Coordination tables
Index
Introduction ................................................................................................................... I
Back-up .................................................................................................................... 1/1
Discrimination ........................................................................................................... 2/1
Motor protection ....................................................................................................... 3/1
Switch-disconnectors ............................................................................................... 4/1
ABB SACE
Coordination tables
Introduction
ABB SACE I
Coordination tables
Discrimination and back-up
This collection of selectivity and back-up tables for ABB circuit-breakers has been
studied to help select the appropriate circuit-breaker, fulfilling the specific selectivity
and back-up requirements according to the different types of installation.
The tables are divided on the basis of the type of intervention (back-up or selective
protection), and are grouped according to types of circuit-breakers (air, moulded-
case, and miniature), covering all the possible combinations of ABB circuit-breakers.
The technical data, updated to the latest series of miniature, moulded-case and air
circuit breakers on the market, make this publication a comprehensive and simple
tool: once again, ABB SACE makes its consolidated experience in the Low Voltage
sector available to professionals.
II ABB SACE
Coordination tables
Discrimination and back-up
Restricting the field to an analysis of the problem of how to harmonize the action of
the protection devices in the event of overcurrents (overloads and short-circuits) - a
problem covering 90% of the coordination requirements of protection devices in radial
low voltage installations - it is important to remember that:
– overcurrent trip selectivity means “coordination of the operating characteristics of
two or more overcurrent protection devices so that, on occurrence of overcurrents
within established limits, the device supposed to operate within these limits
intervenes, whereas the others do not”1;
– total discrimination means “overcurrent selectivity so that when there are two
overcurrent protection devices in series, the protection device on the load side
provides protection without tripping the other protection device” 2;
– partial discrimination means “overcurrent selectivity so that when there are two
overcurrent protection devices in series, the protection device on the load side
provides protection up to a given overcurrent limit without tripping the other device” 3.
This overcurrent threshold is called the “selectivity limit current I s”4;
– back-up protection means “coordination for protection against overcurrents of two
protection devices in series, where the protection device generally (but not necessarily)
situated on the supply side provides overcurrent protection with or without the aid of the
other protection device and avoids excessive stress on the latter” 5. The current value
above which protection is ensured is called the “switching current I B”6.
Types of coordination
Influence of the electrical parameters of the installation (rated current and
short-circuit current)
If the analysis is restricted to the behaviour of the protection devices with tripping
based on overcurrent releases, the strategy used to coordinate the protection devices
mainly depends on the rated current (In) and short-circuit current (Ik) values in the part
of installation concerned.
Generally speaking, the following types of coordination can be classified:
– current type selectivity;
– time type selectivity;
– zone selectivity;
– energy selectivity;
– back-up.
Now let us examine these various solutions in detail.
IV ABB SACE
Coordination tables
Discrimination and back-up
time delay. Selective circuit-breakers, often of the open type, must be used for the
various levels (category B circuit-breakers according to the IEC 60947-2 Standard)
to guarantee a sufficiently high short-time withstand current;
– the duration of the disturbance induced by the short-circuit current on the power
supply voltages in the zones unaffected by the fault can pose problems with
electromechanical (voltage below the electromagnetic release value) and electronic
devices;
– the number of discrimination levels is limited by the maximum time which can be
withstood by the electrical system without loss of stability.
ABB SACE V
Coordination tables
Discrimination and back-up
Energy-based selectivity
Energy-based coordination is a particular type of selectivity which exploits the
currentlimiting characteristics of moulded-case circuit-breakers. It is important to
remember that a current-limiting circuit-breaker is “a circuit-breaker with a trip time
short enough to prevent the short-circuit current reaching the peak value it would
otherwise reach”7.
In practice, all the ABB SACE moulded-case circuit-breakers in the Isomax and Tmax
ranges have more or less accentuated current-limiting features, obtained by:
– reaching a valid compromise between the capacity of the release to withstand
current values lower than the instantaneous trip thresholds and the repulsion of the
main contacts at short-circuit currents;
– triggering rapid displacement of the arc inside the arcing chambers (magnetic blast)
suitably designed to generate a high arcing voltage;
– placing several arcing chambers in series, with contacts optimised to carry out
different functions (main opening under short-circuit, backup opening with the
principal function of isolation and opposition to the recovery voltage, etc.).
Under short-circuit conditions, these circuit-breakers are extremely rapid (with trip
times of a few milliseconds) and open in the event of a strong asymmetric component.
It is therefore not possible to use the time-current trip curves (load side circuit-
breaker) and no trip limit curves (supply side circuit-breaker), obtained with
symmetrical sine wave forms, to study the coordination. The phenomena are mainly
dynamic (and therefore proportional to the square of the instantaneous current value)
and can be described using the specific let-through energy and no trip limit energy
curves of the supply side circuit-breaker.
What generally happens is that the energy associated with the load side circuit-
breaker trip is lower than the energy value needed to complete the opening of the
supply side circuit-breaker. To ensure a good level of reliability, avoiding any
oversizing or transient contact repulsion phenomena in the circuit-breaker on the
supply side, this calculation should be integrated with additional information, such as
the current limiting curves (peak Ip value - prospective value of the symmetrical
component of the short-circuit current) and the setting for contact repulsion.
This type of selectivity is certainly more difficult to consider than the previous ones
because it depends largely on the interaction between the two devices placed in series
(wave forms, etc.) and requires access to data often unavailable to the end user.
Manufacturers provide tables, slide rules and calculation programs in which the limit
selectivity current values Is under short-circuit conditions between different
combinations of circuit-breakers are given. These values are defined by theoretically
integrating the results of a large number of tests performed in compliance with the
requirements of appendix A of the IEC 60947-2 Standard.
The advantages of using this type of coordination include:
– breaking is fast, with trip times which become shorter as the short-circuit current
increases. This consequently reduces the damage caused by the fault (thermal and
dynamic stresses), the disturbance to the power supply system, the sizing costs,
etc.;
– the discrimination level is no longer limited by the value of the short-time current Icw
withstood by the devices;
– a large number of hierarchically different levels can be coordinated;
VI ABB SACE
Coordination tables
Discrimination and back-up
Back-up protection
With backup protection, discrimination is sacrificed in favour of the need to help the
load side devices which have to interrupt short-circuit currents beyond their breaking
capacity. In this case, over and above the switching current IB, simultaneous opening
of both the protection devices placed in series or, alternatively, of just the supply side
circuit-breaker (a somewhat rare case, typical of a configuration consisting of a supply
side circuit-breaker and a load side isolator).
Manufacturers provide tables derived from tests based on the previously-mentioned
appendix A of the IEC 60947-2 Standard.
These combinations can be calculated according to the instructions given in section
A.6.2 of the above standard, comparing:
– the value of the Joule integral of the device protected at its breaking capacity with
that of the supply side device at the prospective current of the association
(maximum short-circuit current for which backup protection is provided);
– the effects induced in the load side device (e.g. by the arcing energy, maximum
peak current and limited current) at the peak current value during operation of the
protection device against a supply side short-circuit.
Conclusions
Technically a large number of solutions can be realised regarding coordination of the
protection devices in an installation.
Selecting which type of coordination to use in the various zones of the installation is
strictly linked to installation and design parameters and stems from a series of
compromises so that the objectives required in terms of reliability and availability are
achieved keeping the costs and limiting the risks within acceptable limits.
The designer’s task is to choose a solution, for the various installation zones, from
among those available which offers the best balance between technical and financial
requirements according to:
– functional and safety requirements (acceptable risk levels) and reliability (availability
of the installation);
– the reference value of the electrical values;
– the costs (protection devices, control systems, interconnection components, etc.);
– the effects, the admissible duration and the cost of electrical disservices;
– any future evolution of the system.
For each of the proposed solutions, there is a combination of ABB products which can
meet these requirements.
Electromechanical starter
The choice of the starting method and also, if necessary, of the type of motor to be
used depends on the typical resistant torque of the load and on the short-circuit
power of the motor supplying network.
With alternating current, the most commonly used motor types are as follows:
– asynchronous three-phase squirrel-cage motors (AC-3): the most widespread type
due to the fact that they are of simple construction, economical and sturdy; they
develop high torque with short acceleration times, but require elevated starting
currents;
– slip-ring motors (AC-2): characterized by less demanding starting conditions, and
have quite a high starting torque, even with a supply network of low power.
Starting methods
The most common starting methods for asynchronous squirrel-cage motors are
detailed below.
ABB SACE IX
Coordination tables
General notes on motor protection and switching
Starting sequence
By pressing the start button, contactors KL and KY are closed. The timer starts to
measure the start time with the motor connected in star. Once the set time has
elapsed, the first contact of the timer opens the KY contactor and the second contact,
delayed by approximately 50-80 ms, closes the K∆ contactor.
With this new configuration, contactors KL and K∆ closed, the motor becomes
deltaconnected.
The thermal release TOR, inserted in the delta circuit, can detect any 3rd harmonic
currents, which may occur due to saturation of the magnetic pack and by adding to
the fundamental current, overload the motor without involving the line.
With reference to the connection diagram, the equipment used for a Star/Delta starter
must be able to carry the following currents:
3
Ie overload protection release
∆3
Trip classes
The trip classes differentiate between the thermal releases according to their trip curve.
The trip classes are defined in the following table 2:
where Tp is the cold trip time of the thermal release at 7.2 times the set current value
(for example: a release in class 10 at 7.2 times the set current value must not trip
within 4 s, but must trip within 10 s).
It is normal procedure to associate class 10 with a normal start-up type, and class 30
with a heavy duty start-up type.
X ABB SACE
Coordination tables
General notes on motor protection and switching
Coordination type
Type 1
It is acceptable that in the case of short-circuit the contactor and the thermal release
may be damaged. The starter may still not be able to function and must be inspected;
if necessary, the contactor and/or the thermal release must be replaced, and the
breaker release reset.
Type 2
In the case of short-circuit, the thermal release must not be damaged, while the
welding of the contactor contacts is allowed, as they can easily be separated (with a
screwdriver, for example), without any significant deformation.
ABB SACE XI
Coordination tables
Switch-disconnectors
Switch-disconnectors
IntrodBack-uzionep
Back-up protection
The tables given provide the value (in kA, referring to the breaking capacity according
to the IEC 60947-2 Standard) for which the back-up protection among the combination
of selected circuit-breakers is verified. The tables cover the possible combinations
between ABB SACE Tmax and Isomax series of moulded-case circuit-breakers and
those between the above-mentioned circuit-breakers and the ABB series of miniature
circuit-breakers. 1
The values indicated in the tables refer to the voltage:
– Vn of 230/240 V AC for coordination with miniature S9 circuit-breakers
– Vn of 400/415 V AC for all the other coordinations.
Note
The following tables give the breaking capacities at 415 V AC for circuit-breakers
SACE Isomax and Tmax.
Caption
MCB = miniature circuit-breakers (S9, S2, S500)
MCCB = moulded-case circuit-breakers (Tmax, Isomax)
Caption of symbols
For solutions not shown in these tables, please consult the website:
[Link]
or contact ABB SACE
Supply s.* T1 T1 T1 T2 T3 T2 T3 T2 T2
Version B C N S H L
Load s. Char. In [A] Icu [kA] 16 25 36 50 70 85
S931 N C 2..25 4,5 16 16 16 20 10 20 10 20 20 1
32, 40 10 10 10 16 16 16 16
S941 N B,C 2..25 6 16 16 16 20 10 20 10 20 20
32, 40 10 10 10 16 16 16 16
S951 N B,C 2..25 10 16 16 16 25 16 25 16 25 25
32, 40 16 16 16 16
S971 N B,C 2..25 10 16 16 16 25 16 25 16 25 25
32, 40 16 16 16 16
* Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral)
Supply s. T1 T1 T1 T2 T3 T4 T2 T3 T4 T2 T4 T2 T4 T4
Version B C N S H L L V
Load s. Char. In [A] Icu [kA] 16 25 36 50 70 85 120 200
S200L C 6..10 6 16 25 30 36 36 36 36 40 40 40 40 40 40 40 1
13..40 16 16
S200 B,C,K,Z 0.5..10 10 16 25 30 36 36 36 36 40 40 40 40 40 40 40
13..63 16 16
S200M B,C,D 0.5..10 15 16 25 30 36 36 36 50 40 40 70 40 85 40 40
13..63 25 25 60 60
B, C, 0.5..10 25 30 36 36 36 50 40 40 70 40 85 40 40
S200P D,K,Z 13..25 30 36 30 36 50 30 40 60 40 60 40 40
32..63 15 16 25 30 36 25 36 50 25 40 60 40 60 40 40
S280 B,C 80, 100 6 16 16 16 36 16 30 36 16 30 36 30 36 30 30
S290 C,D 80..125 15 16 25 30 36 30 30 50 30 30 70 30 85 30 30
S500 B,C,D 6..63 50 70 70 85 120 200
Supply s. T1 T1 T2 T3 T4 T5 T6 T2 T3 T4 T5 T6 S7 T2 T4 T5 T6 S7 T2 T4 T5 T6 S7 T4 T5
Version C N S H L L L V
Load s. Char. Icu [kA] 25 36 50 70 65 85 120 100 200
T1 B 16 25 36 36 36 30 30 30 50 50 36 36 36 70 40 40 40 85 50 50 50 85 65
1 T1
T1
C 25 36 36 36 36 36 36 50 50 40
50 50 50
40
50
50
50
50 70
50 70
65 65 65
65 65 65
50 85 85 85 70 50 130 100
50 85 100 100 70 50 200 120
T2 50 50 50 50 50 50 70 65 65 65 65 85 100 100 85 85 200 120
T3 N 36 50 50 50 50 50 65 65 65 50 100 100 100 50 200 120
T4 50 50 50 50 65 65 65 50 100 100 65 65 200 120
T5 50 50 50 65 65 50 100 85 65 120
T6 50 40 65 40 70 50
T2 70 70 70 65 85 100 100 85 85 200 130
T3 70 70 70 100 100 100 200 150
T4 S 50 70 70 70 65 100 100 85 85 200 150
T5 70 70 65 100 85 85 150
T6 70 85 85
T2 85 120 120 85 85 200 150
T4 H 70 120 120 100 100 200 180
T5 120 100 100 180
T6 100 85
T2 85 120 120 200 180
T4 L 120 200 200
T5 200
IntroduzioneDiscrimination
Selective protection
The tables given provide the value (in kA, referring to the breaking capacity according
to the IEC 60947-2 Standard) for which the selective protection is verified among the
combination of selected circuit-breakers. The tables cover the possible combinations
between ABB SACE Emax series air circuit-breakers, ABB SACE Tmax and Isomax
series of moulded-case circuit-breakers, and the ABB series of miniature circuit-breakers.
The values in the table represent the maximum value obtainable of discrimination
between supply side circuit-breaker and load side circuit-breaker referring to the voltage:
– Vn of 230/240 V AC for the S9 circuit-breakers and Vn of 400/415 V AC for the supply
side circuit-breakers in the coordination between MCB with the miniature S9 circuit-
breakers.
2 – Vn of 400/415 V AC for all the other coordinations.
These values are obtained following particular specifications which, when not respected,
could give discrimination values which are in some cases much lower than what is
indicated. Some of these are generally valid and are given below, others referring
exclusively to particular types of circuit-breakers will be the subject of a note under the
relative table.
General prescriptions
– Function I of the electronic releases of the supply side circuit-breakers must be
excluded (I3 in OFF);
– The magnetic trip of thermomagnetic (TM) or magnetic only (M) circuit-breakers placed
on the supply side must be ∆ 10 x In and regulated to the maximum threshold;
– It is of prime importance to check that the settings made by the user for the
electronic and thermomagnetic relays of circuit-breakers placed both on the load
and supply side results in time-current curves properly spaced.
Note
The letter T indicates total discrimination for the selected combination; the corresponding
value in kA is obtained by considering the lowest between the breaking capacities (Icu) of
the circuit-breaker on the load side and the circuit-breaker on the supply side.
The following tables give the breaking capacities at 415 V AC for SACE Emax,
Isomax and Tmax circuit-breakers.
Caption of symbols
MCB - S9 @ 230/240 V
Supply s. T1
Version B,C,N
Release TMD TMD, MA
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160** 160 16 20 25 32 40 50
C ∆4 T T T T T T T T T T T T T T T T T T
C 6 T T T T T T T T T T T T T T T T T T
C 10 3 3 3 T T T T T T T 3* 3 3 3 T
2 S931N C
C
4.5 16
20
3 T
3
T
T
T
T
T
T
T
T
T
T
T
T
3*
3*
3
3
T
C 25 T T T T T T 3*
C 32 T T T T T 3*
C 40 T T T T
B-C ∆4 T T T T T T T T T T T T T T T T T T
B-C 6 T T T T T T T T T T T T T T T T T T
B-C 10 3 3 3 4.5 T T T T T T 3* 3 3 3 4.5
S941N B-C 6 16 3 4.5 5 T T T T T 3* 3 4.5
B-C 20 3 5 T T T T T 3* 3
B-C 25 5 T T T T T 3*
B-C 32 T T T T T 3*
B-C 40 T T T T
B-C ∆4 T T T T T T T T T T T T T T T T T T
B-C 6 6 6 6 6 6 6 T T T T T T T T T T T T
B-C 10 3 3 3 4.5 7.5 8.5 T T T T 3* 3 3 3 4.5
S951N B-C 10 16 3 4.5 5 7.5 T T T T 3* 3 4.5
B-C 20 3 5 6 T T T T 3* 3
B-C 25 5 6 T T T T 3*
B-C 32 6 7.5 T T T 3*
B-C 40 7.5 T T T
B-C ∆4 T T T T T T T T T T T T T T T T T T
B-C 6 6 6 6 6 6 6 12 T T T T T T T T T T T
B-C 10 3 3 3 4.5 7.5 8.5 T T T T 3* 3 3 3 4.5
S971N B-C 10 16 3 4.5 5 7.5 T T T T 3* 3 4.5
B-C 20 3 5 6 T T T T 3* 3
B-C 25 5 6 T T T T 3*
B-C 32 6 7.5 T T T 3*
B-C 40 7.5 T T T
Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral)
Load side circuit-breaker 1P+N (230/240 V)
* Value valid only for magnetic only supply side circuit-breaker
* Neutral 50%
2 20
25
3.5
3.5
5
5
2.5
32 4.5
40
2 8
10
T
5
T
8
1.5 2
1.5
3
2
5.5
3
K 10 16 3 5 2
20 3 5
25 4
32
40
50
S200 63
∆2 T T T T T T
3 T T 3 6 T T
4 T T 2 3 6 T
6 T T 1.5 2 3 5.5
8 T T 1.5 2 3 5.5
10 5 8 1 1.5 2 3
Z 10 16 4.5 7 1 1.5 2 3
20 3.5 5 1.5 2 2.5
25 3.5 5 2 2.5
32 3 4.5 2
40 3 4.5
50 3
63
Supply s. S290
Char. D
Icu [kA] 15
Load s. In [A] 80 100
6 6 10
10 6 10
13 6 10
16 6 10
2 B-C-D 50 20
25
6
4.5
7.5
6
32 6
40
50
S500 63
∆5.8 T T
50 5.3..8 10 T
7.3..11 7.5 T
10..15 4.5 10
K 14..20 4.5 6
18..26 4.5
30 23..32
29..37
34..41
38..45
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
6 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T
10 3 3 3 4.5 T T T T T
S200L C 6
13
16
3 3
3
4.5
4.5
T
5
T
T
T
T
T
T
T
T 2
20 3 5 T T T T
25 5 T T T T
32 T T T T
40 T T T
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
∆2 T T T T T T T T T T T
C 3 T T T T T T T T T T T
4 T T T T T T T T T T T
2 6
8
5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
T
T
T
T
T
T
T
T
T
T
10 3 3 3 4.5 7.5 8.5 T T T
10 13 3 3 4.5 7.5 7.5 T T T
16 3 4.5 5 7.5 T T T
B-C 20 3 5 6 T T T
25 5 6 T T T
32 6 7.5 T T
40 7.5 T T
50 7.5 T
S200 63 T
∆2 T T T T T T T T T T T
3 T T T T T T T T T T T
4 T T T T T T T T T T T
6 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T
10 3 3 3 3 5 8.5 T T T
D 10 13 2 2 3 5 8 T T
16 2 2 3 5 8 T T
20 2 3 4.5 6.5 T T
25 2.5 4 6 9.5 T
32 4 6 9.5 T
40 5 8 T
50 5 9.5
63 9.5
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
∆2 T T T T T T T T T T T
3 T T T T T T T T T T T
4 T T T T T T T T T T T
6
8
5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
T
T
T
T
T
T
T
T
T
T
2
10 3 3 3 3 6 8.5 T T T
K 10 16 3 3 4.5 7.5 T T T
20 3 3.5 5.5 6.5 T T
25 3.5 5.5 6 9.5 T
32 4.5 6 9.5 T
40 5 8 T
50 6 9.5
S200 63 9.5
∆2 T T T T T T T T T T T
3 T T T T T T T T T T T
4 T T T T T T T T T T T
6 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T
10 3 3 3 4.5 8 8.5 T T T
Z 10 16 3 4.5 5 7.5 T T T
20 3 5 6 T T T
25 5 6 T T T
32 6 7.5 T T
40 7.5 T T
50 7.5 T
63 T
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
∆2 T T T T T T T T T T T
C 3 T T T T T T T T T T T
4 T T T T T T T T T T T
2 6
8
5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
T
T
T
T
T
T
T
T
10 3 3 3 4.5 7.5 8.5 T T T
15 13 3 3 4.5 7.5 7.5 12 T T
16 3 4.5 5 7.5 12 T T
B-C 20 3 5 6 10 T T
25 5 6 10 T T
32 6 7.5 12 T
40 7.5 12 T
50 7.5 10.5
63 10.5
∆2 T T T T T T T T T T T
3 T T T T T T T T T T T
4 T T T T T T T T T T T
6 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
8 5.5 5.5 5.5 5.5 5.5 10.5 12 T T T
S200M D 15 10 3 3 3 3 5 8.5 T T T
16 2 2 3 5 8 13.5 T
20 2 3 4.5 6.5 11 T
25 2.5 4 6 9.5 T
32 4 6 9.5 T
40 5 8 T
50 5 9.5
63 9.5
∆2 T T T T T T T T T T T
3 T T T T T T T T T T T
4 T T T T T T T T T T T
6 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
8 5.5 5.5 5.5 5.5 5.5 10.5 12 T T T
10 3 3 3 3 6 8.5 T T T
K 15 16 3 3 4.5 7.5 10 13.5 T
20 3 3.5 5.5 6.5 11 T
25 3.5 5.5 6 9.5 T
32 4.5 6 9.5 T
40 5 8 T
50 6 9.5
63 9.5
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
∆2 T T T T T T T T T T T
C 3 15 15 15 15 15 15 15 15 17* T T
4 15 15 15 15 15 15 15 15 17* T T
25
6
8
5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
15
15
17*
17*
T
T
T
T
2
10 3 3 3 4.5 7.5 8.5 17* T T
13 3 3 4.5 7.5 7.5 12 20* T
16 3 4.5 5 7.5 12 20* T
B-C 20 3 5 6 10 15 T
25 5 6 10 15 T
32 6 7.5 12 T
15 40 7.5 12 T
50 7.5 10.5
S200P 63 10.5
∆2 T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 17* T T
4 15 15 15 15 15 15 15 15 17* T T
6 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 17* T T
25 8 5.5 5.5 5.5 5.5 5.5 10.5 12 17* T T
10 3 3 3 3 5 8.5 17* T T
D 13 2 2 3 5 8 13.5 T
16 2 2 3 5 8 13.5 T
20 2 3 4.5 6.5 11 T
25 2.5 4 6 9.5 T
32 4 6 9.5 T
15 40 5 8 T
50 5 9.5
63 9.5
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
∆2 T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 17* T T
4 15 15 15 15 15 15 15 15 17* T T
2 25
6
8
5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
15
12
17*
17*
T
T
T
T
10 3 3 3 3 6 8.5 17* T T
K 13 3 3 5 7.5 10 13.5 T
16 3 3 4.5 7.5 10 13.5 T
20 3 3.5 5.5 6.5 11 T
25 3.5 5.5 6 9.5 T
32 4.5 6 9.5 T
15 40 5 8 T
50 6 9.5
S200P 63 9.5
∆2 T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 17* T T
4 15 15 15 15 15 15 15 15 17* T T
6 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 17* T T
25 8 5.5 5.5 5.5 5.5 5.5 10.5 12 17* T T
Z 10 3 3 3 4.5 8 8.5 17* T T
16 3 4.5 5 7.5 12 20* T
20 3 5 6 10 15 T
25 5 6 10 15 T
32 6 7.5 12 T
15 40 7.5 12 T
50 7.5 10.5
63 10.5
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
Supply s. T1
Version B,C,N
Release TM
Iu [A] 160
Load s. Char. Icu [kA] In [A] 16 20 25 32 40 50 63 80 100 125 160
6 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 20* 25* T
10 4.5 4.5 4.5 4.5 8 10 20* 25* T
13 4.5 4.5 4.5 7.5 10 15 25* T
B-C-D 50
16
20
4.5 4.5
4.5
7.5
7.5
10
10
15
15
25*
25*
T
T
2
25 6 10 15 20* T
32 7.5 10 20* T
40 10 20* T
50 15 T
S500 63 T
∆5.8 36 36 T T T T T T T T T
50 5.3..8 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T
7.3..11 4.5 4.5 4.5 4.5 8 T T T T
10..15 4.5 4.5 4.5 7.5 10 15 T T
K 14..20 4.5 4.5 7.5 10 15 T T
18..26 4.5 7.5 10 15 T T
30 23..32 6 10 15 20* T
29..37 7.5 10 20* T
34..41 10 20* T
38..45 15 T
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
10 3* 3 3 3 4.5 T T T T T T T T T
2 S200L C 6
13
16
3* 3
3*
3
3
4.5
4.5
T
5
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
20 3* 3 5 T T T T T T T
25 3* 5 T T T T T T T
32 3* T T T T T T T
40 5.5* T T T T T
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
∆2 T T T T T T T T T T T T T T T T T
C 3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
2
8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
10 3* 3 3 3 4.5 7.5 8.5 T T T T T T T
10 13 3* 3 3 4.5 7.5 7.5 T T T T T T T
16 3* 3 4.5 5 7.5 T T T T T T
B-C 20 3* 3 5 6 T T T T T T
25 3* 5 6 T T T T T T
32 3* 6 7.5 T T T T T
40 5.5* 7.5 T T T T
50 3* 5* 7.5 T T T
S200 63 5* T T
∆2 T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
10 3* 3 3 3 3 5 8.5 T T T T T T T
D 10 13 2* 2 2 3 5 8 T T T T T
16 2* 2 2 3 5 8 T T T T T
20 2* 2 3 4.5 6.5 T T T T T
25 2* 2.5 4 6 9.5 T T T T
32 4 6 9.5 T T T T
40 3* 5 8 T T T
50 2* 3* 5 9.5 9.5 9.5
63 3* 9.5 9.5
* Value valid with supply side magnetic only circuit-breaker
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
∆2 T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
2 6
8
5.5* 5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10 3* 3 3 3 3 6 8.5 T T T T T T T
K 10 16 2* 3 3 4.5 7.5 T T T T T T
20 2* 3 3.5 5.5 6.5 T T T T T
25 2* 3.5 5.5 6 9.5 T T T T
32 4.5 6 9.5 T T T T
40 3* 5 8 T T T
50 2* 3* 6 9.5 9.5 9.5
S200 63 3* 9.5 9.5
∆2 T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
8 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T
10 3* 3 3 3 4.5 8 8.5 T T T T T T T
Z 10 16 3* 3 4.5 5 7.5 T T T T T T
20 3* 3 5 6 T T T T T T
25 3* 5 6 T T T T T T
32 3* 6 7.5 T T T T T
40 5.5* 7.5 T T T T
50 4* 5* 7.5 T T T
63 5* T T
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
∆2 T T T T T T T T T T T T T T T T T
C 3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6
8
5.5* 5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
10 3* 3 3 3 4.5 7.5 8.5 T T T T T T T
15 13 3* 3 3 4.5 7.5 7.5 12 T T T T T T
16 3* 3 4.5 5 7.5 12 T T T T T
B-C 20 3* 3 5 6 10 T T T T T
25 3* 5 6 10 T T T T T
32 3* 6 7.5 12 T T T T
40 5.5* 7.5 12 T T T
50 3* 5* 7.5 10.5 10.5 10.5
63 5* 10.5 10.5
∆2 T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T T T T T
8 5.5 5.5 5.5 5.5 5.5 10.5 12 T T T T T T T
10 3* 3 3 3 3 5 8.5 T T T T T T T
S200M D 15 16 2* 2 2 3 5 8 13.5 T T T T
20 2* 2 3 4.5 6.5 11 T T T T
25 2* 2.5 4 6 9.5 T T T T
32 4 6 9.5 T T T T
40 3* 5 8 T T T
50 2* 3* 5 9.5 9.5 9.5
63 3* 9.5 9.5
∆2 T T T T T T T T T T T T T T T T T
3 T T T T T T T T T T T T T T T T T
4 T T T T T T T T T T T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 T T T T T T T T
8 5.5 5.5 5.5 5.5 5.5 10.5 12 T T T T T T T
10 3* 3 3 3 3 6 8.5 T T T T T T T
K 15 16 2* 3 3 4.5 7.5 10 13.5 T T T T
20 2* 3 3.5 5.5 6.5 11 T T T T
25 2* 3.5 5.5 6 9.5 T T T T
32 4.5 6 9.5 T T T T
40 3* 5 8 T T T
50 2* 3* 6 9.5 9.5 9.5
63 3* 9.5 9.5
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
∆2 T T T T T T T T T T T T T T T T T
C 3 15 15 15 15 15 15 15 15 15 17 T T T T T T T
4 15 15 15 15 15 15 15 15 15 17 T T T T T T T
2 25
6
8
5.5* 5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
15
15
17
17
T
T
T
T
T
T
T
T
T
T
T
T
10 3* 3 3 3 4.5 7.5 8.5 17 T T T T T T
13 3* 3 3 4.5 7.5 7.5 12 20 T T T T T
16 3* 3 4.5 5 7.5 12 20 T T T T
B-C 20 3* 3 5 6 10 15 T T T T
25 3* 5 6 10 15 T T T T
32 3* 6 7.5 12 T T T T
15 40 5.5* 7.5 12 T T T
50 3* 5* 7.5 10.5 10.5 10.5
S200P 63 5* 10.5 10.5
∆2 T T T T T T T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 15 17 T T T T T T T
4 15 15 15 15 15 15 15 15 15 17 T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 17 T T T T T T
25 8 5.5 5.5 5.5 5.5 5.5 10.5 12 17 T T T T T T
10 3* 3 3 3 3 5 8.5 17 T T T T T T
D 13 2* 2 2 3 5 8 13.5 T T T T
16 2* 2 2 3 5 8 13.5 T T T T
20 2* 2 3 4.5 6.5 11 T T T T
25 2* 2.5 4 6 9.5 T T T T
32 4 6 9.5 T T T T
15 40 3* 5 8 T T T
50 2* 3* 5 9.5 9.5 9.5
63 3* 9.5 9.5
* Value valid with supply side magnetic only circuit-breaker
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
∆2 T T T T T T T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 15 17 T T T T T T T
4 15 15 15 15 15 15 15 15 15 17 T T T T T T T
25
6
8
5.5* 5.5 5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
10.5
10.5
15
12
17
17
T
T
T
T
T
T
T
T
T
T
T
T
2
10 3* 3 3 3 3 6 8.5 17 T T T T T T
K 13 2* 3 3 5 7.5 10 13.5 T T T T T
16 2* 3 3 4.5 7.5 10 13.5 T T T T
20 2* 3 3.5 5.5 6.5 11 T T T T
25 2* 3.5 5.5 6 9.5 T T T T
32 4.5 6 9.5 T T T T
15 40 3* 5 8 T T T
50 2* 3* 6 9.5 9.5 9.5
S200P 63 3* 9.5 9.5
∆2 T T T T T T T T T T T T T T T T T
3 15 15 15 15 15 15 15 15 15 17 T T T T T T T
4 15 15 15 15 15 15 15 15 15 17 T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 17 T T T T T T
25 8 5.5 5.5 5.5 5.5 5.5 10.5 15 17 T T T T T T
10 3* 3 3 3 4.5 8 8.5 17 T T T T T T
Z 16 3* 3 4.5 5 7.5 12 20 T T T T
20 3* 3 5 6 10 15 T T T T
25 3* 5 6 10 15 T T T T
32 3* 6 7.5 12 T T T T
15 40 5.5* 7.5 12 T T T
50 4* 5* 7.5 10.5 10.5 10.5
63 5* 10.5 10.5
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 160 160
C-D-K 80 4
S290 15 100 4
C 125 4
2
Tmax T2 - S500 @ 400/415 V
Supply s. T2
Version N,S,H,L
Release TM, M EL
Iu [A] 160
Load s. Char. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
6 4.5 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 20 25 36 36 36 36 36
10 4.5* 4.5 4.5 4.5 4.5 8 10 20 25 36 36 36 36 36
13 4.5* 4.5 4.5 4.5 7.5 10 15 25 36 36 36 36 36
16 4.5* 4.5 4.5 7.5 10 15 25 36 36 36 36
B-C-D 50 20 4.5* 4.5 7.5 10 15 25 36 36 36 36
25 4.5* 6 10 15 20 36 36 36 36
32 4.5* 7.5 10 20 36 36 36 36
40 5* 10 20 36 36 36
50 5* 7.5* 15 36 36 36
S500 63 5* 36 36
∆5.8 36 36 36 36 36 36 36 36 36 36 36 50** 50** 50** 50** 50** 50**
50 5.3..8 4.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 36 36 36 50** 50** 50** 50** 50**
7.3..11 4.5* 4.5 4.5 4.5 4.5 8 36 36 36 50** 50** 50** 50** 50**
10..15 4.5* 4.5 4.5 4.5 7.5 10 15 T T T T T T
K 14..20 4.5* 4.5 4.5 7.5 10 15 T T T T T
18..26 4.5* 4.5 7.5 10 15 T T T T T
30 23..32 4.5* 6 10 15 20 T T T T
29..37 4.5* 7.5 10 20 T T T
34..41 5* 10 20 T T T
38..45 5* 7.5* 15 T T T
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
6 T T T T T T T
8 T T T T T T T
10 T T T T T T T
S200L C 6
13
16
T
5
T
T
T
T
T
T
T
T
T
T
T
T
2
20 5 T T T T T T
25 5 T T T T T T
32 T T T T T T
40 4 T T T T T
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
∆2 T T T T T T T
C 3 T T T T T T T
4 T T T T T T T
2 6
8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10 7.5 8.5 T T T T T
10 13 7.5 7.5 T T T T T
16 5 7.5 T T T T T
B-C 20 5 6 T T T T T
25 5 6 T T T T T
32 6 7.5 T T T T
40 7.5 T T T T
50 5* 7.5 T T T
S200 63 5* 6* T T T
∆2 T T T T T T T
3 T T T T T T T
4 T T T T T T T
6 T T T T T T T
8 T T T T T T T
10 5 8.5 T T T T T
D 10 13 3 5 8 T T T T
16 3 5 8 T T T T
20 3 4.5 6.5 T T T T
25 2.5 4 6 9.5 T T T
32 4 6 9.5 T T T
40 5 8 T T T
50 3* 5 9.5 T T
63 3* 5* 9.5 T T
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
∆2 T T T T T T T
3 T T T T T T T
4 T T T T T T T
6
8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
10 6 8.5 T T T T T
K 10 16 4.5 7.5 T T T T T
20 3.5 5.5 6.5 T T T T
25 3.5 5.5 6 9.5 T T T
32 4.5 6 9.5 T T T
40 5 8 T T T
50 3* 6 9.5 T T
S200 63 3* 5.5* 9.5 T T
∆2 T T T T T T T
3 T T T T T T T
4 T T T T T T T
6 T T T T T T T
8 T T T T T T T
10 8 8.5 T T T T T
Z 10 16 5 7.5 T T T T T
20 5 6 T T T T T
25 5 6 T T T T T
32 6 7.5 T T T T
40 7.5 T T T T
50 5* 7.5 T T T
63 5* 6* T T T
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
∆2 T T T T T T T
C 3 T T T T T T T
4 T T T T T T T
2 6
8
10.5
10.5
T
T
T
T
T
T
T
T
T
T
T
T
10 7.5 8.5 T T T T T
15 13 7.5 7.5 12 T T T T
16 5 7.5 12 T T T T
B-C 20 5 6 10 T T T T
25 5 6 10 T T T T
32 6 7.5 12 T T T
40 7.5 12 T T T
50 5* 7.5 10.5 T T
63 5* 6* 10.5 T T
∆2 T T T T T T T
3 T T T T T T T
4 T T T T T T T
6 10.5 T T T T T T
8 10.5 12 T T T T T
S200M 10 5 8.5 T T T T T
D 15 16 3 5 8 13.5 T T T
20 3 4.5 6.5 11 T T T
25 2.5 4 6 9.5 T T T
32 4 6 9.5 T T T
40 5 8 T T T
50 3* 5 9.5 T T
63 3* 5* 9.5 T T
∆2 T T T T T T T
3 T T T T T T T
4 T T T T T T T
6 10.5 T T T T T T
8 10.5 12 T T T T T
10 6 8.5 T T T T T
K 15 16 4.5 7.5 10 13.5 T T T
20 3.5 5.5 6.5 11 T T T
25 3.5 5.5 6 9.5 T T T
32 4.5 6 9.5 T T T
40 5 8 T T T
50 3* 6 9.5 T T
63 3* 5.5* 9.5 T T
* Value valid with supply side magnetic only circuit-breaker
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
∆2 T T T T T T T
C 3 15 15 17 T T T T
4 15 15 17 T T T T
25
6
8
10.5
10.5
15
15
17
17
T
T
T
T
T
T
T
T
2
10 7.5 8.5 17 T T T T
13 7.5 7.5 12 20 T T T
B-C 16 5 7.5 12 20 T T T
20 5 6 10 15 T T T
25 5 6 10 15 T T T
32 6 7.5 12 T T T
15 40 7.5 12 T T T
50 5* 7.5 10.5 T T
S200P 63 5* 6* 10.5 T T
∆2 T T T T T T T
3 15 15 T T T T T
4 15 15 T T T T T
6 10.5 15 T T T T T
25 8 10.5 12 T T T T T
10 5 8.5 T T T T T
D 13 3 5 8 13.5 T T T
16 3 5 8 13.5 T T T
20 3 4.5 6.5 11 T T T
25 2.5 4 6 9.5 T T T
32 4 6 9.5 T T T
15 40 5 8 T T T
50 3* 5 9.5 T T
63 3* 5* 9.5 T T
* Value valid with supply side magnetic only circuit-breaker
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
∆2 T T T T T T T
3 15 15 17 T T T T
4 15 15 17 T T T T
2 25
6
8
10.5
10.5
15
12
17
17
T
T
T
T
T
T
T
T
10 6 8.5 17 T T T T
K 13 5 7.5 10 13.5 T T T
16 4.5 7.5 10 13.5 T T T
20 3.5 5.5 6.5 11 T T T
25 3.5 5.5 6 9.5 T T T
32 4.5 6 9.5 T T T
15 40 5 8 T T T
50 3* 6 9.5 T T
S200P 63 3* 5.5* 9.5 T T
∆2 T T T T T T T
3 15 15 17 T T T T
4 15 15 17 T T T T
6 10.5 15 17 T T T T
25 8 10.5 15 17 T T T T
10 8 8.5 17 T T T T
Z 16 5 7.5 12 20 T T T
20 5 6 10 15 T T T
25 5 6 10 15 T T T
32 6 7.5 12 T T T
15 40 7.5 12 T T T
50 5* 7.5 10.5 T T
63 5* 6* 10.5 T T
* Value valid with supply side magnetic only circuit-breaker
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 160 200 250
C-D-K 80 4* 10 15
S290 15 100 4* 7.5* 15
C 125 7.5*
* Value valid with supply side magnetic only circuit-breaker 2
Supply s. T3
Version N, S
Release TM, M
Iu [A] 250
Load s. Char. Icu [kA] In [A] 63 80 100 125 160 200 250
6 10.5 15 20 25 36 36 36
10 8 10 20 25 36 36 36
13 7.5 10 15 25 36 36 36
16 7.5 10 15 25 36 36 36
B-C-D 50 20 7.5 10 15 25 36 36 36
25 6 10 15 20 36 36 36
32 7.5 10 20 36 36 36
40 10 20 36 36 36
50 7.5* 15 36 36 36
S500 63 5* 6* 36 36 36
∆5.8 36 36 36 36 T T T
50 5.3..8 10.5 36 36 36 T T T
7.3..11 8 36 36 36 T T T
10..15 7.5 10 15 T T T T
K 14..20 7.5 10 15 T T T T
18..26 7.5 10 15 T T T T
30 23..32 6 10 15 20 T T T
29..37 7.5 10 20 T T T
34..41 10 20 T T T
38..45 7.5* 15 T T T
* Value valid with supply side magnetic only circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
6 T T* T T T T T T T T T T T T
8 T T* T T T T T T T T T T T T
10 5 5* 5 T T T T T T T T T T T
2 S200L C 6
13
16
5*
3*
5
5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20 5 T T T T T T T T T T
25 5 T T T T T T T T T T
32 5** T T T T T T T T T T
40 T T T T T T T T T T
* Value valid with supply side magnetic only circuit-breaker
* Value valid with supply side magnetic only MA 52 circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
∆2 T T* T T T T T T T T T T T T
C 3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6
8
7.5
7.5
7.5*
7.5*
7.5
7.5
7.5
7.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
10 5 5* 5 6.5 9 T T T T T T T T T
10 13 5* 5 6.5 8 T T T T T T T T T
16 3* 5 6.5 8 T T T T T T T T T
B-C 20 5 7.5 T T T T T T T T T
25 5 7.5 T T T T T T T T T
32 5** 7.5 T T T T T T T T T
40 6.5 T T T T T T T T T
50 5* T T T T T T T T T
S200 63 T* T* T T T T T T T
∆2 T T* T T T T T T T T T T T T
3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6 7.5 7.5* 7.5 7.5 T T T T T T T T T T
8 7.5 7.5* 7.5 7.5 T T T T T T T T T T
10 5 5* 5 5 9 T T T T T T T T T
D 10 13 5* 4 5.5 T T T T T T T T T
16 4 5.5 T T T T T T T T T
20 4** 5 T T T T T T T T T
25 4** 4.5 T T T T T T T T T
32 4.5* T T T T T T T T T
40 4.5* T* T T T T T T T T
50 T* T* T T T T T T T
63 T* T* T T T T T T
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
∆2 T T* T T T T T T T T T T T T
3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
2 6
8
7.5
7.5
7.5*
7.5*
7.5
7.5
7.5
7.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10 5* 5 5 9 T T T T T T T T T
K 10 16 5* 5 8 T T T T T T T T T
20 5 6 T T T T T T T T T
25 5** 6* T T T T T T T T T
32 5** 6* T* T T T T T T T T
40 5.5* T* T* T T T T T T T
50 5* T* T* T* T T T T T T
S200 63 T* T* T* T* T T T T T
∆2 T T* T T T T T T T T T T T T
3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6 7.5 7.5* 7.5 7.5 T T T T T T T T T T
8 7.5 7.5* 7.5 7.5 T T T T T T T T T T
10 5 5* 5 6.5 9 T T T T T T T T T
Z 10 16 5* 4.5 6.5 8 T T T T T T T T T
20 5 7.5 T T T T T T T T T
25 5 7.5 T T T T T T T T T
32 5** 7.5 T T T T T T T T T
40 6.5 T T T T T T T T T
50 5* T T T T T T T T T
63 T* T T T T T T T T
* Value valid with supply side magnetic only circuit-breaker
* Value valid with supply side magnetic only MA 52 circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
∆2 T T* T T T T T T T T T T T T
C 3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6
8
7.5
7.5
7.5*
7.5*
7.5
7.5
7.5
7.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
10 5 5* 5 6.5 9 T T T T T T T T T
15 13 5* 5 6.5 8 T T T T T T T T T
16 3* 5 6.5 8 T T T T T T T T T
B-C 20 5 7.5 T T T T T T T T T
25 5 7.5 T T T T T T T T T
32 5** 7.5 T T T T T T T T T
40 6.5 T T T T T T T T T
50 5* T T T T T T T T T
63 T* T* T T T T T T T
∆2 T T* T T T T T T T T T T T T
3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6 7.5 7.5* 7.5 7.5 T T T T T T T T T T
8 7.5 7.5* 7.5 7.5 T T T T T T T T T T
S200M 10 5 5* 5 5 9 T T T T T T T T T
D 15 16 4 5.5 T T T T T T T T T
20 4** 5 T T T T T T T T T
25 4** 4.5 T T T T T T T T T
32 4.5* T T T T T T T T T
40 4.5* T* T T T T T T T T
50 T* T* T T T T T T T
63 T* T* T T T T T T
∆2 T T* T T T T T T T T T T T T
3 T T* T T T T T T T T T T T T
4 T T* T T T T T T T T T T T T
6 7.5 7.5* 7.5 7.5 T T T T T T T T T T
8 7.5 7.5* 7.5 7.5 T T T T T T T T T T
10 5* 5 5 9 T T T T T T T T T
K 15 16 5* 5 8 T T T T T T T T T
20 5 6 T T T T T T T T T
25 5** 6* T T T T T T T T T
32 5** 6* T* T T T T T T T T
40 5.5* T* T* T T T T T T T
50 5* T* T* T* T T T T T T
63 T* T* T* T* T T T T T
*Value valid with supply side magnetic only circuit-breaker
* Value valid with supply side magnetic only MA 52 circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
∆2 T T* T T T T T T T T T T T T
C 3 15 15* 15 15 15 T T T T T T T T T
4 15 15* 15 15 15 T T T T T T T T T
2 25
6
8
7.5
7.5
7.5*
7.5*
7.5
7.5
7.5
7.5
15
15
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10 5 5* 5 6.5 9 T T T T T T T T T
13 5* 5 6.5 8 T T T T T T T T T
16 3* 5 6.5 8 T T T T T T T T T
B-C 20 5 7.5 T T T T T T T T T
25 5 7.5 T T T T T T T T T
32 5** 7.5 T T T T T T T T T
15 40 6.5 T T T T T T T T T
50 5* T T T T T T T T T
S200P 63 T* T* T T T T T T T
∆2 T T* T T T T T T T T T T T T
3 15 15* 15 15 15 T T T T T T T T T
4 15 15* 15 15 15 T T T T T T T T T
6 7.5 7.5* 7.5 7.5 15 T T T T T T T T T
25 8 7.5 7.5* 7.5 7.5 15 T T T T T T T T T
10 5 5* 5 5 9 T T T T T T T T T
D 13 5* 4 5.5 T T T T T T T T T
16 4 5.5 T T T T T T T T T
20 4** 5 T T T T T T T T T
25 4** 4.5 T T T T T T T T T
32 4.5* T T T T T T T T T
15 40 4.5* T* T T T T T T T T
50 T* T* T T T T T T T
63 T* T* T T T T T T
* Value valid with supply side magnetic only circuit-breaker
* Value valid with supply side magnetic only MA 52 circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
∆2 T T* T T T T T T T T T T T T
3 15 15* 15 15 15 T T T T T T T T T
4 15 15* 15 15 15 T T T T T T T T T
25
6
8
7.5
7.5
7.5*
7.5*
7.5
7.5
7.5
7.5
15
15
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
10 5* 5 5 9 T T T T T T T T T
K 13 5* 5 5 8 T T T T T T T T T
16 5* 5 8 T T T T T T T T T
20 5 6 T T T T T T T T T
25 5** 6* T T T T T T T T T
32 5** 6* T* T T T T T T T T
15 40 5.5* T* T* T T T T T T T
50 5* T* T* T* T T T T T T
S200P 63 T* T* T* T* T T T T T
∆2 T T* T T T T T T T T T T T T
3 15 15* 15 15 15 T T T T T T T T T
4 15 15* 15 15 15 T T T T T T T T T
6 7.5 7.5* 7.5 7.5 15 T T T T T T T T T
25 8 7.5 7.5* 7.5 7.5 15 T T T T T T T T T
Z 10 5 5* 5 6.5 9 T T T T T T T T T
16 5* 4.5 6.5 8 T T T T T T T T T
20 5 7.5 T T T T T T T T T
25 5 7.5 T T T T T T T T T
32 5** 7.5 T T T T T T T T T
15 40 6.5 T T T T T T T T T
50 5* T T T T T T T T T
63 T* T T T T T T T T
*Value valid with supply side magnetic only circuit-breaker
* Value valid with supply side magnetic only MA 52 circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 160 200 250 160 250 320
C-K 80 5 11 T T T T
100 5* 8 T 12 T T
S290 C 15 125 8* 12 T T
2 D 80
100
5 11
8
T
T
T
12
T
T
T
T
* Value valid with supply side magnetic only circuit-breaker
Supply s. T4
Version N,S,H,L,V
Release TM, M EL
Iu [A] 250 250 320
Load s. Char. Icu [kA] In [A] 20 25 32 50 80 100 125 160 200 250 100 160 250 320
6 7.5 7.5* 7.5 7.5 16 T T T T T T T T T
10 6.5 6.5* 6.5 6.5 11 T T T T T T T T T
13 6.5 5* 6.5 6.5 11 T T T T T T T T T
B-C 50
16
20
5*
4*
6.5
6.5
6.5
6.5
11
11
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
25 6.5 11 T T T T T T T T T
32 6.5 8 T T T T T T T T T
40 5* 6.5 T T T T T T T T T
50 5* 7.5 T T T T T T T T
63 5* 7 T T T T T T T
6 7.5 7.5* 7.5 7.5 16 T T T T T T T T T
10 6.5 6.5* 6.5 6.5 11 T T T T T T T T T
13 5* 6.5 11 T T T T T T T T T
16 6.5 11 T T T T T T T T T
S500 D 50 20 6.5* 11 T T T T T T T T T
25 6.5* 11 T T T T T T T T T
32 8* T T T T T T T T T
40 6.5* T* T T T T T T T T
50 7.5* T* T T T T T T T
63 7* T* T T T T T T
∆5.8 40** 40*/** 40** 40** 40** T T T T T T T T T
50 5.3..8 6 6* 6 6 40** T T T T T T T T T
7.3..11 5* 5 5 40** T T T T T T T T T
10..15 5* 5 12 T T T T T T T T T
K 14..20 5 12 T T T T T T T T T
18..26 5* 12* T T T T T T T T T
30 23..32 5* 12* T* T T T T T T T T
29..37 5* 8* T* T* T T T T T T T
34..41 6* T* T* T T T T T T T
38..45 6* 8* T* T* T T T T T T
*Value valid with supply side magnetic only circuit-breaker (with In = 50 A please refer to MA52 circuit-breakers)
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
16 3 3 3 3 3 3 4 5 10** 10 10 10 10 10 10
2 20
25
3
3
3
3
3
3
3
3
3
3
3
3
4
4
5
5
10** 10
10** 10
10
10
10
10
10
10
10
10
10
10
32 3 3 3 3 3 4 5 10* 10 10 10 10 10
40 3 3 3 3 3 4 5 10* 10 10 10 10 10
B 50 3 3 3 3 3 4 5 10* 10 10 10 10
63 3 3 3 3 4 5 10* 10 10 10
80 3 4 5 10 10 10
100 5 10* 10 10
125 10* 10
160
25 3 3 3 3 3 3 4 5 10** 10 10 10 10 10 10
32 3 3 3 3 3 4 5 10* 10 10 10 10 10
T1 TM 160 40 3 3 3 3 3 4 5 10* 10 10 10 10 10
50 3 3 3 3 3 4 5 10* 10 10 10 10
C 63 3 3 3 3 4 5 10* 10 10 10
80 3 4 5 10 10 10
100 5 10* 10 10
125 10* 10
160
32 3 3 3 3 3 4 5 10* 10 10 10 10 10
40 3 3 3 3 3 4 5 10* 10 10 10 10 10
50 3 3 3 3 3 4 5 10* 10 10 10 10
N 63 3 3 3 3 4 5 10* 10 10 10
80 3 4 5 10 10 10
100 5 10* 10 10
125 10* 10
160
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 800 1000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 100010001250 1600
10 10 10 10 T T T T T T T T T T T T T T
10
10
10
10
10
10
10
10
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
10 10 T T T T T T T T T T T T T T
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
1.6-2.5 T T T T T T T T T T T* T T T T T T T T
2 3.2
4-5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T*
T*
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3 10 10 10 10 10 10 10 15 40** T T* T T T T T T T T
8 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
10 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
12.5 3 3 3 3 3 3 4 5 T T T T T T T T
16 3 3 3 3 3 3 4 5 T T T T T T
TM 160 20 3 3 3 3 3 3 4 5 T* T T T T T
25 3 3 3 3 3 3 4 5 T* T T T T T
32 3 3 3 3 3 4 5 T* T T T T T
T2 N 40 3 3 3 3 3 4 5 30* 30* 30 30 30 30
50 3 3 3 3 3 4 5 30* 30* 30 30 30 30
63 3 3 3 3 4 5 30* 30* 30* 30 30 30
80 3 3* 4 5 25* 25* 25* 25 25
100 4* 5 25* 25* 25* 25
125 25* 25*
160 25*
10 3 4 25 25 25 25 25 25 25
25 3 4 25 25 25 25 25 25
EL 160 63 3 4 25 25 25
100 3 4 25
160 3 4
* Value valid with supply side magnetic only circuit-breaker
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 800 1000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 10001000 1250 1600
T T T T T T T T T T T T T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
1.6-2.5 T T T T T T T T T T T* T T T T T T T T
2 3.2
4-5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T*
T*
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3 10 10 10 10 10 10 10 15 40** T T* T T T T T T T T
8 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
10 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
12.5 3 3 3 3 3 3 4 5 T T T T T T T T
16 3 3 3 3 3 3 4 5 T T T T T T
TM 160 20 3 3 3 3 3 3 4 5 T* T T T T T
25 3 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
32 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
T2 S 40 3 3 3 3 3 4 5 30* 30* 30 30 30 30
50 3 3 3 3 3 4 5 30* 30* 30 30 30 30
63 3 3 3 3 4 5 30* 30* 30* 30 30 30
80 3 3* 4 5 25* 25* 25* 25 25
100 4 5 25* 25* 25* 25
125 25* 25*
160 25*
10 3 4 25 25 25 25 25 25 25
25 3 4 25 25 25 25 25 25
EL 160 63 3 4 25 25 25
100 3 4 25
160 3 4
* Value valid with supply side magnetic only circuit-breaker
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 800 1000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 10001250 1600
T T T T T T T T T T T T T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
1.6-2.5 T T T T T T T T T T T* T T T T T T T T
2 3.2
4-5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T*
T*
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3 10 10 10 10 10 10 10 15 40** T T* T T T T T T T T
8 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
10 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
12.5 3 3 3 3 3 3 4 5 T T T T T T T T
16 3 3 3 3 3 3 4 5 T T T T T T
TM 160 20 3 3 3 3 3 3 4 5 55*/** 55** 55** 55** 55** 55**
25 3 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
32 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
T2 H 40 3 3 3 3 3 4 5 30* 30* 30 30 30 30
50 3 3 3 3 3 4 5 30* 30* 30 30 30 30
63 3 3 3 3 4 5 30* 30* 30* 30 30 30
80 3 3* 4 5 25* 25* 25* 25 25
100 4 5 25* 25* 25* 25
125 25* 25*
160 25*
10 3 4 25 25 25 25 25 25 25
25 3 4 25 25 25 25 25 25
EL 160 63 3 4 25 25 25
100 3 4 25
160 3 4
* Value valid with supply side magnetic only circuit-breaker
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 800 1000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 10001250 1600
T T T T T T T T T T T T T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
55** 55** 55** 55** T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
1.6-2.5 T T T T T T T T T T T* T T T T T T T T
2 3.2
4-5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T*
T*
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3 10 10 10 10 10 10 10 15 40** T T* T T T T T T T T
8 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
10 10 10 10 10 10 10 10 15 40** T* T T T T T T T T
12.5 3 3 3 3 3 3 4 5 T T T T T T T T
16 3 3 3 3 3 3 4 5 70** 70** 70** 70** 70** 70**
TM 160 20 3 3 3 3 3 3 4 5 55*/** 55** 55** 55** 55** 55**
25 3 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
32 3 3 3 3 3 4 5 40*/** 40** 40** 40** 40** 40**
T2 L 40 3 3 3 3 3 4 5 30* 30* 30 30 30 30
50 3 3 3 3 3 4 5 30* 30* 30 30 30 30
63 3 3 3 3 4 5 30* 30* 30* 30 30 30
80 3 3* 4 5 25* 25* 25* 25 25
100 4 5 25* 25* 25* 25
125 25* 25*
160 25*
10 3 4 25 25 25 25 25 25 25
25 3 4 25 25 25 25 25 25
EL 160 63 3 4 25 25 25
100 3 4 25
160 3 4
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 800 1000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 100012501600
T T T T T T T T T T T T T T T T T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
T T T T T T T T T T T T T T T T T T
70** 70** 70** 70** T T T T T T T T T T T T T T
55** 55** 55** 55** T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
40** 40** 40** 40** T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
30 30 30 30 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 25 T T T T T T T T T T T T T T
25 25 25 T T T T T T T T T T T T T T
25 25 T T T T T T T T T T T T T T
Supply s. T1 T2 T3 T4
Version B,
C, N,S,H,L N,S N,S,H,L,V
N
Release TM TM,M EL TM,M TM,M
Iu [A] 160 160 250 250
Load s. In [A] 160 160 25 63 100 160 160 200 250 20 25 32 50 80 100 125 160 200 250
63 3 4 5 7* 7 7 7
2 80
100
3* 4
4*
5
5
7*
7*
7
7*
7
7
N 125 7*
160
200
T3 TM 250 250
63 3 4 5 7* 7 7 7
80 3* 4 5 7* 7 7
100 4* 5 7* 7* 7
S 125 7*
160
200
250
* Value valid with supply side magnetic only circuit-breaker
* Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker
Supply s. T5 T6 S7
Version
N,S,H,L,V N,S,H,L S,H,L
Release TM EL TM,M EL EL
Iu [A] 400 630 400 630 630 800 630 800 1000 1250 1600
1000100012501600
Load s. In [A] 320 400 500 320 400 630 630 800 630 800
20 T T T T T T T T T T T T T T
32 T T T T T T T T T T T T T T
50 T T T T T T T T T T T T T T
80 T T T T T T T T T T T T T T
N, TM 250 100 50* 50* 50* 50* 50* T T T T T T T T
S, 125 50* 50* 50* 50* T T T T T T T T
T4 H, 160 50* 50* 50* T T T T T T T T
L, 200 50* 50* 50* T T T T T T T T
V 250 50* 50* T T T T T T T T
100 50* 50* 50* 50* 50* 50* T T T T T T T T
EL 250 160 50* 50* 50* 50* 50* 50* T T T T T T T T
250 50* 50* 50* T T T T T T T T
320 320 50* T T T T T T T T
* Select the lowest value among what is indicated, the breaking capacity of the supply side
circuit-breaker and the breaking capacity of the load side circuit-breaker
EL TM EL TM,M EL EL
250 320 400 630 400 630 630 800 630 8001000 1250 1600
100 160 250 320 320 400 500 320 400 630 630 800 630 8001000 100012501600
7 7 7 7 25 25 25 25 25 25 T T T T T T T T
7
7
7
7
7
7
25
25
25
25
25
25
25
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T 2
7 7 20 20 20 20 20 20 T T T T T T T T
7 7 20 20 20 20 T T T T T T T T
7 20 20 20 30 T 30 T T T T T
20 20 30 T 30 T T T T T
7 7 7 7 25 25 25 25 25 25 T T T T T T T T
7 7 7 25 25 25 25 25 25 T T T T T T T T
7 7 7 25 25 25 25 25 25 40** T 40** T T T T T
7 7 20 20 20 20 20 20 36 T 36 T T T T T
7 7 20 20 20 20 36 T 36 T T T T T
7 20 20 20 30 T 30 T T T T T
20 20 30 40** 30 40** 40** T T T
Supply s. T6 S7
Version
N,S,H,L S,H,L
Release TM,M EL EL
Iu [A] 630 800 630 8001000 1250 1600
Load s. In [A] 630 800 630 800 100010001250 1600
400 320 30 30 30 30 30 T T T
2 T5
N,
S,
H,
TM
630
400
500
30 30
30
30 T
30 T
T
T
T
T
L, 400 320 30 30 30 30 30 T T T
V EL 400 30 30 30 30 30 T T T
630 630 30 T T T
Supply s. S7
Version
S,H,L
Release EL
Iu [A] 1250 1600
Load s. In [A] 10001250 1600
TM 630 630 T T
800 800 T T
N 630 630 T T T
EL 800 800 T T T
1000 1000 T T
TM 630 630 40 40
800 800 40 40
S 630 630 40 40 40
EL 800 800 40 40 40
T6 1000 1000 40 40
TM 630 630 40 40
800 800 40 40
H 630 630 40 40 40
EL 800 800 40 40 40
1000 1000 40 40
TM 630 630 40 40
800 800 40 40
L 630 630 40 40 40
EL 800 800 40 40 40
1000 1000 40 40
Supply s. E1 E2 E3 E4 E6
Version B N B N S L* N S H V L* S H V H V
Release EL EL EL EL EL
Load s. Iu[A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 3200
1000 1000 2000 1250 1000 1600 3200 1250 1000 1000 2500 4000 4000 5000 4000
1250 1250 1600 1250 1600 1250 1250 6300 5000
1600 1600 2000 1600 2000 1600 1600 6300
2000 2500 2000 2000
3200 2500 2500
B T T T T T T T T
3200
T
3200
T T T T T T T 2
T1 C TM 160 T T T T T T T T T T T T T T T T
N T T T T T T T T T T T T T T T T
N T T T T T T T T T T T T T T T T
T2 S TM,EL 160 T T T T T T T T T T T T T T T T
H T T T 55 65 T T T T T T T T T T T
L T T T 55 65 T T T 75 T T T T T T T
T3 N TM 250 T T T T T T T T T T T T T T T T
S T T T T T T T T T T T T T T T T
N T T T T T T T T T T T T T T T T
S 250 T T T T T T T T T T T T T T T T
T4 H TM,EL 320 T T T 55 65 T T T T T T T T T T T
L T T T 55 65 100 T T 75 85 100 T T 100 T 100
V T T T 55 65 100 T T 75 85 100 T T 100 T 100
N T T T T T T T T T T T T T T T T
S 400 T T T T T T T T T T T T T T T T
T5 H TM,EL 630 T T T 55 65 T T T T T T T T T T T
L T T T 55 65 100 T T 75 85 100 T T 100 T 100
V T T T 55 65 100 T T 75 85 100 T T 100 T 100
N 630 T T T T T T T T T T T T T T T T
T6 S TM,EL T T T T T T T T T T T T T T T T
800
H T T T 55 65 T T T T T T T T T T T
1000
L T T T 55 65 T T T 75 85 T T T T T T
S 1250 T T T T T T T T T T T T T T T T
S7 H EL 1600 T T T 55 T T T T T T T T T T T T
L T T T 55 65 T T T 75 85 T T T T T T
Table valid for Emax circuit-breakers only with PR121/P, PR122/P and PR123/P releases
* Emax L circuit-breakers only with PR122/P and PR123/P releases
IntroduziMotorpronetection
ABB SACE proposes a vast range of coordination solutions for the power supply of
any motor for which protection against short-circuit and overload are of fundamental
importance.
Standard used
–IEC60947-4–1
As protection device, the following tables use the moulded-case circuit-breakers (MCCB)
3 with the following types of releases:
– MF fixed magnetic only release (for Tmax T2 circuit-breakers)
– MA magnetic only release adjustable (for Tmax T2e T3 circuit-breakers)
– PR221/I electronic release (for Tmax T4 and T5 circuit-breakers)
– PR222MP electronic release (for Tmax T4 and T5 circuit-breakers).
The solutions proposed refer to an ambient temperature of 40 °C and to fixed version
apparatus. For higher temperatures, please contact ABB SACE.
Type of starting
– By normal starting, a starting time up to 2 s is intended in accordance with the trip
time of the thermal relays in class 10 A (see table 2).
– By heavy duty, a starting time up to 9 s is intended in accordance with the trip time
of the thermal relays in class 30 (see table 2).
– Two factors must be considered for normal star-delta starting: the speed the motor
has reached at the end of the starting period is 85% higher than the rated one; the
transition time between the star delta connection is 80 ms shorter.
Short-circuit current
– The valid selection for a certain value also covers lower levels of short-circuit. For
example, by selecting 80 kA, protection which is also valid for lower values is
obtained (70, 60..kA, at the same voltage). This means a starter with higher
performances at the required breaking capacity. For more economical solutions,
verifying some specific solutions for lower short-circuit levels is recommended.
Notes
To determine a type of coordination univocally, and therefore the apparatus needed to
carry it out, the following must be known:
– motor power in kW and the type;
– rated installation voltage;
– rated current of the motor;
– short-circuit current at the point of installation;
– type of starting: DOL or Y/∆ - Normal or Heavy - Type 1 o Type 2.
3 P = 200 kW
short-circuit current
rated motor power Ik = 50 kA e
The following information is read from the table (star–delta 400 V 50 kA), in
correspondence with the relative line:
Ie (rated current): 349 A
protection device against short-circuit: T5S630 PR221-I In630 circuit-breaker
magnetic trip threshold: I3 = 4410 A
line contactor: A210
delta contactor: A210
star contactor: A185
thermal relay: E320DU320 adjustable 105-320 A
I
(to adjusted to e = 202 A).
∆
3
Caption of symbols
For solutions not shown in these tables, please consult the website:
[Link]
or contact ABB SACE
3 4
5.5
8.6
11.5
T2N160 MF 11
T2N160 MF 12.5
145
163
A30
A30
TA25DU11
TA25DU14
7.5
10
11
14
11
12.5
7.5 15.2 T2N160 MA 20 210 A30 TA25DU19 13 19 19
11 22 T2N160 MA 32 288 A30 TA42DU25 18 25 25
15 28.5 T2N160 MA 52 392 A50 TA75DU42 29 42 42
18.5 36 T2N160 MA 52 469 A50 TA75DU52 36 52 50
22 42 T2N160 MA 52 547 A50 TA75DU52 36 52 50
30 56 T2N160 MA 80 840 A63 TA75DU80 60 80 65
37 68 T2N160 MA 80 960 A75 TA75DU80 60 80 75
45 83 T2N160 MA 100 1200 A95 TA110DU110 80 110 96
55 98 T3N250 MA 160 1440 A110 TA110DU110 80 110 110
75 135 T3N250 MA 200 1800 A145 TA200DU175 130 175 145
90 158 T3N250 MA 200 2400 A185 TA200DU200 150 200 185
110 193 T4N320 PR221-I In320 2720 A210 E320DU320 100 320 210
132 232 T5N400 PR221-I In400 3200 A260 E320DU320 100 320 260
160 282 T5N400 PR221-I In400 4000 A300 E320DU320 100 320 300
200 349 T5N630 PR221-I In630 5040 AF400 E500DU500 150 500 400
250 430 T6N630 PR221-I In630 6300 AF460 E500DU500 150 500 430
290 520 T6N800 PR221-I In800 7200 AF580 E800DU800 250 800 580
315 545 T6N800 PR221-I In800 8000 AF580 E800DU800 250 800 580
355 610 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800 750
3 4
5.5
8.6
11.5
T2H160 MF 11
T2H160 MF 12.5
145
163
A30
A50
TA25DU11
TA25DU14
7.5
10
11
14
11
12.5
7.5 15.2 T2H160 MA 20 210 A50 TA25DU19 13 19 19
11 22 T2H160 MA 32 288 A50 TA42DU25 18 25 25
15 28.5 T2H160 MA 52 392 A50 TA75DU42 29 42 42
18.5 36 T2H160 MA 52 469 A50 TA75DU52 36 52 50
22 42 T2H160 MA 52 547 A50 TA75DU52 36 52 50
30 56 T2H160 MA 80 840 A63 TA75DU80 60 80 65
37 68 T2H160 MA 80 960 A75 TA75DU80 60 80 75
45 83 T2H160 MA 100 1200 A95 TA110DU110 80 110 96
55 98 T4H250 PR221-I In160 1360 A110 TA110DU110 80 110 110
75 135 T4H250 PR221-I In250 1875 A145 E200DU200 60 200 145
90 158 T4H250 PR221-I In250 2500 A185 E200DU200 60 200 185
110 193 T4H320 PR221-I In320 2720 A210 E320DU320 100 320 210
132 232 T5H400 PR221-I In400 3200 A260 E320DU320 100 320 260
160 282 T5H400 PR221-I In400 4000 A300 E320DU320 100 320 300
200 349 T5H630 PR221-I In630 5040 AF400 E500DU500 150 500 400
250 430 T6H630 PR221-I In630 6300 AF460 E500DU500 150 500 430
290 520 T6H800 PR221-I In800 7200 AF580 E800DU800 250 800 580
315 545 T6H800 PR221-I In800 8000 AF580 E800DU800 250 800 580
355 610 T6H800 PR221-I In800 8000 AF750 E800DU800 250 800 650
3 4
5.5
7.8
10.5
T2H160 MF 8.5
T2H160 MF 11
110
145
A30
A30
TA25DU11
TA25DU14
7.5
10
11
14
8.5
11
7.5 13.5 T2H160 MA 20 180 A30 TA25DU19 13 19 19
11 19 T2H160 MA 32 240 A30 TA42DU25 18 25 25
15 26 T2H160 MA 32 336 A50 TA75DU32 22 32 32
18.5 32 T2H160 MA 52 469 A50 TA75DU42 29 42 42
22 38 T2H160 MA 52 547 A50 TA75DU52 36 52 45
30 52 T2H160 MA 80 720 A63 TA75DU63 45 63 63
37 63 T2H160 MA 80 840 A75 TA75DU80 60 80 70
45 75 T2H160 MA 100 1050 A95 TA110DU90 65 90 90
55 90 T4H250 PR221-I In160 1200 A110 TA110DU110 80 110 100
75 120 T4H250 PR221-I In250 1750 A145 E200DU200 60 200 145
90 147 T4H250 PR221-I In250 2000 A185 E200DU200 60 200 185
110 177 T4H250 PR221-I In250 2500 A210 E320DU320 100 320 210
132 212 T5H400 PR221-I In320 3200 A260 E320DU320 100 320 220
160 260 T5H400 PR221-I In400 3600 A300 E320DU320 100 320 280
200 320 T5H630 PR221-I In630 4410 AF400 E500DU500 150 500 400
250 410 T6H630 PR221-I In630 5355 AF460 E500DU500 150 500 430
290 448 T6H630 PR221-I In630 6300 AF580 E500DU500* 150 500 500
315 500 T6H800 PR221-I In800 7200 AF580 E800DU800 250 800 580
355 549 T6H800 PR221-I In800 8000 AF580 E800DU800 250 800 580
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3 4
5.5
6.9
9.1
T2L160 MF 8.5
T2L160 MF 11
110
145
A30
A30
TA25DU8.5
TA25DU11
6
7.5
8.5
11
8.5
11
7.5 12.2 T2L160 MF 12.5 163 A30 TA25DU14 10 14 12.5
11 17.5 T2L160 MA 20 240 A30 TA25DU19 13 19 19
15 23 T2L160 MA 32 336 A50 TA75DU25 18 25 25
18.5 29 T2L160 MA 52 392 A50 TA75DU32 22 32 32
22 34 T2L160 MA 52 469 A50 TA75DU42 29 42 42
30 45 T2L160 MA 52 624 A63 TA75DU52 36 52 52
37 56 T2L160 MA 80 840 A75 TA75DU63 45 63 63
45 67 T2L160 MA 80 960 A95 TA80DU80 60 80 80
55 82 T2L160 MA 100 1200 A110 TA110DU90 65 90 90
75 110 T4H250 PR221-I In160 1440 A145 E200DU200 60 200 145
90 132 T4H250 PR221-I In250 1875 A145 E200DU200 60 200 145
110 158 T4H250 PR221-I In250 2250 A185 E200DU200 60 200 170
132 192 T4H320 PR221-I In320 2720 A210 E320DU320 100 320 210
160 230 T5H400 PR221-I In400 3600 A260 E320DU320 100 320 240
200 279 T5H400 PR221-I In400 4000 A300 E320DU320 100 320 280
250 335 T5H630 PR221-I In630 4725 AF400 E500DU500 150 500 400
290 394 T6L630 PR221-I In630 5040 AF460 E500DU500 150 500 430
315 440 T6L630 PR221-I In630 6300 AF580 E500DU500* 150 500 500
355 483 T6L630 PR221-I In630 6300 AF580 E800DU800 250 800 500
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3 4
5.5
8.6
11.5
T2N160 MF 11
T2N160 MF 12.5
145
163
A30
A30
TA25DU11*
TA450SU60 4
7.5
10
11
15
11
12.5
7.5 15.2 T2N160 MA 20 210 A30 TA450SU60 3 13 20 20
11 22 T2N160 MA 32 288 A30 TA450SU60 2 20 30 32
15 28.5 T2N160 MA 52 392 A50 TA450SU80 2 23 40 40
18.5 36 T2N160 MA 52 469 A50 TA450SU80 2 23 40 40
22 42 T2N160 MA 52 547 A50 TA450SU60 40 60 50
30 56 T2N160 MA 80 840 A63 TA450SU80 55 80 65
37 68 T2N160 MA 80 960 A95 TA450SU80 55 80 80
45 83 T2N160 MA 100 1200 A110 TA450SU105 70 105 100
55 98 T3N250 MA 160 1440 A145 TA450SU140 95 140 140
75 135 T3N250 MA 200 1800 A185 TA450SU185 130 185 185
90 158 T3N250 MA 200 2400 A210 TA450SU185 130 185 185
110 193 T4N320 PR221-I In320 2720 A260 E320DU320 100 320 220
132 232 T5N400 PR221-I In400 3200 A300 E320DU320 100 320 300
160 282 T5N400 PR221-I In400 4000 AF400 E500DU500 150 500 400
200 349 T5N630 PR221-I In630 5040 AF460 E500DU500 150 500 430
250 430 T6N630 PR221-I In630 6300 AF580 E500DU500*** 150 500 430
290 520 T6N800 PR221-I In800 7200 AF750 E800DU800 250 800 750
315 545 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800 750
355 610 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800 750
* Provide a by-pass contactor of the same size during motor start-up
* Set trip class 30 on the Type E relays
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3 4
5.5
7.8
10.5
T2H160 MF 8.5
T2H160 MF 11
110
145
A30
A30
TA25DU11*
TA25DU14*
7.5
10
11
14
8.5
11
7.5 13.5 T2H160 MA 20 180 A30 TA450SU60 4 10 15 15
11 19 T2H160 MA 32 240 A30 TA450SU80 3 18 27 27
15 26 T2H160 MA 32 336 A50 TA450SU60 2 20 30 32
18.5 32 T2H160 MA 52 469 A50 TA450SU80 2 28 40 40
22 38 T2H160 MA 52 547 A50 TA450SU80 2 28 40 40
30 52 T2H160 MA 80 720 A63 TA450SU60 40 60 60
37 63 T2H160 MA 80 840 A95 TA450SU80 55 80 80
45 75 T2H160 MA 100 1050 A110 TA450SU105 70 105 100
55 90 T4H250 PR221-I In160 1200 A145 E200DU200 60 200 145
75 120 T4H250 PR221-I In250 1750 A185 E200DU200 60 200 185
90 147 T4H250 PR221-I In250 2000 A210 E320DU320 100 320 210
110 177 T4H250 PR221-I In250 2500 A260 E320DU320 100 320 220
132 212 T5H400 PR221-I In320 3200 A300 E320DU320 100 320 220
160 260 T5H400 PR221-I In400 3600 AF400 E500DU500 150 500 400
200 320 T5H630 PR221-I In630 4410 AF460 E500DU500 150 500 430
250 410 T6H630 PR221-I In630 5355 AF580 E500DU500*** 150 500 430
290 448 T6H630 PR221-I In630 6300 AF750 E500DU500*** 150 500 500
315 500 T6H800 PR221-I In800 7200 AF 750 E800DU800 250 800 750
355 549 T6H800 PR221-I In800 8000 AF 750 E800DU800 250 800 750
* Provide a by-pass contactor of the same size during motor start-up
* Set trip class 30 on the Type E relays
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3 4
5.5
6.9
9.1
T2L160 MF 8.5
T2L160 MF 11
110
145
A30
A30
TA25DU8.5*
TA25DU11*
6
7.5
8.5
11
8.5
11
7.5 12.2 T2L160 MF 12.5 163 A30 TA450SU60 4 10 15 12.5
11 17.5 T2L160 MA 20 240 A30 TA450SU60 3 13 20 20
15 23 T2L160 MA 32 336 A50 TA450SU60 2 20 30 30
18.5 29 T2L160 MA 52 392 A50 TA450SU80 2 27.5 40 40
22 34 T2L160 MA 52 469 A50 TA450SU80 2 27.5 40 40
30 45 T2L160 MA 52 624 A63 TA450SU60 40 60 52
37 56 T2L160 MA 80 840 A75 TA450SU60 40 60 60
45 67 T2L160 MA 80 960 A95 TA450SU80 55 80 80
55 82 T2L160 MA 100 1200 A145 TA450SU105 70 105 100
75 110 T4H250 PR221-I In160 1440 A145 E200DU200 60 200 145
90 132 T4H250 PR221-I In250 1875 A185 E200DU200 60 200 170
110 158 T4H250 PR221-I In250 2125 A210 E320DU320 100 320 210
132 192 T4H320 PR221-I In320 2720 A260 E320DU320 100 320 220
160 230 T5H400 PR221-I In400 3200 A300 E320DU320 100 320 280
200 279 T5H400 PR221-I In400 3600 AF400 E500DU500 150 500 400
250 335 T5H630 PR221-I In630 4725 AF460 E500DU500 150 500 430
290 394 T6L630 PR221-I In630 5040 AF580 E500DU500*** 150 500 430
315 440 T6L630 PR221-I In630 6300 AF750 E500DU500*** 150 500 500
355 483 T6L630 PR221-I In630 6300 AF750 E500DU500*** 150 500 500
* Provide a by-pass contactor of the same size during motor start-up
* Set trip class 30 on the Type E relays
* Connection Kit not available. To use the connection kit, replace with relay E800DU800
3 160
200
282
349
T5N400 PR221-I In400
T5N630 PR221-I In630
3600
4410
A185
A210
A185
A210
A145
A185
E200DU200
E320DU320
60-200
100-320
250 430 T5N630 PR221-I In630 5670 A260 A260 A210 E320DU320 100-320
290 520 T6N630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150-500
315 545 T6N800 PR221-I In800 7200 AF400 AF400 A260 E500DU500 150-500
355 610 T6N800 PR221-I In800 8000 AF400 AF400 A260 E500DU500 150-500
3 200
250
279
335
T5H400 PR221-I In400
T5H630 PR221-I In630
3400
4410
A210
A210
A210
A210
A145
A185
E320DU320
E320DU320
100-320
100-320
290 394 T5H630 PR221-I In630 5040 A260 A260 A210 E320DU320 100-320
315 440 T6L630 PR221-I In630 5760 AF400 AF400 A210 E500DU500 150-500
355 483 T6L630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150-500
3 250
290
370
436
T6H800 PR222MP In630
T6H800 PR222MP In630
252-630
252-630
4410
5040
AF460
AF460
460
460
315 500 T6H800 PR222MP In630 252-630 5040 AF580 580
355 549 T6H800 PR222MP In630 252-630 5670 AF580 580
* For heavy-duty start set the electronic release tripping class to class 30
* In case of normal start use AF300
IntroduzioneSwitch-disconnectors
The following tables give the coordination between circuit-breakers and switch-
disconnectors of the following series: Tmax, Isomax, OT and OTEL.
The tables give the value of the maximum short-circuit current in kA for which
protection between the combination of circuit-breaker - switch-disconnector is verified,
for voltages up to 415 V.
The MCCB-OT-OETL tables are also valid at a voltage of 440 V. It is important to
check that the breaking capacities at 440 V (present in the technical catalogues of the
circuit-breakers) are compatible with the installation data.
With regard to the switch-disconnectors of the Emax series, on the other hand, it must
be checked that the short-circuit current value at the point of installation is lower than
the value of the short-time withstand current (Icw) of the switch-disconnector and that
the peak current value is lower than the making capacity current value (Icm).
The protection against overload of the Emax switch-disconnector must also be
checked. This can be carried out by means of an Emax series circuit-breaker of the
same size. Please consult the “Emax Low Voltage air circuit-breakers” technical
catalogue for the characteristics of Emax switch-disconnectors.
Note
The letter T indicates the switch-disconnector protection up to the breaking-capacity
of the circuit-breaker.
The following tables give the breaking capacities at 415 V AC for Isomax and Tmax
circuit-breakers.
Caption
MCS = switch-disconnectors derived from the moulded-case circuit-breakers (Tmax TD, Isomax SD)
MCCB = moulded-case circuit-breakers (Tmax, Isomax) 4
SD = switch-disconnectors
OT = OT series switch-disconnectors
OETL = OETL series switch-disconnectors
Ith = traditional thermal current at 40 °C in free air
Icw = short-time withstand current r.m.s. for 1 second
Caption of symbols
For solutions not shown in these tables, please consult the website:
[Link]
or contact ABB SACE
4 V
N
200
36
200* 200 200
36*
200
36
200
36
200
36
200
36
200
36
200
36
S 50 400 50* 50 50 50 50 50 50
T5 H 70 70* 70 70 70 70 70 70
630
L 120 120* 120 120 120 120 120 120
V 200 200* 200 200 200 200 200 200
N 35 630 35* 35* 35 35 35
S 50 50* 50* 50 50 50
T6 H 70 800 70* 70* 70 70 70
1000
L 100 100* 100* 100 100 100
S 50 1250 50* 50* 50
S7 H 65 65* 65* 65
1600
L 100 100* 100* 100
Icw[kA] 0.5 0.5 0.5 1 1.5 1.5 2.5 2.5 4 8-15 17-50
Ith [A] 25 32 40 63 80 100 115 125 200 200-400 630 - 1600
Supply s. Release In [A]
16 4 4 4 7 20 20 T T T T T
20 4 4 4 7 20 20 T T T T T
25 4 4 4 7 18 18 T T T T T
32 4 4 4 7 18 18 T T T T T
40 4** 4 4 7 18 18 T T T T T
T1 TM 50 4** 4 6 18 18 T T T T T
63 4** 6 18 18 T T T T T
80 6** 16 16 T T T T T
100 16** 16 T T T T T
125 16 T T T T T
160 16** T** T T T T
16 20 20 20 50 T T T T T T T
20 14 14 14 36 T T T T T T T
25 12 12 12 25 70 70 T T T T T
32
40
12
12**
12
10
12
10
25
20
70
36
70
36
T
T
T
T
T
T
T
T
T
T 4
TM 50 10** 10 20 36 36 T T T T T
63 10** 20 36 36 T T T T T
T2 80 7** 16 16 50 50 T T T
100 16** 16 50 50 T T T
125 16 50 50 T T T
160 16** 50** 50 T T T
25 10 10 10 16 50 50 T T T T T
EL 63 8* 8* 8* 12 30 30 T T T T T
100 8* 8* 6* 16* 16 50 50 T T T
160 6* 16* 16* 50* 50 T T T
63 3,5** 5 8 8 25 25 T T T
80 5** 8 8 24 24 T T T
100 8** 8 21 21 T T T
T3 TM 125 8** 20 20 40 T T
160 18** 18 36 T T
200 18** 36 T T
250 36 T T
20 8 8 8 20 T T T T T T T
32 6** 6 6 12 40 40 T T T T T
50 6** 6 12 40 40 T T T T T
T4 TM 80 8** 16 16 50 50 T T T
100 10** 10 19 20 100 100 T
160 10** 19 20 100 100 T
250 20** 100 100 T
EL 100-320 10* 10* 19* 20* 100* 100* T
Select the lowest value between the Icu of the circuit-breaker and the value indicated
* Maximum setting of the overload threshold PR2xx = 1.28*Ith OTxx/OETLxx
* I1 = 0.7 x I
Select the lowest value between the Icu of the circuit-breaker and the value indicated
* Maximum setting of the overload threshold PR2xx = 1.28*Ith OTxx/OETLxx
* I1 = 0.7 x I
[Link]