Vibration Level Switch Specification

The document is an index list for vibration level switches. It contains 11 entries listing vibration level switches with details like tag number, type, equipment number, insertion length, and revision number. Each switch is identified with a unique tag number and associated with a specific piece of equipment and nozzle. Lengths and other technical specifications vary between switches.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
261 views12 pages

Vibration Level Switch Specification

The document is an index list for vibration level switches. It contains 11 entries listing vibration level switches with details like tag number, type, equipment number, insertion length, and revision number. Each switch is identified with a unique tag number and associated with a specific piece of equipment and nozzle. Lengths and other technical specifications vary between switches.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

INDEX LIST

Vibration Level Switch

Item Equipment Active Length Insertion Length


Tag No. Type PID Number Nozzle Number Rev. No Remark
No. No. (mm) (mm)

1 100-LSHH-003 Vibration Level Switch VF003-PR-PID-100002 T-101A N2 1220 B.V 2

2 100-LSHH-004 Vibration Level Switch VF003-PR-PID-100003 T-101B N2 1220 B.V 2

3 110-LSHH-003 Vibration Level Switch VF003-PR-PID-110002 T-102A N2 1600 B.V 2

4 110-LSHH-004 Vibration Level Switch VF003-PR-PID-110003 T-102B N2 1600 B.V 2

5 200-LSHH-003 Vibration Level Switch VF003-PR-PID-200002 T-201A N2 1600 B.V 2

6 200-LSHH-004 Vibration Level Switch VF003-PR-PID-200003 T-201B N2 1600 B.V 2

7 210-LSHH-003 Vibration Level Switch VF003-PR-PID-210002 T-202A N2 1600 B.V 2

8 210-LSHH-004 Vibration Level Switch VF003-PR-PID-210003 T-202B N2 1600 B.V 2

9 220-LSHH-003 Vibration Level Switch VF003-PR-PID-220002 T-203A N2 1691 B.V 2

10 220-LSHH-004 Vibration Level Switch VF003-PR-PID-220003 T-203B N2 1691 B.V 2

11 600-LSL-001 Vibration Level Switch VF003-PR-PID-600002 T-604 N8 200 B.V 2

B.V = By Vendor
Sheet 3 of 20
1 Tag Number 100-LSHH-003
2 Service Normal Diesel Tank
3 P&ID No. VF003-PR-PID-100002
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-101A
8 Nozzle No. Nozzle size Schedule R-10 2" 40
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Normal Diesel Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 3.825
17 Density (kg/m³) : Upper Lower - 850
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 4 of 20
1 Tag Number 100-LSHH-004
2 Service Normal Diesel Tank
3 P&ID No. VF003-PR-PID-100003
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-101B
8 Nozzle No. Nozzle size Schedule R-10 2" 40
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Normal Diesel Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 3.825
17 Density (kg/m³) : Upper Lower - 850
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 5 of 20
1 Tag Number 110-LSHH-003
2 Service Premium Diesel Tank
3 P&ID No. VF003-PR-PID-110002
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-102A
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Premium Diesel Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 3.825
17 Density (kg/m³) : Upper Lower - 850
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 7 of 20
1 Tag Number 110-LSHH-004
2 Service Premium Diesel Tank
3 P&ID No. VF003-PR-PID-110003
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-102B
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Premium Diesel Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 3.825
17 Density (kg/m³) : Upper Lower - 850
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 8 of 20
1 Tag Number 200-LSHH-003
2 Service G92 Tank
3 P&ID No. VF003-PR-PID-200002
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-201A
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 92 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 10 of 20
1 Tag Number 200-LSHH-004
2 Service G92 Tank
3 P&ID No. VF003-PR-PID-200003
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-201B
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 92 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 11 of 20
1 Tag Number 210-LSHH-003
2 Service G95 Tank
3 P&ID No. VF003-PR-PID-210002
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-202A
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 95 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 13 of 20
1 Tag Number 210-LSHH-004
2 Service G95 Tank
3 P&ID No. VF003-PR-PID-210003
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-202B
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 95 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 14 of 20
1 Tag Number 220-LSHH-003
2 Service G95 Tank
3 P&ID No. VF003-PR-PID-220002
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-203A
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 95 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 16 of 20
1 Tag Number 220-LSHH-004
2 Service G95 Tank
3 P&ID No. VF003-PR-PID-220003
4 Area Classification Location Zone 2 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A106 Gr.B
7 Equipment No. T-203B
8 Nozzle No. Nozzle size Schedule - 2" 80
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Gasoline 95 Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 0.5625
17 Density (kg/m³) : Upper Lower - 750
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C +0.01/-0.0025 barg
20 Connection Size Type & Rating 2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Top Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (below flange face) See index list and Information sheet use for Level Switch
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on High level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number -
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No. -
51 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 3-Aug-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 17 of 20
1 Tag Number 600-LSL-001
2 Service Additive tank
3 P&ID No. VF003-PR-PID-600002
4 Area Classification Location Zone 1 Field
GENERAL 5 Line No. Line Size Schedule - - -
6 Line Internal Diameter Pipe Material - A312 Gr.TP316L
7 Equipment No. T-604
8 Nozzle No. Nozzle size Schedule N8 1 1/2" 40S
9
10 Upper Fluid Name Fluid Phase - -
11 Lower Fluid Name Fluid Phase Additive Liquid
12 Minimum Normal Maximum Units
13 Normal Level (From bottom of tank) - mm
0
PROCESS 14 Temperature AMB 70 C
CONDITIONS
15 Pressure - 0.01 barg
16 Viscosity (Upper / Lower) (cP) - 15
17 Density (kg/m³) : Upper Lower - 1000
18 Corrosive Erosive Toxic No No No
0
19 Design Temperature Design Pressure 70 C Full Liquid +0.08/-0.05 barg
20 Connection Size Type & Rating 1 1/2" ANSI 150 # RF
21 Model No. B.V
22 Orientation Style Horizontal Mounting Turning Fork
23 Material Sheath 316 SS -
PROBE
24 Insertion Length (beside flange face) See Information sheet use for Level Switch(500mm)
25 Inactive Length B.V
26 Probe Diameter B.V
27 Application -
28 Location Control cabinet(Din rail mounting)
29 Explosion Protection Enclosure - IP20
AMPLIFIER
30 Power Supply Electrical Connection 24VDC Wire terminal
31 Output 1 SPDT, 2A@24VDC
32 Type 2 wire-Namur
33 Explosion Protection Enclosure EExd IIB T4 IP65 as minimum
34 Rating Deadband - Mfr. Std
SWITCH 35 Power Supply Electrical Connection 24 VDC 1/2" NPT
36 Housing Aluminum
37 Contacts Status Open on Low level
38
39 Compensation Cable -
40 Local Indicator -
OPTIONS
41
42
43 Manufacturer B.V
44 Model B.V
PURCHASE 45 Purchase Order No. -
46 Serial Number
47
48 Drawing No. -
ADDITIONAL 49 Certification CO, CQ, SIL certification, explosion proof certificate
FEATURES
50 Information Drawing No.
52 SIL SIL 3
Notes:
1. SS tag name to be stamped with Tag No., Manufacturer Name, Model No. shall be provided on the instrument.
2. B.V. = By Vendor.
3. [Link] = Manufacturer Standard
4. SS= Stainless Steel
5. One cable glands 1/2" NPT will be used for power supply & control signal. All metal plug (ATEX) to seal any unused point

2 N.N. Luan 24-Oct-18 For Construction [Link]/[Link] [Link]


Vibration Level Switch
1 N.N. Luan 25-Sep-18 For Approval [Link]/[Link] [Link]
0 N.N. Luan 30-Jun-18 For Approval [Link]/[Link] [Link]
No. Made By Date Description Check Appr Code: Doc. No: VF003-IN-SPE-0007 Sheet 19 of 20