TM Series: Multi-Channel (4 Channel / 2 Channel) Modular Type PID Control

The TM Series are multi-channel modular PID controllers that can control up to 124 channels across 31 modules connected in series. Key features include isolated input channels with 1000V dielectric strength, heating and cooling control, USB connectivity for parameter monitoring and setup, and easy maintenance via connector modules. Ordering information specifies module type, number of channels, output type, power supply, and accessories.

Uploaded by

Hùng Vũ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views8 pages

TM Series: Multi-Channel (4 Channel / 2 Channel) Modular Type PID Control

The TM Series are multi-channel modular PID controllers that can control up to 124 channels across 31 modules connected in series. Key features include isolated input channels with 1000V dielectric strength, heating and cooling control, USB connectivity for parameter monitoring and setup, and easy maintenance via connector modules. Ordering information specifies module type, number of channels, output type, power supply, and accessories.

Uploaded by

Hùng Vũ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

TM Series

Multi-channel(4 channel / 2 channel) modular type PID control


NEW
Features
● Multi-channel(4 channel/ 2 channel) simultaneous controlling possible
● High-speed sampling cycle(4 channel : 100ms, 2 channel : 50ms)
● No communication and power supply for expansion
modules required by using side connectors
: Max. 31 units (124 channels / 62 channels)
● Input channel isolated design(Dielectric strength 1,000 VAC)
● Heating/Cooling simultaneous controlling
● Allows parameter setting and monitoring by USB port of PC
: only for using DAQMaster or USB to Serial converter
(SCM-US, sold separately)
● Easy maintenance via connector type connection
: Sensor input connector, control output connector,
power/communication connector
● Multi input / Multi range
● Heater disconnection function(CT input)
※ CT, sold separately : CSTC-E80LN, CSTC-E200LN
Please read “Caution for your safety” in operation
manual before using.

User manual
●Visit our website ([Link]) to download user manual and communication manual.
●User manual describes for specifications and function, and communication manual describes for RS485 communication
(Modbus RTU protocol) and parameter address map data.

Integrated device management program(DAQMaster)


●DAQMaster is a integrated device management program for convenient
management of parameters and multiple device data monitoring.
●Visit our website ([Link]) to download user manual and integrated device management program
< Computer specification for using software > < DAQMaster screen >
Item Recommended specification
Processor IBM PC compatible computer with Intel Pentium Ⅲ or
above
Operating system Windows 98 / NT / XP / Vista / 7
RAM Over 256MB
Hard disk Over 1GB of available space
VGA Over 1024×768
Communication port RS232 Serial port, USB port

Ordering information
TM 4 N 2 R B
Module type B Basic module
E Expansion module
R Relay output
2 Channel
Control output C Current or SSR output selectable
R Relay output
4 Channel
S SSR drive output
Power supply
2 24VDC
2 Alarm1+Alarm2 Relay output
Sub output 2 Channel
4 Alarm1+Alarm2+Alarm3+Alarm4 Relay output
4 Channel N None(※No sub output)
Channel 2 2 Channel
4 4 Channel
Item
TM Multi-channel modular temperature controller
※Make sure to purchase both expansion module and basic module together because power supply/communication terminals are
provided with basic modules only.

H-10
Multi-Channel Module type PID Control

Specifications (A)
Photo
electric
TM2- TM2- TM2- TM2- TM2- TM2- TM2- TM2- TM4- TM4- TM4- TM4- sensor
Series 22RB 42RB 22RE 42RE 22CB 42CB 22CE 42CE N2RB N2RE N2SB N2SE
(B)
4 Channel Fiber
2 Channel
Channel (Each channel insulated- optic
(Each channel insulated-Dielectric strength 1,000 VAC) sensor
Dielectric strength 1,000 VAC)
Power Supply 24VDC (C)
Door/Area
Allowable voltage range 90 to 110% of rated voltage sensor

Power consumption Max. 5W(At maximum load)


(D)
Indicating type Non-indicating type Parameter setting & monitoring with external devices (PC or PLC) Proximity
sensor
Input RTD DPt100Ω, JPt100Ω 3 wire (Allowable line resistance : Max. 5Ω)
type Thermocouple K, J, E, T, L, N, U, R, S, B, C, G, PLII(13types) (E)
Pressure
RTD sensor
(Bigger one either PV ±0.5% or ±1℃) ±1digit Max.
Indicating Thermocouple※1
(F)
accuracy CT input (±5% F.S.) ±1digit Max. - Rotary
encoder
Current output (±1.5% F.S.) ±1digit Max. -
Influence of RTD (G)
(Bigger one either PV ±0.5% or ±2℃) ±1digit Max.(In case of thermocouple input, it is ±5℃ at -100℃ below.) Connector/
Temperature Socket
※2
Thermocouple ●Thermocouples L, U, C, G, R, S, B : (Bigger one either PV ±0.5% or ±5℃) ±1digit Max.

Relay 250VAC 3A 1a - 250VAC 3A 1a - (H)


Temp.
Control SSR - 12VDC ±3V 30mA Max. - 22VDC ±3V30mA controller

output Max.
Current - DC 4-20mA or DC 0-20mA -
(I)
SSR/
selectable(Load 500Ω Max.) Power
controller
Relay 250VAC 3A 1a -
Sub output
Communication RS485 Communication output(Modbus RTU) (J)
Counter
CT input 0.0-50.0A(Primary current meaurement range) ※CT ratio = 1/1000 -
Event ●Contact input: ON Max. 1kΩ, OFF Min. 100kΩ
input ●Non-contact input: ON Max. 1.5V residual voltage, (K)
Digital input - Timer
OFF Max. 0.1mA leakage current
●Outflow current : Approx. 0.5mA
(L)
Control Heating, cooling Panel
ON/OFF control mode, P, PI, PD, PID control mode meter
method Heating&cooling
(M)
Hysteresis 1 to 100℃/℉(0.1 to 100℃/℉) variable 1 to 100 digit Tacho/
Speed/ Pulse
Proportional band (P) 0.1 to 999.9℃ meter

Integral time (I) 0 to 9999 sec.


(N)
Derivative time (D) 0 to 9999 sec. Display
unit
Control period (T) 0.1 to 120.0 sec.(Only relay and SSR output type)
Manual reset value 0.0 to 100.0% (O)
Sensor
Sampling period 50ms(2 channel synchronous sampling) 100ms(4 channel synchronous sampling) controller

Dielectric strength 1000VAC 50/60Hz for 1 min. (between power source terminal and input terminal) (P)
Switching
Vibration resistance 0.75mm amplitude at frequency of 5 to 55Hz(for 1 min.) in each of X, Y, Z directions for 2 hours power
supply
Relay Mechanical Min. 10,000,000 operations
life cycle Electrical Min. 100,000 operations (250 VAC 3A resistance load) (Q)
Stepping
motor&
Insulation resistance 100MΩ(at 500VDC megger) Driver&Controller

Noise resistance Square shaped noise by noise simulator (pulse width 1㎲) ±0.5kV (R)
Graphic/
Ambient -10 to 50℃, storage: -20 to 60℃ Logic
Environ temperature panel
-ment Ambient
humidity 35 to 85%RH, storage: 35 to 85%RH (S)
Field
network
Expansion connector device
Accessory
Power / communication connector[※Basic module only]
(T)
Insulation type Double insulation or reinforced insulation (Mark: , Dielectric strength between the measuring input part Software
and the power part : 1kV)
Approval
(U)
Approx. Approx. Approx. Approx. Approx. Approx. Approx. Approx. Approx. Approx. Approx. Approx. Other
Unit weight
144g 152g 135g 143g 139g 148g 130g 139g 174g 166g 160g 152g
※1. In case of thermocouple K, T, N, J, E at -100℃ below and L, U, PlatinelⅡ, it is ±2℃ ±1digit Max.
In case of thermocouple B, indicating accuracy cannot be ensured under 400℃.
In case of thermocouple R, S at 200℃ below and thermocouple C, G, it is 3℃ ±1digit Max.
※2. Applied when used out of range 23 ±5℃.
※Environment resistance is rated at no freezing or condensation.

H-11
TM Series
Connections and block diagram
●TM2 Series
1 ADC 13
CURRENT CT1 + V + ㎃ SSR OUT1 CURRENT OUT1 RELAY OUT1
2 - - 12VDC ±3V DC0/4-20mA 250VAC 3A 1a
0.0A-50.0A 14 30mA Max. Load 500Ω Max.
CT2 ADC
3 OUTPUT
DIGITAL
DI-1
4
CIRCUIT 15 RELAY AL1 OUT
250VAC 3A 1a
INPUT DI-2
5 CONTROL 16
RELAY AL2 OUT
CIRCUIT 17 250VAC 3A 1a
6
A
7 18
CH1 IN B + + ㎃ SSR OUT2 CURRENT OUT2 RELAY OUT2
+ 8 ADC
19 - V - 12VDC ±3V DC0/4-20mA 250VAC 3A 1a
B' 30mA Max. Load 500Ω Max.
-
9
TC RTD OUTPUT 20 RELAY AL3
A
10 CIRCUIT 250VAC 3A 1a
CH2 IN B 21
11 ADC RELAY AL4
+ 250VAC 3A 1a
- B' 12 22
TC RTD
RS485 POWER
CIRCUIT CIRCUIT
1 2 3 4 5 ※ RELAY AL3/4 is available only for TM2-42 model.
A B NC - +
RS485 SOURCE
24VDC
●TM4 Series
A
CH1 IN 1 13
B + SSR OUT1 RELAY OUT1
2 ADC - V 22VDC ±3V 250VAC 3A 1a
14 30mA Max.
B'
TC RTD 3
A 15
4
CH2 IN CONTROL
B 16 SSR OUT2 RELAY OUT2
5 ADC +
CIRCUIT - V 22VDC ±3V 250VAC 3A 1a
B' 17 30mA Max.
6
TC RTD OUTPUT
A CIRCUIT
7 18 RELAY OUT3
CH3 IN + SSR OUT3
B 250VAC 3A 1a
8 ADC - V 22VDC ±3V
19 30mA Max.
B'
TC RTD 9
A 20
10
CH4 IN B 21 SSR OUT4 RELAY OUT4
11 ADC + 22VDC ±3V 250VAC 3A 1a
+ - V 30mA Max.
- B' 12 22
TC RTD
RS485 POWER
CIRCUIT CIRCUIT
1 2 3 4 5
A B NC - +
RS485 SOURCE
Serial
24VDC
※Port A
: Available for SCM-US(USB/Serial Convertor)
single module

RS485 RS232 USB

SCM-38I
(RS232/RS485 converter)

PC
RS485 USB
※This connector
1 2 3 4 5 is available only <RS485 communication
for standard SCM-US48I support external device>
※Port B model (USB/RS485 converter
: Available for (TM - B).
single/multi - +
RS485 A(+)

RS485 B(-)

N.C

SOURCE
module 24VDC 5W

GP-S070
PLC GP-S057
GP-S044

H-12
Multi-Channel Module type PID Control

Dimensions (A)
Photo
electric
sensor

(B)
Fiber
optic
sensor

(C)
Door/Area
sensor
100
110

37

(D)
Proximity
sensor

(E)
Pressure
sensor

17
(F)
Rotary
85 19 3 30 encoder

104
(unit: mm) (G)
Connector/
Socket

Installation (H)
Temp.
controller
●Connector connection ●Multi module connection
④ (I)
SSR/
Power
controller
Control output ③
Input sensor connector (J)
connector Counter
③ ③

⑤ (K)
Timer


② (L)
Panel
meter

(M)
Tacho/
Speed/ Pulse
TM - B TM - E TM - E meter
(Basic module) (Expansion module) (Expansion module)
Power / Communication
connector (Port B) ※① Remove END cover for both basic modules and expansion modules. (N)
② Insert expansion connectors. Display
※TM - B ③ Connect an expansion module without space.
unit

④ Fix the LOCK switch by pushing it in the LOCK direction. (O)


⑤ Mount the END cover at each side. Sensor
※Up to 30 expansion modules can be connected to a basic module. controller

Use an adequate power supply system for the power input specifications
(P)
and overall capacity. Switching
[Maximum power (155W=31ea X 5W) is required when connecting power
supply
31 units]
(Q)
●Bolt Inserting Stepping
M4 Bolt motor&
M4 Bolt ② Driver&Controller

① (R)
Graphic/
Logic
panel

(S)
Field
110

network
device

(T)
Software

② (U)
Other

① Pull each Rail Lock switch up and down. ② Insert the bolts to fix.
(Tightening torque is 0.5N·m to 0.9N·m.)

H-13
TM Series
●DIN Rail Installation
[Installation method] [Removal method]

② ②

① Put the top edge of the rail Lock on the top edge or the DIN rail. ① Press down the module body.
② Push the module body in while pressing down. ② Pull the module body forward.

Using END PLATE(Sold separately, Not ※Make sure to install the unit vertically to the ground.
available from Autonics), Fix firmly to attach.

Vertical Installation Horizontal Installation


(O) (X)
Parts description
TM2 Series TM4 Series
1. Indicating LED(TM2 Series)
7 7 Alarm output
Status Auto
Initial power on Control N.O N.C
6 6 Indi- ※1 tuning
5 cating output OFF(OPEN) ON(CLOSE) OFF(OPEN) ON(CLOSE) ※2

LED
1 3 2 3
PWR LED
※3 Green Green - - - - Green
4 4 CH1 LED 2400bps-Flashing Power ON-RED - - - - Flashing

8 8 CH2 LED 4800bps-Flashing Power ON-RED - - - - Flashing


Power ON-
AL1 LED 9600bps-Flashing Light OFF Light ON Light ON Light OFF Light OFF
YELLOW※4
Power ON-
AL2 LED 19200bps-Flashing Light OFF Light ON Light ON Light OFF Light OFF
YELLOW※5
AL3 LED 38400bps-Flashing - Light OFF Light ON Light ON Light OFF Light OFF
AL4 LED - - Light OFF Light ON Light ON Light OFF Light OFF

9 9 2. Indicating LED(TM4 Series)


Status
Indicating LED Initial power on※1 Control output Auto tuning※2
3. PC loader port(Port A) ※3
: Integrated device management program PWR LED Green Green Green
(DAQMaster, free download on our site) is CH1 LED 2400bps- Flashing ON - RED Flashing
for setting parameter by PC through USB to
Serial converter (SCM-US, sold separately). CH2 LED 4800bps- Flashing ON - RED Flashing
4. Communication address setting switch (SW1) CH3 LED 9600bps- Flashing ON - RED Flashing
: Used to set communication address.
5. Communication address group change switch CH4 LED 19200bps- Flashing ON - RED Flashing
(SW2) 38400bps- Flashing - -
: When communication address is over 16,
select +16. ※1. In case of initial power on, default communication speed will be
Ex) For setting 20 address, set the communication flashing for 5 sec. (1 sec. cycle).
address group change switch (SW) as +16 and set
※2. Each CH3 LED will be flashing during auto tuning (1 sec. cycle).
the commuicaiton address setting switch (SW1) as 4.
6. Lock switch ※3. Power LED will be flashing while communicating with external units
: Used for fixing units to DIN rail or to the wall (1 sec. cycle).
7. Rail lock ※4. Light ON when control type for CH1 is heating & cooling type and cooling
: Used for fixing units to DIN rail or to the wall output is provided.
8. END cover ※5. Light ON when control type for CH2 is heating & cooling type and cooling
: Remove it when connecting each module. output is provided.
9. Power supply/Communications connector(Port B)
: Only Basic module(TM - 2 B)
H-14
Multi-Channel Module type PID Control

Input sensor type and temperature range (A)


Photo
electric
Input sensor No. Dot Display Input range(℃) Input range(℉) sensor

0 1 K(CA).H -200 to 1350 -328 to 2462 (B)


K(CA) Fiber
1 0.1 K(CA).L -200.0 to 1350.0 -328.0 to 2462.0 optic
sensor
2 1 J(IC).H -200 to 800 -328 to 1472
J(IC) (C)
3 0.1 J(IC).L -200.0 to 800.0 -328.0 to 1472.0 Door/Area
sensor
4 1 E(CR).H -200 to 800 -328.0 to 1472
E(CR)
5 0.1 E(CR).L -200.0 to 800.0 -328.0 to 1472.0 (D)
Proximity
6 1 T(CC).H -200 to 400 -328 to 752 sensor
T(CC)
7 0.1 T(CC).L -200.0 to 400.0 -328.0 to 752.0
(E)
B(PR) 8 1 B(PR) 0 to 1800 32 to 3272 Pressure
sensor
Thermocouple R(PR) 9 1 R(PR) 0 to 1750 32 to 3182
S(PR) 10 1 S(PR) 0 to 1750 32 to 3182 (F)
Rotary
N(NN) 11 1 N(NN) -200 to 1300 -328 to 2372 encoder

C(TT)※1 12 1 C(TT) 0 to 2300 32 to 4172


G(TT)※2 13 1 G(TT) 0 to 2300 32 to 4172 (G)
Connector/
Socket
14 1 L(IC).H -200 to 900 -328 to 1652
L(IC)
15 0.1 L(IC).L -200.0 to 900.0 -328.0 to 1652.0 (H)
Temp.
16 1 U(CC).H -200 to 400 -328 to 752 controller
U(CC)
17 0.1 U(CC).L -200.0 to 400.0 -328.0 to 752.0
(I)
Platinel II 18 1 PLII 0 to 1400 32 to 2552 SSR/
Power
19 1 JPt100.H -200 to 600 -328 to 1112 controller
JPt 100Ω
20 0.1 JPt100.L -200.0 to 600.0 -328.0 to 1112.0
RTD (J)
21 1 DPt100.H -200 to 600 -328 to 1112 Counter
DPt 100Ω
22 0.1 DPt100.L -200.0 to 600.0 -328.0 to 1112.0
(K)
※1. C(TT) : Same as existing W5(TT). ※2. G(TT) : Same as existing W(TT). Timer
※Default : K(CA).H
(L)
Error indication Panel
meter

Input sensor open error Over temperature range


(M)
PWR LED Red ON Tacho/
Speed/ Pulse
CH1 LED RED Flashing (for 0.5 sec.) meter

CH2 LED RED Flashing (for 0.5 sec.)


(N)
CH3 LED※1 RED Flashing (for 0.5 sec.) Display
unit
CH4 LED ※1 RED Flashing (for 0.5 sec.)
Communication output (decimal) '31000' output '30000 (upper limit)' output, '-30000 (lower limit)' output (O)
Sensor
Dedicated program 'OPEN' indication 'HHHH (upper limit)' indication , 'LLLL (lower limit)' indication controller

※1. Only for TM4 Series(4CH). (P)


Switching

Communication setting power


supply

A function for external parameter setting & monitoring with PC or PLC. (Q)
Stepping
motor&
●Interface ●Communication speed indication Driver&Controller

Application Standard Compliance with EIA RS 485 ①Current communication speed will be flashing in case (R)
Graphic/
Max. connection 31 units(communication address setting: 01 to 31) of initial power ON for 5 sec. (1 sec. cycle). Logic
panel
Communication type Two wire, Half Duplex
Synchronization method Asynchronous (S)
Field
Communication distance Max. 800m network
device
Communication speed(bps) 2400, 4800, 9600(default),19200, 38400
Communication response time 5 to 99ms (T)
Software
Start Bit 1bit(fixed)
Stop Bit 1bit, 2bit(default)
Parity Bit None(default), Odd, Even ※One module communication is allowed for Port A. (U)
Other

Data Bit 8bit(fixed) Communication speed is fixed to 9600bps.


※Multiple communication is allowed for Port B. It is
Protocol Modbus RTU required to reset controller's Power(Power OFF →
※Overlapped address setting is not allowed on the same Power ON) after changing communication speed.
communication line. ※Simultaneous monitoring can not be done for Port A
Twisted Pair wires(for RS485 communication) must be and B since Port A is for parameter setting only.
used for communication cable. ※If connects communication through Port A, Port B will
be disconnected communication automatically.

H-15
TM Series
●Communication address setting
①Set the communication address using SW1 and SW2.
Setting range is 01 to 31. (※In case setting 00, communication is not available.)

SW1

SW2 ※Default : SW1 : 1, SW2 : +0


0 1 2 3 4 5 6 7 8 9 A B C D E F
+0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
+16
+0
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
+16

Sold separately
●Communicatoin converter
[SCM-38I(RS232C to RS485 converter)] [SCM-US48I(USB to RS485 converter)] [SCM-US(USB to Serial converter)

●Current transformer(CT)
[CSTC-E80LN]
Current 100mA to 80A Current 1000:1
measuring range (Rb=10Ω) ratio 10
F=50㎐
OUTPUT IN VOLTS RMS(V)

Wire wounded 31Ω±10% 2.0 grade Ta=25℃


resistance Accuracy (5A to 80A) 100Ω

ø23.3 ※Rb: Burden resistor


ø7 (unit: mm) 1 10Ω
3
K(Black)
3.8

0.1
L(White)

0.01
26.5 150
10.5

0.001
0.1 1 10 100 1000
SENSED CURRENT IN AMPS RMS(Io)

[CSTC-E200LN]
Current 100mA to 200A Current 1000:1 F=50㎐
measuring range (Rb=10Ω) ratio 10
OUTPUT IN VOLTS RMS(V)

Ta=25℃ 100Ω
Wire wounded 20Ω±10% Accuracy 2.0 grade
resistance (5A to 200A)
10Ω
ø37.1 ※Rb: Burden resistor
ø13 1
(unit: mm)
3
K(Black)
0.1
4.5
10

L(White)

0.01
40.8 150

0.001
0.1 1 10 100 1000
13.5

SENSED CURRENT IN AMPS RMS(Io)

※Do not supply primary current in case that CT output is open. High voltage will be generated in CT output.

H-16
Multi-Channel Module type PID Control

Proper usage (A)


Photo

Simple failure diagnosis Caution for using electric


sensor

●When indicating LED is flashing every 0.5 sec. or when 1. Use DC power only. (B)
Fiber

error message is indicated on external units 2. Keep the ambient temperature -10℃ to 50℃ optic
sensor

①It represents input sensor open error. Cut off the 3. For more accurate controlling, start temperature
power of controller and check input sensor connection. controlling approx. 20 minutes later after connecting (C)
Door/Area
If sensor is properly connected, disconnect sensor line input sensors and supplying power. sensor

from the controller and short the input terminal (+) / 4. In case indicating accuracy does not meet the
(D)
(-). Then, make sure that current indoor temperature specification, check Input Bias parameter first. Proximity
sensor
is indicated. If current indoor temperature is properly 5. Power switch or a circuit breaker must be installed for
indicated, it represents no errors detected. If external proper application. (E)
unit displays 'HHHH' or 'LLLL', please contact our A/S 6. Make sure that the power switch or a circuit breaker Pressure
sensor
center.(Current indoor temperature checking is available installed near operators.
only if selecting thermocouple type.) 7. This unit is solely allowed for temperature controlling (F)
Rotary
②Make sure proper input sensors are selected. application. Do not apply this unit as a voltage meter or encoder

●When no output is operated current meter.


(G)
①Check output indicating LED at the front. In case 8. When line extension is required, please use Connector/
Socket
output indicating LED does not work properly, please specified compensation line. If not, there occurs
check each parameter setting again. In case output temperature difference at the joint part between (H)
indicating LED works properly, disconnect the output thermocouples and extension lines. Temp.
controller
terminal and check controller's output type (Relay 9. In case of using RTD, line connection must be done with
contact, SSR, Current) again. 3 wires. When line extension is required, use the same (I)
SSR/
wire with material, thickness and length. Different line Power
●When external units receive no response or error data controller

①Check communication converter first. [RS232C to resistance may cause temperature difference.
RS485 converter(SCM-38I, sold separately), USB to 10. Make sure controller ’s line connection must be (J)
Counter
RS485 converterserial(SCM-US48I, sold separately) separated from high voltage line or power supply
USB to Serial converter(SCM-US, sold separately)] line in order to prevent induced noise.
(K)
②Do not install the unit with overlapping communication 11. If it is required that power supply line should be Timer

converter lines and AC power supply lines. connected near input signal line, use line filter on
③Use separate power supply (24VDC) for communication controller’s power supply line and input signal line must (L)
Panel
converter if possible. be shielded. meter

④Strong external noise could be a possible cause for 12. Avoid installing controllers adjacent to high frequency
(M)
this symptom. Please contact our A/S center. In noise generating units including high frequency Tacho/
Speed/ Pulse
addition, analyze the main cause that triggers strong soldering machine, high frequency sewing machine, meter
noise and take measures to prevent it. Even though and high capacity SCR controllers and motors.
(N)
this unit complies with proper noise resistance 13. Avoid using the unit near radio, TV or wireless Display
unit
standards, consistent noise induction could affect machines that may cause high frequency interference.
internal circuit break. 14. When changing input sensors, power off the controller (O)

●When communication does not work properly first. Connect input sensors as specified and supply Sensor
controller

①Check converter's power supply and connection. the power again. Then, change & download related
②Check communication setting.
(P)
parameters using PC loader program. Switching
③Check main body's connections to external units. 15. Use (-) driver screws (2mm) or use plastic driver power
supply
screws. If not, it might cause product damage. (Q)
16. Twist Pair wires must be used for communication cable. Stepping
motor&
Connect Ferrite Bead at each end of line in order to Driver&Controller

reduce the effect of external noise. (R)


Graphic/
17. Avoid installing the unit with overlapping communication Logic
panel
line and AC power line together.
18. Draw a draft while using the controllers. In case of (S)
Field
installing at a closed area, please take measures for network
device
ventilation.
19. Installation environment (T)
Software
①It shall be used indoor. ②Altitude Max. 2000m.
③Pollution Degree 2 ④Installation CategoryⅡ.
※Please keep the above precautions to avoid malfunction (U)
Other
and damages.
.

H-17