30kVA HipulseD
30kVA HipulseD
SR.NO. DESCRIPTION
1 SCOPE OF SUPPLY
2 TECHNICAL SPECIFICATIONS
3 GENERAL ARRANGEMENT DETAILS
4 DISPLAY & MIMIC DETAILS
5 DESIGNATION OF PARTS AND SINGLE LINE DIAGRAM
6 SYSTEM DESCRIPTION
7 BILL OF MATERIAL-MAJOR COMPONENTS
8 ELECTRICAL WIRING DIAGRAM
9 BATTERY DETAILS
10 HEAT LOSS CALCULATION
11 QUALITY ASSURANCE PLAN
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited)
VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
SCOPE OF SUPPLY
SUCH 1 SET
1 UPS, Hipulse D, 3 X 1, 30 kVA, Input 415V, Output 230 V AC, 50 Hz with 02 Nos
A. SPD at Input
2 Parallel Kit 01 No
6 MODBUS 01 No
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited)
VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
TECHNICAL SPECIFICATIONS
A. UPS SYSTEM
a) GENERAL
1 Make Vertiv Energy Private Limited
2 Type Double Conversion True On-line UPS system.
3 Reference standard IEC 62040-3
4 No. of cabinets 03 Nos.
Dimension of UPS System (Rectifier + Charger+ UPS1 &2 : W1000mm X D900mm X H1870mm
5
Inverter + Static Switch) (W x D x H) SCVS: W600mm X D900mm X H1850mm
6 Overall dimension (W x D x H) W2600mm X D900mm X H1870mm
7 Ambient temperature 40°C
8 Configuration Parallel Redundant
b) RECTIFIER / BATTERY CHARGER
3Ph, Full Wave, Advanced PFC rectifier with
1 Type
IGBT based charger.
2 Input voltage 415 V AC 3 Ph, 3 W (+10% /-10% )
3 Frequency ± % variation 50 Hz ±10%
4 Regulation at Nominal Voltage ±1%
5 Ripple content in DC output with battery <1%
Ripple content in DC output without battery at
6 <1%
charger output
7 Power factor at rated load ≥0.92 at full load and Nominal input Voltage
c) STATIC INVERTER
1 Type IGBT Based PWM technology
2 AC output voltage 230V
3 AC output voltage ± % Regulation ±1%
4 Frequency ± variation 50 Hz (+/- 0.1Hz)
5 Rated full load capacity at 0.9 power factor 30kVA/ 24kW
6 Total harmonic content at 100% linear load <2%
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
load
8 Overload capacity i) 110% for 60 Min
ii) 125% for 10 Min
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited)
VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
iii) 150% for 1 Min
9 Slew rate 0.2 Hz/ Sec
d) STATIC TRANSFER SWITCH
1 Type SCR-SCR Based
2 Rated voltage 1600V
3 Rated current 92A/95A/107A
4 Transfer time No break in Sync mode
<10 msec. in async. Mode
5 Overload capacity i) 110% for 60 Min
ii) 125% for 10 Min
iii) 150% for 60 sec
iv) 1000% for 100msec.
e) MANUAL BYPASS SWITCH
1 Type Load Break Switch
250A(2X125A ,2P IN //EL) LOAD
2 Rated current
BREAK SWITCH
B. BATTERY
1 Type SMF _120AH_12V
2 Rated voltage 384 V DC
3 No. of Batteries. 32 No's (12 Volt Each Block )
4 Minimum cell voltage during duty cycle ECV 1.75V/cell
5 Maximum charging current 12A
6 Battery Backup time 60 min
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited)
VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
TECHNICAL SPECIFICATIONS- SCVS
SR NO DESCRIPTION SPECIFICATIONS
1 Make Vertiv Approved
2 Type Servo
3 Ambient temp 40°C
4 No. of phases 3Ph -1Ph
5 Frequency 50 Hz
6 Capacity 30kVA
7 Input Voltage 415 V AC 3 Ph, 3 W (+10% /-10%)
8 AC Rated Output Voltage 230V (+/-1%)
9 Frequency ± % Variation 50 Hz (+/-5%)
10 Over Load Protection 110% for 10 mins
11 Input Fault Level 10kA
12 Others
a. Ingress protection : IP-41
b. Paint Shade : RAL 7035
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
1 2 3 4 5 6 7 8
155MK22-FV
TOP VIEW
A A
PANEL DIMENSIONS :-
B B
MATERIAL :-
UPS SCVS
Input OK Inverter ON Load On Inverter To Load Input OK Inverter ON Load On Inverter To Load
Input Input
C C
PAINTING DETAILS FOR FRAME & BASE FRAME :-
#
# #
E E
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm.
FRONT VIEW DIAGRAM
155MK22-FV 00
TOLERANCE ± 0.5 SHEET 1 OF 3
UNLESS OF 2X30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
B B
SCVS UPS 1 UPS 2
C C
D D
E E
FRONT SIDE
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm.
FOUNDATION DETAILS
155MK22-FD 00
TOLERANCE ± 0.5 SHEET 2 OF 3
UNLESS OF 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
COPPER ALUMINIUM
C C
# EARTHING BUSBAR
D D
#
BATTERY
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm.
TERMINATION DETAILS
155MK22-TB 00
TOLERANCE ± 0.5 SHEET 3 OF 3
UNLESS OF 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
Description of key functions
When pressed, you can changeover from group parameters to group alarms.
SHIFT KEY Also if acknowledge key is pressed followed by shift key, you get into setting
mode. In this mode you can view & alter Date & Time parameters. To
change press shift key, parameters will be selected then to change setting
use UP or DOWN key. To skip press shift key
UP KEY
a) To increase any value during setting.
b) To see the set of parameters or group which is UP in order to that which is
displayed presently
ACKNOWLEDGE KEY
To silence alarm in case of any fault.
INVERTER ON KEY
a) To turn ON Inverter.
I b) To reset Inverter fault after corrective action is taken.
With Date & Time parameters on LCD display, Press first acknowledge key,
RTC SETTING
then shift key to enter in RTC setting mode. Use UP/ DOWN key change the
setting of day, date & time. SHIFT key is used to select day, date & time.
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
STORED FAULTS In alarm group, using DOWN key, we can see the stored faults in that group.
To see previous fault press DOWN key & see recent fault stored press UP key
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
1) INDICATIONS ON MIMIC :-
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
2) METERING :-
• Parameters displayed on LCD display :-
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
3) FAULT INDICATED ON LCD DISPLAY:-
Inverter Off
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
Fan Fail
d) Bypass Fan Fail
Load on manual byp
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
B) PROTECTIONS :-
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
C) POTENTIAL FREE CONTACTS :-
One relay contact for each (Rating : 230V AC, 1 Amp)
D) CONNECTIVITY: -
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 12 08 19
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
1 2 3 4 5 6 7 8
155MK22-SLD
A A
B UPS 1 B
BATTERY
C C
UPS 2
D D
BATTERY
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-SLD 00
SINGLE LINE DIAGRAM
TOLERANCE ± 0.5 SHEET 1 OF 1
UNLESS OF 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. 31.03.22
(formerly Emerson Network Power (India) Private Limited) VRS
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
SYSTEM DESCRIPTION
Scope
The UPS shall provide high quality conditioned AC power to the equipment loads. The UPS shall automatically provide
continuity of electrical power, in case of failure of mains (AC utility source) within the defined limits. The system consists of
a solid state Converter with Battery Charger, PWM Inverter, Automatic static bypass transfer circuit, and integral
maintenance bypass circuit.
There can be various configurations of UPS systems in single phase or three phase output
Two UPS are connected in parallel redundant configuration. The outputs of two systems are paralleled, paralleling unit to
form common AC bus. In case of failure of one UPS, the entire load is transferred to the other one. Thus both the UPS
should be able to provide 100% load individually. In case of failure of both the systems (mains-fail & battery-low) the load
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
is automatically transferred to bypass source via static switch without any interruption.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
On rectification of the fault or mains resumption, the load is retransferred. Both UPS is backed by a separate battery.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
MAJOR BILL OF MATERIAL - UPS
SR. QTY/
PART NO DESCRIPTION SPECIFICATION
NO. UPS
1 L3 INPUT REACTOR 3PH INPUT CHOKE 1
OUTPUT TRANSFORMER
2 TM2 PRI:0-280V, SEC:0-240V, 30kVA 1
(WITH INBUILT CHOKE)
3 L6 PARALLEL CHOKE PARALLEL CHOKE 1
THYRISTOR DIODE MODULE
4 VTD1 TO VTD3 56A/57A/58A/1600V 3
FOR RECTIFIER BRIDGE
5 VQM5 IGBT FOR BUCK-BOOST 200A / 1200V 1
6 VQM1 & VQM3 IGBT FOR INV.BRIDGE 300A / 1200V 2
SCR-SCR MODULE IN INV
7 VTT1 & VTT2 92A/95A/107A/1600V 2
PATH & BYP STSW
8 F1 TO F3 FUSES AT INPUT 160AMP (SEMICONDUCTOR FUSE) 3
9 F4,F4A FUSE AT BATTERY PATH 200AMP (SEMICONDUCTOR FUSE) 2
10 F6 FUSE AT BYPASS PATH 200AMP (SEMICONDUCTOR FUSE) 1
11 Q1 INPUT BREAKER MCCB 60/63A 3P AC/DC 1
12 Q2 BATTERY BREAKER MCCB 100A 3P AC/DC 1
250A(2X125A ,2P IN //EL) LOAD
13 S8 OUTPUT SWITCH 1
BREAK SWITCH
250A(2X125A ,2P IN //EL) LOAD
14 S1 MANUAL BYPASS SWITCH 1
BREAK SWITCH
250A(2X125A ,2P IN //EL) LOAD
15 S10 BYPASS INPUT SWITCH 1
BREAK SWITCH
16 C8 DC CAPACITOR AT ,INV 10000uFD/350V DC 8
17 C7 DC CAPACITOR AT BATT 10000uFD/315V DC 2
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
APPROVED MAKE LIST
FOR UPS: -
COMPONENT
SR.NO. APPROVED MAKE
DESCRIPTION
POWER YASHO/RISHABH/DATSONS /SS ENTERPRISE /
1
TRANSFORMER Trafomec /Intelux
2 SCR-DIODE MODULE IXYS/SEMIKRON
3 SCR-SCR MODULE IXYS/SEMIKRON
4 IGBT MITSUBISHI/SEMIKRON/INFINEON
5 POWER FUSE GE/EATON/MERSON (FERRAZ)
6 BREAKER(MCCB) ABB/ SCHNEIDER/C & S
7 BREAKER (MCB) LEGRAND/SCHNEIDER/CHINT/NADER
8 POWER SWITCH HPL/SOCOMEC
9 DC CAPACITOR ALCON/ RIFA /ITELCOND
10 AC CAPACITOR EPCOS/ DUCATI
11 FAN ebm NADI/SUNON/NISIKI/HICOOL/ECOFIT
MIRACLE/ ROLLIFLEX/ IND.GLASS /TONY CAB. /
12 POWER CABLES
RR / POLYCAB /FINOLEX
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
TWO YEARS OF MANDATORY SPARES
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
1 2 3 4 5 6 7 8
155MK22-W01
A A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W01 00
POWER WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 1 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W02 00
POWER WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 2 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W03 00
POWER WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 3 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W04 00
POWER WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 4 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
A A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W05 00
POWER WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 5 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
XM15
A TB FOR PFC A
B B
C C
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-W06 00
CONTROL WIRING DIAGRAM
TOLERANCE ± 0.5 SHEET 6 OF 6
UNLESS 2x30kVA HIPULSE D PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS DRAWN NSS 31.03.22
= 30 X 0.8 X 1000
192 X 1.75 X 0.93
= 76.80 Amp.
A4
VERTIV ENERGY PRIVATE LIMITED CHKD.
(formerly Emerson Network Power (India) Private Limited) VRS 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
1 2 3 4 5 6 7 8
155MK22-FV
A +VE TO UPS A
1 2 3 4
BATTERY DETAILS.
5 6 7 8 9 10 11
B B
12 13 14 15 16 17 18
19 20 21 22 23 24 25
-VE TO UPS
26 27 28 29 30 31 32
D D
E E
THIS DOCUMENT IS THE PROPERTY OF
-
PRIOR PERMISSION IS PROHIBITED.
MATERIAL: ALL
VERTIV ENERGY PRIVATE LIMITED.
DIMENSIONS
TITLE :-
IN mm. 155MK22-FV 00
BATTERY ARRANGEMENT FOR
TOLERANCE ± 0.5 SHEET 1 OF 3
UNLESS 120AH - 32NOS. PGP 31.03.22
TREATMENT : HOLES: ±0.2 APPD.
OTHERWISE BS101 (FBCH227)
STATED. ANGLES: ±0.5 CHKD. VRS 31.03.22
F SCALE: NTS
FOR 30 KVA DRAWN NSS 31.03.22
SYSTEM : HIPULSE D
kVA : 30 kVA
BATTERY AH : 120 AH
RECTIFIER OUTPUT POWER =I/P power at inverter + Battery charging power : 31.39 kW
POWER LOSS IN RECTIFIER = Rectifier i/p power - Rectifier o/p power : 0.97 kW
THIS DOCUMENT IS THE PROPERTY OF VERTIV ENERGY PRIVATE LIMITED.
REPRODUCTION OR USE WITHOUT PRIOR PERMISSION IS PROHIBITED.
TOTAL POWER LOSS = Power loss in rectifier + Power loss in inverter : 2.78 kW
A4
VERTIV ENERGY PRIVATE LIMITED CHKD. VRS
(formerly Emerson Network Power (India) Private Limited) 31.03.22
Plot No. 115/2, Ramtekadi Industrial Area, Hadapsar, Pune, Maharashtra, INDIA - 411013 DRAWN NSS 31.03.22
VERSION 0.0
Vertiv Energy Private Limited QUALITY PLAN FOR
UNINTERRUPTED POWER SUPPLY
Project Name:- SATNA CEMENT WORKS System Rating: - HIPULSE D(3X1)-2X30kVA, 230VAC
Name of Customer: - BIRLA CORPORATION LTD. Consignee:- --
REVISION STATUS.
10
9
8
7
6
5
4
3
2
1
31.03.2022 First issue 0
1 2 3 4 5 6 7 8 9 10
Page no. Date Revision details Rev
.no.
Notes: Abbreviations.
1 - Vertiv Energy Private Limited, 2 – Manufacturer, Anand Tambe
3 – Customer/Consultant Narendra Lokhande
P– Performed , R– Review of documents, W – witness
MF.FT - Testing process. Prepared By :- Name & Sign Approved By:- Name & Sign
Notes: Abbreviations.
1 - Vertiv Energy Private Limited, 2 – Manufacturer, Anand Tambe
3 – Customer/Consultant Narendra Lokhande
P– Performed , R– Review of documents, W – witness
MF.FT - Testing process. Prepared By :- Name & Sign Approved By:- Name & Sign
Notes: Abbreviations.
1 - Vertiv Energy Private Limited, 2 – Manufacturer, Anand Tambe
3 – Customer/Consultant Narendra Lokhande
P– Performed , R– Review of documents, W – witness
MF.FT - Testing process. Prepared By :- Name & Sign Approved By:- Name & Sign
Notes: Abbreviations.
1 - Vertiv Energy Private Limited, 2 – Manufacturer, Anand Tambe
3 – Customer/Consultant Narendra Lokhande
P– Performed , R– Review of documents, W – witness
MF.FT - Testing process. Prepared By :- Name & Sign Approved By:- Name & Sign
Sr. Activity Test Method Acceptance Norms Sample size Agency Comments
No. P W R
1 Bought out accessories
1.1 Visual Inspection. Visual Inspection. Specifications. 100% 2 1 3
1.2 Test report verification. 2 1 3
1.3 Functional testing. Electrical Testing. 100% 2 1 3
2 Packing Inspection
2.1 Size and Quantity Visual Inspection. VEPL Drawings & 100% 1 - -
2.2 Packing type. Handling, storage 1 - -
2.3 Marking. Instruction) 1 - -
Note:
1. If Test certificates of major components required, Pls. inform during QAP approval stage.
2. Batteries & UPS accessories applicable as per PO.
Notes: Abbreviations.
1 - Vertiv Energy Private Limited, 2 – Manufacturer, Anand Tambe
3 – Customer/Consultant Narendra Lokhande
P– Performed , R– Review of documents, W – witness
MF.FT - Testing process. Prepared By :- Name & Sign Approved By:- Name & Sign