GASENSOR TECHNOLOGY MODEL Ultra FL800
Description Multi-Spectrum lnfrared
Flame Detector
The Model Ultra FL800 is an advanced multi-spectrum
infrared (MSIR) flame detector based on the Artificial
Intelligence Recognition Technology. The Ultra FL800 is
provided with wider field of view and further detection
range because of a multi-spectrum infrared sensor array
with a sophisticated BP Neural Network Technology
system .
The Ultra FL800 can see typical fires such as those
produced by alcohol, heptane, gasoline, jet fuels and
hydrocarbons. In addition, it can also detect and identify
non-flame signals, for example arc-welding, hot objects,
sunlight and moonlight. The Ultra FL800 is designed to
only alarm for the conditions that caused by real flame
signal, and highly immune to false alarms for non-flame
signals.
The Ultra FL800’s electronics are housed in a stainless
steel explosion-proof enclosure. The detector is available
with the following output configurations:
● 4-20mA stepped output
● Dual RS485 communications
● HART communication
● Warning, alarm and fault relays
Benefits Features
• Increased range and wide FOV (field of view) • Multi-Spectrum IR (MSIR) Sensor Array
• Provides excellent false alarm immunity • BP Neural Network Technology (NNT)
• Build in test for optical path integrity and electronic • Continuous Optical Path Scanning (COPS)
circuitry.
• Redundant Communication Outputs
• Versatile for use in a variety of applications
• Event Logging
• Support diagnostic PC software
• Test Mode
• Used to check all outputs (used with test lamp)
Applications
• Aircraft Hangars • Fuel Loading Facilities
• Chemical Plants • Gas Turbines
• Compressor Stations • LNG/LPG Processing and Storage Facilities
• Drilling and Production Platforms • Refineries
• Electrostatic Paint Spray Booths
MODEL Ultra FL800
System Specifications Environmental Specifications
Spectral Range: 2 - 5 microns (IR) Operating/Storage Temperature Range:
Maximum Range: 65 m - 40°F to + 185°F (- 40°C to + 85°C)
Typical Response Time: ≤ 3s (at 30m with n-Heptane Operating Humidity Range:
fire 0.1 square meter)
0% to 95% RH, non-condensing
≤ 5s at 65m
Maximum Field of View: 90° Horizontal / Vertical
Accessories: Test lamp, mounting bracket
Classification: Mechanical Specifications
Explosive-proof : II 2G Ex db IIC T5 Gb ( Ta = - 40°C to + 85°C )
II 2G Ex db IIC T6 Gb ( Ta = - 40°C to + 70°C ) Housing: 316 Stainless steel
Weight: 2.5 kg
II 2D Ex tb IIIC T100°C Db IP67
Cable Entries : Two entries 3/4 ins NPT, others optional
Protection Level : IP67
SIL 2 Certified
Display Type : LED Displays
100
Warranty: Two Years
124
152
205.50
51
Electrical Specifications
110 4X 6 85
Input Power: 20-36 VDC , 24 VDC @ 150mA (3.6W)
270
Analog Signal: 0-20 mA (600 ohms maximum)
120.50
3.5-20 mA (HART)
Fault Mode: 0 mA to 0.2 mA
Test Mode: 8.0 mA , ± 0.2 mA
60
COPS Fault: 2 mA , ± 0.2 mA
Ready Mode: 4.5 mA , ± 0.2 mA
WARN Mode: 16 mA , ± 0.2 mA
ALARM Mode: 20 mA , ± 0.2 mA
Relay Contact Rating: 5 A @ 250 VAC, 5 A @ 30 VDC [Link]
Baud Rate: 4800, 9600, 19200, or 38400 bit/s
HART: HART 7, HART Device Descriptor Language
[Link]
Standard Configuration: Ultra FL800-1-1-1 Figure 1: Outline and Mounting Dimensions
Publication #: DS-FL800-D0718
Specifications subject to change without notice. GT-TD-DS.04
Gasensor Technology [Link]
Add : 71 Ubi Crescent # 04-01 Excalibur Centre Singapore 408571
Tel : ( +65 ) 6744 6268 Fax : ( +65 ) 6744 6269
E-mail : sales @ [Link]
Web : WWW . [Link]