138kV All Steel H-Frame Structures

The document provides a chart showing maximum allowable spans for 138kV ALL STEEL H-FRAME STRUCTURES based on different design criteria including steel pole strength, specified conductor configurations, tangent structure design, and NESC Heavy Loading guidelines.

Uploaded by

krunal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

138kV All Steel H-Frame Structures

The document provides a chart showing maximum allowable spans for 138kV ALL STEEL H-FRAME STRUCTURES based on different design criteria including steel pole strength, specified conductor configurations, tangent structure design, and NESC Heavy Loading guidelines.

Uploaded by

krunal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

138kV

ALL STEEL H-FRAME STRUCTURES

DESIGN CRITERIA FOR MAXIMUM ALLOWABLE SPANS CHART


29'-4"
7'-4" 7'-4" 7'-4" 7'-4" 1. Allowable spans based on steel pole strength only. Clearances have not been considered.
2. Designs include specified conductor configurations plus 2 x 3/8" diameter EHS shield wires
3. Tangent Structures
4. Based on NESC Heavy Loading with 1/2" radial ice & 4lb/ft2 wind.
7'-0"
5. Steel pole classes as per NESC Grade "B" or CSA Grade "1" guidelines.
C
L 6. Height of cross brace may vary dependant upon groundline and slip-joint location
7. To suit customer's requirem ents, other H-Fram e structure designs may be available for different steel pole
lengths and classes, conductor configurations, line angles and loading criteria.
Allowable spans will change accordingly.

6'-0"

14'-0"

GROUND LINE

10% + 2'-0"