PLC Connection Guide
MODBUS RTU (Adjustable)
Supported Series : MODBUS RTU CONTROLLER
Website : [Link]
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS RTU (Adjustable)
PLC I/F RS485 RS232/RS485
9600/19200/3840
Baud rate 9600
0/57600/115200
Data bits 8 7,8
Parity Even Even, Odd, None
Stop bits 1 1,2
PLC sta. no. 1 0-255
Online simulator YES
Extend address mode YES
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B 0x DDDDD 1 ~ 65535 Output bit
B 1x DDDDD 1 ~ 65535 Input bit (read only)
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read only)
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_multi_coils DDDDD 1 ~ 65535 Write multiple coils
W 3x DDDDD 1 ~ 65535 Input Register (read only)
W 4x DDDDD 1 ~ 65535 Output Register
W 5x DDDDD 1 ~ 65535 4x double word swap *Note1
DW 5x (32-bit) DDDDD 1 ~ 65535 4x double word
W 6x DDDDD 1 ~ 65535 4x single word write
PLC Connection Guide
*Note1: Please assign all the addresses to Even addresses, or all to Odd addresses, in
order to prevent communication failure.
*Note2: EBPro V6.03.02 or later supports 64 bits data type (cMT Series only), but please
note that the address limit range is 48 bits in maximum..
*Note3:
Address type “5x” is mapping to Hold Reg. The communication protocol of “5x” is almost
the same as “4x” except that “5x” swaps double words.
If 4x contains the following information:
Address 1 2 3 4 5 6 ...
Data in word 0x1 0x2 0x3 0x4 0x5 0x6
Data 0x0201 0x0403 0x0605
For 5x, it will be:
Address 1 2 3 4 5 6 ...
Data in word 0x1 0x2 0x3 0x4 0x5 0x6
Data 0x0102 0x0304 0x0506
Modbus RTU function code:
0x 0x01 Read coil 0x05 Write single coil
0x_multi_coils 0x01 Read coil 0x0f Write multiple coils
1x 0x02 Read discrete input N/A for writing operation
3x 0x04 Read input register N/A for writing operation
4x 0x03 Read holding register 0x10 Write multiple registers
5x 0x03 Read holding register 0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x 0x03 Read holding register 0x06 Write single register
(Note: 6x is limited to device of one word only)
PLC Connection Guide
Setting Instructions:
1. Go to [System Parameter Settings] ,click [New] to add a new device - MODBUS
RTU (Adjustable),as shown below:
2. After adding MODBUS RTU (Adjustable) driver, [Add Address Range Limit] button will
be enabled as below. Users can set maximum read/write command size here.
[Link]-command size (words): Pull down to select PLC reading range.
[Link]-command size (words): Pull down to select PLC writing range.
PLC Connection Guide
Note:
MODBUS RTU (adjustable) usage
Users can decide the address range via setting value on Parameter 1. For example, when
users set 5 to Parameter 1, the address range will be 5 ~ 65535.
PLC Connection Guide
Wiring Diagram:
RS232 (Diagram 1 ~ Diagram 3)
Diagram 1
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103 / cMT3151
eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150
MT-iE MT8073iE / MT8102iE
MT-XE MT8092XE
MT-iP MT6103iP / MT8102iP
HMI PLC
COM1 COM3
RS232 RS232 RS232
9P Female 9P Female
Rx 2 8 TXD
Tx 3 7 RXD
GND 5 5 GND
RTS
CTS
PLC Connection Guide
Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD
mTV mTV
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE /
MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8121XE / MT8150XE / MT8090XE
HMI PLC
COM1
RS232 RS232
9P Female
Rx 2 TXD
Tx 3 RXD
GND 5 GND
RTS
CTS
Diagram 3
MT-iE MT8050iE / MT8053iE
MT-iP MT6051iP / MT8051iP / MT6071iP / MT8071iP
HMI PLC
COM1
RS232 RS232
9P Female
Rx 9 TXD
Tx 6 RXD
GND 5 GND
RTS
CTS
PLC Connection Guide
RS485 4W (Diagram 4 ~ Diagram 7)
Diagram 4
cMT Series cMT3151
eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE
MT-XE MT8121XE / MT8150XE
HMI PLC
COM1
RS485 4W RS485 4W
9P Male
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND
Diagram 5
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD
mTV mTV
HMI PLC
COM2
RS485 4W RS485 4W
9P Female
Rx- 7 TX-
Rx+ 6 TX+
Tx- 9 RX-
TX+ 8 RX+
GND 5 GND
PLC Connection Guide
Diagram 6
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103
MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE
MT-iP MT6071iP / MT8071iP / MT6103iP / MT8102iP
HMI PLC
COM2
RS485 4W RS485 4W
9P Male
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND
Diagram 7
MT-iE MT8050iE / MT8053iE
MT-iP MT6051iP / MT8051iP
HMI PLC
COM1
RS485 4W RS485 4W
9P Female
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND
PLC Connection Guide
RS485 2W (Diagram 8 ~ Diagram 13)
Diagram 8
cMT Series cMT3151
eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150
HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 6 D-
Data+ 2 9 D+
GND 5 5 GND
Diagram 9
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD
mTV mTV
HMI PLC
COM2 COM3
RS485 2W RS485 2W RS485 2W
9P Female 9P Female
Data- 7 4 D-
Data+ 6 1 D+
GND 5 5 GND
PLC Connection Guide
Diagram 10
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE
MT-XE MT8121XE / MT8150XE
HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 7 D-
Data+ 2 8 D+
GND 5 9 GND
Diagram 11
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103
MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE
MT-iP MT6103iP / MT8102iP
HMI PLC
COM2 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 6 D-
Data+ 2 9 D+
GND 5 5 GND
PLC Connection Guide
Diagram 12
MT-iE MT8050iE / MT8053iE
MT-iP MT6051iP / MT8051iP
HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Female 9P Female
Data- 1 7 D-
Data+ 2 8 D+
GND 5 5 GND
Diagram 13
MT-iP MT6071iP / MT8071iP
HMI PLC
COM2
RS485 2W RS485 2W
9P Female
Data- 1 D-
Data+ 2 D+
GND 5 GND