Continuous Load Calculation for Luminaires
Continuous Load Calculation for Luminaires
(REVISED)
A TECHNICAL REPORT
PRESENTED TO
IN PARTIAL FULFILLMENT OF
THE REQUIREMENTS
SUBMITTED BY:
i|Page
Juan Delacruz
REE-
APRIL 2018
ii | P a g e
PREFACE
iii | P a g e
for project implementation towards the ongoing constructions of the
project.
iv | P a g e
And now, to my family who are always there keeping me inspired,
and all my children who unexpectedly are all doing good on their
own studies are keeping me more inspired in doing this technical
engineering report.
v|Page
TABLE OF CONTENTS
PREFACE............................................................................... iii
vii | P a g e
[Link] N.1 Over current protection devices (OCPD) ..... Error!
Bookmark not defined.
3.2.4 SUMMARY OF VOLTAGE DROP AND CABLE SCHEDULE
............................................ Error! Bookmark not defined.
viii | P a g e
[Link] Electrical Single Line Riser Diagram of Al Khair Tower
......................................... Error! Bookmark not defined.
[Link] Electrical Single Line Diagram with Fault Locations
......................................... Error! Bookmark not defined.
[Link] System Impedance Diagram ....Error! Bookmark not
defined.
3.5.4 Symmetrical 3-Phase short circuit current calculation
............................................ Error! Bookmark not defined.
x|Page
3.6.9 MDB-1 Calculation of Setting Values for Sub-Feeder Error!
Bookmark not defined.
xi | P a g e
4.1.1 Switchgear Distribution Board ........Error! Bookmark not
defined.
4.1.9 Power Wires and Cables 600V and Less: Error! Bookmark
not defined.
xii | P a g e
CHAPTER 5 – CONCLUSION AND RECOMMENDATION ..... Error!
Bookmark not defined.
LIST OF TABLES
Table 15 - Tabulated Loads for MDB-2 & MDB-3 ... Error! Bookmark
not defined.
xv | P a g e
Table 32 - Essential computed line Impedance required ........ Error!
Bookmark not defined.
LIST OF FIGURE
xvii | P a g e
Figure 18 - Simplified Impedance at point A to B .. Error! Bookmark
not defined.
xviii | P a g e
Figure 31 - Zero Sequence Impedance when Generator is use Error!
Bookmark not defined.
xix | P a g e
Figure 45 - HRC PPE Required Label Error! Bookmark not defined.
Figure 46 - Arc Flash PPE by HRC ... Error! Bookmark not defined.
LIST OF FORMULA
xx | P a g e
Formula 15 - primary 3 Phase Short Circuit - Symmetrical .... Error!
Bookmark not defined.
Symbol Description
∠ angle
° degrees
A Ampere
AF Ampere Frame
AT Ampere Trip
BS British Standard
xxi | P a g e
Cu Copper
eff Efficiency
Ei Incident Energy
En Normalize Energy
Ip Circuit Protection
If Fault Current
k Rating factor
km kilo meter
kV kilo Volt
kW kilo Watt
L Length in km or m
xxii | P a g e
LT Long time (for Breaker Setting)
pu Per unit
PB Panelboard
t Time in sec.
xxiii | P a g e
V Volt
Vf Fault Voltage
X Reactance
Z impedance
Ω Ohms
xxiv | P a g e
SUMMARY
xxvi | P a g e
Over all view of this the author would like to emphasize that aside
from the technical specification and international standards, the
understanding of the local regulations shall be considered.
Coordinating with local authorities is required and to perform of
visual riser diagram is one of significant and effective
implementation during construction.
xxvii | P a g e
CHAPTER 1
INTRODUCTION
O
1|Page
CHAPTER 1 – INTRODUCTION
1.1 PROJECT DESCRIPTION
2|Page
Figure 2 – Termination of 13.8kV power supply to RMU
3|Page
Figure 3 - Al-Khair Tower Google Maps Location
January February March April May June July August September October November December
Avg. 23.3 23.3 25.3 27.3 29.9 30.7 32 32.1 31.1 29.2 27.2 24.8
Temperature
(°C)
Min. 16.5 16.4 18.4 20 22.6 23.3 25.4 26 24.5 22.4 20.5 18.3
Temperature
(°C)
Max. 30.2 30.2 32.3 34.7 37.2 38.1 38.7 38.2 37.8 36.1 33.9 31.3
Temperature
(°C)
Avg. 73.9 73.9 77.5 81.1 85.8 87.3 89.6 89.8 88.0 84.6 81.0 76.6
Temperature
(°F)
Min. 61.7 61.5 65.1 68.0 72.7 73.9 77.7 78.8 76.1 72.3 68.9 64.9
Temperature
(°F)
Max. 86.4 86.4 90.1 94.5 99.0 100.6 101.7 100.8 100.0 97.0 93.0 88.3
Temperature
(°F)
Precipitation 10 1 2 4 1 0 0 0 0 0 18 16
/ Rainfall
(mm)
4|Page
control and construction management, this ensure project outcomes
are of the highest standard. The Project features the following;
5|Page
A. Complete electrical design in accordance with the requirements by
the owner, code of practice, local standard regulation as well as
related International Standard.
c. Extra Low Voltage / Low Current System such as Fire Detection and
Alarm system, Telephone and Data Structured System, Acces
Control System, Public Address System.
6|Page
CHAPTER 2
DESIGN CRITERIA
7|Page
CHAPTER 2 – DESIGN CRITERIA
8|Page
This section will enumerate the electrical requirements,
specifications, applicable codes and standards used, engineering
practices and local authority regulations and requirements.
9|Page
2.2 Voltage rating and system frequency
Voltage: ±5%
11 | P a g e
to the farthest outlet does not exceed 5 percent, will provide
reasonable efficiency of operation.”
Note: Single line diagram design criteria for voltage drop is mention
again on figure 4 page 33
CHAPTER 3
ELECTRICAL
CALCULATIONS
12 | P a g e
13 | P a g e
CHAPTER 3 – ELECTRICAL CALCULATIONS
Using the architectural design for lighting and power loads as per
extracted from NFPA 70, NEC 2014, table 220.12, offices lighting
loads calculated with 39VA/m2, the receptacle power outlets loads
calculated with 11VA/m2 or 180VA per single receptacle and 360VA
per double receptacle power outlets, and with considerations per
client requirements, the following loads are tabulated below;
14 | P a g e
Table 1 - General lighting load by occupancy
15 | P a g e
A. (PP-T) Typical Offices (550M² South & North Wings)
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : PP-T PANTRY SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : OFFICES (TYP) MOUNTING : SURFACE
16 | P a g e
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : PP-C1 ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : MEZZ FLOOR MOUNTING : SURFACE
17 | P a g e
C. PP-P2, Ground Floor
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : PP-P2 ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : GF MOUNTING : SURFACE
18 | P a g e
D. PP-P3, Ground Floor
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO PANEL NAME : PP-P3 ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : GF MOUNTING : SURFACE
19 | P a g e
E. PP-C TO G (Typical)
PROJECT NAME : AL KHAIR TOWER ENGINEER : PANEL NAME : PP-C (TYP TO G) ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : 3F/6F/…….15F MOUNTING : SURFACE
LIGHTING AT 3F COMMON AREAS 3x2.5 15 1 16 1.455 1 2 2.100 16 1 17+2+2 3x2.5 LIGHTING AT 3F ELEV LOBBY
LIGHTING AT 3F COMMON AREAS 3x2.5 12+2+2+1 1 16 1.551 3 4 1.455 16 1 15 3x2.5 LIGHTING AT 4F HALLWAY
LIGHTING AT 4F ELEV LOBBY 3x2.5 17+2+2 1 16 2.100 5 6 1.551 16 1 12+2+2+1 3x2.5 LIGHTING AT 4F COMMON AREAS
LIGHTING AT 5F HALLWAY 3x2.5 15 1 16 1.455 7 8 2.100 16 1 17+2+2 3x2.5 LIGHTING AT 5F ELEV LOBBY
LIGHTING AT 5F COMMON AREAS 3x2.5 12+2+2+1 1 16 1.551 9 10 1.080 20 1 6 3x4 POWER OUTLET AT 3F COMMON AREAS
POWER OUTLET AT 3F COMMON AREAS 3x4 6 1 20 1.080 11 12 1.080 20 1 6 3x4 POWER OUTLET AT 4F COMMON AREAS
POWER OUTLET AT 4F COMMON AREAS 3x4 6 1 20 1.080 13 14 1.080 20 1 6 3x4 POWER OUTLET AT 5F COMMON AREAS
POWER OUTLET AT 5F COMMON AREAS 3x4 6 1 20 1.080 15 16 0.100 20 1 9 3x4 POWER OUTLET FOR CAMERA 3F/4F/5F
FCU FOR 3F COMMON AREAS 3x4 4 1 20 1.463 17 18 1.463 20 1 4 3x4 FCU FOR 4F COMMON AREAS
FCU FOR 5F COMMON AREAS 3x4 4 1 20 1.463 19 20 20 1 SPARE
SPARE 1 20 21 22 20 1 SPARE
SPACE 1 20 23 24 1 SPACE
SUB TOTAL / PHASE 5.453 4.182 4.643 5.280 2.635 4.094 SUB TOTAL /PHASE
MAIN BUS RATING : 100A
TOTAL / PHASE 10.733 6.817 8.737
20 | P a g e
F. LP-EX, Ground Floor
21 | P a g e
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : LP-EX ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : GF MOUNTING : SURFACE
22 | P a g e
G. PP-A, Ground Floor
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C. PANEL NAME : PP-A ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : GF MOUNTING : SURFACE
LIGHTING AT GF COMMON AREAS 3x2.5 8+4+2 1 16 0.840 1 2 1.104 16 1 10+1+1 3x2.5 LIGHTING AT GF ELEV. LOBBY
LIGHTING AT GF COMMON AREAS 3x2.5 4+2 1 16 0.648 3 4 0.912 16 1 6+1 3x2.5 LIGHTING AT GF HALLWAY
LIGHTING AT GF COMMON AREAS 3x2.5 1+3+5 1 16 0.405 5 6 16 1 30 3x2.5 SPARE
SPARE 1 16 7 8 1.320 16 1 22 3x2.5 LIGHTING AT ELEV. 1
LIGHTING AT ELEV. 2 3x2.5 22 1 16 1.320 9 10 1.320 16 1 22 3x2.5 LIGHTING AT SERVICE ELEV.
LIGHTING AT ELEV. 3 3x2.5 22 1 16 1.320 11 12 1.320 16 1 22 3x2.5 LIGHTING AT ELEV. 4
LIGHTING AT MAIN LOBBY 3x2.5 8 1 16 1.200 13 14 1.800 16 1 8+1 3x2.5 LIGHTING AT MAIN LOBBY
LIGHTING AT MAIN LOBBY 3x2.5 8+1+1 1 16 1.800 15 16 1.512 16 1 9+1 3x2.5 LIGHTING AT MAIN LOBBY
SPARE 1 16 17 18 0.500 20 1 1 3x4 SPLIT UNIT AT CONTROL ROOM
POWER OUTLET AT GF LOBBY 3x4 3 1 20 1.080 19 20 1.440 20 1 4 3x4 POWER OUTLET AT GF RECEPTION
POWER OUTLET AT GF COMMON AREAS 3x4 4 1 20 0.720 21 22 0.900 20 1 5 3x4 POWER OUTLET AT GF COMMON AREAS
POWER OUTLET AT GF COMMON AREAS 3x4 4 1 20 0.720 23 24 1.080 20 1 3 3x4 POWER OUTLET AT ELEV. PIT
POWER OUTLET AT ELEV. PIT 3x4 2 1 20 0.720 25 26 0.720 20 1 2 3x4 POWER OUTLET AT ELEV. PIT
POWER OUTLET FOR CAMERA AT GF/FF-P 3x2.5 21 1 20 0.200 27 28 1.000 20 1 1 3x2.5 BMS
FACP 3x2.5 4 1 20 1.000 29 30 1.000 20 1 1 3x2.5 CCTV
PAPB 3x2.5 3 1 20 1.000 31 32 1.000 20 1 1 3x2.5 ACP
MDF 3x2.5 2 1 20 1.000 33 34 1.500 20 1 1 3x4 WATER HEATER
WATER HEATER 3x4 1 1 20 1.500 35 36 1.680 20 1 1+1 3x4 HAND DRYER
HAND DRYER 3x4 1+1 1 20 1.680 37 38 1.500 20 1 5 3x4 EXHAUST FAN AT TRANSFORMER
EXHAUST FAN AT EE/[Link] 3x4 4 1 20 1.170 39 40 3.600 30 1 1 3x6 SPLIT UNIT AT SCECO ROOM
SPLIT UNIT AT SCECO ROOM 3x6 1 1 30 3.600 41 42 1.238 20 1 5 3x4 FCU-COMMON AREAS
SPARE 1 20 43 44 2.500
SPARE 1 20 45 46 2.500 30 3 1 5x6 AHU G-O1
SPARE 1 20 47 48 2.500
SPARE 1 20 49 50 20 1 SPARE
SPACE 1 51 52 1 SPACE
SPACE 1 53 54 1 SPACE
SUB TOTAL / PHASE 6.520 6.858 8.545 11.384 13.244 9.318 SUB TOTAL /PHASE
MAIN BUS RATING : 125A
TOTAL / PHASE 17.904 20.102 17.863
23 | P a g e
H. PP-H, Attic Floor
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : PP-H ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : ATTIC MOUNTING : SURFACE
LIGHTING AT 18F HALLWAY 3x2.5 14+2 1 16 1.380 1 2 1.950 16 1 17+1 3x2.5 LIGHTING AT 18F ELEV LOBBY
LIGHTING AT 18F COMMON AREAS 3x2.5 3+8+3+5 1 16 1.476 3 4 1.278 16 1 8+6+1+1 3x2.5 LIGHTING AT ATTIC COMMON AREAS
LIGHTING AT ATTIC COMMON AREAS 3x2.5 2+6+1+1 1 16 1.170 5 6 0.720 16 1 12 3x2.5 LIGHTING AT SOUTH LOWER ROOF
LIGHTING AT NORTH LOWER ROOF 3x2.5 12 1 16 0.720 7 8 1.080 16 1 6 3x4 POWER OUTLET AT 18F COMMON AREAS
POWER OUTLET AT 18F COMMON AREAS 3x4 6 1 16 1.080 9 10 1.260 16 1 6+2+1 3x4 POWER OUTLET AT ATTIC COMMON AREAS
POWER OUTLET AT ATTIC COMMON AREAS 3x4 6+2+1 1 16 1.260 11 12 1.050 16 1 6 3x4 POWER OUTLET AT SOUTH LOWER ROOF
POWER OUTLET AT NORTH LOWER ROOF 3x4 6 1 20 1.080 13 14 3.600 20 1 1 3X6 SPLIT UNIT AC - ELEC. ROOM (2T)
SPLIT UNIT - MACHINE RM (3T) 3X6 1 1 40 5.400 15 16 5.400 40 1 1 3X6 SPLIT UNIT AC - MECH. ROOM (3T)
SPLIT UNIT AC - SERVICE (1.5T) 3X6 1 1 30 2.700 17 18 3.600 30 1 1 3X6 SPLIT UNIT - MACHINE RM (2T)
SPLIT UNIT - MACHINE RM (2T) 3X6 1 1 30 3.600 19 20 2.700 30 1 1 3X6 SPLIT UNIT AC - SERVICE (1.5T)
SPARE 1 30 21 22 30 1 SPARE
SPARE 1 30 23 24 30 1 SPARE
SPARE 1 20 25 26 20 1 SPARE
SPACE 1 27 28 1 SPACE
SPACE 1 29 30 1 SPACE
SUB TOTAL / PHASE 6.780 7.956 5.130 9.330 7.938 5.370 SUB TOTAL /PHASE
MAIN BUS RATING : 100A
TOTAL / PHASE 16.110 15.894 10.500
24 | P a g e
I. PP-B, Mezzanine Floor
25 | P a g e
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C. PANEL NAME : PP-B ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : MEZZ FLOOR MOUNTING : SURFACE
LIGHTING AT MF COMMON AREAS 3x2.5 2+3+2+1 1 16 0.990 1 2 1.416 16 1 14+1+1 3x2.5 LIGHTING AT MF ELEV LOBBY
LIGHTING AT MF COMMON AREAS 3x2.5 8+2+5 1 16 1.182 3 4 1.377 16 1 2+2+5+3 3x2.5 LIGHTING AT FF COMMON AREAS
LIGHTING AT FF ELEV LOBBY 3x2.5 14 1 16 0.728 5 6 1.182 16 1 2+8+3+5 3x2.5 LIGHTING AT FF COMMON AREAS
LIGHTING AT 2F ELEV LOBBY 3x2.5 17+2+2 1 16 2.100 7 8 1.350 16 1 12+1+2+1 3x2.5 LIGHTING AT 2F HALLWAY
LIGHTING AT 2F COMMON AREAS 3x2.5 15 1 16 1.152 9 10 1.440 16 1 5 3x4 POWER OUTLET AT MF COMMON AREAS
POWER OUTLET AT MF COMMON AREAS 3x4 6+1 1 20 1.080 11 12 1.080 20 1 4+1 3x4 POWER OUTLET AT FF COMMON AREAS
POWER OUTLET AT FF COMMON AREAS 3x4 5 1 20 0.720 13 14 1.080 20 1 6 3x4 POWER OUTLET AT 2F COMMON AREAS
POWER OUTLET AT 2F COMMON AREAS 3x4 6 1 20 1.080 15 16 0.150 20 1 20 3x4 POWER OUTLET FOR CAMERA - MF/FF/RF-P
WATER HEATER-MF 3x4 1 1 20 1.500 17 18 1.500 20 1 1 3x4 WATER HEATER-MF
WATER HEATER-FF 3x4 1 1 20 1.500 19 20 1.680 20 1 1+1 3x4 HAND DRYER-MF
HAND DRYER-MF 3x4 1+1 1 20 1.680 21 22 1.260 20 1 2 3x4 HAND DRYER-FF
FCU FOR MF COMMON AREAS 3x4 5 1 20 1.538 23 24 2.500
FCU FOR FF COMMON AREAS 3x4 5 1 20 1.538 25 26 2.500 30 1 1 5x6 AHU MEZZ-01
FCU FOR 2F COMMON AREAS 3x4 4 1 20 1.389 27 28 2.500
2.100 29 30 20 1 SPARE
AHU MEZZ-02 5x6 1 1 30 2.100 31 32 20 1 SPARE
2.100 33 34 20 1 SPARE
SPARE 1 20 35 36 20 1 SPARE
SPARE 1 20 37 38 20 1 SPARE
SPACE 1 39 40 1 SPACE
SPACE 1 41 42 1 SPACE
SUB TOTAL / PHASE 8.948 8.583 6.946 8.026 6.727 6.262 SUB TOTAL /PHASE
MAIN BUS RATING : 100A
TOTAL / PHASE 16.974 15.310 13.208
26 | P a g e
J. PP-P1, Ground Floor
PROJECT NAME : AL KHAIR TOWER ENGINEER : GILBERTO C PANEL NAME : PP-P1 ELECTRICAL ROOM SHEET NO : 01
PROJECT NO. : 08913 DATE : VOLTAGE : 380/220V LOCATION : GF MOUNTING : SURFACE
LIGHTING AT GF PARKING 3x2.5 16+1 16 1 1.740 1 2 1.632 16 1 15+1 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 11 16 1 1.188 3 4 1.200 16 1 11+1 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 11 16 1 1.188 5 6 1.296 16 1 12 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 11 16 1 1.188 7 8 1.296 16 1 12 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 6 16 1 0.648 9 10 1.296 16 1 12 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 18 16 1 1.944 11 12 1.620 16 1 15 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 11 16 1 1.188 13 14 1.296 16 1 12 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 11+1 16 1 1.200 15 16 1.332 16 1 12+3 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT GF PARKING 3x2.5 15 16 1 1.620 17 18 1.188 16 1 11 3x2.5 LIGHTING AT GF PARKING
LIGHTING AT PARKING ELEV 3x2.5 10 16 1 1.080 19 20 16 1 SPARE
POWER OUTLET AT GF PARKING 3x4 6 20 1 1.080 21 22 1.260 20 1 7 3x4 POWER OUTLET AT GF PARKING
SPLIT UNIT AT EE-ROOM 3x4 1 20 1 0.500 23 24 1.200 20 1 6 3x4 POWER OUTLET AT GF PARKING
POWER OUTLET AT GF PARKING 3x4 5 20 1 0.900 25 26 1.188 20 1 4 3x4 POWER OUTLET AT GF PARKING
POWER OUTLET AT GF PARKING 3x4 6 20 1 1.080 27 28 20 1 SPARE
SPARE 20 1 29 30 16 1 SPARE
SPARE 16 1 31 32 16 1 SPARE
SPACE 33 34 1 SPACE
SPACE 35 36 1 SPACE
SUB TOTAL / PHASE 6.096 5.196 5.252 5.412 5.088 5.304 SUB TOTAL /PHASE
MAIN BUS RATING : 100A
TOTAL / PHASE 11.508 10.284 10.556
27 | P a g e
3.2 OVER-CURRENT PROTECTION AND CONDUCTOR SIZE
DETERMINATION
Therefore;
Where;
29 | P a g e
outlets and Water heaters) for tenant’s
(PP-T)
2 FAHU 22
30 | P a g e
2 Water pump (WCP) 10.625
1 Jockey Pump 15
𝑃 𝑥 1000 𝑘𝑉𝐴
IFLC = or
√3 𝑥 𝑉
√3 𝑥 𝑉 𝑥 𝑝𝑓
Non-continuous load
Where;
31 | P a g e
V – Phase to phase voltage (V)
pf – Power factor
32 | P a g e
110.14(C) NEC 2011 Temperature Limitation. The temperature
rating as associated with the ampacity of a conductor shall be
selected and coordinated so as not to exceed the lowest
temperature rating of any connected termination, conductor, or
device. Conductor with temperature rating higher than specified for
terminations shall be permitted to be used for ampacity adjustment,
correction, or both.
𝐶𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 𝐿𝑜𝑎𝑑(𝐴𝑚𝑝𝑠)
Conductor ampacity = Percent adjustment factor
𝑓𝑟𝑜𝑚 𝑡𝑎𝑏𝑙𝑒 310.15(𝐵)(2𝑏)
33 | P a g e
34 | P a g e
Table 4 - Current carrying capacity installed in ground
35 | P a g e
Table 5 - Current carrying capacity in installed in air
36 | P a g e
Table 6 - Group factor installed in cable tray
37 | P a g e
38 | P a g e
Table 7 - Ground thermal resistivity factor of the cable
39 | P a g e
40 | P a g e
Table 8 - Resistance and Reactance of the cable
41 | P a g e
42 | P a g e
Table 9- from table 2, 310.15(B)(2)(B) NEC for applying adjustment
factor
43 | P a g e
Summary of feeder voltage drop design criteria compliant to
the Article 215.2(A)(1)(b) Information note no.2, NEC
44 | P a g e
3.2.1 Distribution Board (DB-Lighting and Power loads)
45 | P a g e
52.631kVA
IFLC = = 75.96A
√3 x 400V
IP ≥ IFLC ≥ 75.96A
𝐶𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 𝐿𝑜𝑎𝑑(𝐴𝑚𝑝𝑠)
A. Conductor ampacity = Percent adjustment factor , (per NEC)
𝑓𝑟𝑜𝑚 𝑡𝑎𝑏𝑙𝑒 310.15(𝐵)(2𝑏)
46 | P a g e
B. Conductor ampacity x STR & GT x GLF, per recommended
of Riyadh cable manufacturer
Where;
75.96A
205A = , 205 A = 90.43A, NEC Version (A)
0.84
47 | P a g e
Formula 2 - Voltage drop formula
Vd = √[Link].L(RcosФ + XsinФ)
Where;
Vd – Voltage drop
Given:
IFLC = 75.96 A
48 | P a g e
X= 0.098 Ω/km from the table 6 page 29
L= 204 meters
page 68 of 90
Solution:
Vd = √3 .IFLC.L(RcosФ + XsinФ)
Vd = √3𝑥75.96𝐴𝑥0.204km(0.494Ω/kmx0.85 + 0.098Ω/kmxsin31.788˚)
Vd = √3𝑥75.96A𝑥0.204(0.4199 + j0.0516)
Vd = √3𝑥75.96𝑥0.204(0.423∠7.0057˚)
Vd = 11.35∠7.0057˚ V
49 | P a g e
𝑽𝒅
% voltage drop = x 100
𝑺𝒆𝒓𝒗𝒊𝒄𝒆 𝒗𝒐𝒍𝒕𝒂𝒈𝒆
𝟏𝟏.𝟑𝟓 𝐕
% voltage drop = x 100 = 2.84%
𝟒𝟎𝟎 𝐕
IFLC = 40.349kVA
√3 x 400V
= 58.3 A
50 | P a g e
IP ≥ IFLC (First Criteria)
IP ≥ IFLC ≥ 58.3 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
24.826 kVA
IFLC = = 35.83 A
√3 x 400 V
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
TCL = 21.99kVA
21.110 kVA
IFLC = √3 x 400 V
= 30.47 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
31.054 kVA
IFLC = = 44.83 A
√3 x 400 V
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
53.634kVA
IFLC = √3 x 400V
= 77.41 A
54 | P a g e
F.1 Over current protection devices (OCPD)
IP ≥ IFLC ≥ 77.41 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
IFLC = 43.672kVA
√3 x 400V
= 63 A
55 | P a g e
G.1 Over current protection devices (OCPD)
IP ≥ IFLC ≥ 63 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
IFLC = 31.751kVA
√3 x 400V
= 45.83 A
56 | P a g e
H.1 Over current protection devices (OCPD)
IP ≥ IFLC ≥ 45.83 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
57 | P a g e
IFLC = 25.236kVA
√3 x 400V
= 36.4 A
IP ≥ IFLC ≥ 36.4 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
58 | P a g e
40.804kVA
IFLC = = 58.89 A
√3 x 400V
IP ≥ IFLC ≥ 58.89 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule.
59 | P a g e
Table 10 - Elevator Electrical Load Capacity
TCL = 12 kVA
In ≥ Ib ≥ 27 A
Ip ≥ Iflc ≥ 27 A
60 | P a g e
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
TCL = 8 kVA
IP ≥ IFLC ≥ 19 A
IP ≥ IFLC ≥ 19 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
61 | P a g e
3.2.3 Pumps Electrical Data
M. Fire pump
62 | P a g e
Figure 5 - Inside the pump room area, this photo was taken after
testing and commissioning the fire pump or firefighting system of
the building.
63 | P a g e
Figure 6 - Fire pump Actual Nameplate Rating
IP ≥ IFLC x 600%
IP = 365 A x 6 = 2190 A
IP ≥ IB ≥ 2000 A
Vd = √3IbL(RcosФ + XsinФ)
Given:
65 | P a g e
IFLC = 365 A = 365 A x 125% = 456.25 Amps minimum
L= 31 meters
Solution:
√3𝑥365A𝑥0.031km(0.197/kmx0.85+0.091/kmxsin31.788˚)
Vd =
2
√3𝑥365𝑥0.031(0.197x0.85+0.091x0.52677)
Vd =
2
√3𝑥365𝑥0.031(0.174∠15.97˚)
Vd =
2
Vd = 1.71∠15.97˚ V
𝟏.𝟕𝟏𝐕
% voltage drop = x 100 = 0.43%
𝟒𝟎𝟎𝐕
66 | P a g e
Therefore: from maximum load current Ib ≥ 365A is compatible of
2set-4Cx120mm²+70mm² insulated, XLPE with 602.04A total de-
rated capacity combined at 90°C maximum operating temperature,
minimum size of cable with consideration of voltage drop is
adequate for fire pump at a distance of 31 meters
Given:
TCL = 12 kW
SF = 1.15
PF = 0.80
EF = 0.90
67 | P a g e
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
12 x 1000
IFLC =
√3 x 400 x0.8x.9
IFLC = 24.1 A
IP ≥ 24.1 A x 6
IP ≥ 144.6 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
TCL = 22 kVA
68 | P a g e
Using 3 Phase formula:
22 kVA
IFLC = = 31.75 A
√3 x 400 V
IP ≥ IFLC x 1.25
IP ≥ 31.75 A x 1.25
IP ≥ 39.7 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
Given:
TCL = 8.5 kW
SF = 1
69 | P a g e
PF = 0.80 EF = 0.95
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
8.5 x 1000
IFLC =
√3 x 400 x0.8x0.95
IFLC = 16.14 A
IP ≥ IFLC x 250% Inverse Time Circuit Breaker per Table 430.52 NEC
2014
IP ≥ 16.14 A x 250%
IP ≥ 41 A
70 | P a g e
Table 11 – Extracted from NEC 2014 Table 430.52, Percentage
Multiplier of Motor Over-Current Protection Devices (OCPD)
OL = IFLC x SF
= 16.14 x 1.15
71 | P a g e
Use 40AT/100AF, 4Pole, 400V, 60Hz, Molded case circuit breaker
(MCCB at EMDB) and 50AT disconnect switch installed at the ground
floor water pump room area
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
Given:
TCL = 9 kW
SF = 1
PF = 0.80 EF = 0.9
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
9 x 1000
IFLC =
√3 x 400 x0.8x0.9
IFLC = 18.05A
72 | P a g e
Q.1 Over current protection devices (OCPD)
IP ≥ IFLC x 175%
IP ≥ 18.05 A x 1.75
IP ≥ 31.6 A
OL = IFLC x SF
= 18.05 x 1.15
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
73 | P a g e
Given:
TCL = 7.5 kW
SF = 1.15
PF = 0.80 EF = 0.9
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
7.5 x 1000
IFLC =
√3 x 400 x0.8x0.9
IFLC = 15.04 A
IP ≥ IFLC x 175% Time Delay fuse rating per Table 430.52 NEC2014
IP ≥ 15.04 A x 1.75
74 | P a g e
IP ≥ 26.32 A
= 15.04 x 1.25
IP ≥ IFLC x 10
IP ≥ 15.04 A x 10 = 150.4 A
75 | P a g e
Solving of voltage drop from CWP-CP to farthest location of pumps
at 15 meters:
Vd = √3IbL(RcosФ + XsinФ)
Given:
IFLC = 15.04A
L= 15 meters
Solution:
Vd = √3𝑥15.04A𝑥0.015km(3.93Ω/kmx0.85 + 0.121Ω/kmxsin31.788˚)
Vd = √3𝑥15.04𝑥0.015(3.93x0.85 + 0.121x0.52677)
Vd = √3𝑥15.04𝑥0.015(3.34∠1.097˚)
Vd = 1.3∠1.097˚ V
𝟏.𝟑𝐕
% voltage drop = x 100 = 0.33%
𝟒𝟎𝟎𝐕
76 | P a g e
Therefore: from maximum load current Ib ≥ 15.04A is compatible of
1set-4Cx6mm²+10mm² G insulated, XLPE with 62.72A de-rated
capacity at 90°C maximum operating temperature, minimum size of
cable with consideration of voltage drop are adequate for chilled
water pump power supply at a farthest distance of 15 meters length
of the cable from CWP to Control Panel.
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
675 kVA
IFLC = = 974.3 A
√3 x 400 V
IP ≥ 974.3 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
78 | P a g e
1 PP-P3 21.99 21.99
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
363.604 x 1000
IFLC =
√3 x 400
IFLC = 524.7 A
IP ≥ IFLC
IP ≥ 524.7 A
79 | P a g e
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
ELEV. ATTIC
5 12 60
FLR
2 ELEV. PARKING 8 16
1 JOCKEY PUMP 15 15
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
80 | P a g e
308.16 x 1000
IFLC =
√3 x 400
IFLC = 444.79 A
IP ≥ IFLC
IP ≥ 444.79 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
81 | P a g e
LOADS kVA LOADS kVA
2 FAHU 1 & 2 22 44
1 EXHAUST FAN 9 9
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
994.4 x 1000
IFLC =
√3 x 400
IFLC = 1435.3 A
IP ≥ IFLC
IP ≥ 1435.3 A
82 | P a g e
Use 2500AT/3000AF, 4Pole, 400V, 60Hz, Molded Case Circuit
Breaker (MCCB) over current protection device of MDB-1, adjusted
setting to 1500A tripping level.
√3IbL(RcosФ + XsinФ
Vd = √3IbL(RcosФ + XsinФ) 𝑜𝑟
N
N = number of cable
Given:
IFLC = 1435.3A
L= 34 meters
Solution:
83 | P a g e
√3x1435.3Ax0.034km(0.0993Ω/kmx0.85+0.090Ω/kmxsin31.788˚)
Vd =
6
√3x1435.3x0.034(0.0993x0.85+0.090x0.52677)
Vd =
6
√3𝑥1435.3𝑥0.034(0.0966∠29.11˚)
Vd =
6
Vd = 1.4∠79.9˚ V
𝟏.𝟒𝐕
% voltage drop = x 100 = 0.35%
𝟒𝟎𝟎𝐕
84 | P a g e
1 CHILLER-2 675 675
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
1350 x 1000
IFLC =
√3 x 400
IFLC = 1948.6 A
IP ≥ IFLC
IP ≥ 1948.6 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
X. Meter Center-1
85 | P a g e
Table 16 - Tabulated Loads for Meter Center-1
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
1137.9 x 1000
IFLC =
√3 x 400
IFLC = 1642.42 A
IP ≥ IFLC
IP ≥ 1642.42 A
86 | P a g e
Use 2500AT/3000AF, 4Pole, 400V, 60Hz, Molded case circuit
breaker (MCCB) over current protection device of Meter Center-1
adjusted setting to 2000A tripping level.
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
Y. Meter Center-2
P x 1000 kVA
IFLC = or
√3 x V x pf √3 x V
707.4 x 1000
IFLC =
√3 x 400
87 | P a g e
IFLC = 1021 A
IP ≥ IFLC
IP ≥ 1021 A
Using the same method for cable size calculation and voltage drop
calculation is shown tabulated in 3.2.2, table-16 to table-21 page
67 to page 72, Summary of voltage drop and cable schedule
88 | P a g e
3.2.4 SUMMARY OF VOLTAGE DROP AND CABLE SCHEDULE
89 | P a g e
Table 18 - Summary of voltage drop and cable schedule - 1
90 | P a g e
91 | P a g e
Table 19 - Summary of voltage drop and cable schedule - 2
92 | P a g e
Table 20 - Summary of voltage drop and cable schedule - 3
93 | P a g e
94 | P a g e
Table 21 - Summary of voltage drop and cable schedule - 4
95 | P a g e
Table 22 - Summary of voltage drop and cable schedule - 5
96 | P a g e
97 | P a g e
Table 23 - Summary of voltage drop and cable schedule - 6
98 | P a g e
3.2.5 Methods of Grounding System Application and
Procedures
ρ 4L ρ L2 2L4
R2GR>S = (ln -1) + (1 - + )
4πL a 4πs 3s2 5s4
99 | P a g e
Formula 4 - Two Grounds, Diameter of Ring D, Diameter of Wire d
ρ 8D 4D
RROW= (ln + ln )
2π D
2 d s
LO
Diameter of Ring of Wire, D =
π
Where:
R1GR, R2GR>S, R2GR<S, RROW = resistance in ohm (Ω)
ρ = soil resistivity in ohm-centimeter (Ω.m)
Lo = length of ring of wire in meter (m)
L = length of electrode in meter (m)
a = radius of electrode in meter (m)
s = spacing of ground electrode in meter (m)
D = diameter of Ring of Wire in meter (m)
d = diameter of wire in meter (m)
100 | P a g e
101 | P a g e
Figure 7 - Grounding System Layout Plan
102 | P a g e
Grounding System Layout Plan – Al Khair Tower
103 | P a g e
Figure 8 - Grounding Installation Details
104 | P a g e
Installation Details
105 | P a g e
Grounding electrode conductor = 120mm2 bare copper
Lo = 297.3 m
Lo 297.3
D= = = 94.63m
π ᴨ
a = 0.0191
RT = R2GR(total) + RROW
ρ 8D 4D
RROW= (ln + ln )
2π D
2 d s
RROW = 0.0360482 Ω
ρ 4L ρ L2 2L4
R2GR>S = (ln -1) + (1 - + )
4πL a 4πs 3s2 5s4
R2GR>S1 = 0.636839 Ω
Using the same formula for other spacing provided, below is the
summary of the grounding resistance of each two grounding rods:
106 | P a g e
Item Description Resistance to Spacing in Total in
Ground (Ω) Meter Parallel
1
= 27.74066041 Ω
RT
RT = 0.0225 Ω
107 | P a g e
108 | P a g e
3.3 TRANSFORMER SIZE CALCULATION & OCPD
109 | P a g e
Diversity factor: The ratio of the sum of the individual non-
coincident maximum demands of various subdivisions of the system
to the maximum demand of the complete system. The diversity
factor is always 1 or greater. The (unofficial) term diversity, as
distinguished from diversity factor refers to the percent of time
available that a machine, piece of equipment, or facility has its
maximum or nominal load or demand (i.e., a 70% diversity means
that the device in question operates at its nominal or maximum load
level 70% of the time that it is connected and turned on).
Therefore:
110 | P a g e
A. Determine the full load current (IFLC)) of the transformer
IFLC = 41.8A
Use OCPD:
IFLC = 1443.4A
111 | P a g e
Use OCPD:
3.3.2 Transformer-2
2 FAHU 1 & 2 22 44
1 EXHAUST FAN 9 9
112 | P a g e
Evaluate for the compliance to the SCECO loads requirements of
transformer capacity = 994.4 kVA x 1.25 = 1243 kVA
Therefore:
Use OCPD:
IFLC = 2165.06A
Use OCPD:
113 | P a g e
Note: Over current protection devices (OCPD) should be fully
coordinated with the total demand current at (V.1 OCPD)
2 ELEV. PARKING 8 16
1 JOCKEY PUMP 15 15
114 | P a g e
TOTAL CONNECTED LOADS = 321 kVA
Therefore:
IFLC = 721.69A
IP ≥ IFLC x 125%
115 | P a g e
Figure 9 - Actual Generator installed name plate:
Hence:
Use:
Therefore:
This is because the breaker would theoretically take the same time
to clear as on initial trip, but since the machine is at higher internal
temperatures at the start of the fault, it would reach a higher than
expected temperature, potentially damaging the machine. This
problem is present in all breakers, and most overcurrent relays.
117 | P a g e
Figure 10 - Generator Decrement Curve
118 | P a g e
3.4.3 Alternator Thermal Damage Curve with MCCB Trip
Curve
119 | P a g e
3.4.4 Alternator Damage Curve
120 | P a g e
Figure 12 - Alternator Damage Curve
122 | P a g e
Step 1: Prepare a system single-line diagram, which is as shown in
electrical schematic diagram with limitations outlined.
For Utility:
For Equipment:
For Cables:
123 | P a g e
Formula 7 - Cable Impedance Per Unit
MVAbase)
Zpu = Zcable( )
kV2 base)
L MVAbase)
Zpu= (R + jX) ( )
N kV2 base)
Where:
N = Number of conductor
Notes:
124 | P a g e
Step 5: Simplify the impedance diagram into simplest form.
kVAbase
I(3Фsc-sym) =
√3 x kVbase x ZT
Where:
125 | P a g e
Base (given) Voltage: kV base (given) = 13.8 kV
MVAbase(new)
Z (source) =
MVAbase(given)
1.5 MVAbase(new)
Z (source) =
500 MVAbase(given)
Z (source) = + j0.003 pu
126 | P a g e
b. Impedance per unit (pu) calculation of Transformer
127 | P a g e
Bases (given) Voltage: kV base (given) = 0.4 kV
ZT = 5.61%, R = 0.00062 Ω
Hence:
2
kVbase(given) MVAbase(new)
Zpu-T = Zpu(given)( kV ) (MVA )
base(new) base(given)
0.4 2 1.5
Zpu-T = 0.0561 ( ) ( )
0.4 1.5
Zpu-T = +j0.0561 pu
Z 2 = R2 + X 2
0.05612 = 0.000622 + X 2
X = 0.0561 pu
128 | P a g e
Feeder Size: 6set-(4Cx240mm² XLPE/PVC)
MVAbase)
Zpu = Zcable( )
kV2 base)
L MVAbase)
Zpu = (R + jX) ( )
N kV2 base)
0.034 1.5
Zpu-C1 = (0.0993 + j0.090) ( 6 ) ( 2)
0.4
129 | P a g e
Zpu-C5 120mm² 0.197 0.091 0.078 1 0.144056 + j0.066544
130 | P a g e
Zpu-C44 240mm² 0.0993 0.09 0.005 2 0.002327 + j0.002109
Given:
MVAbase(new) = 1.5MVA
2
kVbase(given) MVAbase(new)
Zpu = Zpu(given)( kV ) (MVA )
base(new) base(given)
0.4 2 1.5
Zpu-M1 = 0.25(0.4) (0.010625)
Zpu-M1 = j35.3 pu
131 | P a g e
Using the same method of calculation, impedances per unit of other
motors are calculated and tabulated in the table shown in
succeeding pages below.
Moto Motor
Motor r subtransient
Description PF Zl (pu)
Capacity
(hp) reactance
(kW) (kVA)
10.62
Motor 1 8.5 5 0.8 11.4 25% + j35.3
10.62
Motor 2 8.5 5 0.8 11.4 25% + j35.3
149.
Motor 4 2 186.5 0.8 200 17% + j1.4
0.9
Elev. 1-5 11 12 2 15 25% + j31.3
132 | P a g e
133 | P a g e
[Link] Electrical Single Line Riser Diagram of Al Khair Tower
134 | P a g e
135 | P a g e
Figure 14 - Electrical Riser Single Line Diagram with Excluded the Coverage of Fault Calculation
136 | P a g e
137 | P a g e
Figure 15 - Electrical Single Line Riser Diagram Coverage with Short Circuit Calculation
138 | P a g e
[Link] Electrical Single Line Diagram with Fault Locations
139 | P a g e
Figure 16 - Electrical Single Line Diagram with Fault Locations
140 | P a g e
[Link] System Impedance Diagram
141 | P a g e
Figure 17 - Impedance Diagram
142 | P a g e
Figure 18 - Simplified Impedance at point A to B
= 0.064153∠84.73˚ pu
143 | P a g e
Figure 19 - Simplified Impedance point C to D
M5-M14 = 0 + j4 (typical)
Solution:
0.552656+j0.017016+j4
Zpu (C-D) = 0.180994 + j0.083606 + ( )
10
= 0.5398∠64.04 ˚ pu
144 | P a g e
Solving for equivalent impedance (pu) at point C’ combining series
and parallel:
[Link] = j41.67 pu
Solution:
Zpu-C3,E.F
= 2.74875 + j41.87 pu
= 41.96∠86.25˚ pu
Zpu-C4,FAHU1
= 1.694672 + j17.8583 pu
= 17.94∠84.58˚ pu
145 | P a g e
Zpu-C5,FAHU2
= 0.144056 + j17.116544 pu
= 17.12∠89.52˚ pu
Solution:
1
Zpu-C’ = 1 1 1
+ +
41.96∠86.25˚ 17.94∠84.58˚ 17.12∠89.52˚
1
=
0.023832∠−86.25˚+ 0.0556∠−84.58˚+ 0.05842∠−89.52˚
1
=
0.001559−j0.023781 + 0.005252−j0.0554 + 0.0008942−j0.0585
146 | P a g e
1 1
= =
0.0077052−j0.137681 0.1379∠−86.797˚
at point E to F
147 | P a g e
Solution:
Zpu-F equal
1
=
1 1 1 1 1
[ + + + + +
0.0992∠11.3˚ 0.1574∠6.34˚ 0.219∠6.34˚ 0.2011∠6.34˚ 0.184∠6.34˚
1 1 1 1
+ + + +
0.128∠11.3˚ 0.3585∠6.34˚ 0.437∠6.34˚ 0.516∠6.34˚
1 1 1
+ + ]
0.595∠6.34˚ 0.674∠6.34˚ 0.4486∠11.3˚
1
[10.08∠−11.3˚+ 6.35∠−6.34˚+ 4.566∠−6.34˚+ 4.97∠−6.34˚ +5.44∠−6.34˚+
7.8125∠ − 11.3˚ + 2.79∠ − 6.34˚ + 2.3∠ − 6.34˚ + 1.94∠ − 6.34˚ + 1.68∠ − 6.34˚ +
1 1
Zpu-F = =
107.2697−j13.7159 108.143∠−7.2865˚
Zpu-F = 0.0092471∠7.2865˚
Zpu-F = 0.009173+j1.1782 pu
Hence:
148 | P a g e
Substitute;
at point H
Solution;
= 1.868484 + j31.507609 pu
1.868484 + j31.507609
=
5
= 0.3737 + j6.3015218 pu
= 6.326∠86.61˚ pu
Zpu-C36,M1
= 2.267719 + j35.464 pu
= 35.54∠86.34˚ pu
149 | P a g e
Zpu-C37,Pr. Fan1 = Zpu-C38,Pr. Fan2
= 2.74875 + j33.49875 pu
2.74875 + j33.49875
=
2
= 1.3744 + 16.7494 pu
= 16.8057∠85.31˚ pu
= 1.0995 + j46.9595 pu
1.0995 + j46.9595
=
2
= 0.54975 + j23.47975 pu
= 23.4862∠88.66˚ pu
Zpu-C41,M2
= 0.384825 + j35.327825 pu
= 35.33∠89.38˚ pu
Zpu-C42,M3
= 0.426056 + j25.030806 pu
= 25.03444∠89.025˚ pu
Zpu-C43,M4
= 1.44∠86.4˚ pu
Zpu-G = 10%
Solution:
2
kVbase(given) MVAbase(new)
Zpu = Zpu(given)( ) ( )
kVbase(new) MVAbase(given)
0.4 2 1.5
Zpu-G = 0.10(0.4) (0.5)
Zpu-G = j0.3 pu
= 0.002327 + 0.302109 pu
= 0.302∠89.55˚ pu
151 | P a g e
Impedance (pu) at point G to H combining series and parallel:
Solution:
Zpu-H
1
=
1 1 1 1
[ + + +
6.326∠86.61˚ 35.54∠86.34˚ 16.8057∠85.31˚ 23.4862∠88.66˚
1 1 1
+ + +
35.33∠89.38˚ 25.03444∠89.025˚ 1.44∠86.4˚
1
=
[0.1581∠ − 86.61˚ + 0.0282∠ − 86.34˚ + 0.0595∠ − 85.31˚ +
Hence:
Substitute;
= 0.972∠85.64˚ pu
153 | P a g e
Zpu (E-F) 0.068432+j1.220003 1.222∠86.79˚
Note: For three phase fault there is no negative and zero sequence
fault current.
154 | P a g e
Figure 23 - Symmetrical fault current at MDB1 fault-2
155 | P a g e
Apply Thevenin’s Theorem;
Solution:
1
Zpu-ZT = 1 1 1 1 1
[ + + + +
Zpu(A−B) Zpu(E−F) Zpu(G−H) Zpu−C′ Zpu(C−D)
1
=
1 1 1 1
[ + + +
0.064153∠84.73 1.222∠86.79˚ 0.972∠85.64˚ 7.252∠86.797˚
1
+
0.5398∠64.04˚]
1
=
[15.588∠ − 84.73˚ + 0.8183∠ − 86.79˚ + 1.03∠ − 85.64˚ +
0.138∠ − 86.797˚ + 1.853∠ − 64.04˚]
F2 = F1
Solution:
kVAbase
IF2(3Фsc-sym) =
√3 x kVbase x ZT
1500kVA
=
√3 x 0.4kV x 0.052
157 | P a g e
IF2(3Фsc-sym) = 41635.84 A or 41.635 kA
158 | P a g e
Figure 25 - Combine series and parallel impedance at point Fault-3
159 | P a g e
Simplified Impedance at point Fault-3
Solution:
1
Zpu-Eq. Partial’ = 1 1 1 1
[ + + +
Zpu(A−B) Zpu(E−F) Zpu(G−H) Zpu−C′
1
=
1 1 1 1
[ + + +
0.064153∠84.73 1.222∠86.79˚ 0.972∠85.64˚ 7.252∠86.797˚
1
=
[15.588∠ − 84.73˚ + 0.8183∠ − 86.79˚ + 0.8573∠ − 60.76˚ +
0.138∠ − 86.797˚
160 | P a g e
1 1
= =
1.564−j17.504 17.57∠−84.89˚
1
Zpu-Eq. = 1 1
[ + ]
Zpu([Link]′−C2) Zpu(D)
kVAbase
IF3(3Фsc-sym) =
√3 x kVbase x Zpu−Eq
1500kVA
=
√3 x 0.4kV x 0.159
161 | P a g e
Figure 27 - Solve for Symmetrical fault current at F4 when the
Generator is used.
Hence;
Zpu-G = j0.3 pu
1 1 1
= +
Zpu − Eq. Zpu(G − C44) Zpu(H − C30)
162 | P a g e
1 1 1
= +
Zpu − Eq. 0.302∠89.55˚ 0.965∠86.06˚
Therefore:
kVAbase
IF4(3Фsc-sym) =
√3 x kVbase x Zpu−Eq.
500kVA
=
√3 x 0.4kV x 0.2301
163 | P a g e
Therefore; the interrupting withstand rating of the main feeder at
MDB1 should be minimum of 45 kA at 400VAC or above is
acceptable.
(NA Supplement)
164 | P a g e
e) Rated Short-Time Withstand Current (minimum):
165 | P a g e
Formula 10 - Single Line to Ground Fault, The sequence connection
are connected in series
Ia = 3Ia1
If = Ia
Ia2 = Ia1
If = Ib
166 | P a g e
a.3 Double line to Ground Fault (DLG Fault) Impedance
Diagram
If = Ib
Vf
Ia1 =
Z1 + Z2 + Z0
Where:
167 | P a g e
Vf = 1∠0˚
Z0 = Zpu-Tx + Zpu-C1
Z0 = 0.00592 + j0.06088
Solution;
1∠0˚
Ia1 =
2(0.00639 + j0.0516) + 0.00592 + j0.06088
1∠0˚
Ia1 =
0.01278 + j0.1032 + 0.00592 + j0.06088
1∠0˚
Ia1 =
0.0187 + j0.16408
1∠0˚
Ia1 =
0.1652∠83.5˚
Ia1 = 6.0533∠-83.5˚ A
Hence;
Ia = 3Ia1
If = Ia
If = 3 x 6.0533∠-83.5˚ A
If = 18.1599∠-83.5˚ A
168 | P a g e
Using;
ISLG-F2 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
ISLG-F2 = x 18.1599 A
√3 x 0.400
Vf
Ia1 =
Z1 + Z2 + Z0
Where:
Vf = 1∠0˚
Z0 = Zpu-Tx + Zpu-C1
Z0 = 0.00592 + j0.06088
Solution;
169 | P a g e
1∠0˚
Ia1 =
2(0.0954 + j0.13) + 0.00592 + j0.06088
1∠0˚
Ia1 =
0.4∠58˚
Ia1 = 2.5∠-58˚ A
Hence;
Ia = 3Ia1
If = Ia
If = 3 x 2.5 ∠-58˚ A
If = 7.5 ∠-58˚ A
Using;
ISLG-F3 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
ISLG-F3 = x 7.5 A
√3 x 0.400
170 | P a g e
Vf = Ia1 x (Z1 + Z2 + Z0)
Vf
Ia1 =
Z1 + Z2 + Z0
Where:
Vf = 1∠0˚
Z0 = Zpu-G + Zpu-C44
Z0 = 0.002327 + j0.302109
Solution;
1∠0˚
Ia1 =
2(0.00514 + j0.230043) + 0.002327 + j0.302109
1∠0˚
Ia1 =
0.7623∠89.053˚
Ia1 = 1.312∠-89.053˚ A
Hence;
Ia = 3Ia1
If = Ia
If = 3 x 1.312∠-89.053˚ A
If = 3.94∠-89.053˚ A
171 | P a g e
Using;
ISLG-F4 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
500
ISLG-F4 = x 3.94 A
√3 x 0.400
Formulas:
Ia2 = Ia1
If = Ib
Vf = Ia1 x (Z1 + Z2 )
Vf
Ia1 =
Z1 + Z2
Where;
Vf = 1∠0˚
Z1 = Z2 = 0.052∠82.94˚= 0.00639+j0.0516
172 | P a g e
Solving for ILL-F2:
Solution;
1∠0˚
Ia1 =
0.00639 + j0.0516 + 0.00639 + j0.0516
1∠0˚
Ia1 =
0.01278 + j0.1032
1∠0˚
Ia1 =
0.104∠82.98˚
Ia1 = 9.6154∠-82.98˚ A
Hence;
Ia2 = -Ia1
Ia2 = (-1)Ia1
Ia2 = 9.6154∠97.02˚ A
Where;
Ia0 = 0
a² = 1∠-120˚
a = 1∠120˚
173 | P a g e
Substitute,
Ib = If
If = 16.655 ∠-172.98˚ A
Using;
ILL-F2 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
ILL-F2 = x 16.655 A
√3 x 0.400
ILL-F2 = 36059.13 A or 36 kA
Where:
Vf = 1∠0˚
174 | P a g e
Solution;
1∠0˚
Ia1 =
2(0.0954 + j0.13)
1∠0˚
Ia1 =
0.33∠54˚
Ia1 = 3.03∠-54˚ A
Hence;
Ia2 = -Ia1
Ia2 = (-1)Ia1
Ia2 = 3.03∠54˚ A
Where;
Ia0 = 0
a² = 1∠-120˚
a = 1∠120˚
Substitute,
175 | P a g e
Ib = 6.06 ∠180˚ A
Ib = If
If = 6.06 ∠180˚ A
Using;
ILL-F3 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
ILL-F3 = x 6.06 A
√3 x 0.400
Where:
Vf = 1∠0˚
Solution;
1∠0˚
Ia1 =
2(0.00514 + j0.230043 )
1∠0˚
Ia1 =
0.4602∠88.72˚
Ia1 = 2.173∠-88.72˚ A
176 | P a g e
Hence;
Ia2 = -Ia1
Ia2 = (-1)Ia1
Where;
Ia0 = 0
a² = 1∠-120˚
a = 1∠120˚
Substitute,
Ib = 3.8114 ∠0˚ A
Ib = If
If = 3.8114 ∠0˚ A
Using;
ILL-F4 = Ibase x If
177 | P a g e
kVAbase
Ibase =
√3 x kVbase
500
ILL-F4 = x 3.8114 A
√3 x 0.400
If = Ib
Z2 x Z0
Vf = Ia1 (Z1 + )
Z2 + Z0
Vf
Ia1 = Z x Z0
Z1 + 2
Z2 + Z0
Z0 = Zpu-Tx + Zpu-C1
178 | P a g e
Solving for IDLG-F2:
Where;
Vf = 1∠0˚
Z1 = Z2
Z0 = Zpu-Tx + Zpu-C1
Solution;
1∠0˚
Ia1 = 0.052∠82.94˚ x 0.06117∠84.45˚
0.052∠82.94˚ + [ ]
0.052∠82.94˚+ 0.06117∠84.45˚
1∠0˚
Ia1 = 0.00318084∠167.39˚
0.052∠82.94˚ + [ ]
0.113152∠83.75˚
1∠0˚
Ia1 =
0.052∠82.94˚ + 0.02811∠78.757˚
1∠0˚
Ia1 =
0.0800612∠81.5˚
Ia1 = 12.49∠-81.5˚ A
Z0
Ia2 = (-Ia1 ) x
Z2 + Z0
179 | P a g e
0.06117∠84.45˚
Ia2 = (-12.49∠-81.5˚) x
0.052∠82.94˚ + 0.06117∠84.45˚
Ia2 = 6.76∠80.81˚ A
Z2
Ia0 = (-Ia1 ) x
Z2 + Z0
0.052∠82.94˚
Ia0 = (-12.49∠-81.5˚) x
0.052∠82.94˚ + 0.06117∠84.45˚
Ia0 = 5.732∠82.3˚ A
a² = 1∠240˚
a = 1∠120˚
Substitute,
6.76∠80.81˚)
Ib = 18.884∠155.4˚ A
If = Ib = 18.884∠155.4˚ A
Using;
180 | P a g e
IDLG-F2 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
IDLG-F2 = x 18.884 A
√3 x 0.400
IDLG-F2 = 40885.06 A or 41 kA
Where:
Vf = 1∠0˚
Z0 = Zpu-Tx + Zpu-C1
Solution;
Vf
Ia1 = Z x Z0
Z1 + 2
Z2 + Z0
1∠0˚
Ia1 = 0.159∠53.13˚ x 0.06117∠84.45˚
0.159∠53.13˚ + [ ]
0.159∠53.13˚ + 0.06117∠84.45˚
181 | P a g e
1∠0˚
Ia1 =
0.106∠.71.2˚
Ia1 = 9.4∠-71.2˚ A
Z0
Ia2 = (-Ia1 ) x
Z2 + Z0
0.06117∠84.45˚
Ia2 = (-9.4∠-71.2˚) x
0.159∠53.13˚ + 0.06117∠84.45˚
Ia2 = 2.7∠-48.75˚ A
Z2
Ia0 = (-Ia1 ) x
Z2 + Z0
0.159∠53.13˚
Ia0 = (-9.4∠-71.2˚) x
0.159∠53.13˚+ 0.06117∠84.45˚
Ia0 = 6.92∠-81.07˚ A
a² = 1∠240˚
a = 1∠120˚
Substitute,
182 | P a g e
Ib = 6.92∠-81.07˚ + (1∠240˚x9.4∠-71.2˚) + (1∠120˚x2.7∠-48.75˚)
Ib = 7.67∠-161.4˚ A
If = Ib = 7.67∠-161.4˚ A
Using;
IDLG-F3 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
1500
IDLG-F3 = x 7.67 A
√3 x 0.400
Where:
Vf = 1∠0˚
Z0 = Zpu-G + Zpu-C44
Z0 = 0.002327 + j0.302109
Solution;
183 | P a g e
Solving for Ia1
Vf
Ia1 = Z x Z0
Z1 + 2
Z2 + Z0
1∠0˚
Ia1 = 0.230∠88.72˚ x 0.302∠89.55˚
0.230∠88.72˚ + [ ]
0.230∠88.72˚ + 0.302∠89.55˚
1∠0˚
Ia1 =
0.36062∠88.85˚
Ia1 = 2.773∠-88.85˚ A
Z0
Ia2 = (-Ia1 ) x
Z2 + Z0
0.302∠89.55˚
Ia2 = (-2.773∠-88.85˚ x
0.230∠88.72˚ + 0.302∠89.55˚
Ia2 = 1.574∠88.5˚ A
Z2
Ia0 = (-Ia1 ) x
Z2 + Z0
0.230∠88.72˚
Ia0 = (-2.773∠-88.85˚) x
0.230∠88.72˚ + 0.302∠89.55˚
Ia0 = 1.1985∠89.33˚ A
184 | P a g e
Solving for Ib;
a² = 1∠240˚
a = 1∠120˚
Substitute,
1.574∠88.5˚)
Ib = 4.5875∠145.92˚ A
If = Ib = 4.5875∠145.92˚ A
Using;
IDLG-F4 = Ibase x If
kVAbase
Ibase =
√3 x kVbase
500
IDLG-F4 = x 4.5875 A
√3 x 0.400
185 | P a g e
Selected KAIC
186 | P a g e
187 | P a g e
[Link] POSITIVE SEQUENCE IMPEDANCE
188 | P a g e
Figure 28 - Positive Sequence Impedance
189 | P a g e
[Link] Negative Sequence Impedance
190 | P a g e
[Link] Zero Sequence Impedance
191 | P a g e
Figure 30 - Zero Sequence Impedance
192 | P a g e
[Link] Zero Sequence Impedance When Generator is use
193 | P a g e
194 | P a g e
3.5.7 Primary Short Circuit Current Determination
Solution:
1
Zpu-Eq. = 1 1 1 1
+ + +
Zpu(E−F) Zpu(G−H) Zpu−C′ Zpu(C−D)
1
=
1 1 1 1
[ + + +
1.222∠86.79˚ 0.972∠85.64˚ 7.252∠86.797˚ 0.5398∠64.04˚]
195 | P a g e
1
=
[0.8183∠ − 86.79˚ + 1.03∠ − 85.64˚ + 0.138∠ − 86.797˚ + 1.853∠ − 64.04˚]
1 1
= =
0.9429706−j3.64778 3.76769∠−75.506˚
Where;
Z(source) = + j0.003 pu
Solution:
+ 0.0052753125 + j0.00478125
1 1 1
= +
Zpu − Pr Zpu − Eq. T Zpu − Source
1 1 1
= +
Zpu − Pr 0.32599∠77.18˚ 0.003∠90˚
Zpu − Pr = 0.0029734∠89.88˚ pu
or 0.0000062275 + j0.0029734 pu
197 | P a g e
Therefore:
kVA(base−new)
IPrF(3Фsc-sym) =
√3 x kV(base−given) x Zpu−Pr
1500 kVA
IPrF(3Фsc-sym) = = 21105.63 A or 21.1kA
√3 x 13.8kV x 0.0029734
Vf
Ia1 =
Z1 + Z2 + Z0
Where:
Vf = 1∠0˚
Z0-Pr = Zpu-Source
Z1-Pr = Zpu-Pr
198 | P a g e
Z2-Pr = Z1-Pr
Gevin:
Z0-PrF = j0.003 pu
Solution;
1∠0˚
Ia1(SGL-F) =
2(0.0000062275 + j0.0029734 ) + j0.003
1∠0˚
Ia1(SGL-F) =
0.000012455 + j0.0089468
1∠0˚
Ia1(SGL-F) =
0.00894681∠89.92˚
Ia1(SGL-F) = 111.772∠-89.92˚ A
Hence;
Ia = 3Ia1(SGL-F)
If = Ia
Ia-(SLG-PrF) = 3 x 111.772∠-89.92˚ A
Using;
kVAbase
Ibase =
√3 x kVgiven
199 | P a g e
1500
ISLG-PrF = x 335.315∠-89.92˚ A
√3 x 13.8
Formulas:
Ia2 = Ia1
If = Ib
Vf = Ia1 x (Z1 + Z2 )
Vf
Ia1 =
Z1 + Z2
Where:
Vf = 1∠0˚
Z1 = Z2
Z1-Pr = Zpu-Eq. T
Z2-Pr = Z1-Pr
Vf
Ia1(LL-PrF) =
Z1−Pr + Z2−Pr
Gevin:
200 | P a g e
Z1-PrF = 0.0029734∠89.88˚ or 0.0000062275 + j0.0029734 pu
Solution;
1∠0˚
Ia1(LL-PrF) =
2(0.0000062275 + j0.0059468)
1∠0˚
Ia1(LL-PrF) =
0.005946813∠89.88˚
Ia1(LL-PrF) = 168.1573∠-89.88˚ A
Hence;
Ia2 = (-1)Ia1
If = Ib
Ia0 = 0
a² = 1∠240˚
a = 1∠120˚
Substitute;
201 | P a g e
Ib(LL-PrF) = 0 + (1∠240˚ x 168.1573∠-89.88˚) + (1∠120˚ x
168.1573∠89.88˚)
Using;
kVAbase
Ibase =
√3 x kVgiven
1500
ILL-PrF = x 291.62∠0˚
√3 x 13.8
Z1 x Z0
Vf = Ia1 (Z1 + )
Z1 + Z0
Vf
Ia1 = Z x Z0
Z1 + 2
Z2 + Z0
Where:
Vf = 1∠0˚
Z0-Pr = Zpu-Source
Z1-Pr = Zpu-Pr
202 | P a g e
Z2-Pr = Z1-Pr
Gevin:
Z0-PrF = j0.003 pu
Solution;
1∠0˚
Ia1 = 0.0029734∠89.88˚ x 0.003∠90˚
0.0029734∠89.88˚ + [ ]
0.0029734∠89.88˚ + 0.003∠90˚
1∠0˚
Ia1 =
0.0029734∠89.88˚ + 0.0014932∠90.48˚
1∠0˚
Ia1 =
0.00443∠89.76˚
Ia1 = 225.73∠-89.76˚ A
Z0
Ia2 = (-Ia1 ) x
Z2 + Z0
0.003∠90˚
Ia2 = (-225.73∠-89.76˚) x
0.0029734∠89.88˚ + 0.003∠90˚
0.003∠90˚
Ia2 = (-225.73∠-89.76˚) x
0.005974∠89.94˚
203 | P a g e
Ia2 = 117.98∠89.76˚ A
Z2
Ia0 = (-Ia1 ) x
Z2 + Z0
0.0029734∠89.88˚
Ia0 = (-225.73∠-89.76˚) x
0.0029734∠89.88˚ + 0.003∠90˚
0.0029734∠89.88˚
Ia0 = (-225.73∠-89.76˚) x
0.005974∠89.94˚
Ia0 = 112.353∠89.82˚ A
a² = 1∠240˚
a = 1∠120˚
Substitute,
117.98∠89.76˚)
If = Ib
Using;
204 | P a g e
kVAbase
Ibase =
√3 x kVgiven
1500
I(DBL-PrF) = x 303.67∠-168.94˚
√3 x 13.8
Selected KAIC
205 | P a g e
Phase currents are then calculated by using Equations it should be
noted that when analyzing an open-circuit fault, the Thevenin
reduction of each sequence network is not taken from the fault
location as with a short-circuit fault. Instead, the Thevenin
equivalent is taken from one side of the open-circuit fault location,
through the entire network, to the other side of the fault location.
Vb = Vc = 0
V1 = V2
V0 = V1 = V2
206 | P a g e
Figure 34 - Single Open Fault Diagram
Z0 = Zpu-Tx + Zpu-C1
Ia = 0
Vf
Ia1 =
Z1 + Z2 + Z0
Ib = 6.0538∠180˚ pu
Ib = 6.0538∠0˚ pu
kVAbase
Ibase(13.8kV) =
√3 x kVbase
1500
Ibase(13.8kV) = = 62.76 A
√3 x 13.8
207 | P a g e
The current of the line side of transformer are:
Ia = 0
When the fault occurs, no current will flow on the opened phases,
so
Ib = Ic = 0--------------(eq. 1)
I1(a² − a) = I2(a² − a)
I1 = I2----------------------------- (eq. 2)
This means that all sequence and line currents are zero. So, when
phases b and c are opened on the high-voltage side of transformer
and phase a remains energized, no current flows through
transformer.
Extracted From:
Canada
208 | P a g e
209 | P a g e
Figure 35 - Knee Point Voltage
210 | P a g e
211 | P a g e
212 | P a g e
213 | P a g e
214 | P a g e
215 | P a g e
216 | P a g e
217 | P a g e
218 | P a g e
219 | P a g e
220 | P a g e
[Link].1 Summary of Result for CT and Knee Point
Calculations
221 | P a g e
222 | P a g e
3.6 PROTECTION AND COORDINATION DETERMINATION
References:
Figure No.2
Minimum short circuit values for low voltage systems extracted from
IEEE as shown:
224 | P a g e
Figure 36 - Electrical design protection coordination
Typical low voltage power circuit breaker and molded case circuit
breaker (MCCB-Thermal Magnetic tripping curve.
226 | P a g e
3.6.1 Circuit Breaker Time Current Characteristic
227 | P a g e
Figure 37 - Time current characteristic curve
228 | P a g e
3.6.2 Cable Damage Curve
229 | P a g e
230 | P a g e
3.6.3 Time Current Curve Protection Coordination Graph-1
231 | P a g e
0.26 Sec.
232 | P a g e
3.6.4 Time Current Curve Protection Coordination Graph-2
233 | P a g e
0.26 Sec.
The safe stall point represents the maximum time a motor can
sustain a locked rotor condition without damage at a specified
terminal voltage. NEMA MG-1 requires safe stall times not less than
12 seconds for motors less than 500HP and 1000V.
235 | P a g e
Figure 40 - LV Motor Time Current Curve
236 | P a g e
Figure 41 - LV Motor TCC Areas
237 | P a g e
3.6.6 Transformer Equipment Damage Curve
a) Motor characteristic:
Sensor: 40 A, CB Rating
Settings:
239 | P a g e
Long time pick-up current setting or continuous
current (LTPU), at this point, used the maximum
rating of the CB rating which is equal to 40 Amps.
ILTPU = 40 Amps
TSTD = Fixed
IINST. = Fixed
Where:
Note:
Cu./XLPE/PVC
Protective Device:
Brand: Square-D
Interrupting kA: 50 kA
Settings:
241 | P a g e
ILTPU = 700 Amps
TSTD = 0 sec.
Note:
242 | P a g e
Cu./XLPE/PVC
Protective Device:
Brand: Square-D
Settings:
243 | P a g e
Note:
Protective Device:
Brand: Square-D
244 | P a g e
Settings:
TSTD = 3 sec.
equal to 65 kA.
245 | P a g e
equal to 50 kA.
25kA.
Given:
IFL-P = 62.76 A
IFL-S = 2165.12 A
= 1206.82 A
Manufacturer = ABB
= 12.068 A
246 | P a g e
Transformer Full Load Current
Pick-up Setting =
CT Rated Primary
= 62.76 / 100
= 0.6276 A
5.67
PP = TD x (0.0352+ )
M2 −1
Where:
TD = Time-dial setting
(Tp), M > 1
247 | P a g e
IF
M =
IPU
12.068
M =
0.6276
M = 19.3
5.67
0.681 = TD x (0.0352+ )
19.32 −1
TD = 13.5
= 1.5 x 120.82 A
= 1,810.23 A
= 1.20 x 62.76
= 75.312 A
248 | P a g e
During transformer secondary bus fault, the main secondary
protection will isolate the fault while the primary protection will be
acting as back-up protection. During transformer internal fault, the
primary protection will trip, considering bolted internal fault.
Infrequent Fault:
2 25 1250 1569
249 | P a g e
1.5MVA
= x 25 = 1,569 Amps
√3 x 13.8
1500kVA
Full Load Current = = 62.76 Amps
√3 x 13.8
250 | P a g e
[Link] Transformer Damage Curve Infrequent Fault
251 | P a g e
Figure 43 - Transformer Damage Curve (Infrequent Fault)
252 | P a g e
Figure 44 - Transformer Damage Curve (frequent Fault)
This part of the report will verify whether the selected cables for the
secondary feeder cables connected to the fault location can
withstand under short circuit conditions to prevent damage or
dangerous temperature in conductors at certain time.
0.143
IK = 𝑥𝑠
√t
Where;
IK = Short Circuit in kA
Solution:
0.143
IK = x 240 = 48.54 kA
√0.5
Cu./XLPE/PVC
Therefore;
255 | P a g e
3.7 ARC FLASH DETERMINATION
3.7.1 Introduction
Cause:
256 | P a g e
Dangers:
– 0.00304G (IgIbf)
Ig = log10
258 | P a g e
Convert from lg:
Ia = 10lg Ia
Consider Fault 1:
Ibf-F1 = 41.635 kA
V = 0.4 kV
G = 32mm
0.00304 x 32Ig(41.635)
IgIa-F1 = 1.2350
Ia = 17.18 kA
Calculate En:
259 | P a g e
Formula 17 - Incident Energy
Ig En = K1 + K2 + 1.081 Ig Ia + 0.0011 G
Where:
Then:
En = 10Ig En
Consider Fault 1:
G = 32mm
Ig En = 0.7023
En = 5.038 J/cm²
260 | P a g e
Formula 18 -Normalized Incident Energy
𝑡 610 𝑥
𝐸𝑖 = 4.184 ∙ 𝐶𝑓 ∙ 𝐸𝑛 ∙ ( ) ∙ ( )
0.2 𝐷
Where:
𝐶𝑓 = Calculated factor 1.0 for voltage above 1kV, and 1.5 for
261 | P a g e
𝐸𝑖 = 41.104 J/cm²
Convert to cal/cm²
0.239006cal
41.104 J/cm² ∙
1J
𝐸𝑖 = 9.87 cal/cm²
Where:
262 | P a g e
𝐷𝐵 = Distance of the boundary from the arching point (mm)
𝐶𝑓 = Calculated factor 1.0 for voltage above 1kV, and 1.5 for
boundary. EB can be set at 5.0 J/cm² for bare skin (no hood)
x = Distance exponent
Ibf-F1 = 41.635 kA
263 | P a g e
t = 0.26 seconds clearing arcing time
x = 1.473
𝐸𝐵 = 5.0 J/cm²
1
0.26 6101.473 1.473
𝐷𝐵 = [4.184 ∙ 1.5 ∙ 5.038 ∙ ( )∙( )]
0.2 5.0
264 | P a g e
[Link] Summary of Arc Flash Incident Energy per Fault
Location
265 | P a g e
Table 41 - Incident Energy per HRC
266 | P a g e
Notes: Restricted approach for 151-750V is 0.3 meter and limited
approach boundary for exposed fixed circuit is 1meter, As per Table
130.4(D)(a) NFPA 70E, 2015
Conclusions:
267 | P a g e
observed to protect workers from the dangers associated with an
arc flash.
CHAPTER 4
Electrical Material Specifications and Bill
of Quantity
268 | P a g e
CHAPTER 4 – ELECTRICAL MATERIALS AND EQUIPMENT
SPECIFICATIONS
4. The rated withstand voltage shall comply with IEC 76-3. The
transformer shall be 13.8 kV, 3 Phase Primary / 400 V, 3 Phase
Secondary dry type/oil immersed type. Windings shall be of
copper. Full-power tapping shall be provided in the high voltage
windings. Winding connections inside transformers shall be
brazed. The winding arrangement shall be Dyn 11 for three-
phase transformers, in-line, three line cores shall be used. All
metal parts of the core, frame tank, etc., shall be maintained at
earth potential. Transformer is naturally cooled. The indicator
269 | P a g e
shall be a dial-type calibrated in degrees centigrade and fitted
with two adjustable setting contacts, for remote alarm and trip
purpose, and a hand-reset pointer to register the highest
temperature attained.
270 | P a g e
Size neutral bus 100 percent of full load amperes. Bus bar
temperature shall not exceed 90 degrees C under full load.
4.1.4 Panelboards:
271 | P a g e
clearances as required by UL. Where space is indicated, make
100% size neutral bus in each panel for connection of circuit neutral
stripe along its front and bonded to the steel cabinet for connecting
272 | P a g e
ATS shall be the electrically operated type that is mechanically held
in both operating positions. ATS shall be suitable for use in
emergency or standby systems described in NFPA 70. ATS shall be
UL listed, and test reports are approved as being equivalent of test
results and certified test reports as those determined and reported
by UL. ATS shall be electrically-operated contactor or low-voltage
power circuit breaker type rated at 2000A, 4P, 600VAC which shall
be manufactured and tested in accordance with applicable
requirements of IEEE C37.13, IEEE C37.90.1, NEMA ICS 1, NEMA
ICS 2, UL 1008 and UL 1066. ATS shall also conform to NFPA 110
except that the ATS shall not be equipped with either overload or
fault current protective devices and shall be designed and
manufactured to prevent stops in an intermediate or neutral
position during transfer by the use of electrical actuators and
stored-energy mechanisms.
Wire and Cable Conductor Sizes: Wire and cable conductor sizes
termination is made.
273 | P a g e
Conductor Color Coding:
Provide for all service, feeder, branch, control and signaling circuit
and black for neutrals, except where neutrals of more than one
system are installed in same raceway or box, the other neutral shall
Standard or as follows:
Phase R – Red
Phase Y - Yellow
Phase B – Blue
Phase R - Red
Phase Y - Yellow
Phase B - Blue
Ground - Green
Neutral – Black
274 | P a g e
Including service entrances, shall be multicore or single core cables,
degrees C.
C - Assembly: Four insulated conductors are laid up, filled with non-
275 | P a g e
E - Core Identification: Four core- red, yellow, blue and black.
276 | P a g e
encasement surrounding the bank shall be rectangular in cross-
section and shall provide at least 76mm of concrete thickness of
50mm, except separate light and power conduits from control,
signal, and telephone conduits by a minimum concrete thickness of
100mm.
277 | P a g e
bearing, air-cooled by a direct drive centrifugal blower fan, and
4.1.15 Motors:
IEC 34, ISO 9001 and NEMA MG1, except sealed (hermetic-type)
Motors for operation on 220 volt circuits shall have a voltage rating
of 230 volts, 400 volts, 3-phase circuits shall have a voltage rating of
voltage rating and shall have a minus 10% of the motor voltage
rating and shall have a service derating factor not less than 1.15.
278 | P a g e
4.1.16 Motor Sizes:
performed and shall not exceed its full load nameplate current rating
NEMA ICS1 and NEMA ICS2. All controllers shall have thermal
and shall have under voltage release when used with maintained-
279 | P a g e
Wiring method shall be insulated conductors installed in conduit,
exposed installations.
Electrical Metallic Tubing: Allowed for use in spaces, void spaces, and
ELECTRICAL
A SUBSTATION
280 | P a g e
Item Description Qty. Unit
B GENERATOR
D METER CENTER
281 | P a g e
Item Description Qty. Unit
busbar
busbar
282 | P a g e
Item Description Qty. Unit
1 ATS-630A 1 Set
PANEL BOARDS
1 PP-A 1 Set
2 PP-B 1 Set
283 | P a g e
Item Description Qty. Unit
4 PP-H 1 Set
5 PP-P1 1 Set
6 PP-P2 1 Set
7 PP-P3 1 Set
8 PP-C1 1 Set
10 LP-EX 1 Set
1 CWP-CP1 1 Set
2 CWP-CP2 5 Set
3 FF-CP 1 Set
4 WP-CP1 1 Set
5 WP-CP2 1 Set
284 | P a g e
Item Description Qty. Unit
1 4x10mm² 396 Lm
2 4x16mm² 19 Lm
3 4x25mm² 462 Lm
4 4x50mm² 162 Lm
5 4x70mm² 7280 Lm
6 4x120mm² 172 Lm
7 3(4x185mm²) 105 Lm
8 4(4x240mm²) 669 Lm
9 4x300mm² 35 Lm
10 3(4x300mm²) 65 Lm
11 4(4x300mm²) 49 Lm
12 6(4x300mm²) 40 Lm
13 7(4x300mm²) 45 Lm
14 8(4x300mm²) 121 Lm
J EARTH CABLES
285 | P a g e
Item Description Qty. Unit
1 1x6mm² E 396 Lm
2 1x10mm² E 19 Lm
3 1x16mm² E 462 Lm
4 1x25mm² E 162 Lm
5 1x35mm² E 7280 Lm
6 1x70mm² E 172 Lm
7 1x95mm² E 315 Lm
8 1x120mm² E 2676 Lm
9 1x185mm² E 1949 Lm
200cm CT 5 Lm
150cm CT 253 Lm
100cm CT 45 Lm
80cm CT 15 Lm
286 | P a g e
Item Description Qty. Unit
50cm CT 76 Lm
30cm CT 28 Lm
100cm CL 250 Lm
30cm CL 80 Lm
30cm CT 7 Lm
30cm CL 80 Lm
15cm CL 80 Lm
L LIGHT POINTS
287 | P a g e
Item Description Qty. Unit
14 EX2 16 No.
288 | P a g e
Item Description Qty. Unit
15 EL 93 No.
16 W1 116 No.
17 W2 8 No.
1 L1 34 No.
2 L2 48 No.
3 L4 (2-arms) 4 No.
4 L4 (3-arms) 2 No.
5 L5 24 No.
6 L6 4 No.
O WIRING DEVICES
289 | P a g e
Item Description Qty. Unit
weatherproof 82 No.
290 | P a g e
Item Description Qty. Unit
291 | P a g e
Item Description Qty. Unit
Q EARTHING SYSTEM
292 | P a g e
Item Description Qty. Unit
CHAPTER 5
Conclusion and Recommendation
293 | P a g e
294 | P a g e
CHAPTER 5 – CONCLUSION AND RECOMMENDATION
5.1 Conclusion
295 | P a g e
6. Thus, readers of this report will be guided clearly on how the
design of electrical power distribution of the teacher’s staff
housing and other premises have been reviewed and prepared
as well.
5.2 Recommendation
From the specific comments mentioned above and being the one
who review the design of the power distribution for typical office
areas and for services utilities and etc., my recommendation will be
as follows:
296 | P a g e
1. NFPA 70 National Electrical Code 2014 Edition
CHAPTER 6 – AFFIDAVITS
AFFIDAVITS
297 | P a g e
298 | P a g e
6.1 Affidavit of Sole Authorship
299 | P a g e
Philippines Passport
300 | P a g e
PRC ID of Aspirant
301 | P a g e
302 | P a g e
6.2 Affidavit of PEE-1
303 | P a g e
Philippines Passport of PEE-1
304 | P a g e
305 | P a g e
PRC-ID of PEE-1
306 | P a g e
6.3 Affidavit of PEE-2
307 | P a g e
Philippines Passport of PEE-2
308 | P a g e
309 | P a g e
PRC-ID of PEE-2
310 | P a g e
6.4 Affidavit of PEE-3
311 | P a g e
Philippine Passport and PRC ID of PEE-3
312 | P a g e
313 | P a g e
CHAPTER 7 – AUTO-BIORAPHY & CURRICULUM VITEA
7.1 Auto-Biography
AUTO-BIOGRAPHY
314 | P a g e
7.2 Curriculum Vitae
OUTSTANDING ACHIEVEMENTS
315 | P a g e
7.3 Employment, Training and Seminars Certificates
316 | P a g e
317 | P a g e
7.3.2 Training and Seminars CPD points
318 | P a g e
319 | P a g e
320 | P a g e
321 | P a g e
322 | P a g e
323 | P a g e
324 | P a g e