Cable Modelling
List of inputs required:
The below table represents the list of the inputs required for modelling of cable.
Table 1 : List of inputs required
Modelling of Cable:
Step-1: Open EMTPWorks → Create a new document →Save the file.
Step-2: Drag and drop the “cable data” from lines library into GUI.
Step-3: Double click on the cable data → Enter the cable type as single core and number of
cables as 3.
Step-4: Enter the conductor data parameters as shown in below from Table 1.
PWSIM Engineering Solutions PVT LTD B-378/1,Ring Road,1st Stage Peenya | Bangalore 560058
Tel: +91 806 816 0000 [Link]
PAN : AAJCP9604K TAN : AGRP12379D CIN: U74999KA2018PTC114410, PF Reg. N° : PY/PNY/1835463/000
Step-5: Goto the Model tab → Select the model as “Wideband model”
Step-6: Goto cable length → Enter the cable length is 1 km and earth resistivity is 100 Ω.m
PWSIM Engineering Solutions PVT LTD B-378/1,Ring Road,1st Stage Peenya | Bangalore 560058
Tel: +91 806 816 0000 [Link]
PAN : AAJCP9604K TAN : AGRP12379D CIN: U74999KA2018PTC114410, PF Reg. N° : PY/PNY/1835463/000
Step-7: Goto generate tab → Enter the file name → Enable the Run this case.
Step-9: Import Cable parameters
The calculated cable parameters are saved as a text file. The parameters are linked to the
cable model for performing the simulations.
• Drag and drop the ‘wideband line/cable fitter function’ and ‘Wide band Line/Cable” to
GUI
• Double-click on the ‘wideband fitter function’ → Select the data input device name →
click ok.
WB Fitter
• Wide band fitter is running and Mplot will be opened → Click ok.
PWSIM Engineering Solutions PVT LTD B-378/1,Ring Road,1st Stage Peenya | Bangalore 560058
Tel: +91 806 816 0000 [Link]
PAN : AAJCP9604K TAN : AGRP12379D CIN: U74999KA2018PTC114410, PF Reg. N° : PY/PNY/1835463/000
• Double-click on the Wideband line/cable → click “Select data file” → Click ok.
WBline1
WBline1 + WB model
+ WB model
Step-10: Drag and drop the ‘AC voltage source and impedance’ into GUI → Double click on it
and enter the parameters.
• Source tab
o Vm =400 kVRMSLL
o f = 50 Hz
• Impedance tab
o Enable the short-circuit data input → Enter the parameters as shown in below.
PWSIM Engineering Solutions PVT LTD B-378/1,Ring Road,1st Stage Peenya | Bangalore 560058
Tel: +91 806 816 0000 [Link]
PAN : AAJCP9604K TAN : AGRP12379D CIN: U74999KA2018PTC114410, PF Reg. N° : PY/PNY/1835463/000
Step-11: Drag and drop the ‘Power :P(t), Q(t) – 3phase’ from meters library into GUI.
Step-12: Drag and drop the ‘bus to abc’ from pseudo devices library into GUI.
Step-13: Drag and drop the ‘RLC: R’ and ground from RLC branches library into GUI → Double
click on it and enter R = 5Ω.
Step-14: Connect the all components as shown in below.
?i WBline1
VwZ1 + WB model
IC a
+ b
PQ
400kVRMSLL /_0 3-phase c
PQm1
50Hz
?s
+
R1
5
Step-15: To get the output responses click on the ‘View scopes with scopeview’ in simulate
tab → Click on the ‘PQm1/P@control’ and ‘PQm1/Q@control’ in the signal selection window.
PWSIM Engineering Solutions PVT LTD B-378/1,Ring Road,1st Stage Peenya | Bangalore 560058
Tel: +91 806 816 0000 [Link]
PAN : AAJCP9604K TAN : AGRP12379D CIN: U74999KA2018PTC114410, PF Reg. N° : PY/PNY/1835463/000