Operation Manual
ARD-3P Elevator Automatic Rescue Device
1. Introduction
ARD used to provide back-up emergency power supply to lift frequency control system. It has significant advantages such as
installation convenience, wiring simple, high performance cost ratio, etc. In case of power failure, ARD run automatically in the
set time, make the lift car run slowly to the nearby floor to save passengers.
ARD- 3 P 1 1 0 - 4
4:AC380V
2:AC220V
Automatic Rescue Device
037: Apply to inverter below 3.7 KW
3-phase 075: Apply to inverter below 7.5 KW
110: Apply to inverter below 11 KW
150: Apply to inverter below 15 KW
180: Apply to inverter below 18.5 KW
220: Apply to inverter below 22 KW
2. Attentions before installation
2.1. Please be sure to read this manual carefully In order to use ARD
400
correctly.
2.2. This manual applies for the 3-phase output ARD.
2.3. Must be take safety measures before using ARD as follows in order ARD
to avoid people and equipment accident:
Run Switch
2.3.1 Cut off the power supply before installation.
550
2.3.2. Please make sure that the elevator various equipment
grounding good.
2.3.3 In order to prevent the installation or maintenance personnel
cause harm, avoid damage to elevator equipment, please
follow the instruction for use ARD.
2.3.4 Make sure the electric system contact correct between ARD
and elevator. color:
sapphire
190
2.3.5 ARD must be installed by elevator professional technician. or
beige
2.4. This manual introduces ARD’s installation and connection steps,
signal terminal.
2.5. We will not notify if the introduction has changed.
1/3
Operation Manual
3. Terminal definition
3.1. In process of rescue, if it is found that the phase lose protection relay of elevator control cabinet malfunction, shorting
circuit the output contact of the phase lose protection relay by using “Rescue instruction 1”.
3.2. In case of the rescue finish signal can’t be provided by elevator control system, using “Rescue instruction 2” to prevent the
elevator door shutdown automatically after the door opened in floor level, such as connecting to UPS running signal, the
door open button, the light curtain, etc. Automatic running direction selecting function can be used in some elevator
control system such as MONARCH NICE-3000, NEWSTEP AS-380, etc.
4. Installation and connection
4.1. Installation ARD must be after lift running normal. Place ARD in the appropriate location nearby the elevator control panel.
The stent may be used in the machine-room-less lift.
4.2. Disconnecting the elevator grid power. Shut off the power switch on the side of ARD. Connecting the grid power to
terminal “L1, L2, L3” of ARD, connecting “T1, T2, T3” of ARD to the power input terminal of the elevator control panel.
Don’t connect the grid power to the elevator control panel directly. ARD may be damaged and accidental injury if
connection error.
4.3. Typical connection mode:
L1 KM T1 L1 L1 KM T1 L1
L2 T2 L2 L2 T2 L2
L3 T3 L3 L3 T3 L3
Door lock 3
Rescue finish signal UPS running
relay NO. Rescue instruction 2
terminal
6 4
7 ELEVATOR ELEVATOR
HH-ARD-3P CONTROL CONTROL
8 HH-ARD-3P
PANEL PANEL
If the elevator has not the UPS running function, perform
If the elevator has the UPS running function, perform rescue
rescue by using the elevator auto-running flat in low speed
by using this function. No need the rescue finish signal in
function. In this case, the rescue finish signal must be
this case, .
connected.
4.4. Closing the grid power switch after checking all connection. Shut on the power switch on the side of ARD. The green
charging LED flashing that indicating ARD is in charging mode.
4.5. Some parameters of the elevator control system may be adjusted. You can consult our company.
4.6. Cutting off the power grid supply. The green LED and the red LED light up simultaneously.
4.7. The green LED flashing and the red LED extinguish after setting time. ARD provide power to the elevator control panel. If
ARD receive the Rescue finish signal or setting time arriving, ARD stops output power. The red LED light on and the
green LED extinguish. ARD will be in charging mode again if the grid power recover.
2/3
Operation Manual
5. LED Indication
State The red LED The green LED
Standby and charging mode Light off flashing
Power failure and waiting setting time Light on Light on
Providing backup power flashing Light off
Rescue completed Light on Light off
6. Choosing stop time by the dial switch SW1 when the rescue finish signal used
1 Bit 1 = Off Bit 2 = Off Stop output after the rescue finish signal appear 5s
2 Bit 1 = Off Bit 2 = On Stop output after the rescue finish signal appear 10s
3 Bit 1 = On Bit 2 = Off Stop output after the rescue finish signal appear 15s
4 Bit 1 = On Bit 2 = On Stop output after the rescue finish signal appear 20s
ARD will stop output after about 5min. if the rescue finish signal don’t appear.
7. Take the floor level signal as the rescue finish signal
ARD Terminal 5 6 7 8
Elevator controller
24V Floor level signal
(lower level)
8. Maintaining
8.1. Battery must be charged in first using or after a long time unused.
8.2. Please replace the battery if finding battery leakage or other abnormal.
8.3. Propose discharging battery per 3-6 month.
8.4. If the lift need repair, please be sure to close the outside switch of ARD, to prevent accidental injuries.
9. Specification
End