0% found this document useful (0 votes)
671 views9 pages

Murphy - Controlador EMS 447 - Installation Instructions 1 PDF

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
671 views9 pages

Murphy - Controlador EMS 447 - Installation Instructions 1 PDF

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

EMS447 and EMS448 Monitoring Systems EMS-94072N

Revised 10-04
Section 40
(00-02-0200)
Installation and Operation Instructions
Generic for All Versions. S449 Board Included
Please read the following instructions before installing. A visual inspection of this product for damage is recommended before installing.
It is your responsibility to have a qualified technician install the unit and make sure installation conforms with local codes.
GENERAL INFORMATION

EMS448

WARNING EMS447

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT


✔ Disconnect all electrical power to the machine.
✔ Make sure the machine cannot operate during installation. C R

✔ Follow all safety warnings of the machine manufacturer.


Listed for Cl. I, Div. 2, Grps. A, B, C & D hazardous areas on
✔ Read and follow all installation instructions. R
EMS447 (all transistor outputs) and EMS448 (board only).

Sensor Inputs (See page 2 for details)


CAUTION: Certain danger to human and to equipment Electric Gage Senders: Accepts Murphy or equivalent resistance type senders.
such as applied in a mobile or marine application may occur NOTE: Configurations available for 4-20 mA or 0-5 VDC inputs.
if some equipment is stopped without pre-warning. It is Digital Inputs: Accepts three opto-isolated bi-polar inputs (positive or negative),
therefore, recommended that monitored functions be limited typically wired to external shutdown switches. One additional input can be ordered
to alarm only or to alarm before shutdown in such applications. and traded for one transistor output.
Frequency Input: This optically isolated speed sensing input senses a speed signal
Description from a magnetic pickup.
NOTE: The following applies to all EMS447 and EMS448 models. Communications
However, program changes to the micro-processor chip may affect Both models, EMS447 and EMS448, include an RS485 serial port. By using the RS485
operating procedures. See Section “2” of these Instructions for details on port and the necessary software you can monitor the status of your equipment from a
your specific program or the sequence of operations provided with custom remote location. A communications software package and a RS485 to RS232 converter
programmed units. are needed to interface with a PC (IBM ® compatible computer). Set your
The EMS447 and EMS448 Electronic Monitoring Systems/Controllers are communications package to 9600 baud, N-8-1. Terminal emulation mode must be ANSI,
micro-processor based for monitoring and control of equipment functions. and there must be a line in the CONFIG. SYS FILE to define system device as ANSI.
The basic EMS system is programmed for a typical industrial engine power
unit. Custom programming is available to adapt the EMS to a wide variety of S449 Relay Output Boards
engine and equipment requirements. These relay output boards are used for additional relay contact capability. They
Basic programs provide auto-start/manual start and first-out shutdown for require a ribbon cable with solder type, D-subminiature connectors such as our
engine functions such as pressure, temperature, level and overspeed. optional EMS25CAR2 assembly, (see Basic Models and listings, below).
Necessary time delays for start up lockout are included. Operating data is Basic Models
displayed on a 32 character back lit alphanumeric liquid crystal display. EMS447 : Comes in an extruded aluminum enclosure suitable for panel
The EMS operating parameters are configured through a simple three-button mounting. Wiring is via optional wiring harness. Relay boards are available for
interface. Access to the system memory is controlled by entry codes. additional relay contact capability, see listings below:
A password-protected program uses built-in memory to display the EMS25TB: Plug-in terminal block assembly.
alarm/shutdown history, including a display of the last ten shutdowns, when
EMS25RM: Rail mount DIN type terminal block.
and why they occurred and displays all of the engine operating conditions at
EMS25CAR2: Ribbon cable with 2 male D-sub connectors.
time of last shutdown.
EMS25TBCAR2: Ribbon cable with 1 male and 1 female D-sub connector.
Program #01 Features EMS25CAS: Male connector and color coded cable 9 ft. (2.74 m) std. length.
An on-board hourmeter keeps a log of equipment running hours and alerts you EMS25MS: Solder type male connector (D-Subminiature).
when to change oil, filters and perform other routine service. S449-2: Dry Relay board for EMS447 models.
S449-4: Transistor Digital and Dry Relay board for EMS447 models.
Ramp Oil Pressure monitoring protects equipment at both high rated speed and
low idle speed. For instance, based on engine manufacturer’s requirement, EMS448: Comes in a NEMA 4X type enclosure. Wiring is connected directly to
shutdown could occur at 30 lb. (207 kPa) pressure at 1800 RPM or at 5 lb. (34 the S449-3 relay board terminal block located within the enclosure. Relay board for
kPa) at 600 RPM or any shutdown point in between. additional relay contact capability is available.
S449-1: Dry Relay board for EMS448 models only.

EMS-94072N page 1 of 8
EMS447, EMS448 and S449 SPECIFICATIONS

Input Voltage: 10 to 28 VDC. EMS447 Outputs:


Operating Temperature: -4 to 149°F (-20 to 65°C). 3† Transistor digital: 125 mA sinking.
Storage Temperature: -4 to 149°F (-20 to 65°C). 3 Relay: SPST 3A @ 30 VDC N.O. connected to Battery +.
Display: Alphanumeric display, back lit; consists of 2-lines EMS448 (S449-3) and S449-4 (EMS447) Outputs:
each with 16 characters (32 character total). 2 Transistor digital: 125 mA sinking.
4† Dry Relay: 2 SPST, 5A @ 30 VDC, 250 VAC, 1/10 hp @ 120 VAC;
Relative Humidity: 95%RH @ 140°F (60°C).
2 DPDT, 2A @ 220 VDC,250 VAC††.
Communications: RS485 port, standard.
S449-1 (EMS448) and S449-2 (EMS447) Outputs:
EMS447 Enclosure: Aluminum case 1/4 DIN type. 6† Dry Relay: 4 SPST, 5A @ 30 VDC, 250 VAC, 1/10 hp @ 120 VAC;
EMS448 Enclosure: Polyester fiberglass NEMA 4X type. 2 DPDT, 2A @ 220 VDC, 250 VAC††.
EMS447 and EMS448 Sensor Inputs: EMS447 Weight: 2-1/4 lb (1 kg).
Digital: 3* optically-isolated** inputs, (positive voltage or ground) such as EMS448 Weight: 3-1/2 lb (1.5 kg).
from Murphy SWICHGAGE® instruments.
EMS447 Dimensions: 9-1/4 x 8-1/4 x 5-1/4 in. (235 x 210 x 133 mm).
Analog: Up to 8 inputs–accepts a variety of resistive sending units, such as from
EMS448 Dimensions: 12-1/4 x 7-1/4 x 5-3/4 in. (311 x 184 x 146 mm).
Murphy electric gage senders.
NOTE: When resistive sending units are used, one input will be designated for
battery voltage sensing. The use of 2-wire type senders is strongly
* One additional digital input can be ordered and traded for one transistor output.
recommended. Special order analog inputs available (4-20 mA or 0-5 VDC). ** Isolates EMS circuitry from the input circuitry to avoid electrical noise/damage.
Frequency: 1 optically-isolated** input for speed reference, such as MP3298 † One additional output can be ordered and traded for one digital input.
magnetic sensor. †† One DPDT pole has common connected to Battery+. N.O. available fused/unfused.

EMS447 and EMS448 MOUNTING

EMS447 Model EMS448 Model


The EMS447 should be mounted in a location that is accessible to the operator. The EMS448 models have 4 mounting feet, (shipped loose–assemble the feet
EMS447 requires a rectangular mounting hole, (see mounting hole below) and using the screws provided). The customer must provide a hole in the enclosure
sufficient rear clearance for wiring connections. Install the unit in an enclosed for the incoming wiring (see suggested location for wiring hole, below). Use of
location within operating temperatures (-4 to 149°F [-20 to 65°C]). conduit or a strain relief bushing and Meyer’s hub for sealing is recommended.
Front Side Front Side

EMS

2-7/8 in. 2-5/8 in.


(73 mm) (67 mm)
EMS 6-7/8 in.
(175 mm)

5-43/64 in. 5 in.


(144 mm) (127 mm)
1/2 in.
(13 mm)

Rear Mounting Hole

8-1/2 in. 4-3/4 in.


2-5/8 in. (216 mm) (121 mm)
2-43/64 in.
(67 mm) (68 mm)
••••••••••••••
••••••••••••••
Bottom

5-11/32 in. 5-3/8 in.


(135 mm) (137 mm)

Suggested 4 in. 1-1/2 in.


Wiring Hole (102 mm) (38 mm)
Panel Mounting Side View
Panel
Mounting Brackets Mounting Holes
(one each side)
8-15/16 in.
(227 mm)

Set screw 5/16 x 1/2 in.


1/16 in, (8 x 13 mm)
hex wrench 4-Places
8 in. (203 mm) required
4 in.
Clearance for Connectors (102 mm)

EMS-94072N page 2 of 8
HOOKING UP THE EMS

WARNING: DISCONNECT ALL ELECTRICAL POWER BEFORE BEGINNING INSTALLATION AND STOP
ALL MACHINERY BEFORE PERFORMING THE HOOK UP. FOLLOW ALL INSTRUCTIONS.

EMS447 Models Attaching the EMS25TB to the EMS447 model.


Murphy offers optional connector assemblies for easy hook up to the EMS447 1. Remove (2) hex standoffs that hold the DB plug into the housing
module (see options below). Terminal designations, PIN and color codes depend – CAUTION: remove one at a time– and replace with (2) 4-40 x 1/4” screws.
upon the EMS program used. Specific wiring information is supplied with each 2. Remove (2) 6-32 x 1/4” screws that plug holes in back plate.
unit (refer to “Section 2” separate document, of these installation instructions, or 3. Push EMS25TB terminal block onto DB connector.
the detailed sequence of operations provided with custom programmed unit). 4. Place spacers between terminal block and back plate.
5. Attach 6-32 x 1” screws into EMS25TB through spacer and into plate and tighten.

Back View EMS25MS


EMS25TB ••••••••••••••
••••••••••••••
••••••••••••••
••••••••••••••
13 1

EMS25CAS
25 14 GND

S449-2 EMS25RM S449-4


EMS25TBCAR2
••••••••••••••
•••••••••••••• TEST
OFF
AUTO
EMS25CAR2 ••••••••••••••
•••••••••••••• TEST
OFF
AUTO

••••••••••••••
••••••••••••••
1 11 21 31 1 11 21 31
2 12 22 32 2 12 22 32
3 13 23 33 14 15 16 17 18 19 20 21 22 23 24 25 26 3 13 23 33
4 14 24 34 4 14 24 34
5 15 25 35 5 15 25 35
6 16 26 36 1 2 3 4 5 6 7 8 9 10 11 12 13 6 16 26 36
7 17 27 37 •••••••••••••• 7 17 27 37
8 18 28 38 •••••••••••••• 8 18 28 38
9 19 29 39 •••••••••••••• 9 19 29 39
••••••••••••••
10 20 30 40 10 20 30 40

EMS448 Models
Customer must provide conduit hole and make connections directly to the terminals (refer to “Section 2” of these instructions, separate document, or the detailed
located within the enclosure. Terminal designations, PIN and color codes depend sequence of operations provided with custom programmed unit). Optional S449-1
upon the EMS448 program. Specific wiring information is supplied with each unit relay output board can be used instead of S449-3 (standard with EMS448 models).

S449-1
Relay Output Board
31
32
33
34
35
36
37
38
39
40

OFF
AUTO

••••••••••••••
21
22
23
24
25
26
27
28
29
30

•••••••••••••• TEST AUTO


OFF

EMS448
TEST

1 11 21 31
Open 2 12 22 32
3 13 23 33
Enclosure 4 14 24 34
5 15 25 35
View 6 16 26 36
7 17 27 37
8 18 28 38
9 19 29 39
10 20 30 40
11
12
13
14
15
16
17
18
19
20
10
1
2
3
4
5
6
7
8
9

S449-3 Circuit board is


standard with EMS448 units.

EMS-94072N page 3 of 8
INSTALLATION AND SET-UP
The following information is typical for operation of ALL First Time Set-up
EMS Series units. Specific requirements depend upon the
microprocessor program. CAUTION: MAKE SURE ALL S-NUMBERS HAVE
BEEN ADJUSTED OR VERIFIED TO YOUR APPLICATION
Operating the Interface BEFORE PLACING THE UNIT INTO OPERATION.
By using the three membrane buttons and the liquid crystal display, you can make
set-point changes, acknowledge alarms, and scroll through the display. The
The S-numbers and P-numbers (Set point numbers) allow you to customize
graphic below shows the display and buttons.
your EMS unit. Access to the S-numbers and P-numbers is password-protected.
● The ENTER (EXIT) button is used to Confirm a set-point, Get into and out The S-Numbers include operational variables such as Crank/Rest, Warm-
of a display and to Acknowledge alarms. up/Cooldown Times, Alarm and Shutdown points. You will also be able to
▲ The YES (INCREMENT) button is used to Scroll up the display, to Select configure the EMS mode of operation (Automatic or Manual) if applicable.
messages, and Increase values. The P-numbers are used for service acknowledgment and shutdown history.
A complete list including S-numbers and P-numbers, their description and access
▼ The NO (DECREMENT) button is used to Scroll down the display, to Select
codes is included with each EMS unit.
messages, and Decrease values.
The EMS Operating Parameters and field settings are configured through the
three-button key pad and the display window.
DISPLAY WINDOW

How to access the S-numbers


®
Also refer to the “Quick-reference” sheet supplied with this installation.
EMS Controller 1. Turn the power ON, but DO NOT ALLOW EQUIPMENT TO OPERATE.
2. Press the ▼ button until the title page appears:

ENTER INCREMENT BACK

NO SCROLL
TO EXIT
YES
EXIT NEXT DECREMENT

3. Press the ● button until the entry code screen appears:


ENTER YES NO
BUTTON BUTTON BUTTON

The 32-character, two line, liquid crystal display shows monitored information
such as Engine Oil, Engine Temperature, R.P.M. etc., plus on-board information
such as Engine Hours and Battery Voltage. When a shutdown or a service
reminder comes due, the display will show this information, immediately.
4. Press the ▲ or ▼ buttons until appropriate entry code is displayed.
Scrolling Main Displays
(See separate document which shows the entry/access codes for your unit.)
During normal operation, the EMS allows you to scroll through a number of
5. Press the ● button once, the S-numbers main menu will be displayed.
informative displays. You can manually scroll through monitored information by
The display window will show the S-1 screen, for example:
pressing the ▲ (Yes) or the ▼ (No) buttons, or, if program version allows it, you
may set up the EMS for automatic scrolling [Link] a shutdown occurs or
a service reminder comes due, the EMS will display the corresponding
information regardless of the scrolling mode. When first powered up, the EMS
will delay for 1 minute before starting to scroll. When the scrolling mode is
changed, the EMS will not start its scrolling immediately. A 10 second delay must
time out before scrolling begins. 6. Now that you are in the S-numbers, you can go to a specific function by
To set the Automatic scroll mode press the ▼ (No) button until title page appears pressing the ▲ or ▼ buttons then pressing the ● button to enter the specific
(screen below): function. Now you can increase, toggle, or decrease the setpoint.
All Setpoints use the above described procedure. Once you have finished
adjusting the desired S-numbers, you can exit the set-up mode by depressing and
holding the ▼ button until the exit screen is displayed:

Now, press the ● (Enter) and the ▲ (Yes) buttons simultaneously. To set the
Automatic scroll mode to off, press ● (Enter) and ▼ (No) buttons at the same
time. The Automatic scroll off enables you to Manually scroll through the
displays. Your entry choices will be shown. Now press the ● button to set the EMS back into normal operation and scrolling
IMPORTANT: Main displays will vary with each microprocessor program mode (automatic or manual as applicable). If you forget to exit the
available. Refer to the Main displays listing included with your EMS system. S-numbers menu, the EMS will exit for you after a 5 minute delay.

EMS-94072N page 4 of 8
INSTALLATION AND SET-UP continued
How to access the P-numbers Inputs and Outputs Signal Checking
1. Turn the power ON, but DO NOT ALLOW EQUIPMENT TO OPERATE. Before attempting to start your system, check which inputs and outputs are active
2. Press the ▼ button until the title page appears: and properly wired. The diagnostic information for confirming your EMS
input/output setup can be found under the S-numbers menu or the Main Displays.
To access the input/output diagnostic information do the following:
1. Turn the power ON, but DO NOT ALLOW EQUIPMENT TO OPERATE.
2. Press ▲ to see if I/O is in main displays. If not found here, press ▼ until
tittle page appears.
3. Press ● until the entry code screen appears.
3. Press the ● button until the entry code screen appears: 4. Press ▼ or ▲ until appropriate entry code for S-numbers is displayed.
(See separate document which shows the entry/access codes for your unit.)
5. Press the ● button once, the S-numbers main menu will be displayed.
The display window will show the S-1 screen, for example:

4. Press the ▼ or ▲ buttons until appropriate entry code is displayed.


(See separate document which shows the entry/access codes for your unit.)
5. Press the ● button once, the P-numbers main menu will be displayed.
The display window will show the P-1 screen, for example: 6. Press the ● button to access this specific sub-menu.
7. Press the ▲ or ▼ buttons until you see the following screen.

I=Inputs 1 to 4 1 2 3 4

6. Now that you are in the P-numbers, you can go to a specific function by
pressing the ▲ or ▼ buttons then pressing the ● button to enter the specific
function. Now you can increase, toggle, or decrease that setpoint.
The Letter “I”, shown in the upper most-left corner, determines that the screen
Once you have finished adjusting or viewing the desired P-numbers, you can exit displayed shows the EMS inputs.
the set-up mode by holding the ▼ button until the Exit Screen is displayed:
Next to the “I” are the numbers 1-4 which represent the 3 standard digital inputs,
and the additional input (depending on the program configuration).
When the letter “O” is displayed next to input numbers, that means the controller
is NOT SENSING an input signal. The above example shows input 1 has tripped,
for example vibration. Inputs 2, 3 and 4 are not sensed. By resetting the vibration
switch, Input 1 will display “O”.
The next screen will show the balance of the inputs. The example below shows
Now press the ● button to set the EMS back into normal operation and scrolling that the controller is NOT SENSING input signals 5 - 12:
mode (automatic or manual as applicable). If you forget to exit the
P-numbers menu, the EMS will exit for you after a 5 minute delay. I=Inputs 5 to 12 5 6 7 8 9 10 11 12
Note: These are the analog
inputs that may be used as
Acknowledging Service Reminders digital inputs. Depending on
To acknowledge a service reminder, you must first perform the required service the analog signal, an X or an
O may be present.
to your equipment, then, clear the reminder message by accessing the P-numbers.
1. Press the ▼ button until the title page appears:
2. Press the ● button until the entry code screen appears: Press the ▲ button to bring up the outputs
p display:
3. Press the ▼ or ▲ buttons until appropriate entry code is displayed. O=Outputs 1 to 7 1 2 3 4 5 6 7

4. Press the ● button once, the P-numbers main menu will be displayed.
5. Next, using the ▼ or ▲ buttons, scroll to the P-number which represents the
service performed. Press ● button to enter the function and toggle the NO to
YES, using the ▲ button.
If you wish to change any service reminder interval, you may have to do so in The above example shows Output number 4, designated with an “X”. This means
the S-numbers (refer to “Section 2” of these installation instructions, separate that the controller software is calling for that output signal the be turned ON.
document, or the detailed sequence of operations provided with custom A “O” displayed means that the controller software is calling for the designated
programmed unit). output signals to be turned OFF.
6. Now, exit to the main displays. Refer to the “Pin Color Code and Terminal Designation Chart” (program specific
document) and double check the wiring diagram(s) provided with your unit.
To exit S-numbers menu, press and hold the ▼ button until S0 CIRCLE=EXIT
screen appears. Now exit to the main displays.

EMS-94072N page 5 of 8
EMS447 CIRCUIT BOARD

WARNING: DISCONNECT ALL ELECTRICAL POWER AND STOP ALL MACHINERY BEFORE REMOVING
THE EMS447 CIRCUIT BOARD FROM ITS CASE. IT IS YOUR RESPONSIBILITY TO HAVE A TRAINED PERSON
OR A QUALIFIED TECHNICIAN REMOVE AND/OR TROUBLESHOOT THE EMS447 CIRCUIT BOARD.

Removing the Circuit Board Resistors Configuration


Should it becomes necessary to identify your circuit board configuration, Analog Channel # Pin Group A Resistor Group B Resistor
remove the EMS447 circuit board from its case following these steps: 0 2 R16 R17
1. Undo the connector and the screws (on the back of the case). 1 4 R6 R7
2. Undo the stand-offs (also on the back of the unit). 2 17 R8 R9
3. Undo the two Phillips (cross) type screws, on the face plate. 3 16 R4 R5
4 1 R10 R11
4. Gently, pull the circuit board and face plate together out of the
5 15 R14 R15
EMS447 case. 6 14 R12 R13
Identifying Circuit Board Configuration 7 3 R2 R3
The following is important information for troubleshooting purposes.
The EMS447 circuit board configuration designation is controlled by Configuration Group A Resistor Group B Resistor
several factors: (see the call-outs on schematic below). Sender 1.62K 1% 1/2 W 432 1% 1/4 W
The Program Chip is labeled with your Program Number, Version, Date 4 to 20 mA Remove 249 1% 1/2 W
and Checksum. 0 to 5 VDC Remove Remove
The R23 potentiometer is for adjusting viewing angle and contrast. Battery 51K 5% 1/4 W 10K 5% 1/4 W
LK1 determines your input/output configuration. When placed in the IN
position, it enables a 4th digital input and disables the 7th digital output.
When placed in OUT, it disables the 4th digital input and enables the
7th digital output (see specifications section, on page 2).

R23
Potentiometer

Program chip
with Label
RAM Chip or
Clock/RAM Chip
Processor Chip

LK1

Group “A”
Resistors

Group “B”
Resistors

EMS-94072N page 6 of 8
EMS448 CIRCUIT BOARD

WARNING: DISCONNECT ALL ELECTRICAL POWER AND STOP ALL MACHINERY BEFORE OPENING
THE EMS448 ENCLOSURE. IT IS YOUR RESPONSIBILITY TO HAVE A TRAINED PERSON OR A QUALIFIED
TECHNICIAN HANDLE AND/OR TROUBLESHOOT THE EMS448 CIRCUIT BOARD.

Identifying Circuit Board Configuration LK2 information (configuring analog inputs 0-7)
Should it becomes necessary to identify your EMS448 circuit board LK2 is used to configure analog inputs 0 through 7 for a particular
configuration, undo the two latches/screws and open the EMS448 case. program. The choices are: resistive* type sender / digital, 4-20 mA or
Within, you will find the EMS448 circuit board (EMS448 board does 0-5 VDC. The following is based on orientating the board with the
not include terminal blocks). DB25 connector on the bottom. Putting the shunt across the bottom and
The EMS448 circuit board configuration designation is controlled by middle pins, configures the analog input for either a resistive type sender
several factors: (see the call-outs on schematic below) or a ground only digital. Across the middle and top pins configures the
The Program Chip is labeled with your Program Number, Version, Date analog for a 4-20 mA. Leaving the shunt off, configures the analog for a
and Checksum. 0-5 VDC. To display battery VDC, or if the program uses a resistive
LK1 information (Input/Output configuration) type sender on any of the analogs, such as a Murphy ES2P analog 0
LK 1 determines your input/output configuration (see LK1 call-out becomes not available and must have the shunt in the sender/digital
below). When placed in the IN position, it enables a 4th digital input and position. Use only two wire senders and run both wires back to the
disables the 7th digital output. EMS448, one to ground and one to the input. The EMS448 program
When placed in the OUT position, it disables the 4th digital input and used must support the way the analogs are configured.
enables the 7th digital output (see specifications section, on page 2). *Analog 0 has choices: Battery Monitor/ digital/ 4-20 mA /0-5 VDC.

RAM Chip or Processor


Clock/RAM Chip Chip

Program chip
with Label

LK1 information
see above.

LK2 information
see above.

EMS-94072N page 7 of 8
S449 RELAY BOARD

WARNING: DISCONNECT ALL ELECTRICAL POWER AND STOP ALL MACHINERY BEFORE WORKING
ON THE S449 RELAY BOARD. IT IS YOUR RESPONSIBILITY TO HAVE A TRAINED PERSON OR A QUALIFIED
TECHNICIAN HANDLING AND/OR TROUBLE-SHOOT THE S449 RELAY BOARD.

Identifying Circuit Board Configuration The S449 Relay Board used with the EMS447, jumpers LK1, LK2 and
Should it becomes necessary to identify your S449 relay board LK3 will be in the (7) position. The S449 Relay Board used with the
configuration, undo the two latches/screws and open the EMS448 case EMS448; jumpers LK1, LK2 and LK3 will be in the (8) position.
(if applicable). To identify the S449 relay board, look for its 40 screw- If Test–Off–Auto switch is not to be used, jumper JP5 must be in the
type terminals (see schematic below). SHORT position and the Test–Off–Auto switch in OFF (if it is present).
The S449 circuit board configuration designation is controlled by If Test–Off–Auto switch is used, jumper JP5 must be in OPEN.
several factors: (see the call-outs on schematic below).

TEST-OFF-AUTO
LK1 LK2 LK2 Toggle Switch

Jumper
JP5

Terminals Terminals
1 thru 10 21 thru
30

Terminals Terminals
11 thru 31 thru
20 40

Fuse

Warranty
A limited warranty on materials and workmanship is given with this FW Murphy product.
A copy of the warranty may be viewed or printed by going to [Link]/support/[Link]

CONTROL SYSTEMS & SERVICES DIVISION FRANK W. MURPHY, LTD. MACQUARRIE CORPORATION
P.O. Box 1819; Rosenberg, Texas 77471; USA Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. 1620 Hume Highway
+1 281 633 4500 fax +1 281 633 4588 +44 1722 410055 fax +44 1722 410088 Campbellfield, Vic 3061; Australia
e-mail sales@[Link] e-mail sales@[Link] +61 3 9358 5555 fax +61 3 9358 5558
FW Murphy
MURPHY DE MEXICO, S.A. DE C.V. [Link] e-mail murphy@[Link]
P.O. Box 470248
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje MURPHY SWITCH OF CALIFORNIA
Tulsa, Oklahoma 74147 USA
San Luis Potosí, S.L.P.; México 78384 41343 12th Street West
+1 918 317 4100 +52 444 8206264 fax +52 444 8206336 Palmdale, California 93551-1442; USA
D
RE

fax +1 918 317 4266 GI


E

Villahermosa Office +52 993 3162117 +1 661 272 4700 fax +1 661 947 7570
STER

USA–ISO 9001:2000 FM 28221


e-mail sales@[Link] e-mail ventas@[Link] e-mail sales@[Link] UK–ISO 9001:2000 FM 29422

[Link] [Link] [Link]


In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Printed in U.S.A.

EMS-94072N page 8 of 8
QUICK REFERENCE CHART

POWER
UP

NO
NOTE: Screens are shown for
reference only. Your EMS screens may
vary depending on the program used.
MURPHY EMS
P-NUMBER PROGRAM # S-NUMBER
DISPLAYS DISPLAYS
Scrolling
the Main
ENTER Displays ENTER

ENTRY ACTIVE ENTER ENTER NO ENTRY ACTIVE


YES
ENTER CODE: XX ENTER CODE: XX
YES OR NO YES OR NO
SELECTING SELECTING
ENTER SCROLL ON SCROLL OFF ENTER

NO
YES

ENTER ENG SPD 0 RPM ENG SPD 0 RPM ENTER


LINE 1 RUN HOURS XX LINE 1
XXX XXX XXXXXX P1 LINE 1 SELECT S1 LINE 1 SELECT XXX XXX XXXXXX
NO
YES NO YES NO YES
YES YES
ENTER ENTER
NO NO
BATTERY XXVDC
NO
YES
ENTER ENG SPD 0 RPM ENG SPD 0 RPM ENTER
LINE 1 LINE 1
P2 XXX XXX XX ENGINE SPD 0 RPM S2 XXX XXX XX
XXX XXX XXXXXX XXX XXX XXXXXX
YES NO NO YES
YES NO YES
ENTER YES ENTER
NO NO

OIL PR XX PSI

ENTER NO YES ENTER


LINE 1 ENG SPD 0 RPM ENG SPD 0 RPM LINE 1
XXX XXX XXXXXX P3 XX XXXX XX S3 XX XXXX XX XXX XXX XXXXXX
ENGINE TEMP XXF°
YES YES NO NO YES YES
ENTER ENTER
NO NO NO
YES

SELECTOR - AUTO
ENTER ENG SPD 0 RPM ENG SPD 0 RPM ENTER
LINE 1 NO YES LINE 1
XXX XXX XXXXXX P4 XX XXXX XX S4 XX XXXX XX XXX XXX XXXXXX
YES YES NO ST: PANEL READY NO YES YES
ENTER ENTER
NO NO
NO YES

CHG OIL XX HRS


ENTER ENTER
LINE 1 ENG SPD 0 RPM ENG SPD 0 RPM LINE 1
XXX XXX XXXXXX P5 XX XXXX XX NO YES S5 XX XXXX XX XXX XXX XXXXXX
YES NO NO YES
YES YES
ENTER OIL FLT XX HRS ENTER
NO NO

P-Numbers S-Numbers
continue NO Main Displays continue
continue

ENG SPD 0 RPM ENG SPD 0 RPM


P0 CIRCLE = EXIT S0 CIRCLE = EXIT

ENTER MURPHY EMS ENTER

PROGRAM #

You might also like