Arc Flash Report
IEEE 1584:2018
W
Project information
IE
Date 2025-04-02
Input
V
Standard IEEE 1584-2018
SE
E
Voltage 480 V
U
Fault current 20 kA
L
R Normal arcing current Reduced arcing current
IA
Arcing time
C
100 ms 200 ms
P
ER
Equipment type MCC or Panel
M
Working distance 18 in
M
E
Height Width Depth
O
Enclosure size
14 in 12 in 8 in
C
N
E
Electrode confguration
O
R
TI
FO
VCB - Vertical in box
R
IP
T
R CR
O
F
N
Conductor gap 25 mm
R UB
K
TE S
Results
A
A
M
Normal arcing current Reduced arcing current
W E
Arcing current 15.33 kA 13.44 kA
S
VE A
Incident energy 2.4 cal/cm² 4.22 cal/cm²
A
O CH
Arc flash boundary 2 ft, 4 in 3 ft, 4 in
EM R
PPE category 1 2
R PU
TO SE
EA
PL