ICEA T-29-520
IEEE 1202/383 3113A TX 1 Blue, Red Blue 5000 † 1524.0 115.0 52.2 .016 .41 .206 5.23
Rip Cord
Drain Wire
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC Insulation • PVC Jacket
300V 105°C 3115A JX 2 White, Red Black 5000 † 1524.0 315.0 143.0 .016 .41 .332 8.43
NEC: PLTC, ITC, CMG
CEC: CMG FT4 1006A JX 4 White, Red Black 5000 † 1524.0 480.0 217.9 .016 .41 .383 9.73
ICEA T-29-520
IEEE 1202/383 1012A KX 4 Yellow, Red Yellow 5000 † 1524.0 530.0 240.6 .016 .41 .383 9.73
1013A KX 8 Yellow, Red Yellow 5000 † 1524.0 825.0 374.6 .016 .41 .503 12.78
1014A KX 12 Yellow, Red Yellow 5000 † 1524.0 1195.0 542.5 .016 .41 .603 15.32
Rip Cord
Drain Wires
Communication Wire
16 AWG Pairs Solid Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Overall Beldfoil Shield (100% Coverage) • PVC Insulation • PVC Jacket
300V 105°C 1101A EX 1 Purple, Red Purple 10000 † 3048.0 450.0 204.3 .017 .43 .248 6.30
NEC: PLTC, ITC, CMG
CEC: CMG FT4 1000A JX 1 White, Red Black 1000 304.8 42.0 19.1 .017 .43 .248 6.30
ICEA T-29-520 10000 † 3048.0 420.0 190.7
IEEE 1202/383
1018A KX 1 Yellow, Red Yellow 1000 304.8 42.0 19.1 .017 .43 .248 6.30
10000 † 3048.0 420.0 190.7
1023A TX 1 Blue, Red Blue 10000 † 3048.0 450.0 204.3 .017 .43 .248 6.30
Rip Cord
Drain Wire
Multiple pair cables have each pair numbered for ease of identification.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.55
UL Instrumentation Cable
High-Temperature Thermocouple Extension Cables and Thermocouple Wire
Industrial Grade Sunlight- and Oil-Resistant Jackets
High-Temp Extension Cable • 20 AWG Solid Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Plenum • Unshielded • FEP Insulation • FEP Jacket
300V 200°C 83932 KX 2/c Yellow, Red Yellow 500 † 152.4 6.5 3.0 .010 .25 .076 1.93
NEC: PLTC, CL3P 1000 † 304.8 12.0 5.4 x x
.128 3.25
83934 TX 2/c Blue, Red Blue 1000 † 304.8 13.0 6.0 .010 .25 .076 1.93
x x
.128 3.25
High-Temp Extension Cable • 20 AWG Stranded (7x28) Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Plenum • Unshielded • FEP Insulation • FEP Jacket
300V 200°C 83930 JX 2/c White, Red Black 500 † 152.4 7.5 3.4 .010 .25 .082 2.08
NEC: PLTC, CL3P 1000 † 304.8 13.0 6.0 x x
.140 3.56
Plenum • Overall Beldfoil® Shield (100% Coverage) • FEP Insulation • FEP Jacket
300V 200°C 83955 EX 1 pr. Purple, Red Purple 500 † 152.4 9.0 4.1 .010 .25 .145 3.68
NEC: PLTC, CL3P 1000 † 304.8 16.0 7.3
83950 JX 1 pr. White, Red Black 500 † 152.4 9.5 4.3 .010 .25 .145 3.68
1000 † 304.8 16.0 7.3
83952 KX 1 pr. Yellow, Red Yellow 500 † 152.4 9.5 4.3 .010 .25 .145 3.68
Drain Wire
1000 † 304.8 16.0 7.3
83954 TX 1 pr. Blue, Red Blue 500 † 152.4 9.0 4.1 .010 .25 .145 3.68
1000 † 304.8 17.0 7.7
High-Temp Extension Cable • 16 AWG Pairs Solid Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Plenum • Overall Beldfoil Shield (100% Coverage) • FEP Insulation • FEP Jacket
300V 200°C 1114A EX 1 Purple, Red Purple 5000 † 1524.0 160.0 72.6 .010 .25 .172 4.37
NEC: PLTC, CL3P 1115A JX 1 White, Red Black 5000 † 1524.0 155.0 70.4 .010 .25 .172 4.37
1116A KX 1 Yellow, Red Yellow 5000 † 1524.0 160.0 72.6 .010 .25 .171 4.34
Drain Wire
1117A TX 1 Blue, Red Blue 5000 † 1524.0 160.0 72.6 .010 .25 .172 4.37
High-Temp Extension Cable • 16 AWG Pairs Stranded (7x24) Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Plenum • Overall Beldfoil Shield (100% Coverage) • FEP Insulation • FEP Jacket
300V 200°C 83951 JX 1 White, Red Black 500 † 152.4 16.0 7.3 .010 .25 .189 4.80
NEC: PLTC, CL3P 1000 † 304.8 35.0 15.9
83953 KX 1 Yellow, Red Yellow 500 † 152.4 16.0 7.3 .010 .25 .187 4.75
1000 † 304.8 32.0 14.5
Drain Wire
High-Temp Thermocouple Wire • 20 AWG Solid Conductors • (See chart on page 18.53 for conductor specifications by ANSI Type)
Plenum • Unshielded • FEP Insulation • FEP Jacket
300V 200°C 83915 E 2/c Purple, Red Brown 500 † 152.4 7.0 3.2 .010 .25 .076 1.93
NEC: PLTC, CL3P 1000 † 304.8 13.0 6.0 x x
.128 3.25
83900 J 2/c White, Red Brown 100 30.5 2.1 1.0 .010 .25 .076 1.93
500 † 152.4 7.0 3.2 x x
1000 † 304.8 13.0 6.0 .128 3.25
18 • Industrial Cables
83905 K 2/c Yellow, Red Brown 100 30.5 2.1 1.0 .010 .25 .076 1.93
500 † 152.4 7.0 3.2 x x
1000 † 304.8 12.0 5.4 .128 3.25
83910 T 2/c Blue, Red Brown 100 30.5 2.1 1.0 .010 .25 .076 1.93
500 † 152.4 7.0 3.2 x x
1000 † 304.8 12.0 5.4 .128 3.25
FEP = Fluorinated Ethylene-propylene Multiple pair cables have each pair numbered for ease of identification.
†
Final put-up length may vary ±10% from length shown.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.56
UL Instrumentation Cable
600V Tray Cables – Overview
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.57
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket
NEC: TC, NPLF 9341 1 E2 500 152.4 22.0 10.0 .048 1.22 .276 7.01 63 280 2.75 69.85
ICEA S-73-532, ICEA S-61-402 1000 304.8 43.0 19.5
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.58
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Drain Wire
Overall Beldfoil Shield (100% Coverage) • XLPE Insulation • Black PVC Jacket (Green Ground)
NEC: TC-ER, NPLF 3088CE 1 E1 1000 3048.0 66.0 30.0 .048 1.22 .340 8.64 80 356 3.40 86.36
ICEA S-73-532 5000 † 1524.0 375.0 170.3
ICEA S-66-524 Ground
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
Rip Cord
Drain Wire
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket (Options below)
NEC: TC, NPLF 3064A 2 E1 Bulk †† Bulk — — .048 1.22 .493 12.52 185 823 4.75 120.65
ICEA S-73-532
ICEA S-61-402 1093A 4 E1 7500 † 2286.0 1545.0 700.8 .063 1.60 .577 14.66 347 1544 6.00 152.40
ICEA T-29-520
FT4/IEEE 1202/383 1094A 8 E1 5000 † 1524.0 1755.0 796.1 .063 1.60 .745 18.92 672 2989 7.50 190.50
1095A 12 E1 2500 † 762.0 1320.0 598.8 .084 2.13 .944 23.98 997 4435 9.75 247.65
5000 † 1524.0 2875.0 1304.1
3066A 16 E1 Bulk †† Bulk — — .084 2.13 1.046 26.57 1322 5881 10.50 266.70
1096A 24 E1 Bulk †† Bulk — — .084 2.13 1.284 32.61 1971 8767 13.00 330.20
Rip Cord
Drain Wires
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.59
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket
NEC: TC, NPLF 9342 1 E2 500 152.4 27.5 12.7 .048 1.22 .296 7.52 105 467 3.00 76.20
ICEA S-73-532, ICEA S-61-402 1000 304.8 56.0 25.4
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.60
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Drain Wire
Overall Beldfoil Shield (100% Coverage) • XLPE Insulation • Black PVC Jacket (Green Ground)
NEC: TC-ER, NPLF 3090CE 1 E1 1000 3048.0 81.0 39.8 .048 1.22 .390 9.91 130 578 3.90 99.06
ICEA S-73-532 5000 † 1524.0 450.0 204.3
ICEA S-66-524 Ground
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
Rip Cord
Drain Wire
Individually Shielded + Overall Beldfoil Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket (Options below)
NEC: TC, NPLF 1097A 4 E1 5000 † 1524.0 1415.0 641.8 .063 1.60 .640 16.26 554 2464 6.40 162.56
ICEA S-73-532
ICEA S-61-402 1098A 8 E1 2500 † 762.0 1350.0 612.4 .085 2.16 .872 22.15 1072 4768 8.70 220.98
ICEA T-29-520
FT4/IEEE 1202/383 1099A 12 E1 2500 † 762.0 1875.0 850.5 .085 2.16 1.047 26.59 1590 7073 10.50 266.70
3118A 16 E1 Bulk †† Bulk — — .084 2.13 1.234 31.34 1771 7878 12.25 311.15
1100A 24 E1 Bulk †† Bulk — — .085 2.16 1.434 36.42 3144 13985 14.30 363.22
3130A 36 E1 Bulk †† Bulk — — .110 2.79 1.773 45.03 3600 16013 18.00 457.20
Rip Cord
Drain Wires
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.61
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket
NEC: TC, NPLF 9343 1 E2 500 152.4 42.5 19.1 .048 1.22 .358 9.09 160 712 3.75 95.25
ICEA S-73-532 1000 304.8 86.0 39.0
ICEA S-61-402
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
Rip Cord
Drain Wire
Rip Cord
Drain Wire
1234 A E A B PVC-Nylon/PVC
Start Add or Add for C D XLPE/PVC
with replace Exposed
Part letter code Run rating E F FRPO/PVC
No. for desired if desired
conductor, G H XLPE/TPE
insulation & jacket
K L TPE/TPE
M N PVC-Nylon/Oil Res II
Q R XLPE/CPE
S T XLPE/Haloarrest®
**For 1000 and 3000 Series cables only.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.62
UL Instrumentation Cable
600V Tray Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Rip Cord
Overall Beldfoil® Shield (100% Coverage) • PVC/Nylon Insulation • Black PVC Jacket
NEC: TC, NPLF 9344 1 E2 500 152.4 54.0 24.5 .045 1.14 .384 9.75 253 1125 3.75 95.25
ICEA S-73-532 1000 304.8 111.0 50.4
ICEA S-61-402
ICEA T-29-520
FT4/IEEE 1202/383
Rip Cord
Drain Wire
Rip Cord
Drain Wire
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.63
UL Control Cable
600V Type TC Cables — Overview
Cabled non-shielded conductors provide Multi-conductor control cables (10 AWG As an option, Belden offers all PVC-nylon/
a minimal O.D. allowing greater tray and to 18 AWG) are printed alpha-numerically PVC, XLPE/PVC and XLPE/CPE jacketed
conduit fill. Non-shielded control cable may in addition to being color coded per ICEA tray cables with a TC-ER (Exposed Run)
be utilized when recommended by the Table E2. rating, formerly referred to as Open Wiring.
equipment manufacturer and used in a Per NEC Article 336, a TC-ER rated cable
8 AWG and larger are black and numbered
metallic conduit. may be installed in an industrial establishment
per ICEA Method 4.
between a cable tray and the utilization
Overall Shield Refer to Technical Information Section equipment or device. A TC-ER rated cable
Recommended for use in control applications for ICEA color code charts. must meet the crush and impact require-
where signals are transmitted in excess of ments of UL Type MC cable. By eliminating
100 millivolts, except in areas where high Specifications the need for metal conduit and/or armor,
voltage and current sources create exces- using a TC-ER rated cable results in
● UL Subject 1277 Type TC savings in both installation and maintenance.
sive noise interference. The Beldfoil® shield
18 • Industrial Cables
with drain wire provides 100% coverage for ● XLPE/Haloarrest jacketed cables Standard lengths may be subject to
maximum shield effectiveness. Copper tape are UL 1277 TC-LS rated tolerance. Custom lengths may be
shield available upon request. available upon request. Contact the Belden
● UL Subject 1424 (per outline for NPLF
Only 2-conductor round constructions requirements dated May 3, 1979) Electronics Division Customer Service
can be shielded. Flat constructions Department for additional information.
● UL 1685 (UL 1581) Vertical Flame Test
cannot be shielded. 1-800-BELDEN-1
comparable to IEEE 383-1974 (70,000
BTU/hr) Flame Test
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.64
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
18 AWG Multi-conductor Stranded (7x26) Bare Copper Conductors • Overall Beldfoil® Shield (100% Coverage) with Drain Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27325AS 2 E2 Bulk Bulk 34.0 50.6 .045 1.14 .270 6.86 67 298 2.70 68.58
FT4/IEEE 1202/383
ICEA S-73-532 27334AS 3 E2 Bulk Bulk 45.0 67.0 .045 1.14 .280 7.11 90 400 2.80 71.12
ICEA S-95-658
ICEA S-61-402 27326AS 4 E2 Bulk Bulk 60.0 89.3 .045 1.14 .300 7.62 112 498 3.10 81.28
ICEA T-29-520
Rip Cord
Drain Wire
Bulk = 5000 ft. or 10,000 ft. put-up one piece, ±10%. Check length available for specific construction.
Conductor, Insulation and Jacket Options
To Specify: Bare Tinned Insulation/Jacket
12345 A S A B PVC-Nylon/PVC
Start add add C D XLPE/PVC
with Conductor, “S” for
core Insulation, optional E F FRPO/PVC
Part Jacket Beldfoil
No. type Shield G H XLPE/TPE
Note: To specify TC-ER (Exposed Run) rated control cable, simply K L TPE/TPE
replace the second digit of the part number from a 7 to an 8. M N PVC-Nylon/Oil Res II
For example: 27080A with TC-ER rating becomes 28080A. Q R XLPE/CPE
S T XLPE/Haloarrest®
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.65
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
16 AWG Multi-conductor Stranded (7x24) Bare Copper Conductors • Overall Beldfoil® Shield (100% Coverage) with Drain Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27337AS 2 E2 Bulk Bulk 45.0 67.0 .045 1.14 .302 7.67 94 418 3.00 76.20
FT4/IEEE 1202/383
ICEA S-73-532
27331AS 3 E2 Bulk Bulk 55.0 81.8 .045 1.14 .320 8.13 130 578 3.20 81.28
ICEA S-95-658
ICEA S-61-402
ICEA T-29-520
Rip Cord
Drain Wire
Bulk = 5000 ft. or 10,000 ft. put-up one piece, ±10%. Check length available for specific construction. Conductor, Insulation and Jacket Options
To Specify: Bare Tinned Insulation/Jacket
18 • Industrial Cables
12345 A S A B PVC-Nylon/PVC
Start add add C D XLPE/PVC
with Conductor, “S” for
core Insulation, optional E F FRPO/PVC
Part Jacket Beldfoil
No. type Shield G H XLPE/TPE
Note: To specify TC-ER (Exposed Run) rated control cable, simply K L TPE/TPE
replace the second digit of the part number from a 7 to an 8. M N PVC-Nylon/Oil Res II
For example: 27080A with TC-ER rating becomes 28080A. Q R XLPE/CPE
S T XLPE/Haloarrest®
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.66
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
14 AWG Multi-conductor Stranded (7x22) Bare Copper Conductors • Overall Beldfoil® Shield (100% Coverage) with Drain Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27081AS 3 E2 Bulk Bulk 80.0 119.1 .045 1.14 .340 8.64 99 440 3.4 86.36
FT4/IEEE 1202/383
ICEA S-73-532, ICEA S-95-658 27082AS 4 E2 Bulk Bulk 105.0 156.3 .045 1.14 .391 9.93 273 1214 3.9 99.06
ICEA S-61-402,
ICEA T-29-520
Rip Cord
Drain Wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.67
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
Bulk = 5000 ft. or 10,000 ft. put-up one piece, ±10%. Check length available for specific construction.
12345 A S A B PVC-Nylon/PVC
Start add add C D XLPE/PVC
with Conductor, “S” for
core Insulation, optional E F FRPO/PVC
Part Jacket Beldfoil®
No. type Shield G H XLPE/TPE
Note: To specify TC-ER (Exposed Run) rated control cable, simply K L TPE/TPE
replace the second digit of the part number from a 7 to an 8. M N PVC-Nylon/Oil Res II
For example: 27080A with TC-ER rating becomes 28080A. Q R XLPE/CPE
S T XLPE/Haloarrest®
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.68
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
8 AWG Multi-conductor Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27149A 2 ** Bulk Bulk 220.0 327.4 .060 1.52 .560 14.22 384 1709 5.6 142.24
FT4/IEEE 1202/383
ICEA S-73-532 27150A 3 ** 1000 304.8 354.0 527.0 .060 1.52 .590 14.99 576 2563 5.9 149.86
ICEA S-95-658 Bulk Bulk 354.0 527.0
ICEA S-61-402 27151A 4 Bulk Bulk 394.0 327.4 .060 1.52 .650 16.51 768 3418 6.5 165.10
ICEA T-29-520 **
Rip Cord
6 AWG Multi-conductor Stranded (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27152A 2 ** Bulk Bulk 316.0 434.6 .060 1.52 .630 16.00 610 2715 6.3 160.02
FT4/IEEE 1202/383
ICEA S-73-532 27153A 3 ** 1000 304.8 477.0 710.0 .060 1.52 .670 17.02 915 4072 6.7 170.18
ICEA S-95-658 Bulk Bulk 477.0 710.0
ICEA S-61-402 27154A 4 Bulk Bulk 519.0 759.0 .060 1.52 .730 18.54 1220 5429 7.3 185.42
ICEA T-29-520 **
Rip Cord
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.69
UL Control Cable
600V Type TC Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
4 AWG Multi-conductor Stranded (7x12) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27155A 2 ** Bulk Bulk 455.0 677.1 .060 1.52 .770 19.56 970 4317 7.7 195.58
FT4/IEEE 1202/383
ICEA S-73-532 27156A 3 ** Bulk Bulk 630.0 937.6 .080 2.03 .820 20.83 1455 6475 8.2 208.28
ICEA S-95-658 27157A 4 Bulk Bulk 850.0 1265.0 .080 2.03 .950 24.13 1940 8633 9.5 241.30
**
ICEA S-61-402
ICEA T-29-520
Rip Cord
2 AWG Multi-conductor Stranded (7x10) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27158A 2 ** Bulk Bulk 716.0 1065.6 .080 2.03 .970 24.64 1544 6871 9.7 246.38
FT4/IEEE 1202/383
ICEA S-73-532 27159A 3 ** Bulk Bulk 960.0 1428.7 .080 2.03 .990 25.15 2316 10306 9.9 251.46
ICEA S-95-658 27160A 4 Bulk Bulk 1213.0 1805.2 .080 2.03 1.090 27.69 3088 13742 10.9 276.86
ICEA S-61-402
**
ICEA T-29-520
Rip Cord
1 AWG Multi-conductor Stranded (19x14) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
PVC/Nylon Insulation and PVC Jacket Constructions (See chart below for other options)
NEC: TC, NPLF 27161A 3 ** Bulk Bulk — — .080 2.03 1.120 28.45 2919 12990 11.2 284.48
FT4/IEEE 1202/383
ICEA S-73-532
ICEA S-95-658
ICEA S-61-402
ICEA T-29-520
Rip Cord
12345 A S A B PVC-Nylon/PVC
Start add add C D XLPE/PVC
with Conductor, “S” for
core Insulation, optional E F FRPO/PVC
Part Jacket Beldfoil®
No. type Shield G H XLPE/TPE
Note: To specify TC-ER (Exposed Run) rated control cable, simply K L TPE/TPE
replace the second digit of the part number from a 7 to an 8. M N PVC-Nylon/Oil Res II
For example: 27080A with TC-ER rating becomes 28080A. Q R XLPE/CPE
S T XLPE/Haloarrest®
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.70
UL Control Cable
600V Type MC Metal Clad and Teck-Style® Cables — Overview
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.71
UL Control Cable
600V Type MC Metal Clad Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
14 AWG Stranded (7x22) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27243 28243 2 .030 .76 .050 1.27 .48 12.19 .58 14.73 7.3 185.42
27244 28244 3 .030 .76 .050 1.27 .50 12.70 .61 15.49 7.6 193.04
27245 28245 4 .030 .76 .050 1.27 .54 13.72 .64 16.26 7.9 200.66
27246 28246 5 .030 .76 .050 1.27 .57 14.48 .68 17.27 8.4 213.36
27247 28247 6 .030 .76 .050 1.27 .62 15.75 .72 18.29 8.9 226.06
27248 28248 7 .030 .76 .050 1.27 .62 15.75 .72 18.29 8.9 226.06
27269 28269 8 .030 .76 .050 1.27 .69 17.53 .80 20.32 9.4 238.76
27535 28535 9 .030 .76 .050 1.27 .70 17.78 .80 20.32 10.0 254.00
27249 28249 10 .030 .76 .050 1.27 .75 19.05 .85 21.59 10.5 266.70
27250 28250 12 .030 .76 .050 1.27 .77 19.56 .87 22.10 10.8 274.32
27251 28251 15 .030 .76 .050 1.27 .87 22.10 .98 24.89 11.6 294.64
27969 28969 19 .030 .76 .050 1.27 1.00 25.40 1.11 28.19 12.1 307.34
27252 28252 20 .030 .76 .050 1.27 1.03 26.16 1.14 28.96 13.3 337.82
27270 28270 25 .030 .76 .050 1.27 1.10 27.94 1.21 30.73 14.4 365.76
27253 28253 30 .030 .76 .050 1.27 1.18 29.97 1.29 32.77 15.1 383.54
27292 28292 37 .030 .76 .050 1.27 1.14 28.96 1.24 31.50 16.1 408.94
27433 28433 40 .030 .76 .050 1.27 1.28 32.51 1.40 35.56 16.7 424.18
27434 28434 50 .030 .76 .050 1.27 1.40 35.56 1.52 38.61 18.4 467.36
12 AWG Stranded (7x20) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27254 28254 2 .030 .76 .050 1.27 .52 13.21 .62 15.75 7.8 198.12
27255 28255 3 .030 .76 .050 1.27 .54 13.72 .64 16.26 8.0 203.20
27256 28256 4 .030 .76 .050 1.27 .58 14.73 .68 17.22 8.5 215.90
27271 28271 5 .030 .76 .050 1.27 .62 15.75 .72 18.29 9.1 231.14
27272 28272 6 .030 .76 .050 1.27 .67 17.02 .77 19.56 9.6 243.84
27273 28273 7 .030 .76 .050 1.27 .67 17.02 .77 19.56 9.6 243.84
27274 28274 8 .030 .76 .050 1.27 .77 19.56 .88 22.35 10.2 259.08
27538 28538 9 .030 .76 .050 1.27 .76 19.30 .86 21.84 10.8 274.32
27275 28275 10 .030 .76 .050 1.27 .80 20.32 .91 23.11 11.5 292.10
27276 28276 12 .030 .76 .050 1.27 .84 21.34 .94 23.88 11.7 297.18
27277 28277 15 .030 .76 .050 1.27 .94 23.88 1.05 26.67 13.4 340.36
27539 28539 19 .030 .76 .055 1.40 1.05 26.67 1.16 29.46 14.0 355.60
27278 28278 20 .030 .76 .055 1.40 1.16 29.46 1.27 32.26 14.6 370.84
27279 28279 25 .030 .76 .055 1.40 1.26 32.00 1.37 34.80 15.8 401.32
27280 28280 30 .030 .76 .055 1.40 1.29 32.77 1.40 35.56 16.8 426.72
27540 28540 37 .030 .76 .055 1.40 1.44 36.58 1.55 39.37 17.8 452.12
27432 28432 40 .030 .76 .055 1.40 1.50 38.10 1.63 41.40 18.4 467.36
Color Code: Use ICEA Table E2 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.72
UL Control Cable
600V Type MC Metal Clad Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
10 AWG Stranded (7x18) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27257 28257 2 .030 .76 .050 1.27 .56 14.22 .67 17.02 8.4 213.36
27258 28258 3 .030 .76 .050 1.27 .58 14.73 .69 17.53 8.6 218.44
27259 28259 4 .030 .76 .050 1.27 .62 15.75 .74 18.80 9.2 233.68
27281 28281 5 .030 .76 .050 1.27 .68 17.27 .79 20.07 12.8 325.12
27282 28282 6 .030 .76 .050 1.27 .74 18.80 .84 21.34 10.4 264.16
27283 28283 7 .030 .76 .050 1.27 .74 18.80 .84 21.34 10.4 264.16
27284 28284 8 .030 .76 .050 1.27 .81 20.57 .92 23.37 11.2 284.48
27541 28541 9 .030 .76 .050 1.27 .87 22.10 .98 24.89 11.8 299.72
27285 28285 10 .030 .76 .050 1.27 .89 22.61 1.03 26.16 13.3 337.82
27286 28286 12 .030 .76 .050 1.27 1.01 25.65 1.12 28.45 13.7 347.98
27287 28287 15 .030 .76 .050 1.27 1.09 27.69 1.22 30.99 14.8 375.92
27288 28288 20 .030 .76 .055 1.40 1.22 30.99 1.35 34.29 16.2 411.48
27289 28289 25 .030 .76 .055 1.40 1.32 33.53 1.47 37.34 17.8 452.12
27290 28290 30 .030 .76 .055 1.40 1.42 36.07 1.55 39.37 18.6 472.44
8 AWG Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27291 28291 2 .045 1.14 .050 1.27 .70 17.78 .81 20.57 9.8 248.92
27260 28260 3 .045 1.14 .050 1.27 .72 18.29 .82 20.83 10.2 259.08
27261 28261 4 .045 1.14 .050 1.27 .78 19.81 .88 22.35 10.9 276.86
6 AWG Stranded (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27293 28293 2 .045 1.14 .050 1.27 .76 19.30 .87 22.10 10.7 271.78
27262 28262 3 .045 1.14 .050 1.27 .80 20.32 .90 22.86 11.2 284.48
27263 28263 4 .045 1.14 .050 1.27 .87 22.10 .97 24.64 12.1 307.34
Color Code: For sizes 14, 12, 10, use ICEA Table E2 with printed numbers.
For sizes 8 and larger, use ICEA Method 4 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.73
UL Control Cable
600V Type MC Metal Clad Cables
Industrial Grade Sunlight- and Oil-Resistant Jackets
4 AWG Stranded (7x12) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27264 28264 3 .045 1.14 .050 1.27 .90 22.86 1.00 25.40 13.1 332.74
27265 28265 4 .045 1.14 .050 1.27 1.97 50.04 1.08 27.43 14.2 360.68
2 AWG Stranded (7x10) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27267 28267 3 .045 1.14 .050 1.27 1.02 25.91 1.13 28.70 14.7 373.38
27268 28268 4 .045 1.14 .050 1.27 1.11 28.19 1.22 30.99 16.0 406.40
Composite 14 AWG (7x22) and 12 AWG (7x20) Stranded Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27428 28428 3c/14 .030 .76 .050 1.27 .70 17.78 .81 20.57 9.7 246.38
3c/12 .030 .76
Composite 14 AWG (7x22) and 10 AWG (7x18) Stranded Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27429 28429 3c/14 .030 .76 .050 1.27 .74 18.80 .85 21.59 10.2 259.08
3c/10 .030 .76
Composite 14 AWG (7x22) and 8 AWG (7x16) Stranded Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27430 28430 3c/14 .030 .76 .050 1.27 .83 21.08 .94 23.88 11.2 284.48
3c/8 .045 1.14
Composite 14 AWG (7x22) and 6 AWG (7x14) Stranded Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Interlocked Armor • Cross-linked Polyethylene Insulation • PVC Jacket
NEC: MC 27431 28431 3c/14 .030 .76 .050 1.27 .89 22.61 1.01 25.65 12.0 304.80
3c/6 .045 1.14
18 • Industrial Cables
Color Code: For sizes 14, 12, 10, use ICEA Table E2 with printed numbers.
For sizes 8 and larger, use ICEA Method 4 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.74
UL Control Cable
600V Teck-Style® Cables
Dual-Rated Type MC/Teck 90
14 AWG Stranded (7x22) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27840 28840 2 .030 .76 .37 9.40 .56 14.22 .67 17.02 66 294 8.0 203
27841 28841 3 .030 .76 .39 9.91 .58 14.73 .69 17.53 98 436 8.3 211
27842 28842 4 .030 .76 .43 10.92 .62 15.75 .73 18.54 131 583 8.7 221
27843 28843 5 .030 .76 .47 11.94 .66 16.76 .77 19.56 164 730 9.2 234
27844 28844 6 .030 .76 .51 12.95 .70 17.78 .81 20.57 191 850 9.7 246
27845 28845 7 .030 .76 .51 12.95 .70 17.78 .81 20.57 225 1001 9.7 246
27846 28846 8 .030 .76 .58 14.73 .77 19.56 .88 22.35 260 1157 10.5 267
27847 28847 10 .030 .76 .67 17.02 .93 23.62 1.04 26.42 321 1428 12.5 318
27848 28848 12 .030 .76 .69 17.53 .95 24.13 1.06 26.92 388 1726 10.9 277
27849 28849 15 .030 .76 .77 19.56 1.03 26.16 1.14 28.96 481 2140 13.7 348
27850 28850 20 .030 .76 .86 21.84 1.12 28.45 1.23 31.24 649 2887 15.3 389
27851 28851 25 .030 .76 .92 23.37 1.18 29.97 1.30 33.02 810 3603 16.3 414
27852 28852 30 .030 .76 .98 24.89 1.24 31.50 1.36 34.54 975 4337 17.0 432
CSA C22.2 #131
27885 28885 40 .030 .76 1.09 27.69 1.35 34.29 1.47 37.34 1301 5787 18.5 470
FT4 Flame Test, HAZ LOC
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 27886 28886 50 .030 .76 1.19 30.23 1.45 36.83 1.57 39.88 1630 7251 19.8 503
12 AWG Stranded (7x20) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27853 28853 2 .030 .76 .41 10.41 .60 15.24 .71 18.03 104 463 8.5 216
27854 28854 3 .030 .76 .43 10.92 .62 15.75 .73 18.54 156 694 8.8 224
27855 28855 4 .030 .76 .47 11.94 .66 16.76 .77 19.56 207 921 9.2 234
27856 28856 5 .030 .76 .52 13.21 .71 18.03 .82 20.83 260 1157 9.8 249
27857 28857 6 .030 .76 .59 14.99 .78 19.81 .89 22.61 310 1379 10.7 272
27858 28858 7 .030 .76 .59 14.99 .78 19.81 .89 22.61 361 1606 10.7 272
27859 28859 8 .030 .76 .64 16.26 .83 21.08 .94 23.88 415 1846 11.3 287
27860 28860 10 .030 .76 .75 19.05 1.01 25.65 1.12 28.45 520 2313 13.4 340
27861 28861 12 .030 .76 .77 19.56 1.03 26.16 1.14 28.96 619 2753 13.7 348
27862 28862 15 .030 .76 .87 22.10 1.13 28.70 1.25 31.75 718 3194 15.0 381
27863 28863 20 .030 .76 .96 24.38 1.22 30.99 1.33 33.78 1040 4626 15.9 404
27864 28864 25 .030 .76 1.04 26.42 1.30 33.02 1.42 36.07 1301 5787 17.0 432
CSA C22.2 #131
27865 28865 30 .030 .76 1.15 29.21 1.41 35.81 1.53 38.86 1560 6939 18.3 465
FT4 Flame Test, HAZ LOC
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 27887 28887 40 .030 .76 1.20 30.48 1.54 39.12 1.67 42.42 2020 8985 20.0 508
Color Code: Use ICEA Table E2 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.75
UL Control Cable
600V Teck-Style® Cables
Dual-Rated Type MC/Teck 90
10 AWG Stranded (7x18) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27866 28866 2 .030 .76 .46 11.68 .65 16.51 .74 18.80 166 738 9.1 231
27867 28867 3 .030 .76 .48 12.19 .67 17.02 .77 19.56 249 1108 9.4 239
27868 28868 4 .030 .76 .56 14.22 .75 19.05 .84 21.34 330 1468 10.3 262
27869 28869 5 .030 .76 .67 17.02 .86 21.84 .96 24.38 415 1846 11.6 295
27870 28870 6 .030 .76 .67 17.02 .86 21.84 .96 24.38 491 2184 11.6 295
27877 28877 7 .030 .76 .70 17.78 .90 22.86 1.00 25.40 560 2491 12.1 307
27878 28878 8 .030 .76 .75 19.05 .95 24.13 1.05 26.67 640 2847 12.7 323
27879 28879 10 .030 .76 .78 19.81 1.04 26.42 1.15 29.21 801 3563 13.8 351
27880 28880 12 .030 .76 .89 22.61 1.15 29.21 1.26 32.00 960 4270 15.1 384
27881 28881 15 .030 .76 .93 23.62 1.19 30.23 1.30 33.02 1195 5316 15.6 396
27882 28882 20 .030 .76 1.06 26.92 1.32 33.53 1.44 36.58 1600 7117 17.3 439
CSA C22.2 #131
27883 28883 25 .030 .76 1.12 28.45 1.44 36.58 1.58 40.13 1990 8852 19.0 483
FT4 Flame Test, HAZ LOC
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 27884 28884 30 .030 .76 1.28 32.51 1.54 39.12 1.67 42.42 2355 10476 20.0 508
8 AWG Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27871 28871 2 .045 1.14 .59 14.99 .78 19.81 .89 22.61 264 1174 10.7 272
27872 28872 3 .045 1.14 .62 15.75 .81 20.57 .91 23.11 396 1762 10.9 277
27873 28873 4 .045 1.14 .68 17.27 .94 23.88 1.05 26.67 528 2349 12.6 320
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
6 AWG Stranded (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27874 28874 2 .060 1.52 .71 18.03 .97 24.64 1.08 27.43 420 1868 13.0 330
27875 28875 3 .060 1.52 .76 19.30 1.02 25.91 1.13 28.70 630 2802 13.5 343
27876 28876 4 .060 1.52 .88 22.35 1.14 28.96 1.25 31.75 840 3737 15.0 381
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
4 AWG Stranded (7x12) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27894 28894 3 .060 1.52 .91 23.11 1.17 29.72 1.29 32.77 1002 4457 15.5 394
27895 28895 4 .060 1.52 .99 25.15 1.25 31.75 1.37 34.80 1335 5938 16.4 417
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
3 AWG Stranded (7x11) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27896 28896 3 .060 1.52 .96 24.38 1.22 30.99 1.33 33.78 1263 5618 16.0 406
18 • Industrial Cables
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Color Code: For sizes 14, 12, 10, use ICEA Table E2 with printed numbers.
For sizes 8 and larger, use ICEA Method 4 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.76
UL Control Cable
600V Teck-Style® Cables
Dual-Rated Type MC/Teck 90
2 AWG Stranded (7x10) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27888 28888 3 .060 1.52 1.08 27.43 1.28 32.51 1.40 35.56 1593 7086 16.8 427
27889 28889 4 .060 1.52 1.12 28.45 1.38 35.05 1.50 38.10 2124 9448 18.0 457
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG (7x22) and 12 AWG (7x20) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27890 28890 3c/14 .030 .76 .56 14.22 .75 19.05 .86 21.84 202 899 10.3 262
3c/12 .030 .76
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG (7x22) and 10 AWG (7x18) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27891 28891 3c/14 .030 .76 .61 15.49 .80 20.32 .91 23.11 305 1357 10.9 277
3c/10 .030 .76
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG (7x22) and 8 AWG (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27892 28892 3c/14 .045 1.14 .70 17.78 .96 24.38 1.07 27.18 435 1935 12.8 325
3c/8 .030 .76
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG (7x22) and 6 AWG (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum or Steel Armor • Cross-linked Polyethylene Insulation • PVC Inner Jacket • PVC Outer Jacket
NEC: MC 27893 28893 3c/14 .060 1.52 .90 22.86 1.15 29.21 1.26 32.00 655 2914 15.1 384
3c/6 .030 .76
CSA C22.2 #131, FT4 Flame Test, HAZ LOC, CSA C22.2 #0.3 Clause 4.31 Low Acid Gas
Color Code: For sizes 14, 12, 10, use ICEA Table E2 with printed numbers.
For sizes 8 and larger, use ICEA Method 4 with printed numbers.
Non-stocked items. Check length available for specific construction. Minimum order may apply.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.77
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.78
Belden offers a complete line of high performance and high quality Contact Belden Customer Service for other options:
CSA certified instrumentation cables (300V/600V and CIC/ACIC). ● 150V
These cables are designed to minimize noise and signal interference ● XLPE insulation (add D suffix to part number)
to deliver clean signals in harsh petrochemical, pulp and paper ● Thermocouple alloy conductors
and process industry environments, as well as for use in general ● Overall foil shield only
manufacturing operations. ● Other pair and triad counts
20 AWG Pairs Stranded (7x28) TC Conductors • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black and White with Numbers)
CSA C22.2#239, Type CIC 22671* 1 71 106 .045 1.14 .260 6.60
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22638 2 143 213 .045 1.14 .400 10.16
FT4 Flame Test
22639 4 217 323 .045 1.14 .460 11.68
22640 6 320 476 .045 1.14 .570 14.48
22641 8 405 603 .060 1.52 .610 15.49
22676 12 573 853 .060 1.52 .730 18.54
Rip Cord
Drain Wires
22643 16 722 1076 .060 1.52 .810 20.57
22647 24 1103 1641 .080 2.03 1.040 26.42
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet) 22670 36 1548 2304 .080 2.03 1.190 30.23
20 AWG Triads Stranded (7x28) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black, White and Red with Numbers)
CSA C22.2#239, Type CIC 22660* 1 89 132 .045 1.14 .270 6.86
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22662 2 177 263 .045 1.14 .420 10.67
FT4 Flame Test
22663 4 277 412 .045 1.14 .490 12.45
22672 8 521 775 .060 1.52 .650 16.51
22673 16 1000 1488 .080 2.03 .910 23.11
22674 24 1414 2104 .080 2.03 1.110 28.19
Rip Cord
Drain Wires
18 AWG Pairs Stranded (7x26) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black and White with Numbers)
CSA C22.2#239, Type CIC 22645* 1 97 144 .045 1.14 .300 7.62
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22633 2 196 292 .045 1.14 .480 12.19
FT4 Flame Test
22648 4 338 503 .045 1.14 .580 14.73
22634 6 473 704 .060 1.52 .670 17.02
22635 8 570 848 .060 1.52 .730 18.54
22636 12 869 1293 .060 1.52 .920 23.37
Rip Cord
Drain Wires
22654 16 1095 1630 .080 2.03 1.020 25.91
22637 24 1552 2310 .080 2.03 1.260 32.00
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
18 AWG Triads Stranded (7x26) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black, White and Red with Numbers)
CSA C22.2#239, Type CIC 22677* 1 121 180 .045 1.14 .303 7.70
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22678 2 256 381 .045 1.14 .480 12.19
FT4 Flame Test
22679 4 427 636 .060 1.52 .620 15.75
22680 8 597 888 .060 1.52 .710 18.03
22681 16 740 1101 .060 1.52 .770 19.56
22682 24 1130 1682 .080 2.03 .980 24.89
Rip Cord
22683 16 1436 2137 .080 2.03 1.090 27.69
Drain Wires
22684 24 2049 3049 .080 2.03 1.340 34.04
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
*One pair/triad cables have one shield and drain wire TC = Tinned Copper
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.79
16 AWG Pairs Stranded (7x24) TC Conductors • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black and White with Numbers)
CSA C22.2#239, Type CIC 22646* 1 122 182 .045 1.14 .320 8.13
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22628 2 262 390 .045 1.14 .520 13.21
FT4 Flame Test
22629 4 438 652 .060 1.52 .628 15.95
22630 6 603 897 .060 1.52 .740 18.80
22631 8 752 1119 .060 1.52 .800 20.32
22632 12 1148 1708 .080 2.03 1.010 25.65
Rip Cord 22685 16 1461 2174 .080 2.03 1.120 28.45
Drain Wires
22686 24 2091 3112 .080 2.03 1.380 35.05
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
16 AWG Triads Stranded (7x24) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black, White and Red with Numbers)
CSA C22.2#239, Type CIC 22603* 1 152 226 .045 1.14 .329 8.36
CSA C22.2 #0.3 Clause 4.31 Low Acid Gas 22687 2 344 512 .045 1.14 .580 14.73
FT4 Flame Test
22675 4 564 839 .060 1.52 .670 17.02
22688 6 819 1219 .060 1.52 .780 19.81
22689 8 1063 1582 .080 2.03 .940 23.88
22690 12 1524 2268 .080 2.03 1.080 27.43
Rip Cord
Drain Wires
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
TC = Tinned Copper
*One pair/triad cables have one shield and drain wire
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.80
20 AWG Pairs Stranded (7x28) TC Cond. • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage) • Drain Wires
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23543** 26530** 1 140 208 230 342 .020 .51 .26 6.6 .56 14.2
CSA C22.2#174, HLABCD 23534 26531 2 206 307 325 484 .020 .51 .40 10.2 .70 17.8
CSA C22.2#0.3, Clause 4.31
Low Acid Gas 23514 26532 4 255 379 390 580 .020 .51 .46 11.7 .76 19.3
FT4 Flame Test 23513 26533 6 297 442 494 735 .020 .51 .57 14.5 .88 22.4
23503 26534 8 361 537 563 840 .020 .51 .63 16.0 .92 23.4
23521 26535 12 480 714 694 1033 .020 .51 .75 19.1 1.06 26.9
23532 26536 16 600 893 900 1339 .020 .51 .79 20.1 1.16 29.5
23506 26537 24 800 1191 1175 1749 .020 .51 1.05 26.7 1.42 36.1
Rip Cord
Drain Wires 23544 26538 36 1050 1563 1500 2232 .020 .51 1.14 29.0 1.57 39.9
-25°C Installed 23575 26546 50 1468 2185 2010 2991 .020 .51 1.37 34.8 1.75 44.5
-40°C to +105°C (Dry) (75°C Wet)
20 AWG Triads Stranded (7x28) TC Cond. • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage) • Drain Wires
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23545** 26539** 1 139 207 235 350 .020 .51 .27 6.9 .57 14.5
CSA C22.2#174, HLBCD 23546 26540 2 210 313 345 513 .020 .51 .43 10.9 .73 18.5
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 23547 26541 4 270 402 425 632 .020 .51 .50 12.7 .80 20.3
23548 26542 8 444 661 650 967 .020 .51 .69 17.5 1.00 25.4
23571 26553 12 632 941 970 1444 .020 .51 .82 20.8 1.24 31.5
23549 26543 16 740 1101 1090 1622 .020 .51 .91 23.1 1.28 32.5
23550 26544 24 990 1473 1360 2024 .020 .51 1.11 28.2 1.48 37.6
Rip Cord
Drain Wires
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
18 AWG Pairs Stranded (7x26) TC Cond. • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage) • Drain Wires
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23533** 26514** 1 160 238 258 384 .025 .64 .30 7.6 .60 15.2
CSA C22.2#174, HLABCD 23511 26515 2 247 368 384 572 .025 .64 .48 12.2 .78 19.8
CSA C22.2#0.3, Clause 4.31
Low Acid Gas 23530 26516 4 340 506 500 744 .025 .64 .58 14.7 .88 22.4
FT4 Flame Test 23528 26517 6 420 625 644 958 .025 .64 .67 17.0 .98 24.9
23531 26518 8 543 808 827 1230 .025 .64 .73 18.5 1.03 26.2
23524 26519 12 725 1079 1045 1555 .025 .64 .90 22.9 1.28 32.5
23519 26520 16 850 1265 1210 1801 .025 .64 .99 25.1 1.37 34.8
23542 26521 24 1100 1637 1510 2247 .025 .64 1.24 31.5 1.63 41.4
Rip Cord
23554 26555 36 1465 2180 1960 2917 .025 .64 1.41 35.8 1.80 45.7
Drain Wires
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
18 AWG Triads Stranded (7x26) TC Cond. • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage) • Drain Wires
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23505** 26522** 1 175 260 275 409 .025 .64 .33 8.4 .61 15.5
CSA C22.2#174, HLBCD 23516 26523 2 275 409 417 621 .025 .64 .51 13.0 .81 20.6
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 23515 26524 4 385 573 555 826 .025 .64 .62 15.7 .93 23.6
23508 26525 6 535 796 780 1161 .025 .64 .75 19.1 1.11 28.2
23523 26526 8 680 1012 995 1481 .025 .64 .81 20.6 1.18 30.0
23512 26527 12 916 1363 1215 1808 .025 .64 1.03 26.2 1.40 35.6
23537 26528 16 1020 1518 1400 2083 .025 .64 1.13 28.7 1.50 38.1
23536 26529 24 1335 1987 1775 2642 .025 .64 1.37 34.8 1.80 45.7
Rip Cord
Drain Wires
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.81
16 AWG Pairs Stranded (7x24) TC Conductors • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23501** 26500** 1 175 260 280 417 .025 .64 .33 8.4 .62 15.8
CSA C22.2#174, HLABCD 23527 26501 2 280 417 425 635 .025 .64 .52 13.2 .81 20.6
CSA C22.2#0.3, Clause 4.31
Low Acid Gas 23509 26503 4 395 588 570 848 .025 .64 .63 16.0 .93 23.6
FT4 Flame Test 23500 26504 6 510 759 715 1064 .025 .64 .73 18.5 1.03 26.2
23510 26505 8 625 930 910 1354 .025 .64 .79 20.1 1.16 29.5
23525 26506 12 875 1302 1230 1831 .025 .64 1.00 25.4 1.37 34.8
23539 26507 16 1054 1569 1445 2151 .025 .64 1.12 28.2 1.48 37.6
23538 26508 24 1397 2079 1840 2738 .025 .64 1.36 34.5 1.75 44.5
Rip Cord 23568 26551 36 1920 2857 2460 3661 .025 .64 1.60 40.6 1.97 50.0
Drain Wires
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
16 AWG Triads Stranded (7x24) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 23507** 26502** 1 190 282 295 439 .025 .64 .35 8.9 .63 16.0
CSA C22.2#174, HLBCD 23522 26509 2 342 508 500 744 .025 .64 .58 14.7 .90 22.9
CSA C22.2#0.3, Clause 4.31
Low Acid Gas 23520 26510 4 450 670 640 953 .025 .64 .68 17.3 .95 24.1
FT4 Flame Test 23529 26511 6 650 967 928 1381 .025 .64 .78 19.8 1.19 30.2
23526 26512 8 825 1228 1130 1682 .025 .64 .93 23.6 1.30 33.0
23541 26513 12 1082 1610 1511 2249 .025 .64 1.13 28.7 1.50 38.1
23567 26545 16 1285 1912 1705 2537 .025 .64 1.25 31.8 1.64 41.7
23578 26547 24 1725 2567 2200 3274 .025 .64 1.58 40.1 1.95 49.5
Rip Cord
Drain Wires
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
TC = Tinned Copper
*Note: Add D suffix for XLPE insulation. Example: 23501D.
**One pair/triad cables have one foil shield and drain wire
Color Code: Pairs — Black and White with Numbers.
Triads — Black, White and Red with Numbers.
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.82
18 AWG Pairs Stranded (7x26) TC Conductors • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black and White with Numbers)
CSA C22.2#239, Type CIC 22417* 1 109 162 .045 1.14 .32 8.13
CSA C22.2#0.3, Clause 4.31 Low Acid Gas 22405 2 229 341 .045 1.14 .51 12.95
FT4 Flame Test
22404 4 374 557 .060 1.52 .63 16.00
22418 8 632 941 .060 1.52 .79 20.07
22421 12 970 1444 .080 2.03 1.00 25.40
22419 24 1741 2591 .080 2.03 1.36 34.54
Rip Cord
Drain Wires
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
18 AWG Triads Stranded (7x26) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black, White and Red with Numbers)
CSA C22.2#239, Type CIC 22442* 1 131 195 .045 1.14 .34 8.64
CSA C22.2#0.3, Clause 4.31 Low Acid Gas 22443 2 299 445 .060 1.52 .58 14.73
FT4 Flame Test
22444 4 476 708 .060 1.52 .68 17.27
22445 8 893 1329 .080 2.03 .88 22.35
Rip Cord
Drain Wires
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
16 AWG Pairs Stranded (7x24) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black and White with Numbers)
CSA C22.2#239, Type CIC 22416* 1 129 192 .045 1.14 .34 8.64
CSA C22.2#0.3, Clause 4.31 Low Acid Gas 22409 2 229 341 .045 1.14 .59 14.99
FT4 Flame Test
22410 4 469 698 .060 1.52 .68 17.27
22446 6 667 993 .060 1.52 .79 20.07
22411 8 841 1252 .080 2.03 .90 22.86
22412 12 1235 1838 .080 2.03 1.09 27.69
Rip Cord 22447 24 2250 3349 .080 2.03 1.49 37.85
Drain Wires
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
16 AWG Triads Stranded (7x24) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
PVC Insulation • Black PVC Jacket (Color Code: Black, White and Red with Numbers)
CSA C22.2#239, Type CIC 22413* 1 167 249 .045 1.14 .36 9.14
CSA C22.2#0.3, Clause 4.31 Low Acid Gas 22448 2 372 554 .045 1.14 .62 15.88
FT4 Flame Test
22414 4 606 902 .060 1.52 .72 18.29
22415 8 1144 1703 .080 2.03 .96 24.38
Rip Cord
Drain Wires
-25°C Installed
-40°C to +105°C (Dry) (75°C Wet)
TC = Tinned Copper
*One pair/triad cables have one foil shield and drain wire
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.83
18 AWG Pairs Stranded (7x26) TC Cond. • Individual Beldfoil® + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 24511** 25506** 1 154 229 257 382 .030 .76 .32 8.13 .61 15.49
CSA C22.2#174, HLABCD 24512 25514 2 238 354 387 575 .030 .76 .51 12.95 .82 20.83
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 24513 25503 4 335 499 504 750 .030 .76 .63 16.00 .93 23.62
24514 25505 8 536 798 829 1233 .030 .76 .79 20.27 1.15 29.21
24515 25501 12 739 1100 1092 1624 .030 .76 1.00 25.40 1.36 34.54
24520 25517 24 1169 1740 1674 2490 .030 .76 1.36 34.54 1.75 44.45
Rip Cord
Drain Wires
-25°C Installed • -40°C to +105°C (Dry) (75°C Wet)
18 AWG Triads Stranded (7x26) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 24516** 25500** 1 166 247 276 411 .030 .76 .34 8.64 .63 16.00
CSA C22.2#174, HLBCD 24517 25522 2 293 436 455 677 .030 .76 .58 14.73 .89 22.61
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 24518 25520 4 391 582 572 851 .030 .76 .66 16.76 .99 25.15
24519 25523 8 673 1002 988 1470 .030 .76 .88 22.35 1.29 32.77
Rip Cord
Drain Wires
16 AWG Pairs Stranded (7x24) TC Cond. • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 24500** 25504** 1 171 254 279 415 .030 .76 .34 8.64 .64 16.26
CSA C22.2#174, HLABCD 24505 25510 2 299 445 455 677 .030 .76 .59 14.99 .89 22.61
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 24502 25511 4 450 670 583 868 .030 .76 .68 17.27 .98 24.89
24506 25512 6 576 857 880 1310 .030 .76 .79 20.07 1.16 29.46
24503 25513 8 679 1010 1005 1496 .030 .76 .90 22.86 1.27 32.26
24504 25518 12 908 1351 1280 1905 .030 .76 1.09 27.69 1.46 37.08
24510 25519 24 1502 2235 2030 3021 .030 .76 1.49 37.85 1.88 47.75
Rip Cord
Drain Wires
16 AWG Triads Stranded (7x24) TC Conductors • Individual Beldfoil + Polyester Isolation Tape • Overall Beldfoil Shield (100% Coverage)
Interlocked Armor • PVC Insulation* • PVC Inner Jacket • Chrome PVC Outer Jacket
CSA C22.2#239, Type ACIC 24501** 25502** 1 195 290 309 460 .030 .76 .36 9.14 .66 16.76
CSA C22.2#174, HLBCD 24507 25507 2 339 505 465 692 .030 .76 .62 15.75 .94 23.88
CSA C22.2#0.3, Clause 4.31
Low Acid Gas, FT4 Flame Test 24508 25509 4 464 691 793 1180 .030 .76 .72 18.29 1.05 26.67
24509 25508 8 807 1201 1250 1860 .030 .76 .96 24.38 1.33 33.78
18 • Industrial Cables
Rip Cord
Drain Wires
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.84
Part Numbers
No.
8 AWG 6 AWG 4 AWG 3 AWG 2 AWG
of (7 Strand) (7 Strand) (7 Strand) (7 Strand) (7 Strand)
Cond.
600V 1000V 600V 1000V 600V 1000V 600V 1000V 600V 1000V
2 21650 21450 21653 21453 21656 21456 21659 21459 21662 21462
3 21651 21451 21654 21454 21657 21457 21660 21460 21663 21463
4 21652 21452 21655 21455 21658 21458 21661 21461 21664 21464
Part Numbers
No.
1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG
of (19 Strand) (19 Strand) (19 Strand) (19 Strand) (19 Strand)
Cond.
600V 1000V 600V 1000V 600V 1000V 600V 1000V 600V 1000V
2 21665 21465 21668 21468 21671 21471 21674 21474 21677 21477
3 21666 21466 21669 21469 21672 21472 21675 21475 21678 21478
4 21667 21467 21670 21470 21673 21473 21676 21476 21679 21479
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.85
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.86
Rip Cord
-25°C Installed
-40°C to +90°C (Dry) (75°C Wet)
Rip Cord
-25°C Installed
-40°C to +90°C (Dry) (75°C Wet)
Rip Cord
-25°C Installed
-40°C to +90°C (Dry) (75°C Wet)
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.87
Class B stranded bare copper conductors, The combined use of Kellems grips
cross-link polyethylene insulation, bare and pulling eyes is recommended.
copper ground wire, PVC inner jacket,
aluminum steel interlocking armor, PVC
Rip Cord outer jacket. Design Advantages
PVC Inner Jacket ● Galvanized steel interlocking armor
available as an option. Insulation Properties
Interlocked Armor
PVC Outer Jacket XLPE Insulation ● High tensile strength
● Impact- and crush-resistant
Voltage Rating
● Heat-resistant
Introduction 18 to 16 AWG — 600V ACIC
● Excellent elongation
14 to 8 AWG — 600 Volts
Belden® Teck90 and ACIC cables are
● Moisture-resistant
designed to meet demanding industrial 14 to 4/0 AWG — 1000 Volts
needs by combining rugged durability and ● Good low temperature properties
corrosion resistance with flexibility and
easy handling. Temperature Rating Electrical Properties
Teck90 and ACIC Cables are available in ● High insulation resistance
-40°C to 90°C (Dry/Wet)
a wide range of in-stock and custom
● Low dielectric loss
constructions to meet the needs of pulp -25°C installed
and paper, chemical, petroleum and other ● High dielectric strength
demanding industrial and resource industry
environments. They are ideal for use in Application Other Features
wet or dry areas; ventilated, non-ventilated
Teck90 and ACIC are general-purpose ● Corrosion-resistant
or ladder-type cable troughs; ventilated
flexible cableways; and for direct burial. cables used in the pulp and paper, mining, ● Versatile and flexible
petroleum and chemical industries as well
Belden Teck90 Cable is marked with “FT4,” as in commercial buildings. ● Provides cost savings as conduit
“HL” designations, and cable constructions and ducts are not required
are certified to CSA Standard C22.2#131 Teck90 and ACIC may be used under
the following conditions: ● ACIC has a blue jacket
and C22.2#174 for use in a wide range of
hazardous locations. Both inner and outer ● Exposed or concealed wiring ● Rip cord for inner jacket
jackets meet the acid gas evolution in dry or wet conditions
requirement of 14% maximum required by
● In ventilated, non-ventilated or
CSA Standard C22.2#0.3 Clause 4.31. Specifications
ladder-type cable trays in dry
Custom cables are available upon request. or wet conditions ● CSA Standard C22.2#131
● On walls or beams ● CSA Standard C22.2#174
● Directly buried “Cables and Cable Glands for Use
in Hazardous Locations”
● CEC Class I, Division I locations
● CSA Standard C22.2#0.3 Clause 4.31
“Low Acid Gas”
Minimum Bending Radius ● CSA Standard C22.2#0.3 Clause 4.11.4
“Cables with FT4 Marking”
12 times the overall cable diameter 18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.88
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
18 AWG Stranded (7x26) Bare Copper Conductors • 18 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .030″ (.76mm) XLPE Insulation • PVC Inner Jacket • Blue PVC Outer Jacket
CSA C22.2#239 29030 2 163 243 .32 8.13 .52 13.21 .62 15.75 44 196 7.4 187.96
FT4 Flame Test 29031 3 177 263 .34 8.64 .54 13.72 .64 16.26 66 294 7.6 193.04
29032 4 195 290 .37 9.40 .57 14.48 .67 17.02 88 392 8.0 203.20
29033 5 219 326 .41 10.41 .61 15.49 .71 18.03 110 490 8.5 215.90
29034 6 239 356 .45 11.43 .65 16.51 .75 19.05 132 587 9.0 228.60
29035 7 245 365 .45 11.43 .65 16.51 .75 19.05 154 685 9.0 228.60
Rip Cord 29036 8 266 396 .48 12.19 .68 17.27 .78 19.81 176 783 9.3 236.22
29038 10 331 493 .56 14.22 .76 19.30 .87 22.10 220 979 10.6 269.24
29040 12 353 525 .62 15.75 .82 20.83 .93 23.62 264 1175 11.1 281.94
29043 15 401 597 .65 16.51 .85 21.59 .96 24.38 330 1469 11.5 292.10
29048 20 466 694 .73 18.54 .93 23.62 1.04 26.42 440 1958 12.4 314.96
29053 25 589 877 .79 20.07 1.05 26.67 1.16 29.46 550 2448 13.9 353.06
29058 30 698 1039 .88 22.35 1.14 28.96 1.25 31.75 660 2937 15.0 381.00
29068 40 827 1231 .97 24.64 1.23 31.24 1.35 34.29 880 3916 16.2 411.48
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas 29078 50 965 1436 1.09 27.69 1.35 34.29 1.47 37.34 1100 4895 17.6 447.04
16 AWG Stranded (7x24) Bare Copper Conductors • 16 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .030″ (.76mm) XLPE Insulation • PVC Inner Jacket • Blue PVC Outer Jacket
CSA C22.2#239 29017 2 202 301 .34 8.64 .54 13.72 .65 16.51 70 312 7.7 195.58
FT4 Flame Test 29004 3 221 329 .36 9.14 .56 14.22 .66 16.76 105 467 7.9 200.66
29018 4 242 360 .39 9.91 .59 14.99 .70 17.78 140 623 8.3 210.82
29019 5 264 393 .42 10.67 .62 15.75 .73 18.54 175 779 8.6 218.44
29005 6 292 435 .46 11.68 .66 16.76 .77 19.56 210 935 9.1 231.14
29020 7 314 467 .47 11.94 .67 17.02 .77 19.56 245 1090 9.2 233.68
Rip Cord 29021 8 364 542 .50 12.70 .70 17.78 .80 20.32 280 1246 9.6 243.84
29022 10 412 613 .61 15.49 .81 20.57 .92 23.37 350 1558 10.9 276.86
29006 12 441 656 .63 16.00 .83 21.08 .94 23.88 420 1869 11.2 284.48
29023 15 502 748 .68 17.27 .88 22.35 1.00 25.40 525 2336 11.9 302.26
29007 20 636 947 .77 19.56 1.03 26.16 1.13 28.70 700 3115 13.7 347.98
29024 25 845 1258 .89 22.61 1.15 29.21 1.26 32.00 875 3894 15.1 383.54
29008 30 922 1372 .94 23.88 1.20 30.48 1.30 33.02 1050 4673 15.8 401.32
29009 40 1109 1650 1.06 26.92 1.32 33.53 1.41 35.81 1400 6230 17.3 439.42
29016 50 1306 1944 1.19 30.23 1.45 36.83 1.54 39.12 1750 7788 18.8 477.52
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas 29025 60 1390 2070 1.27 32.26 1.53 38.86 1.66 42.16 2100 9345 19.9 505.46
XLPE = Cross-linked Polyethylene
Color Code: #1 conductor is white; remaining conductors are black with number coding. Other color codes available upon request.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.89
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
14 AWG Stranded (7x22) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .030″ (.76mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5500 2 198 296 .36 9.14 .56 14.22 .66 16.76 108 481 7.8 198.12
FT4 Flame Test C5501 3 222 331 .39 9.91 .58 14.73 .66 16.76 162 721 8.2 208.28
C5502 4 251 375 .42 10.67 .62 15.75 .71 18.03 216 961 8.5 215.90
C5503 5 284 424 .47 11.94 .66 16.76 .74 18.80 270 1202 9.0 228.60
C5504 6 317 473 .51 12.95 .70 17.78 .78 19.81 324 1442 9.5 241.30
C5505 7 331 494 .51 12.95 .70 17.78 .78 19.81 378 1682 9.5 241.30
Rip Cord C5506 8 414 618 .58 14.73 .77 19.56 .86 21.84 432 1922 10.4 264.16
C5508 10 510 761 .67 17.02 .93 23.62 .95 24.13 540 2403 12.3 312.42
C5510 12 551 822 .69 17.53 .95 24.13 .97 24.64 648 2884 12.6 320.04
C5513 15 636 949 .77 19.56 1.03 26.16 1.11 28.19 810 3605 14.1 358.14
C5518 20 810 1209 .90 22.86 1.16 29.46 1.24 31.50 1080 4806 15.1 383.54
C5523 25 948 1415 .90 22.86 1.24 31.50 1.33 33.78 1350 6008 16.1 408.94
C5528 30 1047 1563 1.05 26.67 1.30 33.02 1.40 35.56 1620 7209 16.8 426.72
C5529 40 1310 1955 1.20 30.48 1.42 36.07 1.51 38.35 2160 9612 18.3 464.82
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas C6064 50 1620 2418 1.35 34.29 1.60 40.64 1.66 42.16 2700 12015 20.5 520.70
12 AWG Stranded (7x20) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .030″ (.76mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5530 2 225 336 .41 10.41 .60 15.24 .69 17.53 172 765 8.3 210.82
FT4 Flame Test C5531 3 261 390 .43 10.92 .62 15.75 .70 17.78 258 1148 8.6 218.44
C5532 4 301 449 .47 11.94 .66 16.76 .73 18.54 344 1531 9.1 231.14
C5533 5 348 519 .52 13.21 .71 18.03 .78 19.81 430 1914 9.1 231.14
C5534 6 435 649 .59 14.99 .78 19.81 .86 21.84 516 2296 10.5 266.70
C5535 7 450 672 .59 14.99 .78 19.81 .86 21.84 602 2679 10.5 266.70
Rip Cord C5536 8 506 755 .64 16.26 .83 21.08 .92 23.37 688 3062 11.1 281.94
C5538 10 633 945 .75 19.05 1.01 25.65 1.02 25.91 860 3827 13.3 337.82
C5540 12 696 1039 .77 19.56 1.03 26.16 1.12 28.45 1032 4592 13.5 342.90
C5543 15 823 1228 .90 22.86 1.16 29.46 1.24 31.50 1290 5741 15.1 383.54
C5548 20 1035 1545 .99 25.15 1.25 31.75 1.34 34.04 1720 7654 16.5 419.10
C5553 25 1230 1836 1.10 27.94 1.36 34.54 1.45 36.83 2150 9568 17.6 447.04
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas C5558 30 1390 2075 1.20 30.48 1.46 37.08 1.51 38.35 2580 11481 17.6 447.04
XLPE = Cross-linked Polyethylene
Color Code: 2 conductors — Black, White (If required, a Red conductor can be used in place of White.)
3 conductors — Black, Red, Blue (If required, a White conductor can be used in place of Blue.)
4 conductors — Black, Red, Blue, White
5 or more conductors — Black and numbered
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.90
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
10 AWG Stranded (7x18) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .030″ (.76mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5560 2 278 415 .48 12.19 .66 16.76 .72 18.29 296 1317 8.9 226.06
FT4 Flame Test C5561 3 327 488 .50 12.70 .70 17.78 .75 19.05 444 1976 9.2 233.68
C5562 4 405 604 .57 14.48 .77 19.56 .79 20.07 592 2634 10.1 256.64
C5563 5 487 727 .63 16.00 .83 21.08 .93 23.62 740 3293 11.5 292.10
C5564 6 556 830 .68 17.27 .88 22.35 .93 23.62 888 3952 11.5 292.10
C5565 7 627 936 .69 17.53 .89 22.61 .99 25.15 1036 4610 11.8 299.72
Rip Cord C5566 8 739 1103 .74 18.80 .94 23.88 1.00 25.40 1184 5269 12.4 314.96
C5568 10 964 1439 .84 21.34 1.10 27.94 1.24 31.50 1480 6586 14.4 365.76
C5570 12 1067 1593 .93 23.62 1.19 30.23 1.26 32.00 1776 7903 15.6 396.24
C5573 15 1297 1936 .99 25.15 1.25 31.75 1.37 34.80 2220 9879 16.3 414.02
C5578 20 1546 2307 1.13 28.70 1.39 35.31 1.47 37.34 2960 13172 16.9 429.26
C5579 25 1802 2690 1.26 32.00 1.52 38.61 1.60 40.64 3700 16465 19.7 500.38
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas C5580 30 2142 3197 1.34 34.04 1.60 40.64 1.66 42.16 4440 19758 20.6 523.24
8 AWG Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .045″ (1.14mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5583 2 407 607 .59 14.99 .78 19.81 .86 21.84 384 1709 10.6 269.24
FT4 Flame Test C5581 3 471 703 .63 16.00 .83 21.08 .90 22.86 576 2563 10.8 274.32
C5582 4 606 904 .69 17.53 .89 22.61 .97 24.64 768 3418 12.5 317.50
Rip Cord
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.91
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
Composite 14 AWG Stranded (7x22) and 12 AWG Stranded (7x20) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .031″ (.79mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6054 3c/14 369 549 .560 14.22 .75 19.05 .89 22.61 424 1886 8.4 213.36
FT4 Flame Test 3c/12
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG Stranded (7x22) and 10 AWG Stranded (7x18) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .031″ (.79mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6051 3c/14 432 643 .600 15.24 .82 20.83 .92 23.37 608 2705 9.0 228.60
FT4 Flame Test 3c/10
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG Stranded (7x22) and 8 AWG Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .046″ (1.17mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6059 3c/14 608 905 .700 17.78 .89 22.51 .98 24.92 1160 5160 9.8 248.92
FT4 Flame Test 3c/8
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
Composite 14 AWG Stranded (7x22) and 6 AWG Stranded (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .061″ (1.55mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6060 3c/14 849 1264 .810 20.57 1.06 27.00 1.16 29.41 1700 7562 11.6 294.64
FT4 Flame Test 3c/6
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
XLPE = Cross-linked Polyethylene
Color Code: 2 conductors — Black, White (If required, a Red conductor can be used in place of White.)
3 conductors — Black, Red, Blue (If required, a White conductor can be used in place of Blue.)
18 • Industrial Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.92
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
14 AWG Stranded (7x22) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .045″ (1.14mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5701 3 251 374 .47 11.94 .67 17.02 .73 18.54 162 721 9.2 233.68
FT4 Flame Test C5702 4 301 448 .51 12.95 .71 18.03 .81 20.57 216 961 9.7 246.38
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
12 AWG Stranded (7x20) Bare Copper Conductors • 14 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .045″ (1.14mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5730 2 253 377 .48 12.19 .68 17.27 .74 18.80 172 765 9.3 236.22
FT4 Flame Test C5731 3 291 433 .51 12.95 .71 18.03 .76 19.30 258 1148 9.7 246.38
C5732 4 368 548 .59 14.99 .75 19.05 .85 21.59 344 1531 10.8 274.32
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
10 AWG Stranded (7x18) Bare Copper Conductors • 12 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .045″ (1.14mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5760 2 285 424 .56 14.22 .79 19.99 .70 17.71 296 1317 10.3 261.62
FT4 Flame Test C5761 3 389 581 .59 14.99 .79 20.07 .85 21.59 444 1976 10.3 261.62
C5762 4 460 687 .65 16.51 .85 21.59 .90 22.86 592 2634 11.5 292.10
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
8 AWG Stranded (7x16) Bare Copper Conductors • 10 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .045″ (1.14mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5583 2 407 607 .59 14.99 .78 19.81 .86 21.84 384 1709 10.6 269.24
FT4 Flame Test C5581 3 471 703 .63 16.00 .83 21.08 .90 22.86 576 2563 10.8 274.32
C5582 4 606 905 .69 17.53 .89 22.61 .97 24.64 768 3418 12.5 317.50
Rip Cord
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.93
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
6 AWG Stranded (7x14) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .060″ (1.53mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5590 2 567 844 .73 18.54 .99 25.15 1.10 27.94 610 2713 12.8 325.12
FT4 Flame Test C5591 3 685 1019 .78 19.81 1.04 26.42 1.15 29.21 915 4072 13.4 340.36
C5592 4 927 1380 .89 22.61 1.15 29.21 1.24 31.50 1220 5429 14.9 378.46
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
4 AWG Stranded (7x12) Bare Copper Conductors • 8 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .060″ (1.53mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5601 3 961 1430 .91 23.11 1.17 29.72 1.23 31.24 1455 6475 15.2 386.08
FT4 Flame Test C5602 4 1202 1794 .91 23.11 1.25 31.75 1.33 33.78 1940 8633 16.2 411.48
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
3 AWG Stranded (7x11) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .060″ (1.53mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5611 3 1126 1681 .97 24.64 1.23 31.24 1.30 33.02 1836 8170 15.8 401.32
FT4 Flame Test
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
2 AWG Stranded (7x10) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .060″ (1.53mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5621 3 1291 1927 1.02 25.91 1.28 32.51 1.37 34.80 2316 10302 16.5 419.10
FT4 Flame Test C5622 4 1691 2524 1.12 28.45 1.38 35.05 1.48 37.59 3088 13736 17.7 449.58
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
XLPE = Cross-linked Polyethylene
18 • Industrial Cables
Color Code: 2 conductors — Black, White (If required, a Red conductor can be used in place of White.)
3 conductors — Black, Red, Blue (If required, a White conductor can be used in place of Blue.)
4 conductors — Black, Red, Blue, White
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.94
Maximum Minimum
No. Cable Weight Inner Jacket OD Armor OD Outer Jacket
Part Pull Tension Bend Radius
Description of
No. Cond. Lbs./ kg/km Inch mm Inch mm Inch mm Lbs. N Inch mm
1000 Ft.
1 AWG Stranded (19x14) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .080″ (2.03mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5625 3 1620 2411 1.25 31.75 1.51 38.35 1.59 40.39 1980 8807 19.1 485.14
FT4 Flame Test C5626 4 2173 3234 1.34 34.04 1.57 39.88 1.68 42.67 2680 11921 20.2 513.08
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
1/0 AWG Stranded (19x12) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .080″ (2.03mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5627 3 1912 2854 1.34 34.04 1.60 40.64 1.67 42.42 3582 15940 20.0 508.0
FT4 Flame Test 6164 4 2514 3742 1.44 36.58 1.67 42.42 1.78 45.21 4700 20906 21.4 543.56
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
2/0 AWG Stranded (19x11) Bare Copper Conductors • 6 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .080″ (2.03mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 C5635 3 2300 3423 1.40 35.56 1.63 41.40 1.74 44.20 4200 12010 20.9 530.86
FT4 Flame Test 6157 4 3039 4523 1.55 39.37 1.84 46.74 1.95 49.53 5500 24465 23.4 594.36
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
3/0 AWG Stranded (19x10) Bare Copper Conductors • 4 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .080″ (2.03mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6163 3 2905 4324 1.51 38.10 1.80 45.72 1.91 48.26 5020 11121 22.9 579.12
FT4 Flame Test 6179 4 3700 5506 1.67 42.42 1.96 49.78 2.07 52.58 6500 28913 24.8 629.92
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
4/0 AWG Stranded (19x9.5) Bare Copper Conductors • 4 AWG Bare Copper Ground Wire
Aluminum Interlocked Armor • .080″ (2.03mm) XLPE Insulation • PVC Inner Jacket • Black PVC Outer Jacket
CSA C22.2#131 6193 3 3450 5134 1.63 41.40 1.92 48.77 2.03 51.56 6650 29580 24.4 619.76
FT4 Flame Test
\
Rip Cord
HAZ LOC
CSA C22.2#0.3 Clause 4.31 Low Acid Gas
XLPE = Cross-linked Polyethylene
Color Code: 3 conductors — Black, Red, Blue (If required, a White conductor can be used in place of Blue.)
4 conductors — Black, Red, Blue, White
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.95
Cable Specifications
Part
Description AWG Stranding Shield
● CSA C22.2 #38 Type TC Number
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.96
Technical Information
Gland Information for Armored Cables
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.97
Technical Information
LSZH Jacketed Cables and Hazardous Locations Reference
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m
INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.98
Technical Information
FT4/IEEE 1202/
Test UL-1685 (UL-1581) IEEE 383-1974 IEC 323-3 ICEA T-29-520
IEEE 383-2003
Flame Test Chamber Vertical Tray Vertical Tray Vertical Tray Vertical Tray Vertical Tray
Burner Type Ribbon gas burner Ribbon gas burner Ribbon gas burner Ribbon gas burner Ribbon gas burner
Theoretical Heat Input 70,000 BTU/hr 70,000 BTU/hr 70,000 BTU/hr 70,000 BTU/hr 210,000 BTU/hr
Burner Positioning horizontal 3″ 20° up from horizontal 3″ horizontal horizontal 8-1/4″
from samples horizontal 2.95″ from samples 2.95″ from from cable surface
from cable surface 18″ above cable surface 12-1/4″ above
18″ from tray base 11.8" above floor tray bottom 23.6″ above floor tray base
Tray Dimensions 8′ length 9.84′ length 8′ length 11.5′ length 8′ length
12″ width 11.81″ width 12″ width 19.7″ width 12″ width
3″ side flanges 2.85″ side flanges 3″ side flanges none 3″ side flanges
Sample Spacing 1/2 cable diameter 1/2 cable diameter 1/2 cable diameter lesser of 1/2 cable 1/2 cable diameter
diameter and .78″
Duration of 20 minutes 20 minutes 20 minutes 20 minutes 20 minutes
Flame Application
Mode of Failure Cable blistering or Cable char has Cable blistering or Cable charring has Cable blistering or
charring has reached exceeded a length charring has reached reached a height of charring has reached
the top of the sample of 4.92′. the top of the sample 98.4″ above the the top of the sample
after the cable has after the cable has bottom of the burner. after the cable has
self-extinguished. self-extinguished. self-extinguished.
F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m