1 Specifications and information contained are subject to change without notice.
Always refer to install manuals provided with equipment and controls before installation.
S-NET1+
Part number:
P nu
ummber: DB81-02331A
DB
B81-023
33
C
Components
Compon
Compo
RS23-to-RS485 converter USB cable Software update cable
2 Software and driver will need to be downloaded from [Link]
S-NET1+
Installation – New Model
¢ RS485 Communication
Connect TX+ and TX- on the converter F1 and F2 of the outdoor unit or at any
other F1/F2 connection point.
£ USB cable
Connect the USB cable to the PC and the converter
DVM+3
¤ Run S-NET 1 plus.
p
3 Outdoor unit
terminal block
2 USB cable TX- Æ F2
1 TX+ Æ F1
3
S-NET1+
LEDs and Connectors
USB cable connection
Control command from S-NET1+
It blinks whenever indoor unit control commands are delivered from S-NET1+.
Communication state between outdoor and indoor units.
It blinks when there exists data flow on the F1-F2 communication lines.
It blinks even when TX+ and TX- on the converter is connected wrong to the
F1-F2 terminals (TX+ Æ F2, TX- Æ F1).
Power-on indication and communication speed setting
When the USB cable is connected with both the PC and the converter , it blinks
every 0.25 seconds indicating high-speed communication setting.
Connect to indoor/outdoor communication lines
TX+ Æ F1
TX- Æ F2
4
S-NET Pro
Main Window
Configuration
C fi ti
Main menu
Automatic start-up report
generation to PDF file
S-NET pro Site Layout
connection information initialization
Communication state
Software version (flickering)
5
S-NET Pro
Configuration
List of recently opened files Outdoor unit model selection
6
S-NET1+
Part number:
P nu
ummber: DB81-02331A
DB
B81-023
33
C
Components
Compon
Compo
RS23-to-RS485 converter USB cable Software update cable
7 Software and driver will need to be downloaded from [Link]
S-NET Pro
Language Selection
/DQJXDJHVHOHFWLRQ
8
S-NET Pro
Main Menu - Home
Installation
information Outdoor unit valve state
Outdoor unit refrigerant cycling data
Data monitoring tab
9
S-NET Pro
Main Menu - Home ٻێۈۀۏڤ ٻێۇۄڼۏۀڟ
ٻۋۈۀۏٻۏېڪ ٻۀۍېۏڼۍۀۋۈۀۏٻۀڿۄێۏېڪ
ٻێێۀۍګډڣ
ٻۏۄۉېٻۃھڼۀٻۉۄٻۀۍېێێۀۍۋٻےۊۇڊۃۂۄڣ
ٻێێۀۍۋډڧڊ
ٻڿۀۂۍڼۃھێۄڿٻۍۊێێۀۍۋۈۊڞ
ٻډێۄڟ
ٻۉۄٻۀۍېۏڼۍۀۋۈۀۏٻۏۉڼۍۀۂۄۍہۀۍ
ٻڎڇڍڇڌ
ٻۍۊێێۀۍۋۈۊھٻۃھڼۀ
ٻٻڌډۋۈېڮ ٻۀۍېۏڼۍۀۋۈۀۏٻۇۄۊٻڌٻۍۊێێۀۍۋۈۊڞ
Outdoor unit valve state ٻۉۄٻۏۉۀۍۍېھٻۂۉۄۉۉېۍٻۍۊێێۀۍۋۈۊڞ
ٻڎڇڍڇڌٻگڞ
ٻۍۊێێۀۍۋۈۊھٻۃھڼۀ
ٻۏېۊٻڿۉۊڞ ٻۀۍېۏڼۍۀۋۈۀۏٻۏېۊٻۍۀێۉۀڿۉۊڞ
ٻۀۍېۏڼۍۀۋۈۀۏٻۉۊۄۏھېێٻۍۊێێۀۍۋۈۊڞ
ٻۉۊۄۏھېڮ
ٻۍۊێۉۀێ
ٻۀڽېۏںڟ ٻۀۍېۏڼۍۀۋۈۀۏٻۏېۊٻۍۀۇۊۊھٻڽېڮ
ٻڼۋڼھ ٻ۔ۏۄھڼۋڼھٻۂۉۄۉۉېۍٻۏۄۉېٻۍۊۊڿۉڤ
ٻڱڠڠ ٻۀڿۊۈٻۂۉۄۏڼۀۃٻۉۄٻۀڿڼۍۂٻۉۀۋۊٻڱڠڠ
ٻڱڠڠںڤڱڠ ٻۀڿڼۍۂٻۉۀۋۊٻڱڠڠٻڤڱڠ
ٻکڜڡ ٻګڠگڮٻۉڼڡٻۍۊۊڿۏېڪ
ٻکڤٻڤڱڠ ٻۀۍېۏڼۍۀۋۈۀۏٻۉۄٻڤڱڠ
ٻگڰڪٻڤڱڠ ٻۀۍېۏڼۍۀۋۈۀۏٻۏېۊٻڤڱڠ
ٻۇۊۍۏۉۊھٻۀۏڼۍٻےۊۇہٻۏۉڼۍۀۂۄۍہۀڭ
ٻڱڠڠٻڭڣ
ٻۏۄۉېٻڭڣٻۉۄ
ٻڧڪڪڞ ٻہہۊڊۉۊٻۀۑۇڼۑٻۂۉۄۇۊۊھٻۉۄڼڨ
ٻٻڤڱڠ ٻہہۊڊۉۊٻۀۑۇڼۑٻڤڱڠ
ٻڨڰڞڞڜ ٻہہۊڊۉۊٻڣڞڞٻڭڪگڜڧڰڨڰڞڞڜ
ٻڱڠڠٻڟڪ ٻہہۊڊۉۊٻۀۑۇڼۑٻۇۊێٻڱڠڠ
10
S-NET Pro
Main Menu - Home
Number of outdoor units
N
TTotal capacity of outdoor units
Number of indoor units
N
SSum of indoor unit capacities
Number of MCUs (HR)
N
Outdoor unit data monitoring
11
S-NET Pro
Main Menu - Home
Main outdoor unit
M
SSub1 outdoor unit
SSub2 outdoor unit
Outdoor unit data monitoring
12
S-NET Pro
Main Menu - Home
Indoor unit operation data
13
S-NET Pro
Main Menu - Home
ٻۈۀۏڤ ٻۉۊۄۏڼۉڼۇۋۓڠ
ٻ۔ۏۄھڼۋڼھٻۏۄۉېٻۍۊۊڿۉڤ
ٻډڼۋڼڞ ٻۏڼۀۃٻۉۊٻۂۉۄڿۉۀۋۀڿٻۀۇڽڼۄۍڼڱڃ
ٻڄڿڼۊۇ
ٻۀڿۊڨ ٻۀڿۊۈٻڊۉڼہڊۏڼۀۃڊۇۊۊھ
ٻڿۀۀۋڮ ٻڿۀۀۋێٻۉڼڡ
ٻۋۈۀۏٻۏۀڮ ٻۀۍېۏڼۍۀۋۈۀۏٻۂۉۄۏۏۀڮ
ٻۋۈۀۏۉڤ ٻۀۍېۏڼۍۀۋۈۀۏٻۈۊۊڭ
ٻۀڿۄێۉۄٻۍۊۏڼۍۊۋڼۑڠ
ٻکڤٻڜڱڠ
ٻۀۍېۏڼۍۀۋۈۀۏ
ٻۀڿۄێۏېۊٻۍۊۏڼۍۊۋڼۑڠ
ٻگڰڪٻڜڱڠ
ٻۀۍېۏڼۍۀۋۈۀۏ
ٻڱڠڠ ٻڄګڠگڮڋړڏٻۙٻڋڃۀڿڼۍۂٻۉۀۋۊٻڱڠڠ
14
S-NET Pro
Main Menu - Home
Indoor unit installation information
15
S-NET Pro
Main Menu - Home
MCU address
M
MCU port operation mode
M
MCU port address
adddre xx-xx-xx [Link]
(indoor unit main address)
MCU operation state Year Month Date Version
16
S-NET Pro
Main Menu - Home
Item explain
MCU Addr. MCU Address
M address
MCU MCU oper. MCU operation mode
MCU
MCU port operation mode
A,B,C,D,E,F
Indoor unit address and running mode
port
Prevent refrigerant stack and
LBV
evaporator freezing
Refrigerant flow control between
EEV 1 outdoor unit and indoor unit in main
MCU port
ort address
adddre heating mode
(indoor unit main address)
MCU operation state
Refrigerant sub cooling control that
EEV 2
flow inside MCU
17
S-NET Pro
Main Menu - Home
- Address 01 : Main outdoor unit
- Address 02 : Sub1 outdoor unit
- Address 03 : Sub2 outdoor unit
- Address 04 : Sub3 outdoor unit
System cycle diagram
18
S-NET Pro
Main Menu – Home Window Arrangement
$UURZNH\IRUZLQGRZDUUDQJHPHQW
YHUWLFDOO\KRUL]RQWDOO\
19
- Used to view the multiple windows in the screen
S-NET Pro
Main Menu – Home Window Arrangement
20
S-NET Pro
Main Menu – Backup
Communication backup data storage location
Stored data file in .dvr extension
21
S-NET Pro
Main Menu – Backup
- Upload of 30-minute backup data before system error
- Applicable to DVM+3 (HR), DVM+4 (HR), DVM Water(10HP), Super FJM
- File name : Modelname_EEPROM_Date_Time.xls
- File save location :
1. Default : C:\...\My Documents\S-NET pro\RecordData
2. User-set location
22
S-NET Pro
Main Menu – Backup
Set the backup data storage location
Open backup data to replay
operation
23
S-NET Pro
Main Menu – Grid Export
Press the “Enter Select Mode” button
1. All the parameters which can be displayed start
flickering in gray.
2. Double-click the parameter Æ Automatic grid
window generation
24
Operation data monitoring in Excel grid display with elapsed time
S-NET Pro
Main Menu – Grid Export
Grid display interval setting
25
S-NET Pro
Main Menu – Grid Export
1. Press the selected grid data in blue.
2. Press Delete to remove the data from the grid display.
26
S-NET Pro
Main Menu – Grid Export
All the cycle parameters are displayed in the Grid Export window.
27
S-NET Pro
Main Menu – Grid Export (Save as Excel File)
Save all the grid data to an Excel file.
NOTE : Make sure to set the Grid Export window before
saving to the Excel file.
(KNGUCXGVQ'ZEGN
28
NOTE : File save to Excel in S-NET1+
Simply click Start to save all the cycle
parameters to an Excel file in S-NET1+.
29
S-NET Pro
Main Menu – Grid Export (Save as Excel File)
- File
Fil save llocation C ㄔ ㄔMy
ti : C:ㄔ.. ㄔM DocumentsㄔS-NET
D t ㄔS NET proㄔDataExport
ㄔD
Excel file save location
Communication backup data save location
30
S-NET Pro
Main Menu – Grid Export (Save as Excel File)
31
S-NET Pro
Trend Graph
Operation mon
Operatio
Operation monitoring
itorin
ngg in graph display
Add/delete data in graph window
A
A
Add/delete graph windows
((max. 4 graph windows)
32
S-NET Pro
Trend Graph
Add data to be displayed in the graph window Æ All the parameters which
can be graphically display start flickering.
33
S-NET Pro
Trend Graph
Double-click data to add Æ Automatic graph display
start
34
S-NET Pro
Trend Graph
Y-axis scale setting
Automatic Y-axis
adjustment
Graph span setting
- Max. 6 data graphs per window
7LPH6SDQ
35
S-NET Pro
Trend Graph
1. Select data to delete.
2. Press Delete.
36
S-NET Pro
Trend Graph – Replay
Replay at x1~x32 speed
- Drag the scrollbar to the desired
time
- Start/End time display
37
S-NET Pro
Main Menu – Add On
Wireless/wired remote control
disabled
Communication packet Indoor unit control panel
monitoring
38
S-NET Pro
Main Menu – Add On
Refrigerant quantity check
Indoor unit & interface
module communication state
39
S-NET Pro Future models will have this capability. DVM Plus II, DVM Plus III, CAC,
RAC, and Mini DVM cannot use this feature.
Main Menu – Add On
&$&'90*OREDOZD\RSWLRQFRGHDQGIXQFWLRQDORSWLRQVHWWLQJ
$SSOLHGRQO\WR*OREDOZD\FDVVHWWHVIRUDVM+4 and 2011 CAC inverter outdoor
units
- Must be connected to F1/F2 lines where indoor and outdoor units are communicating
successfully
40
S-NET Pro
Main Menu – Help
41
S-NET Pro
Main Menu – Help
Normal operation judgment criteria (cooling, heating)
42
S-NET Pro
Main Menu – Help
Software version
Functions restricted to non-authorized persons
1. Oil balance, oil recovery, defrost operation
2. No replay with backup data
43